Technical characteristics of 3-phase Alternators

Page 1 of 2 pages

G1R355SB
Manufacturer
Model
Continuous rating at class H rise (125C)

Crompton Greaves Ltd.


G1R355SB
kVA 400
kW 320
Continuous rating at class F rise (105C)
kVA
350
kW 280
Power Factor (LAG)
0.8
Governing Specification
IS: 13364 (Part 1 & 2), IS: 4722,
BS 5000 (PART 99), IEC 34.
Frequency
50 Hz
Speed in rpm
1500 rpm
Voltage Ph PH / Ph N
415 V / 240 V
Rated line current (at class H rise)
Amps
557
Number of phases
3
Excitation system
Brushless
Voltage regulator type
AVR-UVR-7
Voltage regulation
+/- 1%
10% overload capacity
1 Hour in every 6 hours
Maximum permissible unbalance load
25%
Motor starting capacity under ideal conditions#
300% of Rated Current for 10 seconds
Insulation system of all windings
Class H
Enclosure
IP 23
Short circuit current capacity
3 times FL current for 3 seconds.
Damper winding fitted on poles
Yes
Waveform distortion (% THD) between line - line
No load < 2.5%. Non distorting balanced linear load < 5%
Radio interference
As per VDE 0875 (N). For other standards consult factory
Cooling air requirement
80 m3 / min
Maximum over speed
2250 rpm
NDE bearing
6314.2RS
Stator winding
6 leads, double layer, 2/3 pitch
Weight of wound stator assembly
kg 520
Weight of wound rotor assembly
kg
468
Weight of complete alternator
kg
1114
WR inertia
kgm 6.69
Gross weight
kg
1289
Packing case size (L X B X H)
mm
1585 X 960 X 1220
% Efficiency, FL
%
94.1
% Efficiency, FL
% 94.7
% Efficiency, FL
% 93.5
% Reactance (Full load)*
Xd
250
Xd 12
Xd 10
Xq 197
X2 15
X0 7
Time constants (mSec)
TdO 2200
Td 100
Td 26
Ta 22
Short circuit ratio
(1 / Xd) 0.400
Excitation Amps
NL
0.5
FL (0.8 PF) 2.2 (52)
Stator winding resistance (per PH)
Ohm (25C)
0.0061
Rotor winding resistance
Ohm (25C)
2.46
Auxiliary winding resistance
Ohm (25C) 0.23
Exciter stator resistance
Ohm (25C)
20.12
Exciter rotor resistance (L L)
m-Ohm (25C) 0.09
Transient voltage dip at FL 0.8 PF
15 to 18% and recovery within 500 mSec
Transient voltage rise at FL 0.8 PF
18 to 20%
Non linear load capability (6 pulse UPS with filters)
66%
Specifications are subject to change without notice. Please confirm the specifications with us before ordering.
Note: 1. Full Load refers to 125C ratings. 2. Voltage Regulation and Temperature Rise clause are not applicable for
Over Load Condition and unbalance load condition. 3. Excitation data gives maximum values which are not generally
encountered during steady state operation and are given only for selecting proper cable sizes and metering. 4. Above
mentioned rating are applicable only for ambient temperature 50C, Altitude upto 1000 m and power factor 0.8 lag to
UPF. For different site conditions, refer derating factors. 5. # Transient behavior i.e. Voltage DIP & RISE is not
applicable. 6. Efficiency figure are subject to tolerance as per IS standard. 7. Technical data is same for Single Bearing
and Double Bearing alternators except the model number will start with G1 instead of G2 and there will be no bearing
on DE side.