General
Specifications

R3

I/O Module Nest


I/O Module
(for RIO)

GS 33Y06K40-31E

GENERAL
This GS covers the specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS
1000 systems.

STANDARD SPECIFICATIONS
I/O Module Nest
Power Supply: 5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/PFCD
Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack, or Model PFCS/PFCD Field Control Station
External Dimensions: 125 (W) x 130 (D) x 248 (H); AMN51: 137.5 (W) x 225 (D) x 254 (H); AMN52: 233.3 (W) x 225 (D) x
254 (H)
Weight: Max. 2.5 kg (AMN52. This weight does not include I/O Modules.)
CS3000
Models

Names

CS1000

AFS10S/AFS10D
AFS20S/AFS20D

PFCS
PFCD

Installation Restrictions
(See next page)

AMN11

Nest for Analog I/O Modules

AMN12

High-Speed Nest for Analog I/O Modules

AMN21

Nest for Relay I/O Modules

AMN31

Nest for Terminal I/O Modules

AMN32

Nest for Connector I/O Modules

AMN33

Nest for Communication Modules

AMN34

Nest for Multipoint Control Analog I/O Modules

AMN51

Nest for Communication Cards

(*3)

AMN52

Nest for PROFIBUS Communication Module

(*5)

(*5)

(*4)

(*1)

(*2)

T01E.EPS

:
Installable
*1, *2, *3, *4: See next page.
*5:
Installable in R2.10 or later.

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel: 81-422-52-5634 Fax: 81-422-52-9802

GS 33Y06K40-31E
Copyright Jan. 2001
4th Edition Jun.1,2003

<<Contents>> <<Index>>

Installation Restrictions for I/O Module Nest


Model AMN12 High-speed Nest for Analog I/O Modules (*1)
-Always install in Nest No. 1 (See Figures 1, 2 and 5).
-Do not install any I/O module nests in Nests No. 2 through No. 4 (See Figures 1, 2 and 5).
-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5 (See Figures 2 and 5).
Model AMM22T Multiplexer Module Installed in AMN31 Nest for Terminal I/O Modules (*2)
-Do not install non-AMM22T I/O module below Multiplexer Module (See Figures 3, 4 and 8) because AMM22T is a module
for thermocouple entry. If there were a heat source below the module, a reference junction compensation error occur.
-If there is another module (heat source) below Multiplexer Module when using 19" Rack Mountable Type, a thermal shield
must be inserted between the multiplexer module and the heat source (See Figures 6 and 7).
Model AMN51 Nest for Communication Cards (*3)
-Only one nest is installable in PFCS/PFCD. Its position is fixed as Nest No. 2.
Cabinet Mountable Type
Figure 4
Figure 3
(Permitted) (Not Permitted)

Figure 2
(Permitted)

Figure 1
(Permitted)

Model
AMN12

Model
AMN12

Nest No.1

Empty

Empty

Nest No.2

Empty

Empty

Nest No.3

Empty

Empty

Nest No.4

: Model AMM22T
Multiplexer Module

Nest No.5

Non-AMM22T
: I/O module

Module nest
for non-AMN12

F01E.EPS

ANS50/AND50 connected to
AFS10S/AFS10D 19-inch Rack Mountable Type FCU
Figure 5
(Permitted)
Model
AMN12

19-inch Rack Mountable Type ANS50, AND50, PFCS and PFCD


Figure 6
(Permitted)

Figure 7
(Not permitted)

Figure 8
(Not permitted)

Nests No.1 and 2


from the left

Heat Source

Nests No.3, 4 and 5


from the left
Empty
Module nest for non-AMN12
Thermal Shield

Heat Source

: Model AMM22T
Multiplexer Module

Non-AMM22T
: I/O module

Note: Figure 7 will be applied to only PFC.


F02E.EPS

AMN52 Nest for PROFIBUS Communication Module


-Only one nest is installable in PFC. Its position is fixed as Nests No. 1 and 2. AMN52 cannot be combined with AMN51.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>

I/O Modules to be Installed in Control Stations


I/O Module(s) to be Installed
Models

I/O Module Names

CENTUM CS 1000

CENTUM CS 3000

PFCS-S,
PFCD-S

PFCS-E,
PFCD-E

PFCS-H,
PFCD-H

AFS10S,AFS10D,
AFS20S,AFS20D

Analog I/O Modules

AAM10

Current/Voltage Input Module (Simplified Type)

AAM11

Current/Voltage Input Module

AAM11B

Current/Voltage Input Module (supports BRAIN)

AAM21

mV, Thermocouple, and RTD Input Module

AAM21J

mV, Thermocouple, and RTD Input Module


(supports IEC584-1995, IEC751-1995)

APM11

Pulse Input Module

AAM50

Current Output Module

AAM51

Current/Voltage Output Module

AMC80

Multipoint Control Analog I/O Module

AMM32T

Relay I/O Modules

ADM15R

Relay Input Module

ADM55R

Relay Output Module

Multiplexer Modules (16 Points, Terminal Type)

AMM12T

Voltage Input Multiplexer Module

AMM22M

mV Input Multiplexer Module

AMM22T

Thermocouple Input Multiplexer Module

Thermocouple Input Multiplexer Module


AMM22TJ
(supports IEC584-1995)

RTD Input Multiplexer Module

RTD Input Multiplexer Module


AMM32TJ
(supports IEC751-1995)

AMM42T

2-Wire Transmitter Input Multiplexer Module

AMM52T

Output Multiplexer Module

Multiplexer Modules (Connector Type)

AMM12C

Voltage Input Multiplexer Module

AMM22C

mV Input Multiplexer Module

AMM25C

mV Input Multiplexer Module with Thermocouple Interface


(15 Points, RJC Input port added)

AMM32C

RTD Input Multiplexer Module (16 Points)

AMM32CJ

RTD Input Multiplexer Module (16 Points, conforms to


IEC751-1995)

Digital I/O Modules

ADM11T

Contact Input Module (16 Points, Terminal Type)

ADM12T

Contact Input Module (32 Points, Terminal Type)

ADM51T

Contact Output Module (16 Points, Terminal Type)

ADM52T

Contact Output Module (32 Points, Terminal Type)

ADM11C

Contact Input Module (16 Points, Connector Type)

ADM12C

Contact Input Module (32 Points, Connector Type)

ADM51C

Contact Output Module (16 Points, Connector Type)

ADM52C

Contact Output Module (32 Points, Connector Type)

Communication Modules

ACM11

RS-232C Communication Module

ACM12

RS-422/RS-485 Communication Module

ACM21

RS-232C General-purpose Communication Card

ACM22

RS-422/RS-485 General-purpose Communication Card

ACM71

Ethernet Communication Module (for PFCS/PFCD)

ACF11

Fieldbus Communication Module

ACP71

PROFIBUS Communication Module

:
- :

T02E-1.EPS

Installable
Not installed

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>

Types of I/O Modules and Max. No. of Modules to be Installed into I/O Module Nests
Max. No. of Modules to be Installed in I/O Module Nests
Models
-

I/O Module Names

AMN11
AMN12

AMN21 AMN31

AMN32

AMN33 AMN34 AMN51 AMN52

Analog I/O Modules

AAM10

Current/Voltage Input Module (Simplified Type)

AAM11

Current/Voltage Input Module

AAM11B

Current/Voltage Input Module (supports BRAIN)

AAM21

mV, Thermocouple, and RTD Input Module

AAM21J

mV, Thermocouple, and RTD Input Module


(supports IEC584-1995, IEC751-1995)

APM11

Pulse Input Module

AAM50

Current Output Module

AAM51

Current/Voltage Output Module

AMC80

Multipoint Control Analog I/O Module (*5)

Up to
16
modules
can be
installed

2 (*4)

Relay I/O Modules

ADM15R

Relay Input Module

ADM55R

Relay Output Module

Only
1

Multiplexer Modules (16 Points, Terminal Type) (*1)

AMM12T

Voltage Input Multiplexer Module

AMM22M

mV Input Multiplexer Module

AMM22T

Thermocouple Input Multiplexer Module

Thermocouple Input Multiplexer Module


AMM22TJ
(supports IEC584-1995)

AMM32T

RTD Input Multiplexer Module

AMM32TJ RTD Input Multiplexer Module (supports IEC751-1995)

Up to 2

Up to 2
(*7)

AMM42T

2-Wire Transmitter Input Multiplexer Module

AMM52T

Output Multiplexer Module

Multiplexer Modules (Connector Type) (*1)

AMM12C

Voltage Input Multiplexer Module

AMM22C

mV Input Multiplexer Module (16 Points)

AMM25C

mV Input Multiplexer Module with Thermocouple Interface


(15 Points, RJC Input port added)

AMM32C

RTD Input Multiplexer Module (16 Points)

RTD Input Multiplexer Module (16 Points, conforms to


AMM32CJ
IEC751-1995)

Digital I/O Modules (*1)

ADM11T

Contact Input Module (16 Points, Terminal Type)

ADM12T

Contact Input Module (32 Points, Terminal Type)

ADM51T

Contact Output Module (16 Points, Terminal Type)

ADM52T

Contact Output Module (32 Points, Terminal Type)

ADM11C

Contact Input Module (16 Points, Connector Type)

ADM12C

Contact Input Module (32 Points, Connector Type)

ADM51C

Contact Output Module (16 Points, Connector Type)


Contact Output Module (32 Points, Connector Type)

ADM52C
-

Up to 4
(Up to 2
modules
can be
installed in
AFS0)
(*8)

Up to 2
(*2)

Up to 4
(*3)

Communication Modules

ACM11

RS-232C Communication Module

RS-422/RS-485 Communication Module

Up to 2
(*4)

ACM12

ACM21

RS-232C General-purpose Communication Card (*5)

ACM22

RS-422/RS-485 General-purpose Communication Card


(*5)

ACM71

Ethernet Communication Module (for PFCS/PFCD)

ACF11

Fieldbus Communication Module

2 (*8)

ACP71

PROFIBUS Communication Module

4 (*9)

Up to 2
(*5)

T02E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>
*1:
*2:
*3:

*4:
*5:
*6:
*7:

*8:

*9:

The Multiplexer Module and Digital I/O Module cannot be installed in the same I/O Module Nest.
When the operation mode of Model ADM52T is in time-proportioning ON/OFF in installing in AFS10S/AFS10D/AFS20S/
AFS20D, only one module can be installed in Slot 1 (see table below).
The table in next page shows installation restrictions by operation mode when installing in AFS10S/AFS10D/AFS20S/AFS20D
(No modules can be installed in Slots marked N/A).
When the operation mode of ADM51C is time-proportioning ON/OFF, two modules can be installed in Slots 1 and 3. However,
when installing one module only, a general ADMC can be installed in Slots 3 and 4.
When the operation mode of ADM52C is pulse -width-output, two modules can be installed in Slots 1 and 3. However, when
installing one module only, a general ADMC can be installed in Slots 3 and 4.
When the operation mode of ADM52C is in time -proportioning ON/OFF, only one module can be installed in Slot 1.
Installing two modules in one nest allows one to use a pair of redundant modules or two sets of module.
These modules cannot be installed on CENTUM CS 1000 Release 1.
This module and ACM11/ACM12 cannot be installed in the same AMN33 Nest for Communication Modules.
The module can be installed in Slots 1 and 3 only. Other IOMs cannot be installed in Slot 2 or 4. The module can be combined
with AMM12C, AMM22C, AMM32C, AMM32CJ and AMM25C in the same I/O module nest, and AMM12T, AMM22M, AMM22T
and AMM22TJ can be installed in Slots 1 and 3. When using AFS10S/AFS10D/AFS20S/AFS20D, Terminal Type Multiplexer
Modules cannot be installed in AMN32.
AMM12C, AMM22C, AMM25C, AMM32C, and AMM32CJ can be combined with AMM12T, AMM22M, AMM22T and AMM22TJ in
the PFCS/PFCD Field Control Station (Use AMN32 Nest). In this case, one Terminal Type Multiplexer Module and up to two
Connector Type Multiplexer Modules can be installed. When combining these modules, the Terminal Type is installed in Slot 1
or 3 and no module can be installed in Slot 2 or 4 (right slot of Slot 1 or 3). In the AFS10S/AFS10D/AFS20S/AFS20D, up to two
modules can be installed in Slot 1 and 2.
Up to four ACP71 modules can be installed in the PFCS/PFCD Field Control Station. AMN52 is used for ACP71 only.
AMN32
Models

AMN31

Functions

ADM52T

Time-proportioning ON/OFF output

ADM51C

Time-proportioning ON/OFF output

Slot 1

Slot 2

Slot 3

Slot 4

N/A

N/A

One-shot Pulse-width-output

N/A

N/A

Time-proportioning ON/OFF output

N/A

N/A

N/A

ADM52C

Slot 1

Slot 2

N/A

T03E.EPS

Communication Module Installation Restrictions in Control Stations


CS 1000
Nest

AMN33 (*1)

Module
Total of ACM11
and ACM12

ACF11 (*5)

CS 3000

PFCS-S
PFCD-S

PFCS-E
PFCD-E

PFCS-H
PFCD-H

AFS10S, AFS10D,
AFS20S, AFS20D

(*2)

Max. 4 (*3) (*4)

Max. 4 (*3) (*4)

Max. 6 (*3)

No restriction

No restriction

No restriction

No restriction

AMN51 (*6)

Total of ACM21,
ACM22 and
ACM71

Max. 2 (*4)

Max. 2 (*4)

AMN52 (*6)

ACP71

Max. 4 (*4)

Max. 4 (*4)

T21E.EPS

*1:
*2:

*3:

*4:
*5:
*6:

ACM11/12 cannot be combined with ACF11 in the same AMN33 nest.


The maximum number of ACM11/12 modules to be installed in PFCS-S/PFCD-S is restricted by subsystem communication
packages.
-Up to two modules can be used for a single communication.
-Up to three modules can be used for one pair of redundant communications (two modules) and a single communication (one
module).
-Up to four modules can be used for two pairs of redundant communications.
Up to four ACM11/ACM12 modules can be installed in the PFCS-E, PFCD-E, PFCS-H, and PFCD-H. Up to six ACM11/ACM12
modules can be installed in the AFS0. Redundant configuration does not affect the maximum number of ACM11/ACM12
modules.
ACM11/ACM12, ACM21/ACM22/ACM71, and ACP71 can be combined in the same control station. Up to the maximum number
of modules can be installed.
The maximum number of ACF11 modules is restricted by physical space of control stations or application capacity.
AMN51 and AMN52 cannot be combined in the same control station (Only one of them can be installed).

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>

Protection of RIO Module Vacant Slots


When I/O modules are not installed, dummy covers should be provided for the backboard connectors to protect them against
corrosion.
T9081EF: Dummy frame for AMN1 Nest (Analog I/O Module )
T9081FB: Dummy frame for RJC (AMN1 Nest )
T9081CV(*1): Dummy plate for AMN3 Nest (Digital I/O Module, Multiplexer Module, etc.)
T9081PV: Dummy plate for AMN5 Nest (Communication Module)
*1:

The width of T9081CV is same as that of Multiplexer Module (Connector Type) or Digital I/O module (Connector type). So, in
some cases, two T9081CV are required for one vacant slot.

AMM31

AMM12T
T9081CV

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

F16E.EPS

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>
Analog I /O Module
Current/Voltage Input Modules
These modules receive 4-20 mA from 2-wire transmitters and 1-5 V standardized signals. They can also receive signals
other than standard 4-20 mA or 1-5 V signals. AAM11B can be combined with a transmitter which supports BRAIN
communications. Use our BRAIN terminal to specify parameters for a transmitter.

Analog I/O module

F03E.EPS

Items

Specifications

Model

AAM11, AAM11B

Input signal
Input resistance
Allowable input
voltage/current

0 to 10 V DC
1 M at power-up (100 k at powerdown)

250 

-10 to 30 V DC

40 mA DC or less

Supplying power to
transmitter
Auxiliary voltage
output
Square root extraction
Accuracy
Effect of ambient
temperature change
Data update period
Current consumption
Signal isolation
How installed
How connected
How input signals are
specified

0 to 20 mA DC
(*1), (*2)
(It is possible to supply power to a transmitter.)

25.0 to 25.5 V DC
(Output current limit: 60 mA DC or less )

1 to 5 V DC; Output resistance: 1  or less;


Allowable load resistance: 10 k or more; Signal ground is shared with system
Specify whether to use square root extraction.
Voltage input: 4 mV; Current input: 16 A; Auxiliary voltage output: 12 mV
For 10C change:
Voltage input: 4 mV +  0.15 % of specified value
Current input: 32 A
Auxiliary voltage output: 24mV
50 ms
300 mA or less (5.0 V DC)
Input signals are isolated between systems
Withstanding voltage: 1500 V AC/min
Installed in the I/O Module Nest
Connected to the terminals of the I/O Module Nest with M4 screws
Specify input signals and range by software setting.
T04E.EPS

*1:
*2:

This module can be combined with MTL barrier 728. In this case, wiring resistance must be 10  or less and the minimum
operating voltage of the 2-wire transmitter must be 12 V DC or less.
When the power of AAM11 is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250 ) to current-output module
and share voltage output.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>
Current/Voltage Input Module (Simplified Type)
This module receives 4-20 mA from 2-wire transmitters and 1-5 V standardized signals.
Items

Specifications

Model

AAM10
1 to 5 V DC

4 to 20 mA DC
(*1), (*2)
(It is possible to supply power to a transmitter)

Input resistance

1 M at power-up (100 k at powerdown)

250 

Allowable input
voltage/current

-10 to 30 V DC

40 mA DC or less

Input signal

Transmitter power
supply

Auxiliary voltage
output

None

Square root extraction

None

Accuracy
Effect of ambient
temperature change

Voltage input: 4 mV; Current input: 16mA


For 10 C change: Voltage input: 8mV
Current input:
32A

Data update period

50 ms

Current consumption

250 mA or less (5.0 V DC)

Signal isolation
How installed
How connected
How input signals are
specified

25.0 to 25.5 V DC
(Output current limit: 60 mA DC or less )

Input signals are isolated between systems.


Withstanding voltage: 1500 V AC/min
Installed in the I/O Module Nest.
Connected to the terminals of the I/O Module Nest with M4 screws.
Specify input signals and range by software setting.
T05E.EPS

*1:
*2:

This module can be combined with MTL barrier 728. At this time, wiring resistance must be 10  or less and the lowest
operating voltage of the 2-wire transmitter must be 12 V DC or less.
When the power of AAM10 is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250  ) to current-output module
and share voltage output.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

<<Contents>> <<Index>>
Small Electric Power Input Module
This module receives signals from mV, thermocouple, RTD and potentiometer.
Item

Specifications

Model

AAM21, AAM21J (*4)

Input signal

mV

JIS,IEC Standard
Thermocouple type K, T,
J, E, B (*1), R, S, IEC
Standard type N

RTD JIS Pt100 or 3-wire


JIS Pt100 (DIN Pt100) type

Input range

-50 to 150 mV

-50 to 150 mV

0 to 333 

0 to 30,000 (*2)

Allowable input voltage -0.5 to 4.0 V DC (between terminals B-C)


Input resistance

1 M V at power-up (3 k V at power-down)

Accuracy

20 V

Data update period

100 ms

20 V

Signal source resistance 1000  or less

3-wire potentiometer's
total resistance 100 to
2,000 

0.08 V

0.2 %

150  or less (wiring resistance per wire)

RJC input

-10 to 70 C

RJC accuracy

Within  1 C (*3)

Measuring current

1 mA

Auxiliary voltage
output

1 to 5 V DC (Signal ground is shared with system)


Output resistance: 1  or less
Allowable load resistance: 10 k or more
Output range: 0.5 to 5.5 V DC
Accuracy: 12 mV

Burnout detection

Select from UP/DOWN/OFF

Burnout detection time Within 60 sec


Burnout detection
current
How installed

0.1 A (terminal B only)


Installed in AMN11 Nest for Analog I/O Modules

How connected

Connected to the terminals of the I/O module nest with M4 screws

Signal isolation

Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min

Current consumption
Input linearization

150 mA or less (5.0 V DC)


None

Available

Effect of signal source 1 k of signal source resistance: Input conversion


 20 V or less
resistance/wiring
resistance (burnout is
OFF)

Effect of ambient
temperature change

How input signals are


specified

For 10 C change:

mV input:
Thermocouple input:
RTD input:
Potentiometer input:
Auxiliary voltage output:

Available

None

Wiring resistance 10  for


terminals A and C: Input
conversion40 m or less
(Wiring of terminals A and
C must have the same
resistance)

40 V
40 V
0.16 
0.4 % of span
24 mV

Specify input signals and range by software setting.


T06E.EPS

*1:
*2:
*3:

Type B does not carry out temperature compensation.


The input conversion is effective only if total resistance is within 100 to 2000 , and the span is 50 % or more of the total
resistance. Total resistance can be combined up to 30 k.
If measured temperature is lower than 0 C, multiply the above value by the following coefficient (K):

K=
*4:

Thermoelectric power per degree at 0 C


Thermoelectric power per degree at measured temperature

F04E.EPS

The use of AAM21J as termocouple input and RTD input conforms to IEC584-1995, IEC751-1995.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

10

<<Contents>> <<Index>>
Option Specifications for Thermocouple
When using the AAM21 for thermocouple input, order the temperature compensation module for each channel.
Description
Model

AAM21, AAM21J

Option Code

/RJ

Temperature Compensation Module for Thermocouple Input

T07E.EPS

Pulse Input Module


This module receives contact ON/OFF, voltage pulse and current pulse.
Item

Specifications

Model
Input signal
Input frequency
Data update period
Min. input pulse width

APM11
2-wire type: Contact ON/OFF, voltage pulse, current pulse (It is possible to supply power to a transmitter)
3-wire type: Power supply type voltage pulse
0 to 10 kHz
10 ms
40 s or more

Input signal level

Contact input
Relay contact, transistor contact
Detecting level open: 100 k or more; Closed: 200  or less
Contact capacity : 15 V DC, 15 mA or more at 12 V power supply; 30 V DC, 30 mA or more at 24 V
power supply
Voltage/current pulse input (The values of voltage converted from current input are as follows:)
VH (high level) 3 to 24 V DC
VL (low level) -1 to 8 V DC
Swing VH-VL 3V
Signal source resistance 1 k or less

Shunt resistance

Select from 200/510/1000 /OFF

Pull-up resistance

68 k (12 V or 24 V)

Transmitter power
supply

12 V DC  10%, 35 mA or less; 24 V DC  10%, 24 mA or less (Output current limit: 40 mA DC or less)

Auxiliary output signal

Output signal: Transistor contact (Open collector); Output contact capacity: 30 VDC, 30 mA or less
Signal ground is shared with the system.

Current consumption

400 mA or less (5.0 V DC)

Signal isolation
How installed

Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
Installed in the I/O Module Nest.

How connected

Connected to the terminal of the I/O Module Nest with M4 screws.

How input signal


sare specified

Specify input signals and range by software setting.


T08E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

11

<<Contents>> <<Index>>
Current/Voltage Output Module
This module outputs 4 to 20 mA DC and 0 to 10 V DC.
Item

Specifications

Model

AAM51

Output signal
Output resistance
Allowable load
resistance
Output range

0 to 10 V DC

4 to 20mA DC

1  or less

500 k or more

10 k or more

0 to 750 

-0.3 to 10.3 V DC

1.0 to 21.5 mA DC

Output voltage limit


Output current limit

Output open detection

Voltage output: 12 mV

Accuracy
Effect of ambient
temperature change

Data update period


Current consumption

0.65 mA or less
Current output: 48 A

For 10 C change: Voltage output: 4 mV + 0.15 % of specified value


Current output: 32 A

Effect of load resistance 2 k load connection: 4 mV


change

Signal isolation

25.5 V DC or less

60 mA DC or less

0 to 750  load resistance change: 16 A

20 ms; Step response is 150 ms


300 mA or less (5.0 V DC)
Output signals are isolated between systems. Withstanding voltage: 1500 V AC/min

How installed

Installed in the I/O Module Nest.

How connected

Connected to the terminas of the I/O Module Nest with M4 screws.

How output signals


are specified

Specify output signals and range by software setting.


T09E.EPS

Current Output Module


This module outputs 4 to 20 mA DC.
Item

Specifications

Model

AAM50

Output signal
Output resistance
Allowable load resistance

4 to 20mA DC
500 k or more
0 to 750 

Output range

1.0 to 21.5 mA DC

Output voltage limit

25.5 V DC or less

Output open detection


Accuracy
Effect of ambient temperature change
Effect of load resistance change
Data update period
Current consumption
Signal isolation
How installed
How connected
How output signals are specified

0.65 mA or less
Current output: 48 A

For 10C change: Current output  32 A


For 0 to 750  load resistance change:  16 A
20 ms; Step response is 100 ms
250 mA or less (5.0 V DC)
Output signals are isolated between systems.
Withstanding voltage: 1500 V AC/min
Installed in the I/O Module Nest.
Connected to the terminals of the I/O ModuleNest with M4 screws.
Specify output signals and range by software setting.
T10E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

12

<<Contents>> <<Index>>
Multipoint Control Analog I/O Module
This module controls 8-point analog loop. It can be made redundant.

AMC80

F12E.EPS

Item

Specifications

Model
No. of input points

Input

AMC80
8

Input signal

1 to 5 V DC (differential, non-isolated inputs)

Input resistance

500 k or more (at power-up)/100 k or more (at power-down)

Allowable input voltage

-30 to 30 V DC

Accuracy

64 mV

Effect of ambient temperature change For 10 C change: 8 mV


Input data update period

45 mS

Step response time

300 mS

Input signal isolation

No isolation between system and field, and between channels

Allowable common mode voltage

5 V or less

No. of output points

Output signal

4 to 20 mA DC

Output resistance

500 k or more

Allowable load resistance

0 to 750 

Output range

1.25 to 22 mA

Output current

25.5 V DC or less

Output open detection

0.65 mA or less

Output accuracy

648A

Output

Effect of ambient temperature change For 10 C change: 32 A

Common

Output data update period

45 mS

Output step response

100mS

Output signal isolation

No isolation between system and field, and between channels

Current consumption

2A Max. (5 V DC)

How installed

Installed in the AMN34 Nest for Multipoint Control Analog I/O


Modules

Wiring

KS1 cable
T11E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

13

<<Contents>> <<Index>>

Relay I/O Modules


These modules receive or output digital signals from/to the field through relays. They have 16 relay points.

Relay
I/O Module

F05E.EPS

Item

Specifications

Model

ADM15R

Input rating

24 V DC 8.3 mA10 % Induction load

Input format

Non-voltage contact (between terminals A-B)


Terminal B is common with system common.

(*1)

Relay operation time

10 msec or less

(*2)

Relay return time

10 msec or less

(*2)

Power consumption
How installed
How connected

2 A or less (5.0 V DC)


Installed in the relay I/O module nest.
Connected to the terminal of the relay I/O module nest with M4 screws.
T12E.EPS

*1:
*2:

24 V DC is supplied from the built-in power supply.


Operation and return time of the relay; must add communication process time between supervisory computer and module.
Item

Specifications

Model

ADM55R

Suffix codes

-1: Reset action during on-line maintenance


-2: Hold action during on-line maintenance

Output rating

250 V AC 1.5 A or less


125 V DC 0.1 A or less
24 V DC 1.5 A or less

Output format

A contact between terminals AC


B contact between terminals BC

Relay operation time


Relay return time
Power consumption
How installed
How connected

(*2)

10 msec or less

(*1)

10 msec or less

(*1)

2 A or less (5.0 V DC)


Installed in the relay I/O module nest.
Connected to the terminal of the relay I/O module nest with M4 screws.
T13E.EPS

*1:
*2:

Operation and return time of the relay; must add communication process time between supervisory computer and module.
Output hold action of ADM55R-2 is effective in status output mode.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

14

<<Contents>> <<Index>>

Multiplexer Module
These modules receive up to 16 points from DC voltage, mV, thermocouple and RTD. Measuring inputs can be specified per
point.
AMM32T
AMM32TJ

AMM12T
AMM22M
AMM22T
AMM22TJ

AMM12C
AMM22C
AMM32C
AMM32CJ
AMM25C

Terminal Type
Multiplexer Module

Connector Type
Multiplexer Module

Item

F06E.EPS

Specifications

Model

AMM12T
AMM12C

AMM22M
AMM22C

AMM22T
AMM22TJ (*2)

AMM32T
AMM32TJ (*3)
AMM32C
AMM32CJ (*3)

Input

16

16

16

16

AMM25C

15

Input signal

DC voltage

mV

RTD
Thermocouple IEC
Standard Type K, T, J, E, JIS Pt100 or JIS Pt100
B, R,
(DIN Pt 100)
3-wire type
IEC Standard Type N

Termocouple IEC
Standard Type K, T, J,
E, B, R, S
IEC Standard Type N,
mV.
Channel 16 is used for
RJC port.

Input range

-10 to 10 V DC

-100 to 100 mV DC

-100 to 100 mV DC

-100 to 100 mV

Allowable input voltage

-30 to 30 V DC

-0.5 to 4.0 V DC

-0.5 to 4.0 V DC

Input resistance
Signal isolation
Data update period
Accuracy
Disconnection
detection time
Disconnection
detection current
Allowable signal source
resistance
Allowable wiring resistance

1 M

How installed
How connected
Effect of
ambient temperature change
Current consumption

-0.5 to 4.0 V DC
1 M

Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
1s
4 mV

40 V
-

10 sec. Max.

0.1 

1 k Max.

40 V

0.15 

1 k Max.

150  max. (per wire)

-10 to 70

1 C (*1)

200 V AC

40 V

Burnout detection
Input parallel connection

RJC input
RJC accuracy
Allowable common mode
voltage
Measuring current

-200 to 600C

15 V 10 %

200 V AC

1 mA

Select from UP/DOWN/OFF.

Permitted (burnout OFF)

Permitted (burnout
OFF)

Not permitted

Installed in the I/O module nest.


Connected to the terminal of the I/O module with M4 screws. Use a KS1, KS2 or KS3 cable for AMM12C, a KS1 cable
for AMM22C/AMM25C, and a KS8 cable for AMM32C.
For 10 C change : DC voltage: 8 mV or less
mV input: 80 V or less
For 10 C change :
Thermocouple input: 80 V or less
RTD Input: 0.3  or less
80 V or less
500 mA or less (5.0 V DC)

How input signals are specified Specify input signals and range by software setting.

*1:

If measured temperature is lower than 0 C, multiply the above value by the following coefficient (K):

K=
*2:
*3:

T14E.EPS

Thermoelectric power per degree at 0 C


Thermoelectric power per degree at measured temperature

F04E.EPS

AMM22TJ conforms to IEC584-1995.


AMM32TJ/AMM32CJ conforms to IEC751-1995.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

15

<<Contents>> <<Index>>

2-Wire Transmitter Input/Output Multiplexer Modules


AMM42T receives up to sixteen 4-20 mA DC signals from a 2-wire transmitter. AMM52T outputs up to sixteen 4-20 mA DC
signals to a 2-wire transmitter.
Input/output signals are not isolated between system and field, and between channels.
AMM 42T
AMM 52T

Do not
use

F07E.EPS

Item

Specifications

Model
Input signal

AMM42T

AMM52T

4 to 20 mA DC

Output signal

4 to 20 mA DC

Allowable input voltage 40 mA or less


Transmitter power
supply

23.5 to 24.5 V DC (output power limit: 60 mA or less)

Input resistance

250 (can be changed to 70  when connected to barrier)

Output resistance

500 k or over

Allowable load
resistance

0 to 750 

Output range

1.0 to 21.5 mA DC

Output voltage limit

Signal isolation
Data update period
Accuracy
Current consumption
How installed
How connected
Effect of ambient
temperature change

25.5 V DC or less

No isolation between system and field, and between


channels

No isolation between system and field, and between


channels

1 second

1 second

16 A

48 A

4 A Max. (5.0 V DC)

4 A Max. (5.0 V DC)

Installed in the I/O module nest.

Installed in the I/O module nest.

Connected to the terminals of the I/O module nest with M4


screws.

Connected to the terminals of the I/O module nest


with M4 screws.

For 10 C change: 32 A

For 10 C change: 32 A


T15E.EPS

Note: These modules can be combined with MTL Barrier 787S by setting input resistance to 70 . In this case, wiring resistance must
be 10  or less and the minimum operating voltage of 2-wire transmitter must be 12 V DC or less.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

16

<<Contents>> <<Index>>

Digital I/O Modules


These modules receive and output 16 or 32 contact I/O points.

Digital I/O module


(connector type)

Digital I/O module


(terminal type)

F08E.EPS

Item

Specifications

Type
Model
No. of I/O points
Input signal

Terminal type

Connector type

ADM11T

ADM12T

ADM11C

ADM12C

16 points

32 points

16 points

32 points

Contact input: OFF signal 100 k or more; ON signal 200  or less


Voltage input: OFF signal 4.5 to 25 V DC; ON signal 1 V DC, 200  or less

Contact rating

5 V DC, 20 mA min. (external contact standard)

Pulse width

40 ms min.

Pulse period

10 Hz max.

Power consumption

600 mA max. (5.0 V DC)

Function
Status input
Push-button input

Detection function of ON/OFF status


Function which counts edges of push-button pulses

Signal isolation

Common minus side


every 16 points

Each point

How installed

Installed in the I/O module nest

How connected

Connected to the I/O module nest terminal


with M4 screws

Terminal board

Each point

Common minus side


every 16 points

KS2 or KS3 cable

KS9 or KS10 cable

TE16

TE32
T16E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

17

<<Contents>> <<Index>>
Item

Specifications

Type

Terminal type

Model
Suffix codes

ADM51T

ADM51C

ADM52C

16 points

32 points

-1 :Reset action during on-line maintenance


-2 :Hold action during on-line maintenance (*1)

No. of I/O points


Output signal

Connector type
ADM52T

16 points

32 points

Transistor contact

Contact rating

Resistive load/Inductive load: 30 V DC, 100 mA max.

Pulse width

0.1 to 7200 s: Setting at time of pulse type, pulse width mode

Pulse width resolution

20 ms

Power consumption

600 mA max. (5.0 V DC)

Function
Status output
Pulse type output
Pulse width output
Time proportional ON/OFF

Output function of ON/OFF status


Pulse type output function of status
One-shot pluse width output function
Time proportional ON/OFF

Signal isolation

Common minus side


every 16 points

Each point

Common minus side


every 16 points

Each point

How installed

Installed in the I/O module nest

How connected

Connected to the I/O module nest terminal


with M4 screws

CPU halt status /


Communication bus
termination status

Detection time and output mode can be set when selecting the abnormal detection mode.

Terminal board

KS2 or KS3 cable

KS9 or KS10 cable

TE16

TE32
T17E.EPS

*1:

Output hold action of ADM51T-2, ADM52T-2, ADM51C-2, ADM52C-2, is effective in status output mode.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

18

<<Contents>> <<Index>>

Communication Module
With subsystem communication packages, data is sent/received to/from subsystems such as PLCs via serial communications.
ACM11

F09E.EPS

Item

Specifications

Model
Interface

ACM11

ACM12

RS-232C (1 port)

RS-422 or RS-485 (1 port)

How connected

Point-to-point

Point-to-point, Multipoint

How communicates

Half-duplex

How synchronizes

Start-stop synchronization

Communication speed

1200/2400/4800/9600/19200 bps

Transmission code

ASCII/binary

Character length

7/8 bit

Stop bit length

1/2 bit

Parity check

None/odd/even (Note: No parity cannot be specified at 19200 bps.)

When a signal is
received after data
transmission

1 ms (standard); immediately (in special case)

1 ms

Transmission distance

Max. 15 m

Max. 1200 m (Total length)

How installed

Installed in the Communication Module Nest


(These modules cannot be combined with ACF11. ACM11 can be combined with ACM12.)

Wiring

KB3, AKB141, AKB143 (RS-232C modem)


KB4, AKB142, AKB144 (RS-232C null-modem)
cable

3 pairs shielded cable


AKB161 (Cable to connect ACM12 and FA500; Max.
100 m)

How connected

D-sub 25 pin (female)

Connected to the terminal (6 poles) with M4 screws.

Current consumption

1 A (5.0 V DC)
T18E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

19

<<Contents>> <<Index>>

Communication Card
With user programs, subsystems such as PLCs are connected to the Field Control Station via serial communications.
ACM21
RDY
RCV
SND

CN1

F10E.EPS

Item

Specifications

Model
Interface

ACM21

ACM22

RS-232C (1 port)

RS-422 or RS-485 (1 port)

How connected

Point-to-point

Point-to-point, Multipoint

How communicates

Half-duplex

How synchronizes

Start-stop synchronization

Communication speed

1200/2400/4800/9600/19200/38400 bps

Transmission code

ASCII/binary

Character length

7/8 bit

Stop bit length

1/2 bit

Parity check

None/odd/even

When a signal is
received after data
transmission

1 ms (usually)

1 ms

Transmission distance

Max. 15 m

Max. 1200 m (Total length)

How installed

Installed in the Communication Card Nest (Can be combined with ACM71)

Wiring

KB3, AKB141, AKB143 (RS-232C modem)


KB4, AKB142, AKB144 (RS-232C null-modem)
cable

3 pairs shielded cable


AKB161 (Cable to connect ACM12 and FA500; Max.
100 m)

How connected

D-sub 25 pin (female)

Connected to the terminal (6 poles) with M4 screws.

Current consumption

1 A (5.0 V DC)
T19E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

20

<<Contents>> <<Index>>

Ethernet Communication Module (for PFCS/PFCD)


Subsystems are connected to the Field Control Station via Ethernet communications.
ACM71
RDY
RCV
SND

CN1

F14E.EPS

Item

Specifications

Model
Physical Layer Interface
How connected
Connector
Communication speed
Transmission route
Transmission distance
No. of ports
Media access control
Display spec
Current consumption
Weight
How installed

ACM71
IEEE802.3
10BASE-T
Point-to-point. Connected to hub.
RJ45
10 Mbps
100 V twisted-pair cable (not shielded)
100 m per segment
One port
CSMA/CD
SND: Displays that data is sent to a network.
RCV: Displays that data is received from a network.
RDY: Displays that hardware is normal.
1.2 A or less (5.0V DC)
0.3 kg
Installed in the Communication Module Nest. The module can be combined
with ACM21, ACM22
T22E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

21

<<Contents>> <<Index>>

Fieldbus Communication Module


The Fieldbus Communication Module sends/receives data to/from fieldbus-connected field devices.
ACF11

F13E.EPS

Item

Specifications

Model
Interface
Communication speed
Function

ACF11
FOUNDATION Fieldbus (Low speed voltage mode)
31.25 kbps
LAS function
Network power supply function

Field Device Connection

CS 3000: See Foundation Fieldbus Communication Package (for ACF11)


(GS 33Q03L50-31E).
CS 1000: See Foundation Fieldbus Communication Package (for ACF11)
(GS 33S03L50-31E).

Network power supply

Output voltage: 18 to 20 V DC
Continuous output current: 80 mA or less
Transient output current: 100 mA or less (20 msec or less)
Output ON/OFF: Specify in the card (When using external power supply, the
output is OFF.

Current consumption

1.4 A or less (5.0 V DC)

Signal isolation

Signals are isolated between field and system. Withstanding voltage: 1500 V
AC/min.

Bus connection

Connect two terminals with M4 screws. Terminal: detachable


Compliant terminator: YCB138

How installed

Installed in the Communication ModuleNest. The module cannot be


combined with ACM11/ACM12 Communication Module.
T20E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

22

<<Contents>> <<Index>>

ACP71 PROFIBUS Communication Module


The ACP71 PROFIBUS Communication Module sends/receives data to/from I/O devices which support PROFIBUS-DP.
ACP71

F15E.EPS

Item

Specifications

Model

ACP71

Transmission spec

EIA-RS485-compliant

Communication speed

9600 bps to 12 Mbps

Signal isolation
Connector
How connected
Transmission route
Transmission distance

Yes
D-Sub 9 pin (Female)
T connector (Detachable on line.)
Shielded twisted-pair cable (*1)
Max. 1.2 km per segment (when communication speed is 9600 bps)

No. of ports

One port

Display spec

RDY: Displays that ACP71 is ready.


MRDY: Displays that communication modules are ready.
MRUN: Displays that data is now sent/received.
MERR: Displays that an error is detected on the media.

Configuration port
Current consumption

Connector: D-Sub 9 pin (male)


Interface: RS-232C (not isolated)
1.2 A or less (5.0V DC)
T23E.EPS

*1:

Refer to PROFIBUS Specification EN50170 Volume 2.

NI-compliant I/O Modules and Their Parameters


I/O modules are compliant with Non-Incendive (NI) rule of CSA Standards. This means that I/O modules can be installed in
Class I, Division 2 hazardous area by installing ANS50/AND50 Node Unit with I/O modules in a cabinet approved by CSA or
local explosion-proof auditor; and directly connected with NI-compliant local devices installed in hazardous area. I/O
modules installed in a device other than ANS50/AND50 Node Unit cannot be installed in hazardous area, but if you install the
device in non-hazardous area, I/O modules can be directly connected with NI-compliant local devices.
For the detailed information of compliance, see System Overview (GS 33Q01B10-31E, GS 33S01B10-31E).
I/O Modules and Parameters
For I/O modules, its parameters, and connectivity, refer to Installation Guidance (TI 33Q01J10-01E or TI 33S01J10-01E).

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

23

<<Contents>> <<Index>>

EXTERNAL DIMENSIONS OF THE I/O MODULE NEST


AMN11, AMN12, AMN21, AMN31, AMN32, AMN33, AMN34, AMN51
Unit:mm
(inch)

M4 screw

236 248
(9.3) (9.8)

113(4.4)

100(3.9)

(0.2)

125(4.9)

30
(1.2)

130(5.1)
F11E.EPS

AMN52
233.3(9.19)
19.3
(0.76)

Unit: mm
(approx. inch)

9.8
(0.39)

145(5.71)

222.3(8.75)

11
(0.43)

254
(10)
236
(9.29)

9
(0.35)

Weight: approx. 2.5 kg (5.51lb)


Normal Allowable Deviation =

(Value of JIS B 0401-1986 Tolerant Class IT 18)


2
F17E.EPS

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation

GS 33Y06K40-31E

Jun.1,2003-00

24

<<Contents>> <<Index>>

ORDERING INSTRUCTION
Specify model and suffix codes.

TRADEMARK
Foundation fieldbus is a registered trademark of Fieldbus Foundation.
CENTUM is a registered trademark of Yokogawa Electric Corporation.
Other product and company names appearing in this document are trademarks or registered trademarks of their respective
holders.

All Rights Reserved. Copyright 2001, Yokogawa Electric Corporation


Subject to change without notice.

GS 33Y06K40-31E

Jun.1,2003-00