Gateway Modbus address mapping for Mk5 controller

ZR160VSD_1 gen. 5 , APF206337

Mk5 controller must be in Mk5 CAN profile !

1900525622 - VSD GraphicPlus 2.0.23.0


17/02/2016 10:53:37

Coils
Name

Coil

Stopped/Running

Unload/Load

General Warning

General ShutdownWarning

General Shutdown

General Service

General StartFailure

Emergency Stop

Manual/Automatic

Local/Remote

10

Analog Inputs
Name

Type

Unit

Salida del compresor

Pressure (mBar)

mBar

dP Filtro de aire

Pressure (mBar)

mBar

Presin de aceite

Pressure (mBar)

mBar

Refrigerador intermedio

Pressure (mBar)

mBar

Salida del compresor

Temperature

0.1 C

Salida Elemento 1

Temperature

0.1 C

Entrada Elemento 2

Temperature

0.1 C

Salida Elemento 2

Temperature

0.1 C

Entrada agua refrigeracin

Temperature

0.1 C

Salida agua refrigeracin BP

Temperature

0.1 C

Salida agua refrigeracin

Temperature

0.1 C

Temperatura de aceite

Temperature

0.1 C

Calculated Analog Inputs


Name

Type

Unit

Refrigerador agua DT LP

Temperature

0.1 C

Digital Inputs
Name
Parada de emergencia
Arranque/parada remoto
Fallo convertidores
Seleccin de ajuste de Presin
Purga condensados IC
Purga condensados AC

Digital Outputs
Name
Funcionando
Carga/Descarga
Operacin automtica
Aviso general
Parada por alarma general
Purga refrigerador intermedio
Purga refrigerador posterior
Permiso de marcha de motor principal

Counters
Name

Unit

Horas de marcha

Horas en carga

Arranques de motor

Count

Rel de carga

Count

VSD 1-20% RPM

VSD 20-40% RPM

VSD 40-60% RPM

VSD 60-80% RPM

VSD 80-100% RPM

Volumen acumulado

_1000_m3

Horas del mdulo

Paradas de emergencia

Count

Paradas directas

Count

Special Alarms
Name
Presin de control no vlida
Alarma Convertidor 1 del Motor
Purga Condensado IC no OK
Purga Condensado AC no OK

Comunicacin Mdulo Expansin

Main Motor Speed


Register 801 : Required RPM
Register 802 : Actual RPM

Machine Control Mode


Register 702 , LO byte
Name

Value

2a - Local Start/Stop & Pressure Sensing

3a - Remote Start/Stop, Local Pressure Sensing

4a - Communication Start/stop, Local Pressure Sensing

2b - Local Start/Stop, Digital Contact Pressure Sensing

16

3b - Remote Start/Stop, Digital Contact Pressure Sensing

17

4b - Communication Start/Stop & SPS Control

18

4c - Communication Start/Stop & Speed Control

34

4d - ES Controlled

50

2e - Local Start/Stop & 4-20mA Speed Control

64

3e - Remote Start/Stop & 4-20mA Speed Control

65

4e - Communication Start/Stop & 4-20mA Speed Control

66

Machine Mechanical State


Register 701 , HI byte
Name

Value

Stop

Unload

Loaded

General Status
Register 703
Name

Bit

PreWarning

General Warning

General Shutdown Warning

General Shutdown

General Service

General Start Failure

Emergency Stop

Manual/Automatic

Local/Remote

Week Timer

PreWarning Service Running Hours

10

PreWarning Service Accumulated Volume

11

PreWarning Service Analog Input

12

PrePermissive

13

Test Mode

14

ESi Status
Register 709
Name

Value

PowerUp ES

8209

Local Operation ES

8225

Central Stop ES

8242

Shutdown ES
Automatic Operation ES

8337
24594

Regulation Parameters
Name

Register

Value Read

VSD Setpoint Selection

851

SP1=>1, SP2=>2

VSD Setpoint 1

852

mBar

VSD Setpoint 1

853

mBar

Use ES(i) Pressure Band 1

881

Use ES(i) Pressure Band 2

881

ES(i) Pressure Band 1 - Load

882

mBar

ES(i) Pressure Band 1 - Unload

883

mBar

ES(i) Pressure Band 2 - Load

884

mBar

Commands
Name

Register

Value Read

Start

2001

n/a

Stop

2001

n/a

Unload

2001

n/a

Reset Protection

2004

n/a

Reset Permissive

2004

n/a

Reset Service

2004

n/a

ResetES

2004

n/a

Reset ALL

2004

n/a

for Mk5 controller

k5 CAN profile !

Registers
Status

Value

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Value Interpretation

Values are S16. 32767 = Sensor error.

Registers
Status

Value

Value Interpretation

411

412

Values are S16. 32767 = Sensor error.

Status

Value

0/1

501

502

Disparado / OK

503

504

Parado / En marcha

505

506

Disparado / OK

509

510

Punto de ajuste 1 / Punto de ajuste 2

517

518

Agua / Sin Agua

519

520

Agua / Sin Agua

Registers

Bit

Description

PreWarning

Warning

ShutdownWarning

Shutdown

Service

Permissive

Sensor Error

Set/Not set

SPM valid measurement

13

PrePermissive

Registers
Value

0/1

2551

Parado / En marcha

2554

Descarga / Carga

2555

No / S

2556

S / No

2557

S / No

2558

Abierto / Cerrado

2559

Abierto / Cerrado

2560

No / S

Registers
Value = (65536 x W2) + W1

Reference counters for % calculation

Value W2

Value W1

1001

1002

1003

1004

1005

1006

1007

1008

1009

1010

Running Hours

1011

1012

Running Hours

1013

1014

Running Hours

1015

1016

Running Hours

1017

1018

Running Hours

1023

1024

1025

1026

1027

1028

1029

1030

Registers
Status
2703
2704
2715
2716

2742
Bit

Description

PreWarning

Warning

Shutdown

Value Write
SP1=>1, SP2=>2
n/a
n/a

1
2
n/a
n/a
n/a

Value Write

Info

Start the main machine

Stop the main machine

4
1
2
3
8
255