You are on page 1of 2

Multispectrum Infrared Flame Detector

AutroFlame X33

Features
Single detector for multiple fuels. Certified for 5
different hydrocarbon fuels
Increased coverage due to the increased cone of
vision and the detection ranges for light
hydrocarbon fuels.
Best combination of flame detection and false
alarm rejection (reliable fault diagnostics).
Mechanical design; smaller, lighter, sealed, easier
installation and can easily be retrofitted.
Heated optics, enable optimal performance in
adverse environments.
Calibration, optical testing every minute.
Versions, long range and medium range versions
available.
Explosion / flame proof or increased safety
installations (EExe) in hazardous locations.
Application / Description
The Multispectrum IR Flame Detector is the future
generation detector for performance and technology.
The detector utilizes advanced signal processing
algorithms, supported by an embedded 32-bit
microprocessor, to provide continuous protection in
the presence of false alarm sources and
environments with infrared radiation present.
It is suitable for indoor and outdoor applications that
require the highest level of false alarm rejection and
fire detection performance.
The detector is available in aluminium or 316
stainless steel for installation in the harshest
environments. The Flame Detector has a detection
range to gasoline of over 60m, and a solid cone of
vision for methane. The detector offers fire alarm /
fault relays or isolated 4 -20 mA output.
The AutroFlame X33 provides superior performance
in applications that are at the extremes, and where
background infrared radiation is a normal condition
(Offshore production platforms, Offshore production
ships, Refineries, Production facilities, Loading racks,
Compressor stations, Turbine enclosures).

P-X33/CE, Rev. A, 010404

Protecting environment, life and property...

AutroFlame X33

Technical Specifications

Response Distance

Shipping Weight (g)

Aluminum: 3600g
Stainless steel: 5600g

Enclosure Material

Copper-free aluminum
or 316 stainless steel

Power Consumption

9.0W maximum during operating


conditions

Temperature Range

Operating: -40C to +70C


Storage: -55 to + 85C
Humidity: 0-95% RH 100%

Operating Voltage

24VDC
Operating range is 18 to 32vdc.

Vibration
Conduit Entry Size
Mounting
Certification

Meets MILSPEC 810C,


method 514.2, curve AW
Male, inch NPT or 25mm
Swivel

Fuel

Size

Gasoline
Gasoline
Diesel **
Methanol
Methane
JP-5 **
JP-5 **

1 x 1 foot (0.1m2)
1 x 1 foot (0.1m2)
1 x 1 foot (0.1m2)
1 x 1 foot (0.1m2)
30 inch plume(0.9m)
2 x 2 foot (0.4 m2)
2 x 2 foot (0.4 m2)

210 (64)*
100 (30)
150 (45)*
150 (45)
100 (30)
210 (64)*
100 (30)

9.4
1.4
9.6
5.7
2.5
9.5
2.6

Gasoline
Gasoline
Diesel **
Methanol
Methane
JP-5 **
JP-5 **

1 x 1 foot (0.1m2)
1 x 1 foot (0.1m2)
1 x 1 foot (0.1m2)
1 x 1 foot (0.1m2)
30 inch plume(0.9m)
2 x 2 foot (0.4 m2)
2 x 2 foot (0.4 m2)

100 (30)
60 (18)
70 (21)
70 (21)
65 (20)
65 (20)
100 (30)

6.0
3.9
7.4
9.7
2.4
0.9
5.7

FMRC/CSA:
Class I, Div. 1, Groups B, C & D;
Class II, Div. 1, Groups E, F, & G;
Class III (T4A).
Class I, Div. 2, Groups A, B, C & D;
Class II, Div. 2, Groups E, F & G;
Class III (T3C).
CENELEC:
Standard Temperature Model
EEx d IIC T6, EEx d e IIC T6
(T amb = 40C to +60C).
EEx d IIC T5, EEx d e IIC T5
(T amb = 40C to +75C).
Extended Temperature Model
EEx d IIC T6, EEx d e IIC T6
(T amb = 55C to +60C).
EEx d IIC T5, EEx d e IIC T5
(T amb = 55C to +75C).
EEx d IIC T4, EEx d e IIC T4
(T amb = 55C to +100C).

Average
Response
Time (sec)

* Outdoor test condition


** 10 sec. Pre-burn, norm. ignition.

DNV Certificate No. A7792


Environmental: Ingress Protection to IP66/
NEMA Type 4X
EMC Directive: CE Certified

Distance
F1 (m)

Part no.
AutroFlame X33 Stainless Steel

4-20 mA

5861-011.3310

AutroFlame X33 Stainless Steel

Relay output

5861-011.3315

AutroFlame X33 Aluminum

4-20 mA

5861-011.3320

AutroFlame X33 Aluminum

Relay output

5861-011.3325

Cone of Vision
Indicated
Distancein
in Feet
Feet for
Indicated
Distance
forGasoline
Methane

Indicated Distance in Feet for Methane

15o

210
180
150

30o
45

120
90
60
30

0o

15o

100
90
80
70
60
50
40
30
20
10

30o
45o

30o

15o

0o
15 o
45o

30o

DETECTOR VERTICAL FIELD OF VIEW


WITH DETEECTOR AT 45o FROM HORIZONTAL

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Oil & Gas, U.K. Phone: +44 1462 624031, fax: +44 4420 79199315.
Oil & Gas Aberdeen, U.K. Phone: +44 1224 749602, fax: +44 1224 775102.
Oil & Gas Houston, U.S. Phone: +1 713 914 3877, fax: +1 713 914 3878.