605 series

Feeder protection REJ603 with HMI603


Application Note: Installation of HMI and Battery

Dear Reader
This application note describes the installation of HMI and battery for the REJ603.

Introduction
The REJ603 relay has add on battery powered HMI (Human Machine Interface) with a unique touch screen
display. With the HMI user can get add-on functionality line segregated trip indication, events with time stamp,
fault record, display of primary values, fault codes etc., which helps in post fault analysis. The HMI also
overcomes the limitation of setting resolution posed by DIP switches and allows finer settings as well as setting
of additional parameters.
The add-on HMI kit (HMI603) can be ordered separately and installation of HMI kit is possible at site on
existing installed relay (REJ603 V1.0 SP1 and V1.5).

Housing to accommodate HMI kit on relay


Connector for battery
Slot for battery insertion

Figure 1 : Installation of HMI603 on REJ603 relay

How to Install HMI603 on relay:


1. Insert new battery in housing and plug in the connector
2. Press the HMI603 casing on left and right side and insert the HMI on relay
3. Insert plastic cover on relay

Document information and revision history


Document ID:
1MDA04204-YN
Issued: issued date
2013-05-23
Revision:
0
Product version:
REJ603 Ver. 1.0 SP1 and 1.5
Document
revision/date

Product version

Document history

0 / 2013-05-23

REJ603 V1.0
SP1 & 1.5

Initial release

Disclaimer
The data, examples and diagrams in this document include solely for the concept or product description and are
not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment
addressed in this document must satisfy themselves that each intended application is suitable and acceptable,
including that any applicable safety or other operational requirements are complied with. In particular, any risks
in applications where a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to
exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any
errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit
contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this document or the application of the equipment.
Contact us:
ABB Limited
Distribution Automation
Maneja
Vadodara 390013, India
Phone +91 265 2604032
Fax +91 265 2638922

ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
Fax +358 10 22 41094

www.abb.com/substationautomation
Copyright 2013 ABB. All rights reserved

You might also like