definition
Introduction
IEC 60 056 and ANSI C37-06
define on one hand the operating conditions,
the rated characteristics, the design and
the manufacture; and on the other hand
the testing, the selection of controls
and installation.
# The circuit breaker is a device that ensures the control and protection
on a network. It is capable of making, withstanding and interrupting
operating currents as well as short-circuit currents.
# The main circuit must be able to withstand without damage:
5 the thermal current = short-circuit current during 1 or 3 s
5 the electrodynamic current:
2.5 Isc for 50 Hz (IEC)
2.6 Isc for 60 Hz (IEC)
2.7 Isc (ANSI), for a particular time constant (IEC)
5 the constant load current.
# Since a circuit breaker is mostly in the "closed" position, the load
current must pass through it without the temperature running away
throughout the equipment's life.
Characteristics
Compulsory rated characteristics
# Rated voltage
# Rated insulation level
# Rated normal current
# Rated short-time withstand current
# Rated peak withstand current
# Rated short-circuit duration
# Rated supply voltage for opening and closing devices
and auxiliary circuits
# Rated frequency
# Rated short-circuit breaking current
# Rated transient recovery voltage
# Rated short-circuit making current
# Rated operating sequence
# Rated time quantities.
Schneider Electric
Gamme
AMTED300014EN_045_05
Switchgear
definition
Upeak (%)
100
90
50
10
standardised wave
(Ur in kV)
7.2
12
17.5
24
36
Impulse withstand
voltage
Power frequency
withstand voltage
(Up in kV)
60
75
95
125
170
(Ud in kV)
20
28
38
50
70
Isc
:
:
:
short-circuit power
operating voltage
short-circuit current
(in MVA)
(in kV)
(in kA)
TED300014EN_045_053.
Gamme
Schneider Electric
Switchgear
definition
0%
35 %
70 %
100 %
t'
Isc
Ir
time
O
O
CO
:
:
# Opening/closing cycle
Assumption: O order as soon as the circuit breaker is closed.
displacement of
contacts
open
position
current flows
time
opening-closing duration
making-breaking duration
contacts are touching in all
poles and order O
energising of
closing circuit
Schneider Electric
Gamme
AMTED300014EN_045_05
Switchgear
definition
closed position
displacement of
contacts
open position
current flows
current flows
temps
making-breaking duration
opening-closing duration
remaking duration
reclosing duration
final extinction in all poles
energisiong of
opening release unit
Example 1 :
( 45 + 10 )
--------------------------45
= 29 5%
Example 2 :
# Supposing that % DC of a MV
circuit breaker is equal to 65% and that
the symmetric short-circuit current that is
calculated (Isym) is equal to 27 kA..
What does Iasym equal?
( % DC ) 2
I as ym = Isy m 1 + 2 ----------------100
= 27kA 1 + 2 ( 0 . 65 )
[A]
= 36.7 kA
36 .7kA
------------------- = 33 . 8kA
1. ( 086 )
TED300014EN_045_053.
% DC
00
90
80
70
60
50
40
30
20
10
0
10
20
30
40
50
60
70
80
90
t : circuit breaker opening duration (Top), increased by half a period at the power frequency (r).
Gamme
Schneider Electric
Switchgear
definition
% DC = 100
+ Tr)
--------------------------------e 1, ... ,4
I (A)
Squence
IAC
IMC
t (s)
IDC
% Isym.
1
2
3
4
5*
% aperiodic
component %DC
20
20
20
20
according to equation
10
20
60
100
100
IMC
IAC
Idc
%DC
:
:
:
:
making current
periodic component peak value (Isc peak)
aperiodic component value
% asymmetry or aperiodic component:
I DC
( Top + Tr )
------------------------------- ( 1 ,... ,4 )
Schneider Electric
Gamme
AMTED300014EN_045_05
Switchgear
definition
U (kV)
Uc
(Ur in kV)
7.2
12
17.5
24
36
TRV
value
Time
Delay
Increase
rate
(Uc in kV)
12.3
20.6
30
41
62
(t3 in s)
52
60
72
88
108
(td in s)
8
9
11
13
16
(Uc/td in kV/s)
0.24
0.34
0.42
0.47
0.57
2
U c = 1. 4 1. 5 ------- U r = 1. 715U r
3
0
td
t3
t d = 0. 15t3
X1
U1
UA - UB = U1 - (-U2) = U1 + U2
si U1 = U2 so UA - UB = 2U
tme delay
time defined to reach Uc
peak TRV voltage in kV
Uc/t3 in kV/s
X2
When a circuit breaker is open and the conductors are not synchronous,
the voltage across the terminals can increase up the sum of voltages in
the conductors (phase opposition).
U2
Rated
voltage
(Ur in kV)
7.2
12
17.5
24
36
TED300014EN_045_053.
TRV
value
Time
Rate of
increase
(Uc in kV)
18.4
30.6
45
61
92
(t3 in s)
104
120
144
176
216
(Uc/td in kV/s)
0.18
0.26
0.31
0.35
0.43
Gamme
Schneider Electric
Switchgear
definition
B
Ic
(A)
400
630
1250
2500
3150
(A)
280
440
875
1750
2200
By definition
2
pu = U r ------3
# The normal value of over-voltage obtained is equal to 2.5 pu, this being:
2
2.5 Ur ------3
X1
Schneider Electric
C2
C3
2n
2
---------------- pu with pu = U r ------2n + 1
3
Gamme
AMTED300014EN_045_05
Switchgear
definition
Up
Ud
Um
Uc
Uf
Uc
Um
Uif
Up
Ud
:
:
:
:
:
:
Uf
Uif
Test at 50 (60) Hz
Impulse test
rms. value
Between turns
Relative
to earth
(4 Ur + 5) kV
4.9 pu + 5 = 31 kV at 6.6 kV
(50% on the sample)
increase time 0.5 s
(4 Ur + 5) kV
4.9 pu + 5 = 31 kV at 6.6 kV
increase time 1.2 s
(2 Ur + 5) kV
2Ur + 1 2(2Ur + 1) 0
14 kV
28 kV 0
1 kV/s
0
1 mn
TED300014EN_045_053.
0C
Installation
Instantaneous ambient
minimal
maximal
average daily maximum value
Indoor
-5C
+40C
35C
Gamme
Outdoor
-25C
+40C
35C
Schneider Electric
Switchgear
definition
# Humidity
Average relative humidity
Indoor equipment
for a period
24 hours
1 month
95 %
90 %
# Altitude
The altitude must not exceed 1 000 metres.
Electrical endurance
The electrical endurance requested by the recommendation is three
breaking operations at Isc.
Merlin Gerin circuit breakers are capable of breaking Isc at least 15 times.
Mechanical endurance
The mechanical endurance requested by the recommendation is 2 000
switching operations.
Merlin Gerin circuit breakers guarantee 10 000 switching operations.
7.2
12
17.5
24
36
Schneider Electric
Rated short-circuit
breaking current
Isc (kV)
10
16
25
40
8
12.5
16
25
40
8
12.5
16
25
40
50
8
12.5
16
25
40
8
12.5
16
25
40
8
12.5
16
25
40
Ir (A)
400
630
400
400
400
400
630
630
630
630
630
630
400
630
630
630
400
630
630
630
630
630
630
Gamme
1250
1250
1250
1600
1600
2500
2500
3150
1250
1250
1250
1250
1600
1600
1600
2500
2500
3150
1600
1600
1600
1600
2500
2500
2500
3150
3150
1600
2500
3150
1600
1600
2500
2500
3150
1600
1600
1600
2500
2500
3150
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
AMTED300014EN_045_05