Microprocessor-based Integrative
Automation Control System

Factory Test Report

(Project Name): TA THANG HYDROPOWER PROJECT


(Item Number): HN/QEH.21-1102020-11

(Date) :

2012-5-15

Hunan Huazi Science&Technology Co., Ltd.

Version2010

/ Released/Revised On 201006

Revised State1

DOC.NOHN/QEH.-0819

Test equipment

According to the test requirements of this project, the instruments meet the test specifications and
within the validity period, type and duration see the certificate content.
Factory test instrumentation required to as follows:
AC and DC voltmeterT19/1-VUT56 MULTMETER
MeggerZC25-4
Resistance box
PW31E PW31E based relay control instrument
WOS02 WOS02 type dual analog circuit breaker tester
CS2674A CS2674APressure tester

Version2010

/ Released/Revised On 201006

Revised State1

DOC.NOHN/QEH.-0819

Contents

Name of panel: G1 Protection Cabinet A ............................................................................................................................... 1


I. Integrate part .............................................................................................................................................. 1
II. Protection, measurement & control part .................................................................................. 1
. Performance test ...................................................................................................................................... 5
1. Test data recording of protection measurement & control unit ....................... 5
2. Protection unit action data and antion type record .............................. 5
1# B ............................................................................................................................................... 13
Name of panel: G1 Protection Cabinet B ............................................................................................................................. 13
I. Integrate part ............................................................................................................................................ 13
II. Protection, measurement & control part ................................................................................ 13
III. Performance test ..................................................................................................................................... 16
1. Test data recording of protection measurement & control unit ..................... 16
2. Protection unit action data and antion type record ............................ 16
2# A .......................................................................................................................................... 20
Name of panel: G2 Protection Cabinet A ............................................................................................................................. 20
I. Integrate part ............................................................................................................................................ 20
II. Protection, measurement & control part ................................................................................ 20
. Performance test .................................................................................................................................... 23
1. Test data recording of protection measurement & control unit ..................... 23
2. Protection unit action data and antion type record ............................ 24
2# B ............................................................................................................................................... 31
Name of panel: G2 Protection Cabinet B ............................................................................................................................. 31
I. Integrate part ............................................................................................................................................ 31
II. Protection, measurement & control part ................................................................................ 31
III. Performance test ..................................................................................................................................... 34
1. Test data recording of protection measurement & control unit ..................... 34
2. Protection unit action data and antion type record ............................ 34
1# A ........................................................................................................................................... 38
Name of panel: T1 Main Transfomer Protection Cabinet A ................................................................................................ 38
I. Integrate part ............................................................................................................................................ 38
II. Protection, measurement & control part ................................................................................ 38
III. Performance test ..................................................................................................................................... 41
1. Test data recording of protection measurement & control unit ..................... 41
2. Protection unit action data and antion type record ............................ 41
1# B ...................................................................................................................................... 50
Name of panel: T1 Main Transfomer Protection Cabinet B ................................................................................................ 50
I. Integrate part ............................................................................................................................................ 50
II. Protection, measurement & control part ................................................................................ 50
III. Performance test ..................................................................................................................................... 53
1. Test data recording of protection measurement & control unit ..................... 53
2. Protection unit action data and antion type record ............................ 55
2# A ........................................................................................................................................... 60

DOC.NOHN/QEH.-0819

Name of panel: T2 Main Transfomer Protection Cabinet A ................................................................................................ 60


I. Integrate part ............................................................................................................................................ 60
II. Protection, measurement & control part ................................................................................ 60
III. Performance test ..................................................................................................................................... 63
1. Test data recording of protection measurement & control unit ..................... 63
2. Protection unit action data and antion type record ............................ 63
2# B ...................................................................................................................................... 72
Name of panel: T2 Main Transfomer Protection Cabinet B ................................................................................................ 72
I. Integrate part ............................................................................................................................................ 72
II. Protection, measurement & control part ................................................................................ 72
III. Performance test ..................................................................................................................................... 75
1. Test data recording of protection measurement & control unit ..................... 75
2. Protection unit action data and antion type record ............................ 77
110kV ........................................................................................................................................... 82
Name of panel: 110kV Busbar Protection Cabinet .............................................................................................................. 82
I. Integrate part ............................................................................................................................................ 82
II. Protection, measurement & control part ................................................................................ 83
III. Performance test ..................................................................................................................................... 86
110kV ....................................................................................................................... 88
Name of panel: 110kV Busbar Connect protect Cabinet ..................................................................................................... 88
I. Integrate part ............................................................................................................................................ 88
II. Protection, measurement & control part ................................................................................ 89
III. Performance test ..................................................................................................................................... 92
1............................................................................................................................. 92
Test data recording of protection measurement & control unit ......................................................................... 92
2................................................................................................................. 92
Protection unit action data and antion type record ............................................................................................ 92
110kV L1 ............................................................................................................................... 97
Name of panel: 110kV L1 Line Differential Protection Cabinet .......................................................................................... 97
I. Integrate part ............................................................................................................................................ 97
II. Protection, measurement & control part ................................................................................ 98
III. Performance test ................................................................................................................................... 100
1........................................................................................................................... 100
Test data recording of protection measurement & control unit ....................................................................... 100
2............................................................................................................... 101
Protection unit action data and antion type record .......................................................................................... 101
110kV L2 ............................................................................................................................. 105
Name of panel: 110kV L1 Line Differential Protection Cabinet ........................................................................................ 105
I. Integrate part .......................................................................................................................................... 105
II. Protection, measurement & control part .............................................................................. 106
III. Performance test ................................................................................................................................... 108
1........................................................................................................................... 108
Test data recording of protection measurement & control unit ....................................................................... 108
2............................................................................................................... 110

Version2010

/ Released/Revised On 201006

Revised State1

II

DOC.NOHN/QEH.-0819

Protection unit action data and antion type record .......................................................................................... 110
110kV L1 ............................................................................................................................. 114
Name of panel: 110kV L1 Line Distance Protection Cabinet ............................................................................................. 114
I. Integrate part .......................................................................................................................................... 114
II. Protection, measurement & control part .............................................................................. 115
III. Performance test ................................................................................................................................... 117
1........................................................................................................................... 117
Test data recording of protection measurement & control unit ....................................................................... 117
2............................................................................................................... 118
Protection unit action data and antion type record .......................................................................................... 118
110kV L2 ............................................................................................................................. 122
Name of panel: 110kV L1 Line Distance Protection Cabinet ............................................................................................. 122
I. Integrate part .......................................................................................................................................... 122
II. Protection, measurement & control part .............................................................................. 123
III. Performance test ................................................................................................................................... 125
1........................................................................................................................... 125
Test data recording of protection measurement & control unit ....................................................................... 125
2............................................................................................................... 126
Protection unit action data and antion type record .......................................................................................... 126
1# LCULCU1A/B .......................................................................................................................... 130
Name of panel: Unit 1 LCULCU1Cabinet A/B ............................................................................................................. 130
I. Integrate part .......................................................................................................................................... 130
II. Automatic control section .............................................................................................................. 131
2# LCULCU2A/B .......................................................................................................................... 137
Name of panel: Unit 2 LCULCU2Cabinet A/B ............................................................................................................. 137
I. Integrate part .......................................................................................................................................... 137
II. Automatic control section .............................................................................................................. 138
LCULCU4A/B ............................................................................................................................. 144
Name of Panel: Auxiliary LCULCU4Cabinet A/B ........................................................................................................ 144
I. Integrate part .......................................................................................................................................... 144
II. Automatic control part ................................................................................................................... 145
: LCULCU3A/B ............................................................................................................................ 149
Name of Panel: Switching station LCU (LCU3) Cabinet A/B .............................................................................................. 149
I. Integrate part .......................................................................................................................................... 149
II. Automatic control section .............................................................................................................. 149
A ................................................................................................................................................ 155
Name of Panel: Energy Meter Cabinet A ........................................................................................................................... 155
I. Integrate part .......................................................................................................................................... 155
II. Function part .......................................................................................................................................... 156
B ................................................................................................................................................ 159
Name of panel: Energy Meter Cabinet B ........................................................................................................................... 159
I. Integrate part .......................................................................................................................................... 159
II. Function part .......................................................................................................................................... 160
............................................................................................................................................. 162

Version2010

/ Released/Revised On 201006

Revised State1

III

DOC.NOHN/QEH.-0819

Name of Panel: DCS Network Cabinet ............................................................................................................................... 162


I. Integrate part .......................................................................................................................................... 162
II. Function part .......................................................................................................................................... 163
MTC ............................................................................................................................................................ 164
MTC Background Monitoring System ................................................................................................................................ 164
..................................................................................................................................................................... 164
Scope of examination ................................................................................................................................................. 164

Version2010

/ Released/Revised On 201006

Revised State1

IV

DOC.NOHN/QEH.-0819

1# A
Name of panel: G1 Protection Cabinet A
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1 See technical protocols 4.1

No.

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

DOC.NOHN/QEH.-0819

220V
110V220V
110V
Check working power supply of all protection unit

Result

Result

qualified

qualified

DC220V
110VAC220V
110V

7UT612

Device type chenking: the type is


7UT612
drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

qualified

qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

qualified

qualified

I
Check if software edition number in LCD display is conform to the drawing

qualified

qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

.
Detect valuing modification and conservation normal.

qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

qualified

Detect if each outlet action test is normal.

qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

Version2010

respectively, conform to

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
1 Input rated current5A or 1A
in current sampling loop. Circumscribed
device measured value after ratio conversion is compared with the
displayed value, which is in the requirements of range (error no more than
5%). AC analog quantity error is lesser than 10% at 0.2In and 0.1In
2 Input rated voltage 110V
380V in voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
3 Check displayed angle.Access three-phase current and three-phase voltage
in input terminal of protective device three-phase current and three-phase
voltage. They are rated value.The phase difference of each phase voltage
and current is 0.The error between protective device measured value and
circumscribed measuring instrument value not exceed 3Change phase
angle, to 30.45.60.90,and measure phase angle respectively,error within
3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

15

;
1.

Version2010

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

DOC.NOHN/QEH.-0819

2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Version2010

/ Released/Revised On 201006

qualified

Revised State1

DOC.NOHN/QEH.-0819

. Performance test
4.2See technical protocols 4.2
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation

1. Test data recording of protection measurement &


control unit

Unit name (type)

Protection unit
parameter

Debugging
Result

Measuring data recording


Ia1.000A

Ic0.999A

Standard measure

Ua63.50V

Inpspection
Result

Ib0.999A
Ub63.49V

qualified

qualified

qualified

qualified

qualified

qualified

Uc63.51V

Gen.reservel
protection device
7UM622 (DC220V)

Ia2500A
TV

11

Ib2500A

kV/110V Ic2500A

TA 2500 /1
Cos=0.865

Ua6.35kV Ub6.35kV
Uc6.35kV

TVratio 11kV/110V

Uab11kV Ubc11kV

TAratio 2500 /1

Uca11kV

Cos=0.865

P(39876)kW

Q(25800)kVar

Cos

0.86

Gen.differential
protection device
7UT612 (DC220V)

Ia11.001A Ib10.999A

Ic11.000

Standard measure

Ia20.999A Ib21.001A
Ic20.999A

2. Protection unit action data and antion type


record

Protection type

Version2010

Setting
value

Action
value

Action

/ Released/Revised On 201006


Debugging Inpspection
Result
Result

Revised State1

DOC.NOHN/QEH.-0819

Low fixed value

V/F(1.31 ),

segment

t(17.2)s

V/F(1.1 ),t(10)s

24

Gen.over-excitation
protection (24)

High fixed value

V/F(1.41 ),

segment

t(1 )s

V/F( 1.4 ),t( 1 )s

26
Gen.stator winding
inverse OCP (26)

32
Gen.inverse power
protection (32)

Version2010

I1A, t (0.5 )s

P%(-1.84 ), t0s

I2A, t(6.72 )s

P%(-0.186 ),
t0s


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified

send accident signal


stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

/ Released/Revised On 201006

Revised State1

DOC.NOHN/QEH.-0819

Ua=63.5V

start G2 50BF

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

1.06A
I
, t(0.5s)


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified

I 1.1A, t(0.5 )s

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

send accident signal


stop

qualified

qualified

angel(0)
Ub=63.5V
angel(-120)

40
Gen.
loss-of-excitation
protection (40)

Uc=63.5V
Susceptance(0.41)

Angel(120)

Angle(80)

Ia(0.48)A

t(3)s

Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(3)s

50/51/67E
Excitation-transform
er
over-load
protection(50/51/67
E)

51E

Excitation-transform
er OCP (51E)

I1.05A, t (0.5s )

I1A, t (0.5 )s

t050BF
Gen.CB malfunction
protection (50BF)t0

t ( 0.5s )

Version2010

/ Released/Revised On 201006

t(0.5s )

Revised State1

DOC.NOHN/QEH.-0819

Stepout deexcitation

Stepout
send anticipating signal
Trip MT high voltage side
CB

t150BF
Gen.CB malfunction
protection (50BF)t1

59
Stator
winding
over-voltage
protection (59)

100%
I 59N
100% stator winding
one point earth
protection
of
Gen.59N

Version2010

t ( 0.5s )

U 130V , t (3s )

U020v , t ( 0.3s )

t ( 0.5s )

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

Trip MT high voltage


side CB

U138V, t(3s )

start G2 50BF

send accident signal


stop

Stepout deexcitation

Stepout
send anticipating signal

U020.1V,
t( 0.3s )

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

DOC.NOHN/QEH.-0819

I
64R
Excitation loop one
point
earth
protection (64R)

78
Gen.loss-of-sync
protection (78)

Gen.frequency
protection

87G Gen.
longitudinal
differential
protection (87G)

Version2010

Impedance

Impedance

10

10

t( 5 )

t(5)


Stepout deexcitation
send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal


Impedance
Impedance
Za(4.5),Zb(12),
Za(4.5),Zb(12),

Zc(3.6)
Zc(3.6)


Angle90 Angle90
Number

start G2 50BF
Number of
of power swing6

send accident signal


Cycle time
power swing6 stop
1s
Trip time5s Stepout
deexcitation

Stepout
send anticipating signal

F 48Hz, t (1s )

Side1

I 3.3336
A,
Slide2I 0 A,
t(0

)S

F47Hz, t (1s )

Side1I3.4A
Slide2I0A,
t ( 15 )ms

qualified

qualified


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified

start G2 50BF

send accident signal

stop

Stepout deexcitation

qualified

qualified

/ Released/Revised On 201006

Revised State1

DOC.NOHN/QEH.-0819

Stepout
send anticipating signal

Hydraulic

Hydraulic

machinery

machinery

protection

protection

Shaft current

Shaft current

protection t0

protection t0

38
Non-electricity
protection (38)

Version2010

Shaft current

Shaft current

protection t1

protection t1

Fire protection

Fire protection

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal

send accident signal


stop
Stepout deexcitation
Stepout
send anticipating signal

qualified

qualified

qualified

qualified

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

/ Released/Revised On 201006

Revised State1

10

DOC.NOHN/QEH.-0819

Temperature

Temperature

protection 1

protection 1

Temperature

Temperature

protection 2

protection 2


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

Break check of
voltage loop


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

Break check of
voltage loop


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

CB
three-phase
operation box

Version2010

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

11

DOC.NOHN/QEH.-0819

manual closing normal

manual Trip normal

protection action Trip


normal

malfunction protection
action normal

blocking protection
action normal

Regulators
Debugging time 2012-3-20

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

12

DOC.NOHN/QEH.-0819

1# B
Name of panel: G1 Protection Cabinet B
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1See technical protocols 4.1

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

13

DOC.NOHN/QEH.-0819

220V
110V220V
110V
Check working power supply of all protection unit

Result

Result

qualified

qualified

qualified

qualified

DC220V
110VAC220V
110V

7UM612

Device type chenking: the type is 7UM612


drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

qualified

qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

qualified

qualified

I
Check if software edition number in LCD display is conform to the drawing

qualified

qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

qualified

qualified

.
Detect valuing modification and conservation normal.

qualified

qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

qualified

Detect if each outlet action test is normal.

qualified

qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

qualified

qualified

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

qualified

qualified

Version2010

respectively, conform to

/ Released/Revised On 201006

qualified

Revised State1

14

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
4 Input rated current5A or 1A
in current sampling loop. Circumscribed
device measured value after ratio conversion is compared with the
displayed value, which is in the requirements of range (error no more than
5%). AC analog quantity error is lesser than 10% at 0.2In and 0.1In
5 Input rated voltage 110V
380V in voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
6 Check displayed angle.Access three-phase current and three-phase voltage
in input terminal of protective device three-phase current and three-phase
voltage. They are rated value.The phase difference of each phase voltage
and current is 0.The error between protective device measured value and
circumscribed measuring instrument value not exceed 3Change phase
angle, to 30.45.60.90,and measure phase angle respectively,error within
3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

qualified

qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

qualified

qualified

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

qualified

qualified

15

;
1.

qualified

Version2010

/ Released/Revised On 201006

Revised State1

15

DOC.NOHN/QEH.-0819

qualified

2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

III. Performance test


4.2See technical protocols 4.2
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation

1. Test data recording of protection measurement &


control unit

Unit name (type)

Protection unit
parameter

Measuring data recording

Debugging
Result

Inpspection
Result

qualified

qualified

qualified

qualified

Ia 0.999 A Ib 1.000A

Ic 1.001 A
Ua 63.48 V Ub 63.49
V Uc63.49 V

Gen.reservel
protection device
7UM612(DC220V)

Ia 2500 A

Ib 2500

Ua 6.34 kV Ub 6.34

kV

Ic 2500 A
TV

11kV/110V

TA 2500 /1
Cos=0.865

Uc 6.33

kV

Uab 10.98kV Ubc10.98kV


Uca10.98kV
P(41153kW)

Q(23667kVAR)

Cos

0.87

2. Protection unit action data and antion type


record

Version2010

/ Released/Revised On 201006

Revised State1

16

DOC.NOHN/QEH.-0819


Protection type



Setting
Action value
value
Ua=3.929V
Angel0
Ub=3.929V
Angel-120

Impedance
protection24

Uc=3.929V
2.9

Angel120

t( 0s )

Ia=1.35A
Angel0
Ib=1.35A
Angel-120
Ib=1.35A
Angel120

Gen.low
voltage
protection27

U 90V , t
( 1S

U80V, t( 1S )


Debugging Inpspection
Result
Result

Action

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

qualified

qualified

Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)
Susceptance(0.4

Gen.loss-of-excitatio
n protection40

1)
Angle(80)
t(0)s

Uc=63.5V
Angel(120)
Ia(0.48)A
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(0)s

Gen.winding
over-load protection

Version2010

I 1.05A , t
( 0S )

I2A, t(0s )

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

Qualified

qualified

qualified

qualified

/ Released/Revised On 201006

Revised State1

17

DOC.NOHN/QEH.-0819

49S

Take
current memory low
voltage OCP51V

Stator winding
OVP59

I
Gen.stator
winding one-point
earth
protection
59NS

Version2010


send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

U 80V ,I
1.35A, t ( 1S )

U 140v , t
(3s )

U(78V)
I(1.36A)
T(1s)

U150v, t( 3s )

3U030V, t

3U031v,

( 0.3s )

t(0.3s )

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal


shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

/ Released/Revised On 201006

qualified

qualified

Revised State1

18

DOC.NOHN/QEH.-0819

Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)

Gen.negative
sequence
overcurrent(46)

Uc=63.5V
Angel(120)
I2(0.6A),t(3s)

Ia(0.6)A
Angel(-30)
Ib=(0.6)A
Angel(90)
Ic=(0.6)A
Angel(-150)
t(3)s

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

Break check of
voltage loop


send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

Break check of
current loop


send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

Regulators
Debugging time

qualified

qualified

qualified

qualified

qualified

qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

19

DOC.NOHN/QEH.-0819

2# A
Name of panel: G2 Protection Cabinet A
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1 See technical protocols 4.1

No.

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

20

DOC.NOHN/QEH.-0819

220V
110V220V
110V
Check working power supply of all protection unit

Result

Result

qualified

qualified

qualified

qualified

DC220V
110VAC220V
110V

7UT612

Device type chenking: the type is


7UT612
drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

qualified

qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

qualified

qualified

I
Check if software edition number in LCD display is conform to the drawing

qualified

qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

qualified

qualified

.
Detect valuing modification and conservation normal.

qualified

qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

qualified

Detect if each outlet action test is normal.

qualified

qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

qualified

qualified

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

qualified

qualified

Version2010

respectively, conform to

/ Released/Revised On 201006

qualified

Revised State1

21

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
7 Input rated current5A or 1A
in current sampling loop. Circumscribed
device measured value after ratio conversion is compared with the
displayed value, which is in the requirements of range (error no more than
5%). AC analog quantity error is lesser than 10% at 0.2In and 0.1In
8 Input rated voltage 110V
380V in voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
9 Check displayed angle.Access three-phase current and three-phase voltage
in input terminal of protective device three-phase current and three-phase
voltage. They are rated value.The phase difference of each phase voltage
and current is 0.The error between protective device measured value and
circumscribed measuring instrument value not exceed 3Change phase
angle, to 30.45.60.90,and measure phase angle respectively,error within
3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

qualified

qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

qualified

qualified

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

qualified

qualified

15

;
1.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

22

DOC.NOHN/QEH.-0819

2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

. Performance test
4.2See technical protocols 4.2
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation

1. Test data recording of protection measurement &


control unit

Unit name (type)

Protection unit
parameter

Measuring data recording

Debugging
Result

Inpspection
Result

Ia1.000A Ib0.999A
Ic1.000A

Standard measure

Gen.reservel
protection device
7UM622 (DC220V)

Ua63.50V Ub63.50V
Uc63.49V
Ia2500A

TV

11

qualified

qualified

qualified

qualified

qualified

qualified

Ib2500A

kV/110V Ic2500A

TA 2500 /1
Cos=0.865
TVratio 11kV/110V
TAratio 2500 /1
Cos=0.865

Ua6.35kV Ub6.35kV
Uc6.35kV
Uab11kV Ubc11kV
Uca11kV
P(40961)kW Q(23900)kVar
Cos0.86

Gen.differential
protection device
7UT612 (DC220V)

Version2010

Ia10.999A Ib10.999A

Standard measure

Ic11.000A
Ia2 1.000A Ib20.999A
Ic20.999A

/ Released/Revised On 201006

Revised State1

23

DOC.NOHN/QEH.-0819

2. Protection unit action data and antion type


record

Protection type

Setting
value

Action
value

Low fixed value

V/F(1.31 ),

segment

t(17.2)s

V/F(1.1 ),t(10)s

24

Gen.over-excitation
protection (24)

High fixed value

V/F(1.41 ),

segment

t(1 )s

V/F( 1.4 ),t( 1 )s

26
Gen.stator winding
inverse OCP (26)

32
Gen.inverse power
protection (32)

Version2010

I1A, t (0.5 )s

P%(-1.84 ), t0s

I2A, t(6.72 )s

P%(-0.186 ), t
0s


Debugging Inpspection
Result
Result

Action


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified

send accident signal


stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

qualified

qualified

qualified

qualified

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

/ Released/Revised On 201006

Revised State1

24

DOC.NOHN/QEH.-0819

start G2 50BF

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal
Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)

40
Gen.
loss-of-excitation
protection (40)

Susceptance(0.41)
Angle(80)
t(3)s

Uc=63.5V
Angel(120)
Ia(0.48)A
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(3)s

50/51/67E
Excitation-transform
er
over-load
protection(50/51/67
E)

51E

Excitation-transform
er OCP (51E)

Version2010

I1.05A, t (0.5s )

I1A, t (0.5 )s

start G2 50BF

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal

1.06A
I
, t(0.5s)


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

I 1.1A, t(0.5 )s

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

25

DOC.NOHN/QEH.-0819

t050BF
Gen.CB malfunction
protection (50BF)t0

t150BF
Gen.CB malfunction
protection (50BF)t1

59
Stator
winding
over-voltage
protection (59)

100%
I 59N
100% stator winding
one point earth
protection
of
Gen.59N

Version2010

t ( 0.5s )

t ( 0.5s )

U 130V , t (3s )

U020v , t ( 0.3s )

t(0.5s )

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal
Trip MT high voltage side
CB

t ( 0.5s )

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

Trip MT high voltage


side CB

qualified

qualified

U138V, t(3s )

start G2 50BF

send accident signal


stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

U020.1V,
t( 0.3s )

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

Revised State1

26

DOC.NOHN/QEH.-0819

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

I
64R
Excitation loop one
point
earth
protection (64R)

78
Gen.loss-of-sync
protection (78)

Gen.frequency
protection

87G Gen.
longitudinal
differential

Version2010


Stepout deexcitation
send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified


Impedance
Impedance
Za(4.5),Zb(12),
Za(4.5),Zb(12),

Zc(3.6)
Zc(3.6)


Angle90 Angle90
Number

start G2 50BF
Number of
of power swing6

send accident signal


Cycle time
power swing6 stop
1s
Trip time5s Stepout
deexcitation

Stepout
send anticipating signal

qualified

qualified


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified

qualified

qualified

Impedance

Impedance

10

10

t( 5 )

t (5)

F 48Hz, t (1s )

Side1

I 3.3336
A,
Slide2I 0 A,
t(0

)S

F47Hz, t (1s )

Side1I3.4A
Slide2I0A,
t ( 15 )ms

/ Released/Revised On 201006

Revised State1

27

DOC.NOHN/QEH.-0819

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

protection (87G)

Hydraulic

Hydraulic

machinery

machinery

protection

protection

Shaft current

Shaft current

protection t0

protection t0

38
Non-electricity
protection (38)

Version2010

Shaft current

Shaft current

protection t1

protection t1

Fire protection

Fire protection

send accident signal


stop
Stepout deexcitation

Stepout
send anticipating signal

qualified

send accident signal


stop
Stepout deexcitation
Stepout
send anticipating signal

qualified

qualified

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

send accident signal

qualified

qualified

/ Released/Revised On 201006

qualified

Revised State1

28

DOC.NOHN/QEH.-0819

stop

Stepout deexcitation

Stepout
send anticipating signal

Temperature

Temperature

protection 1

protection 1


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

start G2 50BF

send accident signal

stop

Stepout deexcitation

Stepout
send anticipating signal

qualified

Break check of
voltage loop


send accident signal
stop
Stepout deexcitation
Stepout

send anticipating signal

qualified

qualified

Break check of
voltage loop


send accident signal
stop
Stepout deexcitation

qualified

qualified

Version2010

Temperature

Temperature

protection 2

protection 2

/ Released/Revised On 201006

qualified

Revised State1

29

DOC.NOHN/QEH.-0819

Stepout

send anticipating signal


manual closing normal
manual Trip normal
protection action Trip
normal
malfunction protection
action normal
blocking
protection
action normal

CB
three-phase
operation box

Regulators
Debugging time 2012-3-24

qualified

qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

30

DOC.NOHN/QEH.-0819

2# B
Name of panel: G2 Protection Cabinet B
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1See technical protocols 4.1

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

31

DOC.NOHN/QEH.-0819

220V
110V220V
110V
Check working power supply of all protection unit

Result

Result

qualified

qualified

qualified

qualified

DC220V
110VAC220V
110V

7UM612

Device type chenking: the type is 7UM612


drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

qualified

qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

qualified

qualified

I
Check if software edition number in LCD display is conform to the drawing

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

.
Detect valuing modification and conservation normal.

qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

qualified

Detect if each outlet action test is normal.

qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

Version2010

respectively, conform to

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

32

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
10
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
11
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
12
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

15

Version2010

qualified

qualified

qualified

qualified

qualified

qualified

/ Released/Revised On 201006

Revised State1

33

DOC.NOHN/QEH.-0819

1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

qualified

qualified

III. Performance test


4.2See technical protocols 4.2
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation

1. Test data recording of protection measurement &


control unit

Unit name (type)

Protection unit
parameter

Measuring data recording

Debugging
Result

Inpspection
Result

qualified

qualified

qualified

qualified

Ia 0.999 A Ib1.000A

Ic0.999A
Ua 63.49 V Ub 63.49 V
Uc63.50 V

Gen.reservel
protection device
7UM612(DC220V)

Ia 2500 A

Ib 2500

Ua 6.34 kV Ub 6.34

kV

Ic 2500 A
TV

11kV/110V

TA 2500 /1
Cos=0.865

Uc 6.33

kV

Uab 10.99kV Ubc10.97kV


Uca10.98kV
P(41362kW)

Q(23771kVAR)

Cos

0.87

2. Protection unit action data and antion type


record

Version2010

/ Released/Revised On 201006

Revised State1

34

DOC.NOHN/QEH.-0819


Protection type



Setting
Action value
value
Ua=3.929V
Angel0
Ub=3.929V
Angel-120

Impedance
protection24

Uc=3.929V
2.9

Angel120

t( 0s )

Ia=1.35A
Angel0
Ib=1.35A
Angel-120
Ib=1.35A
Angel120

Gen.low
voltage
protection27

U 90V , t
( 1S

U80V, t( 1S )


Debugging Inpspection
Result
Result

Action

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

qualified

qualified

Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)
Susceptance(0.4

Gen.loss-of-excitatio
n protection40

1)
Angle(80)
t(0)s

Uc=63.5V
Angel(120)
Ia(0.48)A
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(0)s

Gen.winding
over-load protection

Version2010

I 1.05A , t
( 0S )

I2A, t(0s )

/ Released/Revised On 201006

Revised State1

35

DOC.NOHN/QEH.-0819

49S

Take
current memory low
voltage OCP51V

Stator winding
OVP59

I
Gen.stator
winding one-point
earth
protection
59NS

Version2010


send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

U 80V ,I
1.35A, t ( 1S )

U(78V)
I(1.36A)
T(1s)

U 140v , t

U150v ,

(3s )

t( 3s )

3U030V, t

3U031v,

( 0.3s )

t(0.3s )

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal


shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

/ Released/Revised On 201006

Revised State1

36

DOC.NOHN/QEH.-0819

Ua=63.5V

start G2 50BF

send accident signal

shut down

Stepout deexcitation

Stepout
send anticipating signal

qualified

qualified

Break check of
voltage loop


send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

qualified

qualified

Break check of
current loop


send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

qualified

qualified

angel(0)
Ub=63.5V
angel(-120)

Gen.negative
sequence
overcurrent(46)

Uc=63.5V
Angel(120)
I2(0.6A),t(3s)

Ia(0.6)A
Angel(-30)
Ib=(0.6)A
Angel(90)
Ic=(0.6)A
Angel(-150)
t(3)s

Regulators
Debugging time 2012-3-27

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

37

DOC.NOHN/QEH.-0819

1# A
Name of panel: T1 Main Transfomer Protection Cabinet A
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1See technical protocols 4.1

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

38

DOC.NOHN/QEH.-0819

Result

220V
110V220V
110V
Check working power supply of all protection unit

Result

Qualified

Qualified

Qualified

Qualified

DC220V
110VAC220V
110V

7UT613
Device type chenking: the type is
drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

Qualified

Qualified

Version2010

7UT613
respectively, conform to

/ Released/Revised On 201006

Revised State1

39

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
13
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
14
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
15
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

Qualified

15

Version2010

/ Released/Revised On 201006

Revised State1

40

DOC.NOHN/QEH.-0819

1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

III. Performance test


4.3See technical protocols 4.3
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation

1. Test data recording of protection measurement &


control unit

Main Tran.
differential
protection device
7UT613
(DC220V)

Debugging
Result

Inpspection
Result

Ia11.000 A Ib10.999 A
Ic11.000 A

Ia20.999A Ib20.999A

Standard measure

Ic21.000 A

Qualified

Qualified

Ia31.000 A Ib31.000A
Ic30.999A

2. Protection unit action data and antion type


record

Action
Protection type Setting value
value

49
main

Version2010

I 1In

I1.5A , t(0s

Action

/ Released/Revised On 201006


Debugging Inpspectio
Result
n Result

Qualified

Qualified

Revised State1

41

DOC.NOHN/QEH.-0819

transformer
over-load
protection


neutral
point
clearance
zero-sequence
current
protection
t051N


neutral
point

Version2010

110kV

110kV

send anticipating signal


send accident signal
Trip MT high voltage side
CB
Trip MT low voltage side
CB
Start low voltage side CB
malfunction
Stop
Trip 110kV bus section CB
Start 110kv system CB
malfunction

I0.4A, t( 2s

I 1A , t( 1.2s )

I0.5A, t( 2s )

I1.1A, t(1.2s )

110kV

110kV

send anticipating signal

send accident signal


Trip MT high voltage side
CB
Trip MT low voltage side
CB
Start low voltage side CB
malfunction
Stop

Trip 110kV bus section CB


Start 110kv system CB
malfunction

Qualified

Qualified

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

42

DOC.NOHN/QEH.-0819

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side


CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

clearance
zero-sequence
current
protection
T151N

t0
T1 overcurrent
Prot.t0

t1
T1 overcurrent

Version2010

I(

1.2In

), t

0.3s

I 2In , t
(

0.1s )

I(

0.8A

), t

0.3s

I1.2A , t
( 0.1s

110kV

110kV

send anticipating signal

send accident signal


Trip MT high voltage side
CB
Trip MT low voltage side
CB
Start low voltage side CB
malfunction
Stop

Trip 110kV bus section CB


Start 110kv system CB
malfunction

Qualified

Qualified

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

43

DOC.NOHN/QEH.-0819

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side


CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

Prot.t1

87T
Transformer
longitudinal
differential
protection
87T

Silde 1
Ia=1*In
I=0.2*In
T(0s)

Silde 2
Ia=0
Angel(180)
T=0s

oil temperature
over-high

Version2010

Angel(0)

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side


CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

Qualified

Qualified

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

44

DOC.NOHN/QEH.-0819

protection

Winding
temperature
over-high
protection 1

Winding
temperature high
protection 1


26Q.26W.63.
71Q1.71Q2.96B

Version2010

Heavy
gas protection 1

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

45

DOC.NOHN/QEH.-0819

.96P
MT
non-electricity
gas protection

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Coller stop trip

pressure release

oil temperature
high protection

Version2010

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

46

DOC.NOHN/QEH.-0819

shutdown
Trip 110kV bus section CB

Light
gas protection 1

Winding
temperature high
protection 1

Cooling fan stop


protection 1

Version2010

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

47

DOC.NOHN/QEH.-0819

Start low voltage side CB


malfunction
shutdown
Trip 110kV bus section CB

Oil level low


protection

Oil level high


protection

Break check of
voltge loop

Version2010

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

48

DOC.NOHN/QEH.-0819

side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Break check of
current loop

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

CB three-phase
operation box

manual closing normal

manual Trip normal

protection action Trip


normal

malfunction protection
action normal

blocking
protection
action normal

Qualified

Qualified

Regulators
Debugging time 2012-4-1

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

49

DOC.NOHN/QEH.-0819

1# B
Name of panel: T1 Main Transfomer Protection Cabinet B
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1See technical protocols 4.1

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

50

DOC.NOHN/QEH.-0819

Result

220V
110V220V
110V
Check working power supply of all protection unit

Result

Qualified

Qualified

7UT613 7SJ632 7SJ622 FCX-22U 7UW50


Device type chenking: the type is 7UT613 7SJ632 7SJ622 FCX-22U 7UW50
respectively, conform to drawing type.

Qualified

Qualified

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

Qualified

Qualified

DC220V
110VAC220V
110V

Version2010

/ Released/Revised On 201006

Revised State1

51

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
16
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
17
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
18
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

Qualified

15

Version2010

/ Released/Revised On 201006

Revised State1

52

DOC.NOHN/QEH.-0819

1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

III. Performance test


4.3See technical protocols 4.3
1. Test data recording of protection measurement &
control unit

Unit name (type)

Protection unit
parameter

Measuring data recording

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Ia 0.999A Ib1.000A

Ic1.000A

Standard measure

7SJ622
Plant service
protector
7SJ622

Ua 63.48 V Ub 63.48 V
Uc 63.49 V
Ia 300 A

Ib 300 A

Ic 300 A
TV

11

kV/110V Ua 6.35

TA 300 /1
Cos=0.865

Uc 6.35

kV Ub 6.35

kV

kV

Uab 10.99 kV Ubc 10.99 kV


Uca 11.00 kV
P( 4968kW ) Q(2850kVAR ) Cos0.87
Ia0.999A Ib0.999A

7SJ632
Main
Tran.reservel
protection
device7SJ632

Ic1.001A
Ua63.50V Ub63.50V
Uc63.49V
Ia300A

Ib300A

Ic300A
TV 110 kV/110V

Ua63kV

TA 300 /1

Uc63kV

Cos=0.865

Uab110kV

Ub63kV
Ubc110kV

Uca110kV
P(49730W ) Q(28570kVAR) Cos0.87

Version2010

/ Released/Revised On 201006

Revised State1

53

DOC.NOHN/QEH.-0819

7UT613
Gen.& Tran.
differential
Protection
Device7UT613

Version2010

Ia11.000A Ib11.000A
Ic11.000A

Standard measure

Ia20.999A Ib21.000A
Ic21.001A

Qualified

Qualified

Ia31.001A Ib31.000A
Ic30.999A

/ Released/Revised On 201006

Revised State1

54

DOC.NOHN/QEH.-0819

2. Protection unit action data and antion type


record



Setting
Protection type
Action value
value

I11.2A,
t 1(2s)

110kV

50/51N
Transformer
110kv
two-section
zero-sequence
current

Version2010

I10.2A,
t 1( 0.5s )

Action

I1.21A, t1(2s )

110kV
send anticipating signal

send accident signal


Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown

Trip 110kV bus section CB

I2.01A, t2(0s )

110KV


110kV
send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start G2 50BF

Start 110kV 50BF

shutdown
Trip 110kV bus section CB

0.21A
I
, t1(0.5s )

110kV
send anticipating signal

send accident signal

50/51
Transformer
two-section
over-current
protection(50/51)

I22A, t 2(0s )


Debugging Inpspection
Result
Result

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

55

DOC.NOHN/QEH.-0819

protection(50/51)

Trip MT high/low voltage


side CB
Start low voltage side CB
malfunction
shutdown

Trip 110kV bus section CB

I20.5A,
t 2(0.1s )

0.51A
I
, t2(0.1s )

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

110kV

50BF
Transformer
110kv
Side
CB
malfunction
protection start

51C
Start cool fan

Version2010

110KV


110kV
send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start G2 50BF

Start 110kV 50BF

shutdown
Trip 110kV bus section CB

I1.05A,
t (0.5s )

I 2.1A, t(13.5A )

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

56

DOC.NOHN/QEH.-0819

(51C)

87GT
Gen-transformer
longitudinal
differential
protection


50/51
Plant
service
transformer
two-section
current
protection
(50/51)

Version2010

110kV


send anticipating signal
send accident signal
Trip MT high/low voltage
side CB
start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

start MT cool fan

Silde 1
Ia=1*In
I=0.2*In
T(0s)

Angel(0)
Silde 2
Ia=0
Angel(180)
T=0s

I 1A , t
( 1S

I 1.5A , t
( 1S

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

110kV
send anticipating signal

send accident signal


Trip MT high voltage side
CB

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Revised State1

57

DOC.NOHN/QEH.-0819

Trip MT low voltage side CB


Start low voltage side CB
malfunction
Stop
Trip 110kV bus section CB

26
Plant
service
transformer
non-electricity
protection (26)

temperature
over-high
protection 1

High
temperature
protection 1

Break check of
current loop

Version2010

110kV
send anticipating signal

send accident signal


Trip MT high voltage side
CB
Trip MT low voltage side CB

Start low voltage side CB


malfunction
Stop
Trip 110kV bus section CB

110kV

send anticipating signal


send accident signal
Trip MT high voltage side
CB
Trip MT low voltage side CB
Start low voltage side CB
malfunction
Stop
Trip 110kV bus section CB


Stepout deexcitation

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

58

DOC.NOHN/QEH.-0819

send accident signal


shut down
Stepout
deexcitation
Stepout

send anticipating signal

manual closing normal

manual Trip normal

protection action Trip


normal

malfunction protection
action normal

blocking protection action


normal

CB three-phase
operation box

Regulators
Debugging time 2012-3-21

Qualified

Qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

59

DOC.NOHN/QEH.-0819

2# A
Name of panel: T2 Main Transfomer Protection Cabinet A
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1See technical protocols 4.1

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

60

DOC.NOHN/QEH.-0819

Result

220V
110V220V
110V
Check working power supply of all protection unit

Result

Qualified

Qualified

Qualified

Qualified

DC220V
110VAC220V
110V

7UT613
Device type chenking: the type is
drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

Qualified

Qualified

Version2010

7UT613
respectively, conform to

/ Released/Revised On 201006

Revised State1

61

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
19
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
20
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
21
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

Qualified

15

Version2010

/ Released/Revised On 201006

Revised State1

62

DOC.NOHN/QEH.-0819

1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

III. Performance test


4.3See technical protocols 4.3
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation

1. Test data recording of protection measurement &


control unit

Main Tran.
differential
protection device
7UT613
(DC220V)

Debugging
Result

Inpspection
Result

Ia10.999 A Ib11.001 A
Ic1 0.999 A

Standard measure

Ia21.000 A Ib21.000 A
Ic2 1.0001 A

Qualified

Qualified

Ia31.001 A Ib31.000A
Ic30.999 A

2. Protection unit action data and antion type


record

Action
Protection type Setting value
value

Version2010

Action

/ Released/Revised On 201006


Debugging Inpspectio
Result
n Result

Revised State1

63

DOC.NOHN/QEH.-0819

49
main
transformer
over-load
protection


neutral
point
clearance
zero-sequence
current
protection
t051N

Version2010

I 1In

I0.4A, t( 2s

I1.5A , t(0s

I0.5A, t( 2s )

110kV

110kV

send anticipating signal


send accident signal
Trip MT high voltage side
CB
Trip MT low voltage side
CB
Start low voltage side CB
malfunction
Stop
Trip 110kV bus section CB
Start 110kv system CB
malfunction

Qualified

Qualified

110kV

110kV

send anticipating signal

send accident signal


Trip MT high voltage side
CB
Trip MT low voltage side
CB
Start low voltage side CB
malfunction
Stop

Trip 110kV bus section CB


Start 110kv system CB
malfunction

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

64

DOC.NOHN/QEH.-0819


neutral
point
clearance
zero-sequence
current
protection
T151N

t0
T1 overcurrent
Prot.t0

Version2010

I 1A , t( 1.2s )

I(

1.2In

), t

0.3s

I1.1A, t(1.2s )

I(

0.8A

), t

0.3s

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side


CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

Qualified

Qualified

110kV

110kV

send anticipating signal

send accident signal


Trip MT high voltage side
CB
Trip MT low voltage side
CB
Start low voltage side CB
malfunction
Stop

Trip 110kV bus section CB


Start 110kv system CB
malfunction

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

65

DOC.NOHN/QEH.-0819

t1
T1 overcurrent
Prot.t1

87T
Transformer
longitudinal
differential
protection
87T

Version2010

I 2In , t
(

0.1s )

I1.2A , t
( 0.1s

Silde 1
Ia=1*In
I=0.2*In
T(0s)

Angel(0)
Silde 2
Ia=0
Angel(180)
T=0s

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side


CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

Qualified

Qualified

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side


CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

66

DOC.NOHN/QEH.-0819

oil temperature
over-high
protection

Winding
temperature
over-high
protection 1

Winding
temperature high
protection 1

Version2010

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

67

DOC.NOHN/QEH.-0819

Heavy
gas protection 1


26Q.26W.63.
71Q1.71Q2.96B
.96P
MT
non-electricity
gas protection

Coller stop trip

pressure release

oil temperature
high protection

Version2010

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

68

DOC.NOHN/QEH.-0819

send accident signal


Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Light
gas protection 1

Winding
temperature high
protection 1

Cooling fan stop


protection 1

Version2010

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

69

DOC.NOHN/QEH.-0819

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Oil level low


protection

Oil level high


protection

Break check of
voltge loop

Version2010

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

70

DOC.NOHN/QEH.-0819

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Break check of
current loop

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

CB three-phase
operation box

manual closing normal

manual Trip normal

protection action Trip


normal

malfunction protection
action normal

blocking
protection
action normal

Qualified

Qualified

Regulators
Debugging time 2012-3-25

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

71

DOC.NOHN/QEH.-0819

2# B
Name of panel: T2 Main Transfomer Protection Cabinet B
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Protection, measurement & control part


4.1See technical protocols 4.1

Version2010

Test Method and Standard

/ Released/Revised On 201006

Debugging

Inpspection

Revised State1

72

DOC.NOHN/QEH.-0819

Result

220V
110V220V
110V
Check working power supply of all protection unit

Result

Qualified

Qualified

7UT613 7SJ632 7SJ622 FCX-22U 7UW50


Device type chenking: the type is 7UT613 7SJ632 7SJ622 FCX-22U 7UW50
respectively, conform to drawing type.

Qualified

Qualified

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%
2110V
380V

5%

3
0
3

Qualified

Qualified

DC220V
110VAC220V
110V

Version2010

/ Released/Revised On 201006

Revised State1

73

DOC.NOHN/QEH.-0819

30 .45 .60 .90 I


3
Data detection:
22
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
23
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
24
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

Qualified

15

Version2010

/ Released/Revised On 201006

Revised State1

74

DOC.NOHN/QEH.-0819

1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

III. Performance test


4.3See technical protocols 4.3
1. Test data recording of protection measurement &
control unit

Unit name (type)

Protection unit
parameter

Measuring data recording

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Ia1.000A Ib0.999A

Ic1.000A

Standard measure

7SJ622
Plant service
protector
7SJ622

Ua 63.48 V Ub 63.49V
Uc 63.48 V
Ia 300 A

Ib 300 A

Ic 300 A
TV

11

kV/110V Ua 6.35

TA 300 /1
Cos=0.865

Uc 6.35

kV Ub 6.35

kV

kV

Uab10.98 kV Ubc 10.99 kV


Uca10.98kV
P(4970kW ) Q(2848kVAR ) Cos0.87
Ia0.999A Ib0.999A

7SJ632
Main
Tran.reservel
protection
device7SJ632

Ic1.000A
Ua63.48V Ub63.47V
Uc63.48V
Ia300A

Ib300A

Ic300A
TV 110 kV/110V

Ua63kV

TA 300 /1

Uc63kV

Cos=0.865

Uab110kV

Ub63kV
Ubc110kV

Uca110kV
P(49720W ) Q(28584kVAR) Cos0.87

Version2010

/ Released/Revised On 201006

Revised State1

75

DOC.NOHN/QEH.-0819

7UT613
Gen.& Tran.
differential
Protection
Device7UT613

Version2010

Ia11.001A Ib11.000A
Ic10.999A

Standard measure

Ia20.999A Ib21.000A
Ic21.000A

Qualified

Qualified

Ia31.001A Ib31.000A
Ic31.000A

/ Released/Revised On 201006

Revised State1

76

DOC.NOHN/QEH.-0819

2. Protection unit action data and antion type


record



Setting
Protection type
Action value
value

I11.2A,
t 1(2s)

110kV

50/51N
Transformer
110kv
two-section
zero-sequence
current

Version2010

I10.2A,
t 1( 0.5s )

Action

I1.21A, t1(2s )

110kV
send anticipating signal

send accident signal


Trip MT high/low voltage
side CB
Start low voltage side CB
malfunction
shutdown

Trip 110kV bus section CB

I2.01A, t2(0s )

110KV


110kV
send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start G2 50BF

Start 110kV 50BF

shutdown
Trip 110kV bus section CB

0.21A
I
, t1(0.5s )

110kV
send anticipating signal

send accident signal

50/51
Transformer
two-section
over-current
protection(50/51)

I22A, t 2(0s )


Debugging Inpspection
Result
Result

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

77

DOC.NOHN/QEH.-0819

protection(50/51)

Trip MT high/low voltage


side CB
Start low voltage side CB
malfunction
shutdown

Trip 110kV bus section CB

I20.5A,
t 2(0.1s )

0.51A
I
, t2(0.1s )

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

110kV

50BF
Transformer
110kv
Side
CB
malfunction
protection start

51C
Start cool fan

Version2010

110KV


110kV
send anticipating signal

send accident signal

Trip MT high/low voltage


side CB

Start G2 50BF

Start 110kV 50BF

shutdown
Trip 110kV bus section CB

I1.05A,
t (0.5s )

I 2.1A, t(13.5A )

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

78

DOC.NOHN/QEH.-0819

(51C)

87GT
Gen-transformer
longitudinal
differential
protection


50/51
Plant
service
transformer
two-section
current
protection
(50/51)

Version2010

110kV


send anticipating signal
send accident signal
Trip MT high/low voltage
side CB
start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

start MT cool fan

Silde 1
Ia=1*In
I=0.2*In
T(0s)

Angel(0)
Silde 2
Ia=0
Angel(180)
T=0s

I 1A , t
( 1S

I 1.5A , t
( 1S

110kV

110kV

send anticipating signal

send accident signal

Trip MT high voltage side


CB

Trip MT low voltage side CB

Start low voltage side CB


malfunction

Stop

Trip 110kV bus section CB

Start 110kv system CB


malfunction

110kV
send anticipating signal

send accident signal


Trip MT high voltage side
CB

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Revised State1

79

DOC.NOHN/QEH.-0819

Trip MT low voltage side CB


Start low voltage side CB
malfunction
Stop
Trip 110kV bus section CB

26
Plant
service
transformer
non-electricity
protection (26)

temperature
over-high
protection 1

High
temperature
protection 1

Break check of
current loop

Version2010

110kV
send anticipating signal

send accident signal


Trip MT high voltage side
CB
Trip MT low voltage side CB

Start low voltage side CB


malfunction
Stop
Trip 110kV bus section CB

110kV

send anticipating signal


send accident signal
Trip MT high voltage side
CB
Trip MT low voltage side CB
Start low voltage side CB
malfunction
Stop
Trip 110kV bus section CB


Stepout deexcitation

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

80

DOC.NOHN/QEH.-0819

send accident signal


shut down
Stepout
deexcitation
Stepout

send anticipating signal

manual closing normal

manual Trip normal

protection action Trip


normal

malfunction protection
action normal

blocking protection action


normal

CB three-phase
operation box

Regulators
Debugging time 2012-4-4

Qualified

Qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

81

DOC.NOHN/QEH.-0819

110kV
Name of panel: 110kV Busbar Protection Cabinet
I. Integrate part

No.

Item

Test Method and Standard

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

82

DOC.NOHN/QEH.-0819

II. Protection, measurement & control part


4.1See technical protocols 4.1

Debugging
Result

Test Method and Standard

220V
110V220V
110V
Check working power supply of all protection unit

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

DC220V
110VAC220V
110V

7UT635
Device type chenking: the type is
drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%

Qualified

Qualified

Version2010

7UT635
respectively, conform to

/ Released/Revised On 201006

Revised State1

83

DOC.NOHN/QEH.-0819

2110V
380V

5%

3
0
3
30 .45 .60 .90 I
3
Data detection:
25
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
26
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
27
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

84

DOC.NOHN/QEH.-0819

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

Qualified

15

;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

85

DOC.NOHN/QEH.-0819

III. Performance test


4.4See technical protocols 4.4
Protection unit action data and antion type
record



Setting
Protection type
Action value
value

Side1
Ia=1A
Ib=1A
Ic=1A

110Kv I

87B1/87B2
110kv I section
bus
DP(87B1/87B2)

Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A

Side1
Ia=1A
Ib=1A
Ic=1A
Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A
T=0s

Side1
Ia=1A
Ib=1A
Ic=1A

110Kv II

87B1/87B2
110kv II section
bus
DP
(87B1/87B2)

Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A

Side1
Ia=1A
Ib=1A
Ic=1A
Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A
T=0s

Version2010


Debugging Inpspection
Result
Result

Action

110kV
send anticipating signal

send accident signal

Trip MT high voltage side CB

Trip MT low voltage side CB

Start high voltage side CB


malfunction

Start low voltage side CB


malfunction
Stop

Trip 110kV bus section CB

110kV
send anticipating signal

send accident signal

Trip MT high voltage side CB

Trip MT low voltage side CB

Start high voltage side CB


malfunction

Start low voltage side CB

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Revised State1

86

DOC.NOHN/QEH.-0819

malfunction
Stop

Trip 110kV bus section CB

Break check of
voltage loop


Stepout deexcitation
send accident signal
shut down
Stepout
deexcitation
Stepout
send anticipating signal

Qualified

Qualified

Break check of
current loop


Stepout deexcitation
send accident signal
shut down
Stepout
deexcitation
Stepout
send anticipating signal

Qualified

Qualified

Regulators
Debugging time 2012-4-8

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

87

DOC.NOHN/QEH.-0819

110kV
Name of panel: 110kV Busbar Connect protect Cabinet
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

88

DOC.NOHN/QEH.-0819

II. Protection, measurement & control part


4.1See technical protocols 4.1

Debug
Conclusion

Inpspection
Result

Qualified

Qualified

7SJ622

Device type chenking: the type is


7SJ622
respectively, conform to
drawing type.

Qualified

Qualified

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%

Qualified

Qualified

No.

Test Method and Standard

220V
110V220V
110V
Check working power supply of all protection unit
DC220V
110VAC220V
110V

Version2010

/ Released/Revised On 201006

Revised State1

89

DOC.NOHN/QEH.-0819

2110V
380V

5%

3
0
3
30 .45 .60 .90 I
3
Data detection:
28
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
29
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
30
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

90

DOC.NOHN/QEH.-0819

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

Qualified

15

;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

91

DOC.NOHN/QEH.-0819

III. Performance test


4.4 4.5See technical protocols 4.4 and 4.5
1.
Test data recording of protection measurement & control unit

Unit name (type)

Busbar
Connection Bay
Protection
Device7SJ622
(DC220V)

Protection unit
parameter

Measuring data recording


Ia1 1.000A Ib11.000A
Ic1 1.001 A

Standard measure

TA 100 /1
TA ratio 100 /1

Ia1 100 A Ib1 100 A


Ic1100

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

2.
Protection unit action data and antion type record

Protection
type

110Kv

50/51
110Kv
busbar
two sections
of overcurrent
protection
50/51

Version2010

Setting
value

I1 2 , t
1( 0.2s )

Action
value

I 2.1 , t1( 0.2s )

Action

110kV

110kV
send anticipating signal

send accident signal


trip MT high/low pressure
side CB
Start high/low pressure side
CB malfunction

Start 110kV bus section CB


malfunction

trip 110kV bus section CB

/ Released/Revised On 201006

Debugging
Result

Inpspection
Result

Qualified

Qualified

Revised State1

92

DOC.NOHN/QEH.-0819

110kV

110kV
I2 1A , t
2( 0.5s

110Kv

110Kv
busbar
charging
protection

110kV

50BF
110kV
subsection
CB
malfunction
Start protection
50BF

Version2010

I1.5A, t
( 0.3s

I 1.1A ,
t2( 0.5s

I 1.5A , t( 0.3s )

send anticipating signal

send accident signal


trip MT high/low pressure
side CB
Start high/low pressure side
CB malfunction

Start 110kV bus section CB


malfunction
trip 110kV bus section CB

110kV

110kV
send anticipating signal

send accident signal


trip MT high/low pressure
side CB
Start high/low pressure side
CB malfunction

Start 110kV bus section CB


malfunction

trip 110kV bus section CB

110kV

110kV

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

send anticipating signal


send accident signal
trip MT high/low pressure
side CB

/ Released/Revised On 201006

Revised State1

93

DOC.NOHN/QEH.-0819

Start high/low pressure side


CB malfunction

Start 110kV system CB


malfunction

trip 110kV bus section CB

current circuit
break line check

Stepout deexcitation
send accident signal
shut down
Stepout
deexcitation
Stepout

send anticipating signal

Qualified

Qualified

CB three-phase
operation box

manual closing normal

manual Trip normal

protection action Trip normal

malfunction
protection
action normal
latch-up protection action
normal

PT
PT
paralleling
device

Device working
power supply
disappear

Version2010

A.B.C

A.B.C

A.B.C

Qualified

Qualified

Qualified

Qualified

Keep primary paralleling


state
Stepout state

power supply disappearing


alarm

/ Released/Revised On 201006

Revised State1

94

DOC.NOHN/QEH.-0819

protection voltage A,B,C


normal

measuring voltage A,B,C


normal

electric energy metering


voltage A,B,C normal

When each side


voltage
transformer
Is out of service

A.B.C

A.B.C

A.B.C
Keep primary state
Stepout state

Process paralleling

power supply disappearing


alarm

protection voltage A,B,C


normal

measuring voltage A,B,C


normal

electric energy metering


voltage A,B,C normal

A.B.C

A.B.C

A.B.C

When bas
section CB is
tripped or
disconnector is
break

Version2010

Keep primary state


Stepout state
rapid Stepout
Process paralleling
power supply disappearing
alarm
protection voltage A,B,C
normal

/ Released/Revised On 201006

Qualified

Qualified

Qualified

Qualified

Revised State1

95

DOC.NOHN/QEH.-0819

measuring voltage A,B,C


normal
electric energy metering
voltage A,B,C normal

Regulators
Debugging time 2012-4-10

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

96

DOC.NOHN/QEH.-0819

110kV L1
Name of panel: 110kV L1 Line Differential Protection Cabinet
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

97

DOC.NOHN/QEH.-0819

II. Protection, measurement & control part


4.1See technical protocols 4.1

No.

Test Method and Standard

220V
110V220V
110V
Check working power supply of all protection unit

Debug
Conclusion

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

DC220V
110VAC220V
110V

7SD610 7SJ624
Device type chenking: the type is
conform to drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%

Qualified

Qualified

Version2010

7SD610 7SJ624

respectively,

/ Released/Revised On 201006

Revised State1

98

DOC.NOHN/QEH.-0819

2110V
380V

5%

3
0
3
30 .45 .60 .90 I
3
Data detection:
31
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
32
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
33
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

99

DOC.NOHN/QEH.-0819

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

15

;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

Qualified

III. Performance test


4.6See technical protocols 4.6
*
Note: According to the properties of fault and operation mode, action can be defined as follows:

1.
Test data recording of protection measurement & control unit

Unit name (type)

Line
optical
differential
protection
device7SD610
(DC220V)

Line reservel
protection
device7SJ624

Version2010

Protection unit
parameter

Standard measure

Measuring data recording

Ia1.000A Ib 1.001 A
Ic0.999A

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Ia.999A Ib1.000 A

Standard measure

Ic1.000A
Ua63.49V Ub63.48V
Uc63.48V

/ Released/Revised On 201006

Revised State1

100

DOC.NOHN/QEH.-0819

Ia 600 A

(DC220V)

Ib 600

Ic 600 A
TV

110 kV/110V

TA 600 /1
Cos=0.865

Ua63.5 kV Ub63.5kV

Qualified

Uc63.5kV
Uab110kV Ubc110kV

Qualified

Uca110kV
P(98292Kw ) Q(57161Kvar ) Cos0.86

2.
Protection unit action data and antion type record

Protection
type

Setting
value

T1=0.5

Action
value

Debugging
Result

Inpspection
Result

T1=0.5

110kV 1

110kV 1
110kV 1

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

T2=0.5s

110kV 1

110kV 1
110kV 1

110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB

Qualified

Qualified

110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79

T2=0.5s

Version2010

Action

/ Released/Revised On 201006

Revised State1

101

DOC.NOHN/QEH.-0819

malfunction
blocking reclosing
Trip 110kV bus section CB

U120V, t(0.5s )

110kV 1
/
25/79
110kV circuit 1
overvoltage/
low-voltage
protection
25/79

U75v, t(1.5 )

I 2.5A , t

110kV 1

50/51N
110kV circuit 1
two-section
zero-sequence
current
protection
50/51N

( 0.1s )

I 0.5A , t
( 1.9s )

Version2010

110kV 1
110kV 1
110kV 1

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

I2.6A , t (0.1s )

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

I0.6A , t (1.9s )

110kV 1
110kV 1
110kV 1

110kV

send anticipating signal

Qualified

Qualified

U122V, t (0.5s )

U70v, t (1.5s )

/ Released/Revised On 201006

Revised State1

102

DOC.NOHN/QEH.-0819

send accident signal


Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

85/87L
110kV circuit 1
longitudinal
differential
protection
85/87L

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

110kV circuit 1
voltage circuit

Qualified

Qualified

110kV 1

67/67Ncc
110kV circuit 1
directional
current
protection
67/67N

Version2010

I 4A , t
( 0.3s

I 4.1A ,
t( 0.3s

/ Released/Revised On 201006

Revised State1

103

DOC.NOHN/QEH.-0819

break
inspection

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

line

110kV
send anticipating signal
send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

110kV 1

110kV circuit 1
current circuit
break
line
inspection

Regulators
Debugging time 2012-4-12

Qualified

Qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

104

DOC.NOHN/QEH.-0819

110kV L2
Name of panel: 110kV L1 Line Differential Protection Cabinet
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

105

DOC.NOHN/QEH.-0819

II. Protection, measurement & control part


4.1See technical protocols 4.1

No.

Test Method and Standard

220V
110V220V
110V
Check working power supply of all protection unit

Debug
Conclusion

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

DC220V
110VAC220V
110V

7SD610 7SJ624
Device type chenking: the type is
to drawing type.

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%

Qualified

Qualified

Version2010

7SD610 7SJ624
respectively, conform

/ Released/Revised On 201006

Revised State1

106

DOC.NOHN/QEH.-0819

2110V
380V

5%

3
0
3
30 .45 .60 .90 I
3
Data detection:
34
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
35
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
36
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

107

DOC.NOHN/QEH.-0819

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

15

;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

Qualified

III. Performance test


4.6See technical protocols 4.6
*
Note: According to the properties of fault and operation mode, action can be defined as follows:

1.
Test data recording of protection measurement & control unit

Unit name (type)

Line
optical
differential
protection
device7SD610
(DC220V)

Line reservel
protection
device7SJ624

Version2010

Protection unit
parameter

Standard measure

Measuring data recording

Ia0.999A Ib1.001A
Ic0.999A

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Ia1.000A Ib1.00A

Standard measure

Ic1.001A
Ua63.49V Ub63.48V
Uc63.48V

/ Released/Revised On 201006

Revised State1

108

DOC.NOHN/QEH.-0819

Ia 600 A

(DC220V)

Ib 600

Ic 600 A
TV

110 kV/110V

TA 600 /1
Cos=0.865

Ua63.5 kV Ub63.5kV

Qualified

Uc63.5kV
Uab110kV Ubc110kV

Qualified

Uca110kV
P(98894Kw ) Q(57156Kvar ) Cos0.86

Version2010

/ Released/Revised On 201006

Revised State1

109

DOC.NOHN/QEH.-0819

2.
Protection unit action data and antion type record

Protection
type

Setting
value

T1=0.5

Action
value

Debugging
Result

Inpspection
Result

T1=0.5

110kV 1
110kV 1
110kV 1

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

T2=0.5s

110kV 1

110kV 1
110kV 1

110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

U122V, t (0.5s )

110kV 1
110kV 1
110kV 1

Qualified

Qualified

110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79

T2=0.5s

110kV 1
/
25/79
110kV circuit 1
overvoltage/
Version2010

U120V, t(0.5s )

Action

/ Released/Revised On 201006

Revised State1

110

DOC.NOHN/QEH.-0819

U70v, t (1.5s )

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

I2.6A , t (0.1s )

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

I0.6A , t (1.9s )

110kV 1
110kV 1
110kV 1

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

low-voltage
protection
25/79

U75v, t(1.5 )

I 2.5A , t
( 0.1s )

110kV 1

50/51N
110kV circuit 1
two-section
zero-sequence
current
protection
50/51N

I 0.5A , t
( 1.9s )

Version2010

/ Released/Revised On 201006

Revised State1

111

DOC.NOHN/QEH.-0819

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

85/87L
110kV circuit 1
longitudinal
differential
protection
85/87L

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

110kV circuit 1
voltage circuit
break
line
inspection

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction

Qualified

Qualified

110kV 1

67/67Ncc
110kV circuit 1
directional
current
protection
67/67N

Version2010

I 4A , t
( 0.3s

I 4.1A ,
t( 0.3s

/ Released/Revised On 201006

Revised State1

112

DOC.NOHN/QEH.-0819

shutdown
Trip 110kV bus section CB

110kV
send anticipating signal
send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

110kV 1

110kV circuit 1
current circuit
break
line
inspection

Regulators
Debugging time 2012-4-1

Qualified

Qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

113

DOC.NOHN/QEH.-0819

110kV L1
Name of panel: 110kV L1 Line Distance Protection Cabinet
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

114

DOC.NOHN/QEH.-0819

II. Protection, measurement & control part


4.1See technical protocols 4.1

Debug
Conclusion

Inpspection
Result

Qualified

Qualified

7SA611

Device type chenking: the type is


7SA611
respectively, conform to
drawing type.

Qualified

Qualified

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%

Qualified

Qualified

No.

Test Method and Standard

220V
110V220V
110V
Check working power supply of all protection unit
DC220V
110VAC220V
110V

Version2010

/ Released/Revised On 201006

Revised State1

115

DOC.NOHN/QEH.-0819

2110V
380V

5%

3
0
3
30 .45 .60 .90 I
3
Data detection:
37
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
38
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
39
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

116

DOC.NOHN/QEH.-0819

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

15

;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

Qualified

III. Performance test


4.6See technical protocols 4.6
*
Note: According to the properties of fault and operation mode, action can be defined as follows:

1.
Test data recording of protection measurement & control unit

Unit name (type)

Protection unit
parameter

Measuring data recording


Ia1.001A

Line reservel
protection
device7SJ624
(DC220V)

Ic0.999A

Standard measure

Ua63.42V

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Ib0.999A
Ub63.36V

Uc63.39V
Ia 600 A

Ib 600

Ic 600 A
TV

110

kV/110V Ua63.5 kV Ub63.5kV

TA 600 /1
Cos=0.865

Uc63.5kV
Uab110kV Ubc110kV
Uca110kV
P(98480Kw ) Q(57164Kvar ) Cos0.86

Version2010

/ Released/Revised On 201006

Revised State1

117

DOC.NOHN/QEH.-0819

2.
Protection unit action data and antion type record

Protection
type

Setting
value

T1=0.5S

Action
value

Action

110kV 1

110kV 1
110kV 1

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

T1=0.5

110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79

110kV 1

110kV 1
110kV 1

110kV
T2=0.5S

T2=0.5S

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

110kV 1


50/51N

Version2010

I 2A , t
( 0.1S

I 2.1A , t
( 0.1S

110kV 1
110kV 1

/ Released/Revised On 201006

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

118

DOC.NOHN/QEH.-0819

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

110kV circuit 1
two-section
overcurrent and
zero-sequence
current
protection
50/51N

I 0.5A , t
( 1.5S

110kV 1

67/67Ncc
110kV circuit 1
directional
current
protection
67/67N

Version2010

I1.5A, t
( 0.5S

I0.6A , t
( 1.5S

I1.6A ,
t(0.5S

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

119

DOC.NOHN/QEH.-0819

110kV 1

85-21
110kV circuit 1
longitudinal
differential
protection 85

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

110kV circuit 1
voltage circuit
break
line
inspection

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

110kV circuit 1
current circuit
break
line
inspection

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

120

DOC.NOHN/QEH.-0819

/Distance
protection
(phase / ground)
(21/21N)

R=10.0 Ohm
X=10.5Ohm
RG=3.0Ohm

Regulators
Debugging time 2012-3-26

U=20V
I=10A

110kV
send anticipating signal

send accident signal

Trip MT high/low voltage side


CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

121

DOC.NOHN/QEH.-0819

110kV L2
Name of panel: 110kV L1 Line Distance Protection Cabinet
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

122

DOC.NOHN/QEH.-0819

II. Protection, measurement & control part


4.1See technical protocols 4.1

Debug
Conclusion

Inpspection
Result

Qualified

Qualified

7SA611

Device type chenking: the type is


7SA611
respectively, conform to
drawing type.

Qualified

Qualified

Check keypress, ensuring sensitive and effective key and correct key name.

Qualified

Qualified

.., I

Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously

Qualified

Qualified

I
Check if software edition number in LCD display is conform to the drawing

Qualified

Qualified

I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.

Qualified

Qualified

.
Detect valuing modification and conservation normal.

Qualified

Qualified

.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.

Qualified

Qualified

Detect if each outlet action test is normal.

Qualified

Qualified

10

Enter DI real-time display screen and monitor each DI quantity displacement;


check if quantity and position of input loop is accord with drawing design
requirement.

Qualified

Qualified

11

15A 1A

5%
0.2In 0.1In 10%

Qualified

Qualified

No.

Test Method and Standard

220V
110V220V
110V
Check working power supply of all protection unit
DC220V
110VAC220V
110V

Version2010

/ Released/Revised On 201006

Revised State1

123

DOC.NOHN/QEH.-0819

2110V
380V

5%

3
0
3
30 .45 .60 .90 I
3
Data detection:
40
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
41
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
42
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.

12

I
5min.
0.01In. 0.05V

Zero drift test. Dont input voltage/current quantity in protective device AC


voltage/current terminal. For a while(eg.min),detect zero drift value of
three-phase current, three-phase voltage and line voltage, in specified
range.(current zero drift value is 0.01In and voltage zero drift value is 0.05V)

Qualified

Qualified

13

Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

124

DOC.NOHN/QEH.-0819

14

//

Check if manual close/open and remote/local is accord with CB requirement of


layout design and agreement. Check opening/closing action of remote control
CB action is normal in remote operation.

Qualified

15

;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.

Qualified

Qualified

Qualified

III. Performance test


4.6See technical protocols 4.6
*
Note: According to the properties of fault and operation mode, action can be defined as follows:

1.
Test data recording of protection measurement & control unit

Unit name (type)

Protection unit
parameter

Measuring data recording

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Ia0.999A Ib0.999 A

Ic1.000A

Standard measure

Line reservel
protection
device7SJ624
(DC220V)

Ua63.48V Ub63.47V
Uc63.48V
Ia 600 A

Ib 600

Ic 600 A
TV

110

kV/110V Ua63.5 kV Ub63.5kV

TA 600 /1
Cos=0.865

Uc63.5kV
Uab110kV Ubc110kV
Uca110kV
P(98432Kw ) Q(57146Kvar ) Cos0.86

Version2010

/ Released/Revised On 201006

Revised State1

125

DOC.NOHN/QEH.-0819

2.
Protection unit action data and antion type record

Protection
type

Setting
value

T1=0.5S

Action
value

Action

110kV 1

110kV 1
110kV 1

110kV

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

T1=0.5

110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79

110kV 1

110kV 1
110kV 1

110kV
T2=0.5S

T2=0.5S

send anticipating signal


send accident signal
Trip 110kV circuit 1 CB

closing 110kV circuit 1 CB


Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

110kV 1

Version2010

I 2A , t
( 0.1S

I 2.1A , t
( 0.1S

110kV 1

/ Released/Revised On 201006

Debugging
Result

Inpspection
Result

Qualified

Qualified

Qualified

Qualified

Qualified

Qualified

Revised State1

126

DOC.NOHN/QEH.-0819

50/51N
110kV circuit 1
two-section
overcurrent and
zero-sequence
current
protection
50/51N

110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

I 0.5A , t
( 1.5S

110kV 1

67/67Ncc
110kV circuit 1
directional
current
protection
67/67N

Version2010

I1.5A, t
( 0.5S

I0.6A , t
( 1.5S

I1.6A ,
t(0.5S

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal

send accident signal

Trip 110kV circuit 1 CB


closing 110kV circuit 1 CB

Start 110kV circuit 1 CB


malfunction
blocking reclosing

Qualified

Qualified

/ Released/Revised On 201006

Revised State1

127

DOC.NOHN/QEH.-0819

Trip 110kV bus section CB

110kV 1

85-21
110kV circuit 1
longitudinal
differential
protection 85

110kV 1
110kV 1

110kV 1

110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

110kV circuit 1
voltage circuit
break
line
inspection

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB

Qualified

Qualified

110kV 1

110kV circuit 1
current circuit
break
line
inspection

110kV

send anticipating signal


send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB

Qualified

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

128

DOC.NOHN/QEH.-0819

malfunction
shutdown
Trip 110kV bus section CB

/Distance
protection
(phase / ground)
(21/21N)

R=10.0 Ohm
X=10.5Ohm
RG=3.0Ohm

Regulators
Debugging time 2012-3-29

U=20V
I=10A

110kV
send anticipating signal

send accident signal

Trip MT high/low voltage side


CB

Start low voltage side CB


malfunction

shutdown

Trip 110kV bus section CB

Qualified

Qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

129

DOC.NOHN/QEH.-0819

1# LCULCU1A/B
Name of panel: Unit 1 LCULCU1Cabinet A/B
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50MBetween normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

130

DOC.NOHN/QEH.-0819

II. Automatic control section


5.3.1 6.3See technical protocols 5.3.1 and 6.3

Debug
Conclusion

Inpspection
Result

CPU I
6ES74123HJ140AB0

2
Check if CPU module type of PLC is consistent with drawing design:
Type: 6ES74123HJ140AB0;
Module No.:2

qualified

qualified

1. 6ES74070KR020AA0
2
2.220V 110V
24V
5V
3..
Check if working power level of power module conforms to drawing design:
1. type: 6ES74070KR020AA0 ( 2 ) in total
2. operating voltage:
220V 110V
24V
3. check if input/output voltage and indicating lamp is normal

qualified

qualified

qualified

qualified

1.
1. 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.
10
3. II
1.input module checking, type:
(1). 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.number: 10
3.check if module input indicating lamp and input signal comform to drawing

qualified

qualified

1.6ES7322BL000AA0
2.
3

qualified

qualified

No.

Test Method and Standard

PLC TYPE

1. CPU
2.

3.
4.
5..
1. Check if PLC CPU module indicating lamp is normal;
2.check communication with background: serial Ethernet

3. check if communication with background is normal;


4. check if PLC program uploading/downloading is normal;
5. check if communication with protector,digital instrument and other device is
normal

Version2010

/ Released/Revised On 201006

Revised State1

131

DOC.NOHN/QEH.-0819

3.

1.Output module checking, type: 6ES7322BL000AA0


2.number: 3
3.check if outputs conform to outlet relay, consistent with laylout design; outlet
relay contact closing/breaking reliable action.

6ES7331KF020AB0
5
6
Check analog quantity acquisition module type: YES

NO
Current mode

voltage mode
Type: 6ES7331KF020AB0
( 5 )in total

The type of touch screen: YES

NO

qualified

qualified

qualified

qualified

MT-8121T
Type: MT-8121T

Check if working power of touch screen is normal

qualified

qualified

Check if PLC communication and indicating lamp are normal; alarm window be
displayed automatically, alarm content conforms to actual alarm signal.

qualified

qualified

Check if interface is clear, and item name conforms to drawing;

qualified

qualified

PLC

Check if DI signal conforms to drawing and PLC input point; data display of
monitoring pictures is correct;

qualified

qualified

Check if Parameters setting can write in PLC correctly;

qualified

qualified

Check if PLC can operate correctly in remote control operation;

qualified

qualified

Check if background monitoring system can adjust time with PLC correctly;

qualified

qualified

Check if function menu and function key are effective and available, contact
points without shift;

qualified

qualified

Vietnam TA THANG Hydropower station

10

P(

) Q(

2.8MW

Uab

11 kV

Vietnam TA THANG Hydropower station )


Electric parameters recording:
Touch screen name:(
P(

11

3.4MW

3.4MW

) Q(

20

Version2010

2.8MW

qualified

qualified

) Uab 11 kV

mA

/ Released/Revised On 201006

qualified

qualified

Revised State1

132

DOC.NOHN/QEH.-0819

1 100 2 100 3 100 4100 5100


6100 7100 8100 9100 10100
11100 12100 13100 14100 15100
16100 17100 18100 19100 20100
21100 22100 23100 24100 25100
26100 27100 28100 29100 30100
31100 32100 33100 34100 35100
36100 37100 38100 39100 40100
RTD PT100:
120
153 253 353 453 553 653
753 853 953 1053 1153
1253 1353 1453 1553 1653
Display analog quantity: YES
NO
Input standard 20 mAtouch screen display
Data 1100Data 2100Data 3100Data 4100Data 5100
Data 6100Data 7100Data 8100Data 9100Data 10100
Data 11100Data 12100Data 13100Data 14100Data 15100
Data 16100Data 17100Data 18100Data 19100Data 20100
Data 21100Data 22100Data 23100Data 24100Data 25100
Data 26100Data 27100Data 28100Data 29100Data 30100
Data 31100Data 32100Data33100Data34100Data35100
Data36100Data37100Data38100Data39100Data40100
Temperature RTD displayPT100:
Input 120
Data 153Data 253Data 353Data 453Data 553Data 653
Data 753Data 853Data 953Data 1053Data 1153Data 12
53Data 1353Data 1453Data 1553Data 1653

meter: YES

NO


CP-T96
0-150v
vlotagemeter: YES

NO type: ARC220E range: (0-150v

qualified

qualified


CP-F96

Frequency metre: YES


NO
type: CP-F96

qualified

qualified

5%

Detect input rated quantity, nd error of meter indicated value and


circumscribed measuring instrument value is not more than 5%

qualified

qualified

qualified

qualified

Synchronizing meter: YES


NO

CP-S96-N/110V
Type: CP-S96-N/110V

Version2010

/ Released/Revised On 201006

Revised State1

133

DOC.NOHN/QEH.-0819

1.
2.
3. 0
30

Detection method:
1.only input voltage in to-be sync. side, and voltage and frequency pointer
deviate upward;
2. only input voltage in system side, and voltage and frequency pointer deviate
downward;
3. input the same voltage in two sides, and voltage and frequency pointer is
horizontal, phase angle pointer to about 0; if angle changes, pointer advance or

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

fall behind 30pointer deviation not exceeding accuracy error.


Manual synchronism: YES

NO

...
Input system voltage and to-be sync.voltage, check if system voltage,
frequency, to-be sync.voltage and frequency meter are indicated when
switching to manual synchronism.

2
When not achieving synchronizing conditions, it be without closing output;
When achieving synchronizing conditions, it can
Synchronizing closing.

3
In the test, Regardless of achieving synchronizing conditions, it can be
closing output.

When system side without voltage, synchronizing voltage relay cant be


4
actuate, no voltage closing; When system side having
voltage, to-be sync.side wiyhout voltage,voltage relay can be block closing
outlet action.

Automatic synchronizing device: YES

NO
DZZB-5
1
1
Type: DZZB-5
No.:1

2
LCD display or nixie tube indicate clearly, with sensitive button, and all kinds of
state indication is right;
3

Version2010

/ Released/Revised On 201006

Revised State1

134

DOC.NOHN/QEH.-0819

5%
input rated voltage in input terminal, and the error of automatic synchronizm
value and circumscribed measuring instrument value is not more than 5%

Check if device can select line by auto/manual. When frequency , voltage


and phase angle reach synchronizing requirements,it can
Give closing order; when frequence difference, it can give speed adjustment
order and exit; when differential pressure,it can give excitation adjustment
order and exit

:
Outlet relay type: YES

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

NO

1
MK3P-I(220V)

36 2+82RCL42404 DC24V
2
Type1: MK3P-I(220V)No.: 36 Type2: RCL42404 DC24V No.:2+82

2
All output contact N.O./N.C.conforms to drawing, and contact output
reliable action

Control switch and button.: YES

NO
1LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/r

1+2+1+1
1
Type1: LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/rNo.: 1 +2+2+2
....
/
All Control switches can operate normally, e.g.,test,synchronized on, accident
2
reset,
opening
increase/decrease,excitation
increase/decrease,CB
opening/closing, contact reliable closing/breaking.

Indicating lamp: YES


NO

AD16-22/R28 AD16-22D/RG23

2 +1
1
Type: AD16-22/R28 AD16-22D/RG23
No.:2+1

qualified

Check if type and voltage class conform to layout design, and lable name
correspond to drawing and actual signal, luminous evenly,


Type of Switching power supply: YES

NO

PF-500-24V


Type: PF-500-24V
No.:3
AC/DC will be mutual standby: YES

NO

Version2010

/ Released/Revised On 201006

Revised State1

135

DOC.NOHN/QEH.-0819

Check if type conforms to layout design,capacity in requirements

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified


Alarm:
YES

NO
1

BJ-1I
Type: BJ-1I

1
No.:1

Accident alarm and fault alarm separately, continuously and loudly

Communication equipment: YES

NO

NC608-4M

1
1
Type: NC608-4M
No.:1
..

2
Check if device type conforms to layout design (including communication
superviser,serial server,optical fiber communication device,etc.)

3
Check if communication with other device and background is normal
2

Regulators
Debugging time 2012-4-14

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

136

DOC.NOHN/QEH.-0819

2# LCULCU2A/B
Name of panel: Unit 2 LCULCU2Cabinet A/B
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50MBetween normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

137

DOC.NOHN/QEH.-0819

II. Automatic control section


5.3.1 6.3See technical protocols 5.3.1 and 6.3

Debug
Conclusion

Inpspection
Result

CPU I
6ES74123HJ140AB0

2
Check if CPU module type of PLC is consistent with drawing design:
Type: 6ES74123HJ140AB0;
Module No.:2

qualified

qualified

1. 6ES74070KR020AA0
2
2.220V 110V
24V
5V
3..
Check if working power level of power module conforms to drawing design:
1. type: 6ES74070KR020AA0 ( 2 ) in total
2. operating voltage:
220V 110V
24V
3. check if input/output voltage and indicating lamp is normal

qualified

qualified

qualified

qualified

1.
1. 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.
10
3. II
1.input module checking, type:
(1). 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.number: 10
3.check if module input indicating lamp and input signal comform to drawing

qualified

qualified

1.6ES7322BL000AA0
2.
3

qualified

qualified

No.

Test Method and Standard

PLC TYPE

1. CPU
2.

3.
4.
5..
1. Check if PLC CPU module indicating lamp is normal;
2.check communication with background: serial Ethernet

3. check if communication with background is normal;


4. check if PLC program uploading/downloading is normal;
5. check if communication with protector,digital instrument and other device is
normal

Version2010

/ Released/Revised On 201006

Revised State1

138

DOC.NOHN/QEH.-0819

3.

1.Output module checking, type: 6ES7322BL000AA0


2.number: 3
3.check if outputs conform to outlet relay, consistent with laylout design; outlet
relay contact closing/breaking reliable action.

6ES7331KF020AB0
5
6
Check analog quantity acquisition module type: YES

NO
Current mode

voltage mode
Type: 6ES7331KF020AB0
( 5 )in total

The type of touch screen: YES

NO

qualified

qualified

qualified

qualified

MT-8121T
Type: MT-8121T

Check if working power of touch screen is normal

qualified

qualified

Check if PLC communication and indicating lamp are normal; alarm window be
displayed automatically, alarm content conforms to actual alarm signal.

qualified

qualified

Check if interface is clear, and item name conforms to drawing;

qualified

qualified

PLC

Check if DI signal conforms to drawing and PLC input point; data display of
monitoring pictures is correct;

qualified

qualified

Check if Parameters setting can write in PLC correctly;

qualified

qualified

Check if PLC can operate correctly in remote control operation;

qualified

qualified

Check if background monitoring system can adjust time with PLC correctly;

qualified

qualified

Check if function menu and function key are effective and available, contact
points without shift;

qualified

qualified

Vietnam TA THANG Hydropower station

10

P(

) Q(

2.8MW

Uab

11 kV

Vietnam TA THANG Hydropower station )


Electric parameters recording:
Touch screen name:(
P(

11

3.5MW

3.5MW

) Q(

Version2010

2.8MW

qualified

qualified

Uab 11 kV

/ Released/Revised On 201006

Revised State1

139

DOC.NOHN/QEH.-0819

20 mA
1 100 2 100 3 100 4100 5100
6100 7100 8100 9100 10100
11100 12100 13100 14100 15100
16100 17100 18100 19100 20100
21100 22100 23100 24100 25100
26100 27100 28100 29100 30100
31100 32100 33100 34100 35100
36100 37100 38100 39100 40100
RTD PT100:
120
153 253 353 453 553 653
753 853 953 1053 1153
1253 1353 1453 1553 1653

qualified

qualified

Display analog quantity: YES


NO
Input standard 20 mAtouch screen display
Data 1100Data 2100Data 3100Data 4100Data 5100
Data 6100Data 7100Data 8100Data 9100Data 10100
Data 11100Data 12100Data 13100Data 14100Data 15100
Data 16100Data 17100Data 18100Data 19100Data 20100
Data 21100Data 22100Data 23100Data 24100Data 25100
Data 26100Data 27100Data 28100Data 29100Data 30100
Data 31100Data 32100Data33100Data34100Data35100
Data36100Data37100Data38100Data39100Data40100
Temperature RTD displayPT100:
Input 120
Data 153Data 253Data 353Data 453Data 553Data 653
Data 753Data 853Data 953Data 1053Data 1153Data 12
53Data 1353Data 1453Data 1553Data 1653

meter: YES

NO


CP-T96
0-150v
vlotagemeter: YES

NO type: ARC220E range: (0-150v

qualified

qualified


CP-F96

Frequency metre: YES


NO
type: CP-F96

qualified

qualified

5%

Detect input rated quantity, nd error of meter indicated value and


circumscribed measuring instrument value is not more than 5%

qualified

qualified

qualified

qualified

Synchronizing meter: YES


NO

CP-S96-N/110V
Type: CP-S96-N/110V

Version2010

/ Released/Revised On 201006

Revised State1

140

DOC.NOHN/QEH.-0819

1.
2.
3. 0
30

Detection method:
1.only input voltage in to-be sync. side, and voltage and frequency pointer
deviate upward;
2. only input voltage in system side, and voltage and frequency pointer deviate
downward;
3. input the same voltage in two sides, and voltage and frequency pointer is
horizontal, phase angle pointer to about 0; if angle changes, pointer advance or

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

fall behind 30pointer deviation not exceeding accuracy error.


Manual synchronism: YES

NO

...
Input system voltage and to-be sync.voltage, check if system voltage,
frequency, to-be sync.voltage and frequency meter are indicated when
switching to manual synchronism.

2
When not achieving synchronizing conditions, it be without closing output;
When achieving synchronizing conditions, it can
Synchronizing closing.

3
In the test, Regardless of achieving synchronizing conditions, it can be
closing output.

When system side without voltage, synchronizing voltage relay cant be


4
actuate, no voltage closing; When system side having
voltage, to-be sync.side wiyhout voltage,voltage relay can be block closing
outlet action.

Automatic synchronizing device: YES

NO
DZZB-5
1
1
Type: DZZB-5
No.:1

2
LCD display or nixie tube indicate clearly, with sensitive button, and all kinds of
state indication is right;

Version2010

/ Released/Revised On 201006

Revised State1

141

DOC.NOHN/QEH.-0819

5%
input rated voltage in input terminal, and the error of automatic synchronizm
value and circumscribed measuring instrument value is not more than 5%

Check if device can select line by auto/manual. When frequency , voltage


and phase angle reach synchronizing requirements,it can
Give closing order; when frequence difference, it can give speed adjustment
order and exit; when differential pressure,it can give excitation adjustment
order and exit

:
Outlet relay type: YES

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

NO

1
MK3P-I(220V)

36 2+82RCL42404 DC24V
2
Type1: MK3P-I(220V)No.: 36 Type2: RCL42404 DC24V No.:2+82

2
All output contact N.O./N.C.conforms to drawing, and contact output
reliable action

Control switch and button.: YES

NO
1LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/r

1+2+1+1
1
Type1: LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/rNo.: 1 +2+2+2
....
/
All Control switches can operate normally, e.g.,test,synchronized on, accident
2
reset,
opening
increase/decrease,excitation
increase/decrease,CB
opening/closing, contact reliable closing/breaking.

Indicating lamp: YES


NO

AD16-22/R28 AD16-22D/RG23

2 +1
1
Type: AD16-22/R28 AD16-22D/RG23
No.:2+1

2
Check if type and voltage class conform to layout design, and lable name
correspond to drawing and actual signal, luminous evenly,


Type of Switching power supply: YES

NO

PF-500-24V


Type: PF-500-24V
No.:3

Version2010

/ Released/Revised On 201006

Revised State1

142

DOC.NOHN/QEH.-0819

AC/DC will be mutual standby: YES

NO

Check if type conforms to layout design,capacity in requirements

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified


Alarm:
YES

NO
1

BJ-1I
Type: BJ-1I

1
No.:1

Accident alarm and fault alarm separately, continuously and loudly

Communication equipment: YES

NO

NC608-4M

1
1
Type: NC608-4M
No.:1
..

2
Check if device type conforms to layout design (including communication
superviser,serial server,optical fiber communication device,etc.)

3
Check if communication with other device and background is normal
2

Regulators
Debugging time 2012-4-20

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

143

DOC.NOHN/QEH.-0819

LCULCU4A/B
Name of Panel: Auxiliary LCULCU4Cabinet A/B
I. Integrate part

Number

Test
items

Test methods and standards

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types


of the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the
lamp in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.

qualified

qualified

Insulation
Resistance Test

500V
50MBetween normal test
atmospheric conditions between the live parts of the
device and non-charged metal and shell, and electrical
contact circuit with open circuit voltage of 500V megger to
measure the insulation resistance value of each grade of
each loopbetween the insulation resistance of not less
than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric
conditions, the device can withstand a frequency of 50Hz,
the test voltage of 2000V, the work lasted one minute
power frequency withstand voltage test without
breakdown phenomenon of flashover and component
damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

144

DOC.NOHN/QEH.-0819

II. Automatic control part


5.3.2 6.4See technical protocols 5.3.2 and 6.4

Debugging
Result

Inpspection
Result

qualified

qualified

qualified

qualified

qualified

qualified

1
Check output model model number
1. 6ES73211BL000AA0
(2) 6ES73217BH000AB0
2. Quantity
8 Blocks
3. II
Check if module input indicator light and input signal match drawings.

qualified

qualified

1
Check output model model number
1. 6ES73221BL000AA0
2. Quantity
2 Blocks
3.

qualified

qualified

Number

Test methods and standards

PLC Model number

PLC MODEL NUMBER :

CPU I
Check if model number of CPU module in PLC matches the drawings.
Model 6ES74123HJ140AB0

Number of modules
2 Blocks

Check if working power supply level of power model match the drawings.
1. Model 6ES74070KR020AA0
total 2

2. Operating voltage220V 110V


24V
5V
3..
Check if input and output voltage is normal or not; check if working
indicator light is under normal condition.
1. CPU
2. Serial port Ethernet

3.
4.
5..

1. Check if CPU module running indicator light of PLC is under normal


condition;
2. Check communication mode with backstage: serial port Ethernet
;
3. Check if backstage communication is under normal condition;
4. Check if program upload and download of PLC is under normal condition;
5. Check if the communication with protector, digtal display panel and other
devices is under normal condition.

Version2010

/ Released/Revised On 201006

Revised State1

145

DOC.NOHN/QEH.-0819

Check if each output point matches outlet relay and drawings; check if Trip
and closing action of contacts of outlet relay is reliable.
Check type of module that collected by analog
quantity Yes

No
6
Current mode

Voltage mode
Model number
6ES7331KF020AB0

2
Blocks
Touch screen model number Yes

No

qualified

qualified

Model number
MT-8121T

qualified

qualified

Check if working power supply of touch sceen is under normal condition;

qualified

qualified

Check if the interface is clear, if indicator light can work in order, if alarm
window will pop-up automatically, and if the alarm contents matches the real
alarm signal.

qualified

qualified

Check if the interface is clear, and if the project name matches the drawings.

qualified

qualified

PLC

Check if DI signal match drawings and input point of PLC, and if data of
electric quantities monitoring interface display correctly.

qualified

qualified

Check if parameters can be written in PLC.

qualified

qualified

Check if PLC can operate correctliy or not, when detect remote operating.

qualified

qualified

Check if backstage monitoring system can compare time with PLC correctly.

qualified

qualified

Check if function menu and fuction key is effective and usable, and if the
contact has no shift.

qualified

10

Name of touch screen station Vietnam TA THANG Hydropower


station

qualified

qualified

11

Analog quantity display Yes

No
20 mA
Input standards20mA current touch screen display
Data1100 Data2100 Data3100 Data4100
Data5100 Data6100 Data7100 Data8100
Data9100 Data10100 Data11100
Data12100 Data13100 Data14100
Data15100 Data16100
RTD Temperature RTD displayPT100:
120 In put 120 resistance
Data153 Data253 Data353 Data453

qualified

qualified

Version2010

/ Released/Revised On 201006

qualified

Revised State1

146

DOC.NOHN/QEH.-0819

Data553 Data653 Data753 Data853


AC sampling device: Yes

No

Model number
ACR220E PZ96-AI3

Blocks

TD1
TD1 High Side
2

Ia 100 A Ib100A Ic100A P(16480kW ) Q(9523Kwar)


Uab110kV Ubc110kV Uca110kV f 50Hz
Cos=0.865
TD2
TD2 High Side

Ia 100 A Ib100A Ic100A P(16500kW ) Q(9518Kwar)


Uab110kV Ubc110kV Uca110kV f 50Hz
Cos=0.865
TD1
TD1 Low Side

Ia 100 A Ib 100 A Ic100 A P( 59kW ) Q( 35kVAR )


Uab 0.4 kV Ubc 0.4 kV Uca 0.4 kV f 50Hz
Cos=0.865
400V
400V Bus coupler current
Ia 100 A

Ib 100 A Ic 100 A

Model number of lockout relay : Yes

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

No

Model
RCL4204 24vdc MK3P-I DC220V
67+2

All output contact normally open and normally close should accord to
drawings, the contacts should output reliable operation.

Switch power supply model number Yes

qualified

Amount

No

Model number
PF-500-24v
Amount
3
Yes
No

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

Alarm Yes
No
1

Model number
BJ-1I

Check if accident alarm separate from malfunction alam, and if the sound is
both continuous and loud.

Communication equipment Yes

Amount
1

No

Model number
NC608-4M
Quantity
1

..

Check if model number accords with design model in drawings(including

Version2010

/ Released/Revised On 201006

Revised State1

147

DOC.NOHN/QEH.-0819

communication management computer,


communication devices, and so on. )
3

serial

server

Optical

fiber

Check if the device communicates with other devices and backstage normally.

Regulators
Debugging time 2012-4-15

qualified

qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

148

DOC.NOHN/QEH.-0819

: LCULCU3A/B
Name of Panel: Switching station LCU (LCU3) Cabinet A/B
I. Integrate part

No.

Check Items

Test Method and Standard

Debug
Conclusion

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.

qualified

qualified

Insulation
Resistance Test

500V
50MBetween normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.

qualified

qualified

II. Automatic control section


5.3.3 6.5See technical protocols 5.3.3 and 6.5

No.

Test Method and Standard

Version2010

/ Released/Revised On 201006

Debug

Inpspection

Revised State1

149

DOC.NOHN/QEH.-0819

Conclusion

Result

CPU I
6ES74123HJ140AB0

2
Check if CPU module type of PLC is consistent with drawing design:
Type:
Module No.:

qualified

qualified

1. 6ES74070KR020AA0
2
2.220V 110V
24V
5V
3..
Check if working power level of power module conforms to drawing design:
1. type:
( 2 ) in total
2. operating voltage: 220V 110V
24V
5V
3. check if input/output voltage and indicating lamp is normal

qualified

qualified

qualified

qualified

1.
1. 6ES73211BL000AA0
(2) 6ES73217BH000AB0
2.
18
3. II
1.input module checking, type:
1. 6ES73211BL000AA0
(2) 6ES73217BH000AB0
2.number: 18
3.check if module input indicating lamp and input signal comform to drawing

qualified

qualified

1.
1. 6ES73211BL000AA0
2.
3
3.

1.input module checking, type:


6ES73211BL000AA0
2.number:3

qualified

qualified

PLC TYPE

1. CPU
2.

3.
4.
5..
1. Check if PLC CPU module indicating lamp is normal;
2.check communication with background: serial Ethernet

3. check if communication with background is normal;


4. check if PLC program uploading/downloading is normal;
5. check if communication with protector,digital instrument and other device is
normal

Version2010

/ Released/Revised On 201006

Revised State1

150

DOC.NOHN/QEH.-0819

3.check if outputs conform to outlet relay, consistent with laylout design; outlet
relay contact closing/breaking reliable action.

6ES73311KF020AB0

6
Check analog quantity acquisition module type: YES

NO
Current mode
voltage mode
Type: 6ES73311KF020AB0
( 1 )in total

The type of touch screen: YES

NO

qualified

qualified

MT-8121T
Type:

qualified

qualified

Check if working power of touch screen is normal

qualified

qualified

Check if PLC communication and indicating lamp are normal; alarm window be
displayed automatically, alarm content conforms to actual alarm signal.

qualified

qualified

Check if interface is clear, and item name conforms to drawing;

qualified

qualified

PLC

Check if DI signal conforms to drawing and PLC input point; data display of
monitoring pictures is correct;

qualified

qualified

Check if Parameters setting can write in PLC correctly;

qualified

qualified

Check if PLC can operate correctly in remote control operation;

qualified

qualified

Check if background monitoring system can adjust time with PLC correctly;

qualified

qualified

Check if function menu and function key are effective and available, contact
points without shift;

qualified

Vietnam TA THANG Hydropower Station


Touch screen name:( Vietnam TA THANG Hydropower Station)

qualified

10

11

20 mA
1100 2100 3100 4100 5100
6100 7100 8100 9100 10100
11100 12100 13100 14100 15100
16100

qualified

qualified

qualified

qualified

Display analog quantity: YES


NO
Input standard 20
mAtouch screen display

Version2010

/ Released/Revised On 201006

Revised State1

151

DOC.NOHN/QEH.-0819

Data 1100Data 2100Data 3100Data 4100Data 5100


Data 6100Data 7100Data 8100Data 9100Data 10100
Data 11100Data 12100Data 13100Data 14100Data 15100
Data 16100

meter: YES

NO


CP-T96
0-150V
Voltmeter: YES

NO
type: CP-T96
range: 0-150V

qualified

qualified

Frequency metre: YES

qualified

qualified

5%

Detect input rated quantity, nd error of meter indicated value and


circumscribed measuring instrument value is not more than 5%

qualified

qualified

qualified

qualified

qualified

qualified

...
Input system voltage and to-be sync.voltage, check if system voltage,
frequency, to-be sync.voltage and frequency meter are indicated when
switching to manual synchronism.

qualified

qualified

When not achieving synchronizing conditions, it be without closing output;

qualified

qualified

Synchronizing meter: YES

CP-F96
NO
type: CP-F96

NO

CP-S96-N/110V
Type: CP-S96-N/110V

1.
2.
3. 0
30

Detection method:
1.only input voltage in to-be sync. side, and voltage and frequency pointer
deviate upward;
2. only input voltage in system side, and voltage and frequency pointer deviate
downward;
3. input the same voltage in two sides, and voltage and frequency pointer is
horizontal, phase angle pointer to about 0; if angle changes, pointer advance or
fall behind 30pointer deviation not exceeding accuracy error.

Manual synchronism: YES

Version2010

NO

/ Released/Revised On 201006

Revised State1

152

DOC.NOHN/QEH.-0819

When achieving synchronizing conditions, it can


Synchronizing closing.

In the test, Regardless of achieving synchronizing conditions, it can be


closing output.

When system side without voltage, synchronizing voltage relay cant be


actuate, no voltage closing; When system side having
voltage, to-be sync.side wiyhout voltage,voltage relay can be block closing
outlet action.

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

Automatic synchronizing device: YES

NO

DZZB-6
1

Type: DZZB-6
No.:1

2
LCD display or nixie tube indicate clearly, with sensitive button, and all kinds of
state indication is right;

5%
3
input rated voltage in input terminal, and the error of automatic synchronizm
value and circumscribed measuring instrument value is not more than 5%

Check if device can select line by auto/manual. When frequency , voltage


4
and phase angle reach synchronizing requirements,it can
Give closing order; when frequence difference, it can give speed adjustment
order and exit; when differential pressure,it can give excitation adjustment
order and exit
:
Outlet relay type: YES

NO

RCL42404 24V MK3P-I


88+2
1
Type: RCL42404(24V) MK3P-I
No.: 88+2

2
All output contact N.O./N.C.conforms to drawing, and contact output
reliable action
1


Control switch No.: YES

NO

LW39-16C-40B-211/2
LW-16C-40B-202A
LW39-16CYS-40B-505/5

1+1+5+5
Type: LW39-16C-40B-211/2
LW-16C-40B-202A
LW39-16CYS-40B-505/5
No.: 1+1+5+5

Version2010

LW39-25-Z1-2002/2
LW39-25-Z1-2002/2

/ Released/Revised On 201006

Revised State1

153

DOC.NOHN/QEH.-0819

....
/
All Control switches can operate normally, e.g.,test,synchronized on, accident
reset,
opening
increase/decrease,excitation
increase/decrease,CB
opening/closing, contact reliable closing/breaking.

Indicating lamp: YES

qualified

qualified

NO

AD16-22D/RG23

5
Type: AD16-22D/RG23
No.:5

qualified

qualified

Check if type and voltage class conform to layout design, and lable name
correspond to drawing and actual signal, luminous evenly,

qualified

qualified

PF-500-24V


Type: PF-500-24V
No.: 3
AC/DC will be mutual standby: YES

NO

qualified

qualified

Check if type conforms to layout design,capacity in requirements

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified

qualified


Type of Switching power supply: YES

NO


Alarm:
YES

NO
1

BJ-1I

1
Type: BJ-1I
No.:1

Accident alarm and fault alarm separately, continuously and loudly

Communication equipment: YES

NO

NC608-4M


1
1
Type: NC608-4M
No.:1
..

2
Check if device type conforms to layout design (including communication
superviser,serial server,optical fiber communication device,etc.)

3
Check if communication with other device and background is normal
2

Regulators
Debugging time 2012-3-24

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

154

DOC.NOHN/QEH.-0819

A
Name of Panel: Energy Meter Cabinet A
I. Integrate part

Number

Test
items

Test methods and standards

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the
lamp in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test
atmospheric conditions between the live parts of the device
and non-charged metal and shell, and electrical contact
circuit with open circuit voltage of 500V megger to measure
the insulation resistance value of each grade of each
loopbetween the insulation resistance of not less than
50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency
withstand voltage test without breakdown phenomenon of
flashover and component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

155

DOC.NOHN/QEH.-0819

II. Function part


See technical protocols 6.9
Name

T1 High Side
Mian


Model number

DSSD341
0.2S
DSSD341
bidirectional
0.2S

T2 High Side
Mian

DSSD341
0.2S
DSSD341
bidirectional
0.2S

110kV line 1
Spare

DSSD341
0.5S
DSSD341
bidirectional
0.5S

Version2010

Test methods and standards


1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.
1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.
1..

2.

3.

/ Released/Revised On 201006

Debugging
Result

Inpspection
Result

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

156

DOC.NOHN/QEH.-0819

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.

110kV line 2
Spare

DSSD341
0.5S
DSSD341
bidirectional
0.5S

T1 High Side
Spare

DSSD341
0.5S
DSSD341
bidirectional
0.5S

T2 High Side

DSSD341

Version2010

1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.
1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.
1..

/ Released/Revised On 201006

qualified

qualified

qualified

qualified

Revised State1

157

DOC.NOHN/QEH.-0819

Spare

0.5S
DSSD341
bidirectional
0.5S

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.

Regulators
Debugging time 2012-4-24

qualified

qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

158

DOC.NOHN/QEH.-0819

B
Name of panel: Energy Meter Cabinet B
I. Integrate part

Number

Test
items

Test methods and standards

Debugging
Result

Inpspection
Result

qualified

qualified

ID

Check the consistence of actual quantity, labels and types of


the cpmponent with that stipulated in the diagram.


Maintenance
of
lightingLighting

Switch on the work power. When open the real door, the
lamp in the panel is on; otherwise, it is off.

qualified

qualified

Panel
size and color
check

Check the panel size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.

qualified

qualified

Insulation
Resistance Test

500V
50M Between normal test
atmospheric conditions between the live parts of the device
and non-charged metal and shell, and electrical contact
circuit with open circuit voltage of 500V megger to measure
the insulation resistance value of each grade of each
loopbetween the insulation resistance of not less than
50M.

qualified

qualified


Dielectric
strength

50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency
withstand voltage test without breakdown phenomenon of
flashover and component damage.

qualified

qualified

Version2010

/ Released/Revised On 201006

Revised State1

159

DOC.NOHN/QEH.-0819

II. Function part


See technical protocols 6.9

Name

1G Spare


Model number

DSSD331
0.5S
DSSD331
bidirectional
0.5S

2G Spare

DSSD341
0.2S DSSD331
0.5S
DSSD341
bidirectional
0.2S DSSD331
bidirectional
0.5S

TD1 Spare

DSSD331
0.5S
DSSD331
bidirectional
0.5S

Version2010

Test methods and standards


1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.
1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.
1..

2.

3.

/ Released/Revised On 201006

Debugging
Result

Inpspection
Result

qualified

qualified

qualified

qualified

qualified

qualified

Revised State1

160

DOC.NOHN/QEH.-0819

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.

TD1 Spare

DSSD331
0.5S
DSSD331
bidirectional
0.5S

1..

2.

3.

1. Add three phase rated current and voltage.The


display of current and voltage is correct, and active/
reactive indicator light flashes normally.
2. When current or voltage missing phase,
corresponding alarm symbol wiil flash, and the alarm
lamp will light.
3. Communicating with backstage monitoring system
is in normal condition, and corresponding display
backstage electrical degree is normal.

Regulators
Debugging time 2012-4-24

qualified

qualified

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

161

DOC.NOHN/QEH.-0819

Name of Panel: DCS Network Cabinet


I. Integrate part

Number

Test
items

Test methods and standards

Debugging
Result

Inpspection
Result

qualified

qualified

Label

Check if model number and quantity of each components


and labels are in line with drawings.


Maintenance
of
lightingLighting

Add operating power supply, opem the rear door, internal


lamp on. After closing door, the internal lamp out.

qualified

qualified

Check the screen size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.

Meet

Qualified

Version2010

/ Released/Revised On 201006

Revised State1

162

DOC.NOHN/QEH.-0819

II. Function part


6.34 6.2.10 See technical protocols 6.34 and 6.2.10

Debugging
Result

Inpspection
Result

..

PCM825
Check if device type conforms to layout design
communication
superviser,serial
See technical (including
protocols 6.34 server,optical fiber communication device,etc.)

Check if communication with other device and


background is normal

qualified

qualified

Check if the synchronizer indicator twinkles


right, the time ynchronized is correct and its
communication with monitoring system is
normal.

qualified

qualified


Model number

Name

communication
management
computer

GPS

DMP-348(DC220V)
See technical
protocols
6.2.10

Test methods and standards

Regulators
Debugging time 2012-4-26

Surveyor
Checking time

Test result

Version2010

/ Released/Revised On 201006

Revised State1

163

DOC.NOHN/QEH.-0819

MTC
MTC Background Monitoring System

Scope of examination

NO.

Test methods and standards

Debugging
Result

Inpspection
Result

... I
Check out if the brand, quantity, oerating voltage and parameters of computer
and display consistent with design requirements.

qualified

qualified

Check out if all communication devices are in normal condition.

qualified

qualified

Check out if double net multimachine hot back-up switch over is normal.

qualified

qualified

Double net multimachine Yes


No

Checked out that communication is normal, and double net multimachine switch
over is normal.

qualified

qualified

qualified

qualified

qualified

qualified

Check out communication status of protection device.

I Protection unit
1 7UM612 7UM622 7UT612 7UT613 7SJ622 7SA611 7SD610
7SJ622 7SJ632 7SJ624 7UT635
Unit name:
7UM612 7UM622 7UT612 7UT613 7SJ622 7SA611 7SD610
7SJ622 7SJ632 7SJ624 7UT635
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal Normal
No need

Read-write constant value Normal Normal


No need

Alarm incident Normal


Abnormal
PLC
PLC communication:
1 1# LCU
Name of panel: Unit 1 LCULCU1Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal

Version2010

/ Released/Revised On 201006

Revised State1

164

DOC.NOHN/QEH.-0819

Telecontrol checkout Normal


Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal

2
2# LCU
Name of panel: Unit 1 LCULCU1Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal
Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal

qualified

qualified

3 LCUA/B
Name of panel: Auxiliary LCULCU4Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal
Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal

qualified

qualified

4
LCUA/B
Name of panel: Switching station LCU (LCU3) Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal
Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal

qualified

qualified

Watt-hour meter communication

Check out that communition and data of watt-hour meter are normal.

qualified

qualified

Regulators
Debugging time 2012-5-12

Surveyor
Checking time

Test result