Microprocessor-based Integrative
Automation Control System
(Date) :
2012-5-15
Version2010
/ Released/Revised On 201006
Revised State1
DOC.NOHN/QEH.-0819
Test equipment
According to the test requirements of this project, the instruments meet the test specifications and
within the validity period, type and duration see the certificate content.
Factory test instrumentation required to as follows:
AC and DC voltmeterT19/1-VUT56 MULTMETER
MeggerZC25-4
Resistance box
PW31E PW31E based relay control instrument
WOS02 WOS02 type dual analog circuit breaker tester
CS2674A CS2674APressure tester
Version2010
/ Released/Revised On 201006
Revised State1
DOC.NOHN/QEH.-0819
Contents
DOC.NOHN/QEH.-0819
Version2010
/ Released/Revised On 201006
Revised State1
II
DOC.NOHN/QEH.-0819
Protection unit action data and antion type record .......................................................................................... 110
110kV L1 ............................................................................................................................. 114
Name of panel: 110kV L1 Line Distance Protection Cabinet ............................................................................................. 114
I. Integrate part .......................................................................................................................................... 114
II. Protection, measurement & control part .............................................................................. 115
III. Performance test ................................................................................................................................... 117
1........................................................................................................................... 117
Test data recording of protection measurement & control unit ....................................................................... 117
2............................................................................................................... 118
Protection unit action data and antion type record .......................................................................................... 118
110kV L2 ............................................................................................................................. 122
Name of panel: 110kV L1 Line Distance Protection Cabinet ............................................................................................. 122
I. Integrate part .......................................................................................................................................... 122
II. Protection, measurement & control part .............................................................................. 123
III. Performance test ................................................................................................................................... 125
1........................................................................................................................... 125
Test data recording of protection measurement & control unit ....................................................................... 125
2............................................................................................................... 126
Protection unit action data and antion type record .......................................................................................... 126
1# LCULCU1A/B .......................................................................................................................... 130
Name of panel: Unit 1 LCULCU1Cabinet A/B ............................................................................................................. 130
I. Integrate part .......................................................................................................................................... 130
II. Automatic control section .............................................................................................................. 131
2# LCULCU2A/B .......................................................................................................................... 137
Name of panel: Unit 2 LCULCU2Cabinet A/B ............................................................................................................. 137
I. Integrate part .......................................................................................................................................... 137
II. Automatic control section .............................................................................................................. 138
LCULCU4A/B ............................................................................................................................. 144
Name of Panel: Auxiliary LCULCU4Cabinet A/B ........................................................................................................ 144
I. Integrate part .......................................................................................................................................... 144
II. Automatic control part ................................................................................................................... 145
: LCULCU3A/B ............................................................................................................................ 149
Name of Panel: Switching station LCU (LCU3) Cabinet A/B .............................................................................................. 149
I. Integrate part .......................................................................................................................................... 149
II. Automatic control section .............................................................................................................. 149
A ................................................................................................................................................ 155
Name of Panel: Energy Meter Cabinet A ........................................................................................................................... 155
I. Integrate part .......................................................................................................................................... 155
II. Function part .......................................................................................................................................... 156
B ................................................................................................................................................ 159
Name of panel: Energy Meter Cabinet B ........................................................................................................................... 159
I. Integrate part .......................................................................................................................................... 159
II. Function part .......................................................................................................................................... 160
............................................................................................................................................. 162
Version2010
/ Released/Revised On 201006
Revised State1
III
DOC.NOHN/QEH.-0819
Version2010
/ Released/Revised On 201006
Revised State1
IV
DOC.NOHN/QEH.-0819
1# A
Name of panel: G1 Protection Cabinet A
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
No.
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
DOC.NOHN/QEH.-0819
220V
110V220V
110V
Check working power supply of all protection unit
Result
Result
qualified
qualified
DC220V
110VAC220V
110V
7UT612
Check keypress, ensuring sensitive and effective key and correct key name.
qualified
qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
qualified
qualified
I
Check if software edition number in LCD display is conform to the drawing
qualified
qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
.
Detect valuing modification and conservation normal.
qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
qualified
qualified
10
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
Version2010
respectively, conform to
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
14
//
15
;
1.
Version2010
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
DOC.NOHN/QEH.-0819
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Version2010
/ Released/Revised On 201006
qualified
Revised State1
DOC.NOHN/QEH.-0819
. Performance test
4.2See technical protocols 4.2
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation
Protection unit
parameter
Debugging
Result
Ic0.999A
Standard measure
Ua63.50V
Inpspection
Result
Ib0.999A
Ub63.49V
qualified
qualified
qualified
qualified
qualified
qualified
Uc63.51V
Gen.reservel
protection device
7UM622 (DC220V)
Ia2500A
TV
11
Ib2500A
kV/110V Ic2500A
TA 2500 /1
Cos=0.865
Ua6.35kV Ub6.35kV
Uc6.35kV
TVratio 11kV/110V
Uab11kV Ubc11kV
TAratio 2500 /1
Uca11kV
Cos=0.865
P(39876)kW
Q(25800)kVar
Cos
0.86
Gen.differential
protection device
7UT612 (DC220V)
Ia11.001A Ib10.999A
Ic11.000
Standard measure
Ia20.999A Ib21.001A
Ic20.999A
Protection type
Version2010
Setting
value
Action
value
Action
/ Released/Revised On 201006
Debugging Inpspection
Result
Result
Revised State1
DOC.NOHN/QEH.-0819
V/F(1.31 ),
segment
t(17.2)s
V/F(1.1 ),t(10)s
24
Gen.over-excitation
protection (24)
V/F(1.41 ),
segment
t(1 )s
26
Gen.stator winding
inverse OCP (26)
32
Gen.inverse power
protection (32)
Version2010
I1A, t (0.5 )s
P%(-1.84 ), t0s
I2A, t(6.72 )s
P%(-0.186 ),
t0s
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
Stepout
send anticipating signal
qualified
qualified
/ Released/Revised On 201006
Revised State1
DOC.NOHN/QEH.-0819
Ua=63.5V
start G2 50BF
Stepout
send anticipating signal
qualified
qualified
1.06A
I
, t(0.5s)
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
I 1.1A, t(0.5 )s
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
qualified
qualified
angel(0)
Ub=63.5V
angel(-120)
40
Gen.
loss-of-excitation
protection (40)
Uc=63.5V
Susceptance(0.41)
Angel(120)
Angle(80)
Ia(0.48)A
t(3)s
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(3)s
50/51/67E
Excitation-transform
er
over-load
protection(50/51/67
E)
51E
Excitation-transform
er OCP (51E)
I1.05A, t (0.5s )
I1A, t (0.5 )s
t050BF
Gen.CB malfunction
protection (50BF)t0
t ( 0.5s )
Version2010
/ Released/Revised On 201006
t(0.5s )
Revised State1
DOC.NOHN/QEH.-0819
Stepout deexcitation
Stepout
send anticipating signal
Trip MT high voltage side
CB
t150BF
Gen.CB malfunction
protection (50BF)t1
59
Stator
winding
over-voltage
protection (59)
100%
I 59N
100% stator winding
one point earth
protection
of
Gen.59N
Version2010
t ( 0.5s )
U 130V , t (3s )
U020v , t ( 0.3s )
t ( 0.5s )
stop
Stepout deexcitation
Stepout
send anticipating signal
U138V, t(3s )
start G2 50BF
Stepout deexcitation
Stepout
send anticipating signal
U020.1V,
t( 0.3s )
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
DOC.NOHN/QEH.-0819
I
64R
Excitation loop one
point
earth
protection (64R)
78
Gen.loss-of-sync
protection (78)
Gen.frequency
protection
87G Gen.
longitudinal
differential
protection (87G)
Version2010
Impedance
Impedance
10
10
t( 5 )
t(5)
Stepout deexcitation
send accident signal
stop
Stepout deexcitation
Stepout
Impedance
Impedance
Za(4.5),Zb(12),
Za(4.5),Zb(12),
Zc(3.6)
Zc(3.6)
Angle90 Angle90
Number
start G2 50BF
Number of
of power swing6
Stepout
send anticipating signal
F 48Hz, t (1s )
Side1
I 3.3336
A,
Slide2I 0 A,
t(0
)S
F47Hz, t (1s )
Side1I3.4A
Slide2I0A,
t ( 15 )ms
qualified
qualified
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
start G2 50BF
stop
Stepout deexcitation
qualified
qualified
/ Released/Revised On 201006
Revised State1
DOC.NOHN/QEH.-0819
Stepout
send anticipating signal
Hydraulic
Hydraulic
machinery
machinery
protection
protection
Shaft current
Shaft current
protection t0
protection t0
38
Non-electricity
protection (38)
Version2010
Shaft current
Shaft current
protection t1
protection t1
Fire protection
Fire protection
Stepout
send anticipating signal
qualified
qualified
qualified
qualified
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
/ Released/Revised On 201006
Revised State1
10
DOC.NOHN/QEH.-0819
Temperature
Temperature
protection 1
protection 1
Temperature
Temperature
protection 2
protection 2
send accident signal
stop
Stepout deexcitation
Stepout
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
Break check of
voltage loop
send accident signal
stop
Stepout deexcitation
Stepout
qualified
Break check of
voltage loop
send accident signal
stop
Stepout deexcitation
Stepout
qualified
CB
three-phase
operation box
Version2010
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
11
DOC.NOHN/QEH.-0819
malfunction protection
action normal
blocking protection
action normal
Regulators
Debugging time 2012-3-20
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
12
DOC.NOHN/QEH.-0819
1# B
Name of panel: G1 Protection Cabinet B
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
13
DOC.NOHN/QEH.-0819
220V
110V220V
110V
Check working power supply of all protection unit
Result
Result
qualified
qualified
qualified
qualified
DC220V
110VAC220V
110V
7UM612
Check keypress, ensuring sensitive and effective key and correct key name.
qualified
qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
qualified
qualified
I
Check if software edition number in LCD display is conform to the drawing
qualified
qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
qualified
qualified
.
Detect valuing modification and conservation normal.
qualified
qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
qualified
qualified
qualified
10
qualified
qualified
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
qualified
qualified
Version2010
respectively, conform to
/ Released/Revised On 201006
qualified
Revised State1
14
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
qualified
qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
qualified
qualified
14
//
qualified
qualified
15
;
1.
qualified
Version2010
/ Released/Revised On 201006
Revised State1
15
DOC.NOHN/QEH.-0819
qualified
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Protection unit
parameter
Debugging
Result
Inpspection
Result
qualified
qualified
qualified
qualified
Ia 0.999 A Ib 1.000A
Ic 1.001 A
Ua 63.48 V Ub 63.49
V Uc63.49 V
Gen.reservel
protection device
7UM612(DC220V)
Ia 2500 A
Ib 2500
Ua 6.34 kV Ub 6.34
kV
Ic 2500 A
TV
11kV/110V
TA 2500 /1
Cos=0.865
Uc 6.33
kV
Q(23667kVAR)
Cos
0.87
Version2010
/ Released/Revised On 201006
Revised State1
16
DOC.NOHN/QEH.-0819
Protection type
Setting
Action value
value
Ua=3.929V
Angel0
Ub=3.929V
Angel-120
Impedance
protection24
Uc=3.929V
2.9
Angel120
t( 0s )
Ia=1.35A
Angel0
Ib=1.35A
Angel-120
Ib=1.35A
Angel120
Gen.low
voltage
protection27
U 90V , t
( 1S
U80V, t( 1S )
Debugging Inpspection
Result
Result
Action
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
qualified
qualified
Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)
Susceptance(0.4
Gen.loss-of-excitatio
n protection40
1)
Angle(80)
t(0)s
Uc=63.5V
Angel(120)
Ia(0.48)A
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(0)s
Gen.winding
over-load protection
Version2010
I 1.05A , t
( 0S )
I2A, t(0s )
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
Qualified
qualified
qualified
qualified
/ Released/Revised On 201006
Revised State1
17
DOC.NOHN/QEH.-0819
49S
Take
current memory low
voltage OCP51V
Stator winding
OVP59
I
Gen.stator
winding one-point
earth
protection
59NS
Version2010
send accident signal
shut down
Stepout
deexcitation
Stepout
U 80V ,I
1.35A, t ( 1S )
U 140v , t
(3s )
U(78V)
I(1.36A)
T(1s)
U150v, t( 3s )
3U030V, t
3U031v,
( 0.3s )
t(0.3s )
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
/ Released/Revised On 201006
qualified
qualified
Revised State1
18
DOC.NOHN/QEH.-0819
Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)
Gen.negative
sequence
overcurrent(46)
Uc=63.5V
Angel(120)
I2(0.6A),t(3s)
Ia(0.6)A
Angel(-30)
Ib=(0.6)A
Angel(90)
Ic=(0.6)A
Angel(-150)
t(3)s
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
Break check of
voltage loop
send accident signal
shut down
Stepout
deexcitation
Stepout
Break check of
current loop
send accident signal
shut down
Stepout
deexcitation
Stepout
Regulators
Debugging time
qualified
qualified
qualified
qualified
qualified
qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
19
DOC.NOHN/QEH.-0819
2# A
Name of panel: G2 Protection Cabinet A
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
No.
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
20
DOC.NOHN/QEH.-0819
220V
110V220V
110V
Check working power supply of all protection unit
Result
Result
qualified
qualified
qualified
qualified
DC220V
110VAC220V
110V
7UT612
Check keypress, ensuring sensitive and effective key and correct key name.
qualified
qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
qualified
qualified
I
Check if software edition number in LCD display is conform to the drawing
qualified
qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
qualified
qualified
.
Detect valuing modification and conservation normal.
qualified
qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
qualified
qualified
qualified
10
qualified
qualified
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
qualified
qualified
Version2010
respectively, conform to
/ Released/Revised On 201006
qualified
Revised State1
21
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
qualified
qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
qualified
qualified
14
//
qualified
qualified
15
;
1.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
22
DOC.NOHN/QEH.-0819
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
. Performance test
4.2See technical protocols 4.2
*
Note: According to the properties of fault and operation mode, action can be defined as follows:
1
2
3
Stop: (1) Switch off the generator CB; (2) Deexcitation (3) Close guide vane
1
2
Stepout deexcitation: (1) (1) Switch off the generator CB; (2) Deexcitation
1Stepout: (1) Switch off the generator CB; (2) Deexcitation
Protection unit
parameter
Debugging
Result
Inpspection
Result
Ia1.000A Ib0.999A
Ic1.000A
Standard measure
Gen.reservel
protection device
7UM622 (DC220V)
Ua63.50V Ub63.50V
Uc63.49V
Ia2500A
TV
11
qualified
qualified
qualified
qualified
qualified
qualified
Ib2500A
kV/110V Ic2500A
TA 2500 /1
Cos=0.865
TVratio 11kV/110V
TAratio 2500 /1
Cos=0.865
Ua6.35kV Ub6.35kV
Uc6.35kV
Uab11kV Ubc11kV
Uca11kV
P(40961)kW Q(23900)kVar
Cos0.86
Gen.differential
protection device
7UT612 (DC220V)
Version2010
Ia10.999A Ib10.999A
Standard measure
Ic11.000A
Ia2 1.000A Ib20.999A
Ic20.999A
/ Released/Revised On 201006
Revised State1
23
DOC.NOHN/QEH.-0819
Protection type
Setting
value
Action
value
V/F(1.31 ),
segment
t(17.2)s
V/F(1.1 ),t(10)s
24
Gen.over-excitation
protection (24)
V/F(1.41 ),
segment
t(1 )s
26
Gen.stator winding
inverse OCP (26)
32
Gen.inverse power
protection (32)
Version2010
I1A, t (0.5 )s
P%(-1.84 ), t0s
I2A, t(6.72 )s
P%(-0.186 ), t
0s
Debugging Inpspection
Result
Result
Action
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
qualified
qualified
qualified
qualified
stop
Stepout deexcitation
Stepout
send anticipating signal
/ Released/Revised On 201006
Revised State1
24
DOC.NOHN/QEH.-0819
start G2 50BF
Stepout
send anticipating signal
Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)
40
Gen.
loss-of-excitation
protection (40)
Susceptance(0.41)
Angle(80)
t(3)s
Uc=63.5V
Angel(120)
Ia(0.48)A
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(3)s
50/51/67E
Excitation-transform
er
over-load
protection(50/51/67
E)
51E
Excitation-transform
er OCP (51E)
Version2010
I1.05A, t (0.5s )
I1A, t (0.5 )s
start G2 50BF
Stepout
send anticipating signal
1.06A
I
, t(0.5s)
send accident signal
stop
Stepout deexcitation
Stepout
I 1.1A, t(0.5 )s
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
25
DOC.NOHN/QEH.-0819
t050BF
Gen.CB malfunction
protection (50BF)t0
t150BF
Gen.CB malfunction
protection (50BF)t1
59
Stator
winding
over-voltage
protection (59)
100%
I 59N
100% stator winding
one point earth
protection
of
Gen.59N
Version2010
t ( 0.5s )
t ( 0.5s )
U 130V , t (3s )
U020v , t ( 0.3s )
t(0.5s )
Stepout
send anticipating signal
Trip MT high voltage side
CB
t ( 0.5s )
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
U138V, t(3s )
start G2 50BF
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
U020.1V,
t( 0.3s )
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
Revised State1
26
DOC.NOHN/QEH.-0819
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
I
64R
Excitation loop one
point
earth
protection (64R)
78
Gen.loss-of-sync
protection (78)
Gen.frequency
protection
87G Gen.
longitudinal
differential
Version2010
Stepout deexcitation
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
Impedance
Impedance
Za(4.5),Zb(12),
Za(4.5),Zb(12),
Zc(3.6)
Zc(3.6)
Angle90 Angle90
Number
start G2 50BF
Number of
of power swing6
Stepout
send anticipating signal
qualified
qualified
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
qualified
qualified
Impedance
Impedance
10
10
t( 5 )
t (5)
F 48Hz, t (1s )
Side1
I 3.3336
A,
Slide2I 0 A,
t(0
)S
F47Hz, t (1s )
Side1I3.4A
Slide2I0A,
t ( 15 )ms
/ Released/Revised On 201006
Revised State1
27
DOC.NOHN/QEH.-0819
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
protection (87G)
Hydraulic
Hydraulic
machinery
machinery
protection
protection
Shaft current
Shaft current
protection t0
protection t0
38
Non-electricity
protection (38)
Version2010
Shaft current
Shaft current
protection t1
protection t1
Fire protection
Fire protection
Stepout
send anticipating signal
qualified
qualified
qualified
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
qualified
qualified
/ Released/Revised On 201006
qualified
Revised State1
28
DOC.NOHN/QEH.-0819
stop
Stepout deexcitation
Stepout
send anticipating signal
Temperature
Temperature
protection 1
protection 1
send accident signal
stop
Stepout deexcitation
Stepout
start G2 50BF
stop
Stepout deexcitation
Stepout
send anticipating signal
qualified
Break check of
voltage loop
send accident signal
stop
Stepout deexcitation
Stepout
qualified
qualified
Break check of
voltage loop
send accident signal
stop
Stepout deexcitation
qualified
qualified
Version2010
Temperature
Temperature
protection 2
protection 2
/ Released/Revised On 201006
qualified
Revised State1
29
DOC.NOHN/QEH.-0819
Stepout
manual closing normal
manual Trip normal
protection action Trip
normal
malfunction protection
action normal
blocking
protection
action normal
CB
three-phase
operation box
Regulators
Debugging time 2012-3-24
qualified
qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
30
DOC.NOHN/QEH.-0819
2# B
Name of panel: G2 Protection Cabinet B
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
31
DOC.NOHN/QEH.-0819
220V
110V220V
110V
Check working power supply of all protection unit
Result
Result
qualified
qualified
qualified
qualified
DC220V
110VAC220V
110V
7UM612
Check keypress, ensuring sensitive and effective key and correct key name.
qualified
qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
qualified
qualified
I
Check if software edition number in LCD display is conform to the drawing
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
.
Detect valuing modification and conservation normal.
qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
qualified
qualified
10
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
Version2010
respectively, conform to
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
32
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
14
//
15
Version2010
qualified
qualified
qualified
qualified
qualified
qualified
/ Released/Revised On 201006
Revised State1
33
DOC.NOHN/QEH.-0819
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
qualified
qualified
Protection unit
parameter
Debugging
Result
Inpspection
Result
qualified
qualified
qualified
qualified
Ia 0.999 A Ib1.000A
Ic0.999A
Ua 63.49 V Ub 63.49 V
Uc63.50 V
Gen.reservel
protection device
7UM612(DC220V)
Ia 2500 A
Ib 2500
Ua 6.34 kV Ub 6.34
kV
Ic 2500 A
TV
11kV/110V
TA 2500 /1
Cos=0.865
Uc 6.33
kV
Q(23771kVAR)
Cos
0.87
Version2010
/ Released/Revised On 201006
Revised State1
34
DOC.NOHN/QEH.-0819
Protection type
Setting
Action value
value
Ua=3.929V
Angel0
Ub=3.929V
Angel-120
Impedance
protection24
Uc=3.929V
2.9
Angel120
t( 0s )
Ia=1.35A
Angel0
Ib=1.35A
Angel-120
Ib=1.35A
Angel120
Gen.low
voltage
protection27
U 90V , t
( 1S
U80V, t( 1S )
Debugging Inpspection
Result
Result
Action
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
qualified
qualified
Ua=63.5V
angel(0)
Ub=63.5V
angel(-120)
Susceptance(0.4
Gen.loss-of-excitatio
n protection40
1)
Angle(80)
t(0)s
Uc=63.5V
Angel(120)
Ia(0.48)A
Angel(52)
Ib=(0.48)A
Angel(-68)
Ic=(0.48)A
Angel(172)
t(0)s
Gen.winding
over-load protection
Version2010
I 1.05A , t
( 0S )
I2A, t(0s )
/ Released/Revised On 201006
Revised State1
35
DOC.NOHN/QEH.-0819
49S
Take
current memory low
voltage OCP51V
Stator winding
OVP59
I
Gen.stator
winding one-point
earth
protection
59NS
Version2010
send accident signal
shut down
Stepout
deexcitation
Stepout
U 80V ,I
1.35A, t ( 1S )
U(78V)
I(1.36A)
T(1s)
U 140v , t
U150v ,
(3s )
t( 3s )
3U030V, t
3U031v,
( 0.3s )
t(0.3s )
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
/ Released/Revised On 201006
Revised State1
36
DOC.NOHN/QEH.-0819
Ua=63.5V
start G2 50BF
shut down
Stepout deexcitation
Stepout
send anticipating signal
qualified
qualified
Break check of
voltage loop
send accident signal
shut down
Stepout
deexcitation
Stepout
qualified
qualified
Break check of
current loop
send accident signal
shut down
Stepout
deexcitation
Stepout
qualified
qualified
angel(0)
Ub=63.5V
angel(-120)
Gen.negative
sequence
overcurrent(46)
Uc=63.5V
Angel(120)
I2(0.6A),t(3s)
Ia(0.6)A
Angel(-30)
Ib=(0.6)A
Angel(90)
Ic=(0.6)A
Angel(-150)
t(3)s
Regulators
Debugging time 2012-3-27
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
37
DOC.NOHN/QEH.-0819
1# A
Name of panel: T1 Main Transfomer Protection Cabinet A
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
38
DOC.NOHN/QEH.-0819
Result
220V
110V220V
110V
Check working power supply of all protection unit
Result
Qualified
Qualified
Qualified
Qualified
DC220V
110VAC220V
110V
7UT613
Device type chenking: the type is
drawing type.
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
Qualified
Qualified
Version2010
7UT613
respectively, conform to
/ Released/Revised On 201006
Revised State1
39
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
14
//
Qualified
Qualified
15
Version2010
/ Released/Revised On 201006
Revised State1
40
DOC.NOHN/QEH.-0819
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Main Tran.
differential
protection device
7UT613
(DC220V)
Debugging
Result
Inpspection
Result
Ia11.000 A Ib10.999 A
Ic11.000 A
Ia20.999A Ib20.999A
Standard measure
Ic21.000 A
Qualified
Qualified
Ia31.000 A Ib31.000A
Ic30.999A
49
main
Version2010
I 1In
I1.5A , t(0s
Action
/ Released/Revised On 201006
Debugging Inpspectio
Result
n Result
Qualified
Qualified
Revised State1
41
DOC.NOHN/QEH.-0819
transformer
over-load
protection
neutral
point
clearance
zero-sequence
current
protection
t051N
neutral
point
Version2010
110kV
110kV
I0.4A, t( 2s
I 1A , t( 1.2s )
I0.5A, t( 2s )
I1.1A, t(1.2s )
110kV
110kV
Qualified
Qualified
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
42
DOC.NOHN/QEH.-0819
110kV
110kV
Stop
clearance
zero-sequence
current
protection
T151N
t0
T1 overcurrent
Prot.t0
t1
T1 overcurrent
Version2010
I(
1.2In
), t
0.3s
I 2In , t
(
0.1s )
I(
0.8A
), t
0.3s
I1.2A , t
( 0.1s
110kV
110kV
Qualified
Qualified
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
43
DOC.NOHN/QEH.-0819
110kV
110kV
Stop
Prot.t1
87T
Transformer
longitudinal
differential
protection
87T
Silde 1
Ia=1*In
I=0.2*In
T(0s)
Silde 2
Ia=0
Angel(180)
T=0s
oil temperature
over-high
Version2010
Angel(0)
110kV
110kV
Stop
Qualified
Qualified
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
44
DOC.NOHN/QEH.-0819
protection
Winding
temperature
over-high
protection 1
Winding
temperature high
protection 1
26Q.26W.63.
71Q1.71Q2.96B
Version2010
Heavy
gas protection 1
110kV
shutdown
110kV
shutdown
Qualified
Qualified
110kV
shutdown
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
45
DOC.NOHN/QEH.-0819
.96P
MT
non-electricity
gas protection
shutdown
pressure release
oil temperature
high protection
Version2010
110kV
shutdown
Qualified
Qualified
110kV
shutdown
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
46
DOC.NOHN/QEH.-0819
shutdown
Trip 110kV bus section CB
Light
gas protection 1
Winding
temperature high
protection 1
Version2010
110kV
Qualified
Qualified
110kV
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
47
DOC.NOHN/QEH.-0819
Break check of
voltge loop
Version2010
110kV
Qualified
Qualified
110kV
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
48
DOC.NOHN/QEH.-0819
side CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB
Break check of
current loop
110kV
Qualified
Qualified
CB three-phase
operation box
malfunction protection
action normal
blocking
protection
action normal
Qualified
Qualified
Regulators
Debugging time 2012-4-1
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
49
DOC.NOHN/QEH.-0819
1# B
Name of panel: T1 Main Transfomer Protection Cabinet B
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
50
DOC.NOHN/QEH.-0819
Result
220V
110V220V
110V
Check working power supply of all protection unit
Result
Qualified
Qualified
Qualified
Qualified
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
Qualified
Qualified
DC220V
110VAC220V
110V
Version2010
/ Released/Revised On 201006
Revised State1
51
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
14
//
Qualified
Qualified
15
Version2010
/ Released/Revised On 201006
Revised State1
52
DOC.NOHN/QEH.-0819
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Protection unit
parameter
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Ia 0.999A Ib1.000A
Ic1.000A
Standard measure
7SJ622
Plant service
protector
7SJ622
Ua 63.48 V Ub 63.48 V
Uc 63.49 V
Ia 300 A
Ib 300 A
Ic 300 A
TV
11
kV/110V Ua 6.35
TA 300 /1
Cos=0.865
Uc 6.35
kV Ub 6.35
kV
kV
7SJ632
Main
Tran.reservel
protection
device7SJ632
Ic1.001A
Ua63.50V Ub63.50V
Uc63.49V
Ia300A
Ib300A
Ic300A
TV 110 kV/110V
Ua63kV
TA 300 /1
Uc63kV
Cos=0.865
Uab110kV
Ub63kV
Ubc110kV
Uca110kV
P(49730W ) Q(28570kVAR) Cos0.87
Version2010
/ Released/Revised On 201006
Revised State1
53
DOC.NOHN/QEH.-0819
7UT613
Gen.& Tran.
differential
Protection
Device7UT613
Version2010
Ia11.000A Ib11.000A
Ic11.000A
Standard measure
Ia20.999A Ib21.000A
Ic21.001A
Qualified
Qualified
Ia31.001A Ib31.000A
Ic30.999A
/ Released/Revised On 201006
Revised State1
54
DOC.NOHN/QEH.-0819
I11.2A,
t 1(2s)
110kV
50/51N
Transformer
110kv
two-section
zero-sequence
current
Version2010
I10.2A,
t 1( 0.5s )
Action
I1.21A, t1(2s )
110kV
send anticipating signal
I2.01A, t2(0s )
110KV
110kV
send anticipating signal
Start G2 50BF
shutdown
Trip 110kV bus section CB
0.21A
I
, t1(0.5s )
110kV
send anticipating signal
50/51
Transformer
two-section
over-current
protection(50/51)
I22A, t 2(0s )
Debugging Inpspection
Result
Result
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
55
DOC.NOHN/QEH.-0819
protection(50/51)
I20.5A,
t 2(0.1s )
0.51A
I
, t2(0.1s )
110kV
110kV
Stop
110kV
50BF
Transformer
110kv
Side
CB
malfunction
protection start
51C
Start cool fan
Version2010
110KV
110kV
send anticipating signal
Start G2 50BF
shutdown
Trip 110kV bus section CB
I1.05A,
t (0.5s )
I 2.1A, t(13.5A )
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
56
DOC.NOHN/QEH.-0819
(51C)
87GT
Gen-transformer
longitudinal
differential
protection
50/51
Plant
service
transformer
two-section
current
protection
(50/51)
Version2010
110kV
send anticipating signal
send accident signal
Trip MT high/low voltage
side CB
start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB
Silde 1
Ia=1*In
I=0.2*In
T(0s)
Angel(0)
Silde 2
Ia=0
Angel(180)
T=0s
I 1A , t
( 1S
I 1.5A , t
( 1S
110kV
110kV
Stop
110kV
send anticipating signal
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Revised State1
57
DOC.NOHN/QEH.-0819
26
Plant
service
transformer
non-electricity
protection (26)
temperature
over-high
protection 1
High
temperature
protection 1
Break check of
current loop
Version2010
110kV
send anticipating signal
110kV
Stepout deexcitation
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
58
DOC.NOHN/QEH.-0819
malfunction protection
action normal
CB three-phase
operation box
Regulators
Debugging time 2012-3-21
Qualified
Qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
59
DOC.NOHN/QEH.-0819
2# A
Name of panel: T2 Main Transfomer Protection Cabinet A
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
60
DOC.NOHN/QEH.-0819
Result
220V
110V220V
110V
Check working power supply of all protection unit
Result
Qualified
Qualified
Qualified
Qualified
DC220V
110VAC220V
110V
7UT613
Device type chenking: the type is
drawing type.
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
Qualified
Qualified
Version2010
7UT613
respectively, conform to
/ Released/Revised On 201006
Revised State1
61
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
14
//
Qualified
Qualified
15
Version2010
/ Released/Revised On 201006
Revised State1
62
DOC.NOHN/QEH.-0819
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Main Tran.
differential
protection device
7UT613
(DC220V)
Debugging
Result
Inpspection
Result
Ia10.999 A Ib11.001 A
Ic1 0.999 A
Standard measure
Ia21.000 A Ib21.000 A
Ic2 1.0001 A
Qualified
Qualified
Ia31.001 A Ib31.000A
Ic30.999 A
Version2010
Action
/ Released/Revised On 201006
Debugging Inpspectio
Result
n Result
Revised State1
63
DOC.NOHN/QEH.-0819
49
main
transformer
over-load
protection
neutral
point
clearance
zero-sequence
current
protection
t051N
Version2010
I 1In
I0.4A, t( 2s
I1.5A , t(0s
I0.5A, t( 2s )
110kV
110kV
Qualified
Qualified
110kV
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
64
DOC.NOHN/QEH.-0819
neutral
point
clearance
zero-sequence
current
protection
T151N
t0
T1 overcurrent
Prot.t0
Version2010
I 1A , t( 1.2s )
I(
1.2In
), t
0.3s
I1.1A, t(1.2s )
I(
0.8A
), t
0.3s
110kV
110kV
Stop
Qualified
Qualified
110kV
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
65
DOC.NOHN/QEH.-0819
t1
T1 overcurrent
Prot.t1
87T
Transformer
longitudinal
differential
protection
87T
Version2010
I 2In , t
(
0.1s )
I1.2A , t
( 0.1s
Silde 1
Ia=1*In
I=0.2*In
T(0s)
Angel(0)
Silde 2
Ia=0
Angel(180)
T=0s
110kV
110kV
Stop
Qualified
Qualified
110kV
110kV
Stop
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
66
DOC.NOHN/QEH.-0819
oil temperature
over-high
protection
Winding
temperature
over-high
protection 1
Winding
temperature high
protection 1
Version2010
110kV
shutdown
Qualified
Qualified
110kV
shutdown
Qualified
Qualified
110kV
shutdown
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
67
DOC.NOHN/QEH.-0819
Heavy
gas protection 1
26Q.26W.63.
71Q1.71Q2.96B
.96P
MT
non-electricity
gas protection
pressure release
oil temperature
high protection
Version2010
110kV
shutdown
Qualified
Qualified
110kV
shutdown
Qualified
Qualified
110kV
shutdown
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
68
DOC.NOHN/QEH.-0819
Light
gas protection 1
Winding
temperature high
protection 1
Version2010
110kV
Qualified
Qualified
110kV
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
69
DOC.NOHN/QEH.-0819
Break check of
voltge loop
Version2010
110kV
Qualified
Qualified
110kV
Qualified
Qualified
110kV
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
70
DOC.NOHN/QEH.-0819
Break check of
current loop
110kV
Qualified
Qualified
CB three-phase
operation box
malfunction protection
action normal
blocking
protection
action normal
Qualified
Qualified
Regulators
Debugging time 2012-3-25
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
71
DOC.NOHN/QEH.-0819
2# B
Name of panel: T2 Main Transfomer Protection Cabinet B
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Debugging
Inpspection
Revised State1
72
DOC.NOHN/QEH.-0819
Result
220V
110V220V
110V
Check working power supply of all protection unit
Result
Qualified
Qualified
Qualified
Qualified
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
2110V
380V
5%
3
0
3
Qualified
Qualified
DC220V
110VAC220V
110V
Version2010
/ Released/Revised On 201006
Revised State1
73
DOC.NOHN/QEH.-0819
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
14
//
Qualified
Qualified
15
Version2010
/ Released/Revised On 201006
Revised State1
74
DOC.NOHN/QEH.-0819
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Protection unit
parameter
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Ia1.000A Ib0.999A
Ic1.000A
Standard measure
7SJ622
Plant service
protector
7SJ622
Ua 63.48 V Ub 63.49V
Uc 63.48 V
Ia 300 A
Ib 300 A
Ic 300 A
TV
11
kV/110V Ua 6.35
TA 300 /1
Cos=0.865
Uc 6.35
kV Ub 6.35
kV
kV
7SJ632
Main
Tran.reservel
protection
device7SJ632
Ic1.000A
Ua63.48V Ub63.47V
Uc63.48V
Ia300A
Ib300A
Ic300A
TV 110 kV/110V
Ua63kV
TA 300 /1
Uc63kV
Cos=0.865
Uab110kV
Ub63kV
Ubc110kV
Uca110kV
P(49720W ) Q(28584kVAR) Cos0.87
Version2010
/ Released/Revised On 201006
Revised State1
75
DOC.NOHN/QEH.-0819
7UT613
Gen.& Tran.
differential
Protection
Device7UT613
Version2010
Ia11.001A Ib11.000A
Ic10.999A
Standard measure
Ia20.999A Ib21.000A
Ic21.000A
Qualified
Qualified
Ia31.001A Ib31.000A
Ic31.000A
/ Released/Revised On 201006
Revised State1
76
DOC.NOHN/QEH.-0819
I11.2A,
t 1(2s)
110kV
50/51N
Transformer
110kv
two-section
zero-sequence
current
Version2010
I10.2A,
t 1( 0.5s )
Action
I1.21A, t1(2s )
110kV
send anticipating signal
I2.01A, t2(0s )
110KV
110kV
send anticipating signal
Start G2 50BF
shutdown
Trip 110kV bus section CB
0.21A
I
, t1(0.5s )
110kV
send anticipating signal
50/51
Transformer
two-section
over-current
protection(50/51)
I22A, t 2(0s )
Debugging Inpspection
Result
Result
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
77
DOC.NOHN/QEH.-0819
protection(50/51)
I20.5A,
t 2(0.1s )
0.51A
I
, t2(0.1s )
110kV
110kV
Stop
110kV
50BF
Transformer
110kv
Side
CB
malfunction
protection start
51C
Start cool fan
Version2010
110KV
110kV
send anticipating signal
Start G2 50BF
shutdown
Trip 110kV bus section CB
I1.05A,
t (0.5s )
I 2.1A, t(13.5A )
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
78
DOC.NOHN/QEH.-0819
(51C)
87GT
Gen-transformer
longitudinal
differential
protection
50/51
Plant
service
transformer
two-section
current
protection
(50/51)
Version2010
110kV
send anticipating signal
send accident signal
Trip MT high/low voltage
side CB
start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB
Silde 1
Ia=1*In
I=0.2*In
T(0s)
Angel(0)
Silde 2
Ia=0
Angel(180)
T=0s
I 1A , t
( 1S
I 1.5A , t
( 1S
110kV
110kV
Stop
110kV
send anticipating signal
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Revised State1
79
DOC.NOHN/QEH.-0819
26
Plant
service
transformer
non-electricity
protection (26)
temperature
over-high
protection 1
High
temperature
protection 1
Break check of
current loop
Version2010
110kV
send anticipating signal
110kV
Stepout deexcitation
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
80
DOC.NOHN/QEH.-0819
malfunction protection
action normal
CB three-phase
operation box
Regulators
Debugging time 2012-4-4
Qualified
Qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
81
DOC.NOHN/QEH.-0819
110kV
Name of panel: 110kV Busbar Protection Cabinet
I. Integrate part
No.
Item
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
82
DOC.NOHN/QEH.-0819
Debugging
Result
220V
110V220V
110V
Check working power supply of all protection unit
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
DC220V
110VAC220V
110V
7UT635
Device type chenking: the type is
drawing type.
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
Qualified
Qualified
Version2010
7UT635
respectively, conform to
/ Released/Revised On 201006
Revised State1
83
DOC.NOHN/QEH.-0819
2110V
380V
5%
3
0
3
30 .45 .60 .90 I
3
Data detection:
25
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
26
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
27
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
84
DOC.NOHN/QEH.-0819
14
//
Qualified
Qualified
15
;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
85
DOC.NOHN/QEH.-0819
Side1
Ia=1A
Ib=1A
Ic=1A
110Kv I
87B1/87B2
110kv I section
bus
DP(87B1/87B2)
Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A
Side1
Ia=1A
Ib=1A
Ic=1A
Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A
T=0s
Side1
Ia=1A
Ib=1A
Ic=1A
110Kv II
87B1/87B2
110kv II section
bus
DP
(87B1/87B2)
Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A
Side1
Ia=1A
Ib=1A
Ic=1A
Slide2
Ia=0A
Ib=0A
Ic=0A
Slide3
Ia=0A
Ib=0A
Ic=0A
T=0s
Version2010
Debugging Inpspection
Result
Result
Action
110kV
send anticipating signal
110kV
send anticipating signal
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Revised State1
86
DOC.NOHN/QEH.-0819
malfunction
Stop
Break check of
voltage loop
Stepout deexcitation
send accident signal
shut down
Stepout
deexcitation
Stepout
send anticipating signal
Qualified
Qualified
Break check of
current loop
Stepout deexcitation
send accident signal
shut down
Stepout
deexcitation
Stepout
send anticipating signal
Qualified
Qualified
Regulators
Debugging time 2012-4-8
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
87
DOC.NOHN/QEH.-0819
110kV
Name of panel: 110kV Busbar Connect protect Cabinet
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
88
DOC.NOHN/QEH.-0819
Debug
Conclusion
Inpspection
Result
Qualified
Qualified
7SJ622
Qualified
Qualified
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
Qualified
Qualified
No.
220V
110V220V
110V
Check working power supply of all protection unit
DC220V
110VAC220V
110V
Version2010
/ Released/Revised On 201006
Revised State1
89
DOC.NOHN/QEH.-0819
2110V
380V
5%
3
0
3
30 .45 .60 .90 I
3
Data detection:
28
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
29
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
30
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
90
DOC.NOHN/QEH.-0819
14
//
Qualified
Qualified
15
;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
91
DOC.NOHN/QEH.-0819
Busbar
Connection Bay
Protection
Device7SJ622
(DC220V)
Protection unit
parameter
Standard measure
TA 100 /1
TA ratio 100 /1
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
2.
Protection unit action data and antion type record
Protection
type
110Kv
50/51
110Kv
busbar
two sections
of overcurrent
protection
50/51
Version2010
Setting
value
I1 2 , t
1( 0.2s )
Action
value
Action
110kV
110kV
send anticipating signal
/ Released/Revised On 201006
Debugging
Result
Inpspection
Result
Qualified
Qualified
Revised State1
92
DOC.NOHN/QEH.-0819
110kV
110kV
I2 1A , t
2( 0.5s
110Kv
110Kv
busbar
charging
protection
110kV
50BF
110kV
subsection
CB
malfunction
Start protection
50BF
Version2010
I1.5A, t
( 0.3s
I 1.1A ,
t2( 0.5s
I 1.5A , t( 0.3s )
110kV
110kV
send anticipating signal
110kV
110kV
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
93
DOC.NOHN/QEH.-0819
current circuit
break line check
Stepout deexcitation
send accident signal
shut down
Stepout
deexcitation
Stepout
Qualified
Qualified
CB three-phase
operation box
malfunction
protection
action normal
latch-up protection action
normal
PT
PT
paralleling
device
Device working
power supply
disappear
Version2010
A.B.C
A.B.C
A.B.C
Qualified
Qualified
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
94
DOC.NOHN/QEH.-0819
A.B.C
A.B.C
A.B.C
Keep primary state
Stepout state
Process paralleling
A.B.C
A.B.C
A.B.C
When bas
section CB is
tripped or
disconnector is
break
Version2010
/ Released/Revised On 201006
Qualified
Qualified
Qualified
Qualified
Revised State1
95
DOC.NOHN/QEH.-0819
Regulators
Debugging time 2012-4-10
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
96
DOC.NOHN/QEH.-0819
110kV L1
Name of panel: 110kV L1 Line Differential Protection Cabinet
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
97
DOC.NOHN/QEH.-0819
No.
220V
110V220V
110V
Check working power supply of all protection unit
Debug
Conclusion
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
DC220V
110VAC220V
110V
7SD610 7SJ624
Device type chenking: the type is
conform to drawing type.
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
Qualified
Qualified
Version2010
7SD610 7SJ624
respectively,
/ Released/Revised On 201006
Revised State1
98
DOC.NOHN/QEH.-0819
2110V
380V
5%
3
0
3
30 .45 .60 .90 I
3
Data detection:
31
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
32
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
33
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
99
DOC.NOHN/QEH.-0819
14
//
Qualified
15
;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Qualified
1.
Test data recording of protection measurement & control unit
Line
optical
differential
protection
device7SD610
(DC220V)
Line reservel
protection
device7SJ624
Version2010
Protection unit
parameter
Standard measure
Ia1.000A Ib 1.001 A
Ic0.999A
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Ia.999A Ib1.000 A
Standard measure
Ic1.000A
Ua63.49V Ub63.48V
Uc63.48V
/ Released/Revised On 201006
Revised State1
100
DOC.NOHN/QEH.-0819
Ia 600 A
(DC220V)
Ib 600
Ic 600 A
TV
110 kV/110V
TA 600 /1
Cos=0.865
Ua63.5 kV Ub63.5kV
Qualified
Uc63.5kV
Uab110kV Ubc110kV
Qualified
Uca110kV
P(98292Kw ) Q(57161Kvar ) Cos0.86
2.
Protection unit action data and antion type record
Protection
type
Setting
value
T1=0.5
Action
value
Debugging
Result
Inpspection
Result
T1=0.5
110kV 1
110kV 1
110kV 1
110kV
Qualified
Qualified
T2=0.5s
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB
Qualified
Qualified
110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79
T2=0.5s
Version2010
Action
/ Released/Revised On 201006
Revised State1
101
DOC.NOHN/QEH.-0819
malfunction
blocking reclosing
Trip 110kV bus section CB
U120V, t(0.5s )
110kV 1
/
25/79
110kV circuit 1
overvoltage/
low-voltage
protection
25/79
U75v, t(1.5 )
I 2.5A , t
110kV 1
50/51N
110kV circuit 1
two-section
zero-sequence
current
protection
50/51N
( 0.1s )
I 0.5A , t
( 1.9s )
Version2010
110kV 1
110kV 1
110kV 1
110kV
Qualified
Qualified
I2.6A , t (0.1s )
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
I0.6A , t (1.9s )
110kV 1
110kV 1
110kV 1
110kV
Qualified
Qualified
U122V, t (0.5s )
U70v, t (1.5s )
/ Released/Revised On 201006
Revised State1
102
DOC.NOHN/QEH.-0819
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
110kV 1
85/87L
110kV circuit 1
longitudinal
differential
protection
85/87L
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
110kV 1
110kV circuit 1
voltage circuit
Qualified
Qualified
110kV 1
67/67Ncc
110kV circuit 1
directional
current
protection
67/67N
Version2010
I 4A , t
( 0.3s
I 4.1A ,
t( 0.3s
/ Released/Revised On 201006
Revised State1
103
DOC.NOHN/QEH.-0819
break
inspection
110kV
line
110kV
send anticipating signal
send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB
110kV 1
110kV circuit 1
current circuit
break
line
inspection
Regulators
Debugging time 2012-4-12
Qualified
Qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
104
DOC.NOHN/QEH.-0819
110kV L2
Name of panel: 110kV L1 Line Differential Protection Cabinet
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
105
DOC.NOHN/QEH.-0819
No.
220V
110V220V
110V
Check working power supply of all protection unit
Debug
Conclusion
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
DC220V
110VAC220V
110V
7SD610 7SJ624
Device type chenking: the type is
to drawing type.
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
Qualified
Qualified
Version2010
7SD610 7SJ624
respectively, conform
/ Released/Revised On 201006
Revised State1
106
DOC.NOHN/QEH.-0819
2110V
380V
5%
3
0
3
30 .45 .60 .90 I
3
Data detection:
34
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
35
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
36
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
107
DOC.NOHN/QEH.-0819
14
//
Qualified
15
;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Qualified
1.
Test data recording of protection measurement & control unit
Line
optical
differential
protection
device7SD610
(DC220V)
Line reservel
protection
device7SJ624
Version2010
Protection unit
parameter
Standard measure
Ia0.999A Ib1.001A
Ic0.999A
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Ia1.000A Ib1.00A
Standard measure
Ic1.001A
Ua63.49V Ub63.48V
Uc63.48V
/ Released/Revised On 201006
Revised State1
108
DOC.NOHN/QEH.-0819
Ia 600 A
(DC220V)
Ib 600
Ic 600 A
TV
110 kV/110V
TA 600 /1
Cos=0.865
Ua63.5 kV Ub63.5kV
Qualified
Uc63.5kV
Uab110kV Ubc110kV
Qualified
Uca110kV
P(98894Kw ) Q(57156Kvar ) Cos0.86
Version2010
/ Released/Revised On 201006
Revised State1
109
DOC.NOHN/QEH.-0819
2.
Protection unit action data and antion type record
Protection
type
Setting
value
T1=0.5
Action
value
Debugging
Result
Inpspection
Result
T1=0.5
110kV 1
110kV 1
110kV 1
110kV
Qualified
Qualified
T2=0.5s
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB
Qualified
Qualified
U122V, t (0.5s )
110kV 1
110kV 1
110kV 1
Qualified
Qualified
110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79
T2=0.5s
110kV 1
/
25/79
110kV circuit 1
overvoltage/
Version2010
U120V, t(0.5s )
Action
/ Released/Revised On 201006
Revised State1
110
DOC.NOHN/QEH.-0819
U70v, t (1.5s )
110kV
I2.6A , t (0.1s )
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
I0.6A , t (1.9s )
110kV 1
110kV 1
110kV 1
110kV
Qualified
Qualified
low-voltage
protection
25/79
U75v, t(1.5 )
I 2.5A , t
( 0.1s )
110kV 1
50/51N
110kV circuit 1
two-section
zero-sequence
current
protection
50/51N
I 0.5A , t
( 1.9s )
Version2010
/ Released/Revised On 201006
Revised State1
111
DOC.NOHN/QEH.-0819
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
110kV 1
85/87L
110kV circuit 1
longitudinal
differential
protection
85/87L
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
110kV 1
110kV circuit 1
voltage circuit
break
line
inspection
110kV
Qualified
Qualified
110kV 1
67/67Ncc
110kV circuit 1
directional
current
protection
67/67N
Version2010
I 4A , t
( 0.3s
I 4.1A ,
t( 0.3s
/ Released/Revised On 201006
Revised State1
112
DOC.NOHN/QEH.-0819
shutdown
Trip 110kV bus section CB
110kV
send anticipating signal
send accident signal
Trip MT high/low voltage side
CB
Start low voltage side CB
malfunction
shutdown
Trip 110kV bus section CB
110kV 1
110kV circuit 1
current circuit
break
line
inspection
Regulators
Debugging time 2012-4-1
Qualified
Qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
113
DOC.NOHN/QEH.-0819
110kV L1
Name of panel: 110kV L1 Line Distance Protection Cabinet
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
114
DOC.NOHN/QEH.-0819
Debug
Conclusion
Inpspection
Result
Qualified
Qualified
7SA611
Qualified
Qualified
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
Qualified
Qualified
No.
220V
110V220V
110V
Check working power supply of all protection unit
DC220V
110VAC220V
110V
Version2010
/ Released/Revised On 201006
Revised State1
115
DOC.NOHN/QEH.-0819
2110V
380V
5%
3
0
3
30 .45 .60 .90 I
3
Data detection:
37
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
38
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
39
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
116
DOC.NOHN/QEH.-0819
14
//
Qualified
15
;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Qualified
1.
Test data recording of protection measurement & control unit
Protection unit
parameter
Line reservel
protection
device7SJ624
(DC220V)
Ic0.999A
Standard measure
Ua63.42V
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Ib0.999A
Ub63.36V
Uc63.39V
Ia 600 A
Ib 600
Ic 600 A
TV
110
TA 600 /1
Cos=0.865
Uc63.5kV
Uab110kV Ubc110kV
Uca110kV
P(98480Kw ) Q(57164Kvar ) Cos0.86
Version2010
/ Released/Revised On 201006
Revised State1
117
DOC.NOHN/QEH.-0819
2.
Protection unit action data and antion type record
Protection
type
Setting
value
T1=0.5S
Action
value
Action
110kV 1
110kV 1
110kV 1
110kV
T1=0.5
110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79
110kV 1
110kV 1
110kV 1
110kV
T2=0.5S
T2=0.5S
110kV 1
50/51N
Version2010
I 2A , t
( 0.1S
I 2.1A , t
( 0.1S
110kV 1
110kV 1
/ Released/Revised On 201006
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
118
DOC.NOHN/QEH.-0819
110kV 1
110kV
send anticipating signal
110kV circuit 1
two-section
overcurrent and
zero-sequence
current
protection
50/51N
I 0.5A , t
( 1.5S
110kV 1
67/67Ncc
110kV circuit 1
directional
current
protection
67/67N
Version2010
I1.5A, t
( 0.5S
I0.6A , t
( 1.5S
I1.6A ,
t(0.5S
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
119
DOC.NOHN/QEH.-0819
110kV 1
85-21
110kV circuit 1
longitudinal
differential
protection 85
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB
Qualified
Qualified
110kV 1
110kV circuit 1
voltage circuit
break
line
inspection
110kV
Qualified
Qualified
110kV 1
110kV circuit 1
current circuit
break
line
inspection
110kV
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
120
DOC.NOHN/QEH.-0819
/Distance
protection
(phase / ground)
(21/21N)
R=10.0 Ohm
X=10.5Ohm
RG=3.0Ohm
Regulators
Debugging time 2012-3-26
U=20V
I=10A
110kV
send anticipating signal
shutdown
Qualified
Qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
121
DOC.NOHN/QEH.-0819
110kV L2
Name of panel: 110kV L1 Line Distance Protection Cabinet
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
122
DOC.NOHN/QEH.-0819
Debug
Conclusion
Inpspection
Result
Qualified
Qualified
7SA611
Qualified
Qualified
Check keypress, ensuring sensitive and effective key and correct key name.
Qualified
Qualified
.., I
Check if LCD display is normal, without black screen, incomplete strokes, black
strip etc. LCD backlight brightness is set unanimously
Qualified
Qualified
I
Check if software edition number in LCD display is conform to the drawing
Qualified
Qualified
I
I
Detect time setting and background monitoring system time hack.Time is
normal after some time. Restore power after electricity is cut off, and time is
normal in cut-off period.
Qualified
Qualified
.
Detect valuing modification and conservation normal.
Qualified
Qualified
.
Check sampling function, displaying correct amplitude, phase, DC deviant of AC
anolog quantity in real-time.
Qualified
Qualified
Qualified
Qualified
10
Qualified
Qualified
11
15A 1A
5%
0.2In 0.1In 10%
Qualified
Qualified
No.
220V
110V220V
110V
Check working power supply of all protection unit
DC220V
110VAC220V
110V
Version2010
/ Released/Revised On 201006
Revised State1
123
DOC.NOHN/QEH.-0819
2110V
380V
5%
3
0
3
30 .45 .60 .90 I
3
Data detection:
40
Input rated current 5A or 1A
in current sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%). AC analog quantity error is lesser than 10% at 0.2In and
0.1In
41
Input rated voltage110V
380Vin voltage sampling loop.
Circumscribed device measured value after ratio conversion is compared
with the displayed value, which is in the requirements of range (error no
more than 5%).
42
Check displayed angle.Access three-phase current and three-phase
voltage in input terminal of protective device three-phase current and
three-phase voltage. They are rated value.The phase difference of each
phase voltage and current is 0.The error between protective device
measured value and circumscribed measuring instrument value not exceed
3Change phase angle, to 30.45.60.90,and measure phase angle
respectively,error within 3.
12
I
5min.
0.01In. 0.05V
Qualified
Qualified
13
Protection and connecting sheet of test part is on, and untested protection and
connecting sheet is off. Access analog CB and put fault voltage and current on
test part protection, making it in action state. Protective outlet contact state
and signal lamp indication state is normal, and DO connecting sheet is effective.
Deflection situation of LCD displayed contact is normal, and accident alarm and
fault alarm contact output are normal.(Notes: according to drawing, set outlet
Trip, checking if output is corresponding. )
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
124
DOC.NOHN/QEH.-0819
14
//
Qualified
15
;
1.
2.
3.
Power test:
1. AC/DC power supply can be in reliable action at limit condition.
2. If positive/negative terminal of DC power supply reverse, device is without
damage.
3. if AC is on suddenly, or sudden power malfunction, or power voltage
rise/descend slowly, device is not in an false action.
Qualified
Qualified
Qualified
1.
Test data recording of protection measurement & control unit
Protection unit
parameter
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Ia0.999A Ib0.999 A
Ic1.000A
Standard measure
Line reservel
protection
device7SJ624
(DC220V)
Ua63.48V Ub63.47V
Uc63.48V
Ia 600 A
Ib 600
Ic 600 A
TV
110
TA 600 /1
Cos=0.865
Uc63.5kV
Uab110kV Ubc110kV
Uca110kV
P(98432Kw ) Q(57146Kvar ) Cos0.86
Version2010
/ Released/Revised On 201006
Revised State1
125
DOC.NOHN/QEH.-0819
2.
Protection unit action data and antion type record
Protection
type
Setting
value
T1=0.5S
Action
value
Action
110kV 1
110kV 1
110kV 1
110kV
T1=0.5
110kV 1
I
25/79
110kV circuit 1
three-phase
primary
reclosure
25/79
110kV 1
110kV 1
110kV 1
110kV
T2=0.5S
T2=0.5S
110kV 1
Version2010
I 2A , t
( 0.1S
I 2.1A , t
( 0.1S
110kV 1
/ Released/Revised On 201006
Debugging
Result
Inpspection
Result
Qualified
Qualified
Qualified
Qualified
Qualified
Qualified
Revised State1
126
DOC.NOHN/QEH.-0819
50/51N
110kV circuit 1
two-section
overcurrent and
zero-sequence
current
protection
50/51N
110kV 1
110kV 1
110kV
send anticipating signal
I 0.5A , t
( 1.5S
110kV 1
67/67Ncc
110kV circuit 1
directional
current
protection
67/67N
Version2010
I1.5A, t
( 0.5S
I0.6A , t
( 1.5S
I1.6A ,
t(0.5S
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
Qualified
Qualified
/ Released/Revised On 201006
Revised State1
127
DOC.NOHN/QEH.-0819
110kV 1
85-21
110kV circuit 1
longitudinal
differential
protection 85
110kV 1
110kV 1
110kV 1
110kV
send anticipating signal
send accident signal
Trip 110kV circuit 1 CB
closing 110kV circuit 1 CB
Start 110kV circuit 1 CB
malfunction
blocking reclosing
Trip 110kV bus section CB
Qualified
Qualified
110kV 1
110kV circuit 1
voltage circuit
break
line
inspection
110kV
Qualified
Qualified
110kV 1
110kV circuit 1
current circuit
break
line
inspection
110kV
Qualified
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
128
DOC.NOHN/QEH.-0819
malfunction
shutdown
Trip 110kV bus section CB
/Distance
protection
(phase / ground)
(21/21N)
R=10.0 Ohm
X=10.5Ohm
RG=3.0Ohm
Regulators
Debugging time 2012-3-29
U=20V
I=10A
110kV
send anticipating signal
shutdown
Qualified
Qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
129
DOC.NOHN/QEH.-0819
1# LCULCU1A/B
Name of panel: Unit 1 LCULCU1Cabinet A/B
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50MBetween normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
130
DOC.NOHN/QEH.-0819
Debug
Conclusion
Inpspection
Result
CPU I
6ES74123HJ140AB0
2
Check if CPU module type of PLC is consistent with drawing design:
Type: 6ES74123HJ140AB0;
Module No.:2
qualified
qualified
1. 6ES74070KR020AA0
2
2.220V 110V
24V
5V
3..
Check if working power level of power module conforms to drawing design:
1. type: 6ES74070KR020AA0 ( 2 ) in total
2. operating voltage:
220V 110V
24V
3. check if input/output voltage and indicating lamp is normal
qualified
qualified
qualified
qualified
1.
1. 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.
10
3. II
1.input module checking, type:
(1). 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.number: 10
3.check if module input indicating lamp and input signal comform to drawing
qualified
qualified
1.6ES7322BL000AA0
2.
3
qualified
qualified
No.
PLC TYPE
1. CPU
2.
3.
4.
5..
1. Check if PLC CPU module indicating lamp is normal;
2.check communication with background: serial Ethernet
Version2010
/ Released/Revised On 201006
Revised State1
131
DOC.NOHN/QEH.-0819
3.
6ES7331KF020AB0
5
6
Check analog quantity acquisition module type: YES
NO
Current mode
voltage mode
Type: 6ES7331KF020AB0
( 5 )in total
NO
qualified
qualified
qualified
qualified
MT-8121T
Type: MT-8121T
qualified
qualified
Check if PLC communication and indicating lamp are normal; alarm window be
displayed automatically, alarm content conforms to actual alarm signal.
qualified
qualified
qualified
qualified
PLC
Check if DI signal conforms to drawing and PLC input point; data display of
monitoring pictures is correct;
qualified
qualified
qualified
qualified
qualified
qualified
Check if background monitoring system can adjust time with PLC correctly;
qualified
qualified
Check if function menu and function key are effective and available, contact
points without shift;
qualified
qualified
10
P(
) Q(
2.8MW
Uab
11 kV
11
3.4MW
3.4MW
) Q(
20
Version2010
2.8MW
qualified
qualified
) Uab 11 kV
mA
/ Released/Revised On 201006
qualified
qualified
Revised State1
132
DOC.NOHN/QEH.-0819
meter: YES
NO
CP-T96
0-150v
vlotagemeter: YES
qualified
qualified
CP-F96
qualified
qualified
5%
qualified
qualified
qualified
qualified
CP-S96-N/110V
Type: CP-S96-N/110V
Version2010
/ Released/Revised On 201006
Revised State1
133
DOC.NOHN/QEH.-0819
1.
2.
3. 0
30
Detection method:
1.only input voltage in to-be sync. side, and voltage and frequency pointer
deviate upward;
2. only input voltage in system side, and voltage and frequency pointer deviate
downward;
3. input the same voltage in two sides, and voltage and frequency pointer is
horizontal, phase angle pointer to about 0; if angle changes, pointer advance or
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Manual synchronism: YES
NO
...
Input system voltage and to-be sync.voltage, check if system voltage,
frequency, to-be sync.voltage and frequency meter are indicated when
switching to manual synchronism.
2
When not achieving synchronizing conditions, it be without closing output;
When achieving synchronizing conditions, it can
Synchronizing closing.
3
In the test, Regardless of achieving synchronizing conditions, it can be
closing output.
NO
DZZB-5
1
1
Type: DZZB-5
No.:1
2
LCD display or nixie tube indicate clearly, with sensitive button, and all kinds of
state indication is right;
3
Version2010
/ Released/Revised On 201006
Revised State1
134
DOC.NOHN/QEH.-0819
5%
input rated voltage in input terminal, and the error of automatic synchronizm
value and circumscribed measuring instrument value is not more than 5%
:
Outlet relay type: YES
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
NO
1
MK3P-I(220V)
36 2+82RCL42404 DC24V
2
Type1: MK3P-I(220V)No.: 36 Type2: RCL42404 DC24V No.:2+82
2
All output contact N.O./N.C.conforms to drawing, and contact output
reliable action
Control switch and button.: YES
NO
1LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/r
1+2+1+1
1
Type1: LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/rNo.: 1 +2+2+2
....
/
All Control switches can operate normally, e.g.,test,synchronized on, accident
2
reset,
opening
increase/decrease,excitation
increase/decrease,CB
opening/closing, contact reliable closing/breaking.
AD16-22/R28 AD16-22D/RG23
2 +1
1
Type: AD16-22/R28 AD16-22D/RG23
No.:2+1
qualified
Check if type and voltage class conform to layout design, and lable name
correspond to drawing and actual signal, luminous evenly,
Type of Switching power supply: YES
NO
PF-500-24V
Type: PF-500-24V
No.:3
AC/DC will be mutual standby: YES
NO
Version2010
/ Released/Revised On 201006
Revised State1
135
DOC.NOHN/QEH.-0819
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Alarm:
YES
NO
1
BJ-1I
Type: BJ-1I
1
No.:1
NO
NC608-4M
1
1
Type: NC608-4M
No.:1
..
2
Check if device type conforms to layout design (including communication
superviser,serial server,optical fiber communication device,etc.)
3
Check if communication with other device and background is normal
2
Regulators
Debugging time 2012-4-14
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
136
DOC.NOHN/QEH.-0819
2# LCULCU2A/B
Name of panel: Unit 2 LCULCU2Cabinet A/B
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50MBetween normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
137
DOC.NOHN/QEH.-0819
Debug
Conclusion
Inpspection
Result
CPU I
6ES74123HJ140AB0
2
Check if CPU module type of PLC is consistent with drawing design:
Type: 6ES74123HJ140AB0;
Module No.:2
qualified
qualified
1. 6ES74070KR020AA0
2
2.220V 110V
24V
5V
3..
Check if working power level of power module conforms to drawing design:
1. type: 6ES74070KR020AA0 ( 2 ) in total
2. operating voltage:
220V 110V
24V
3. check if input/output voltage and indicating lamp is normal
qualified
qualified
qualified
qualified
1.
1. 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.
10
3. II
1.input module checking, type:
(1). 6ES7321BL000AA0
(2) 6ES7321BH010AB0
2.number: 10
3.check if module input indicating lamp and input signal comform to drawing
qualified
qualified
1.6ES7322BL000AA0
2.
3
qualified
qualified
No.
PLC TYPE
1. CPU
2.
3.
4.
5..
1. Check if PLC CPU module indicating lamp is normal;
2.check communication with background: serial Ethernet
Version2010
/ Released/Revised On 201006
Revised State1
138
DOC.NOHN/QEH.-0819
3.
6ES7331KF020AB0
5
6
Check analog quantity acquisition module type: YES
NO
Current mode
voltage mode
Type: 6ES7331KF020AB0
( 5 )in total
NO
qualified
qualified
qualified
qualified
MT-8121T
Type: MT-8121T
qualified
qualified
Check if PLC communication and indicating lamp are normal; alarm window be
displayed automatically, alarm content conforms to actual alarm signal.
qualified
qualified
qualified
qualified
PLC
Check if DI signal conforms to drawing and PLC input point; data display of
monitoring pictures is correct;
qualified
qualified
qualified
qualified
qualified
qualified
Check if background monitoring system can adjust time with PLC correctly;
qualified
qualified
Check if function menu and function key are effective and available, contact
points without shift;
qualified
qualified
10
P(
) Q(
2.8MW
Uab
11 kV
11
3.5MW
3.5MW
) Q(
Version2010
2.8MW
qualified
qualified
Uab 11 kV
/ Released/Revised On 201006
Revised State1
139
DOC.NOHN/QEH.-0819
20 mA
1 100 2 100 3 100 4100 5100
6100 7100 8100 9100 10100
11100 12100 13100 14100 15100
16100 17100 18100 19100 20100
21100 22100 23100 24100 25100
26100 27100 28100 29100 30100
31100 32100 33100 34100 35100
36100 37100 38100 39100 40100
RTD PT100:
120
153 253 353 453 553 653
753 853 953 1053 1153
1253 1353 1453 1553 1653
qualified
qualified
meter: YES
NO
CP-T96
0-150v
vlotagemeter: YES
qualified
qualified
CP-F96
qualified
qualified
5%
qualified
qualified
qualified
qualified
CP-S96-N/110V
Type: CP-S96-N/110V
Version2010
/ Released/Revised On 201006
Revised State1
140
DOC.NOHN/QEH.-0819
1.
2.
3. 0
30
Detection method:
1.only input voltage in to-be sync. side, and voltage and frequency pointer
deviate upward;
2. only input voltage in system side, and voltage and frequency pointer deviate
downward;
3. input the same voltage in two sides, and voltage and frequency pointer is
horizontal, phase angle pointer to about 0; if angle changes, pointer advance or
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Manual synchronism: YES
NO
...
Input system voltage and to-be sync.voltage, check if system voltage,
frequency, to-be sync.voltage and frequency meter are indicated when
switching to manual synchronism.
2
When not achieving synchronizing conditions, it be without closing output;
When achieving synchronizing conditions, it can
Synchronizing closing.
3
In the test, Regardless of achieving synchronizing conditions, it can be
closing output.
NO
DZZB-5
1
1
Type: DZZB-5
No.:1
2
LCD display or nixie tube indicate clearly, with sensitive button, and all kinds of
state indication is right;
Version2010
/ Released/Revised On 201006
Revised State1
141
DOC.NOHN/QEH.-0819
5%
input rated voltage in input terminal, and the error of automatic synchronizm
value and circumscribed measuring instrument value is not more than 5%
:
Outlet relay type: YES
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
NO
1
MK3P-I(220V)
36 2+82RCL42404 DC24V
2
Type1: MK3P-I(220V)No.: 36 Type2: RCL42404 DC24V No.:2+82
2
All output contact N.O./N.C.conforms to drawing, and contact output
reliable action
Control switch and button.: YES
NO
1LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/r
1+2+1+1
1
Type1: LW39-16C-B2-202A/2
LW39-16C-A2-02/1 LW39-16C-90B-22E21
LA39-B2-60Z/rNo.: 1 +2+2+2
....
/
All Control switches can operate normally, e.g.,test,synchronized on, accident
2
reset,
opening
increase/decrease,excitation
increase/decrease,CB
opening/closing, contact reliable closing/breaking.
AD16-22/R28 AD16-22D/RG23
2 +1
1
Type: AD16-22/R28 AD16-22D/RG23
No.:2+1
2
Check if type and voltage class conform to layout design, and lable name
correspond to drawing and actual signal, luminous evenly,
Type of Switching power supply: YES
NO
PF-500-24V
Type: PF-500-24V
No.:3
Version2010
/ Released/Revised On 201006
Revised State1
142
DOC.NOHN/QEH.-0819
NO
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Alarm:
YES
NO
1
BJ-1I
Type: BJ-1I
1
No.:1
NO
NC608-4M
1
1
Type: NC608-4M
No.:1
..
2
Check if device type conforms to layout design (including communication
superviser,serial server,optical fiber communication device,etc.)
3
Check if communication with other device and background is normal
2
Regulators
Debugging time 2012-4-20
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
143
DOC.NOHN/QEH.-0819
LCULCU4A/B
Name of Panel: Auxiliary LCULCU4Cabinet A/B
I. Integrate part
Number
Test
items
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the
lamp in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.
qualified
qualified
Insulation
Resistance Test
500V
50MBetween normal test
atmospheric conditions between the live parts of the
device and non-charged metal and shell, and electrical
contact circuit with open circuit voltage of 500V megger to
measure the insulation resistance value of each grade of
each loopbetween the insulation resistance of not less
than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric
conditions, the device can withstand a frequency of 50Hz,
the test voltage of 2000V, the work lasted one minute
power frequency withstand voltage test without
breakdown phenomenon of flashover and component
damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
144
DOC.NOHN/QEH.-0819
Debugging
Result
Inpspection
Result
qualified
qualified
qualified
qualified
qualified
qualified
1
Check output model model number
1. 6ES73211BL000AA0
(2) 6ES73217BH000AB0
2. Quantity
8 Blocks
3. II
Check if module input indicator light and input signal match drawings.
qualified
qualified
1
Check output model model number
1. 6ES73221BL000AA0
2. Quantity
2 Blocks
3.
qualified
qualified
Number
CPU I
Check if model number of CPU module in PLC matches the drawings.
Model 6ES74123HJ140AB0
Number of modules
2 Blocks
Check if working power supply level of power model match the drawings.
1. Model 6ES74070KR020AA0
total 2
3.
4.
5..
Version2010
/ Released/Revised On 201006
Revised State1
145
DOC.NOHN/QEH.-0819
Check if each output point matches outlet relay and drawings; check if Trip
and closing action of contacts of outlet relay is reliable.
Check type of module that collected by analog
quantity Yes
No
6
Current mode
Voltage mode
Model number
6ES7331KF020AB0
2
Blocks
Touch screen model number Yes
No
qualified
qualified
Model number
MT-8121T
qualified
qualified
qualified
qualified
Check if the interface is clear, if indicator light can work in order, if alarm
window will pop-up automatically, and if the alarm contents matches the real
alarm signal.
qualified
qualified
Check if the interface is clear, and if the project name matches the drawings.
qualified
qualified
PLC
Check if DI signal match drawings and input point of PLC, and if data of
electric quantities monitoring interface display correctly.
qualified
qualified
qualified
qualified
Check if PLC can operate correctliy or not, when detect remote operating.
qualified
qualified
Check if backstage monitoring system can compare time with PLC correctly.
qualified
qualified
Check if function menu and fuction key is effective and usable, and if the
contact has no shift.
qualified
10
qualified
qualified
11
No
20 mA
Input standards20mA current touch screen display
Data1100 Data2100 Data3100 Data4100
Data5100 Data6100 Data7100 Data8100
Data9100 Data10100 Data11100
Data12100 Data13100 Data14100
Data15100 Data16100
RTD Temperature RTD displayPT100:
120 In put 120 resistance
Data153 Data253 Data353 Data453
qualified
qualified
Version2010
/ Released/Revised On 201006
qualified
Revised State1
146
DOC.NOHN/QEH.-0819
No
Model number
ACR220E PZ96-AI3
Blocks
TD1
TD1 High Side
2
Ib 100 A Ic 100 A
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
No
Model
RCL4204 24vdc MK3P-I DC220V
67+2
All output contact normally open and normally close should accord to
drawings, the contacts should output reliable operation.
qualified
Amount
No
Model number
PF-500-24v
Amount
3
Yes
No
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Alarm Yes
No
1
Model number
BJ-1I
Check if accident alarm separate from malfunction alam, and if the sound is
both continuous and loud.
Amount
1
No
Model number
NC608-4M
Quantity
1
..
Version2010
/ Released/Revised On 201006
Revised State1
147
DOC.NOHN/QEH.-0819
serial
server
Optical
fiber
Check if the device communicates with other devices and backstage normally.
Regulators
Debugging time 2012-4-15
qualified
qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
148
DOC.NOHN/QEH.-0819
: LCULCU3A/B
Name of Panel: Switching station LCU (LCU3) Cabinet A/B
I. Integrate part
No.
Check Items
Debug
Conclusion
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the lamp
in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the design
drawings are consistent, consistent with the technical
agreement.
qualified
qualified
Insulation
Resistance Test
500V
50MBetween normal test atmospheric
conditions between the live parts of the device and
non-charged metal and shell, and electrical contact circuit with
open circuit voltage of 500V megger to measure the insulation
resistance value of each grade of each loopbetween the
insulation resistance of not less than 50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency withstand
voltage test without breakdown phenomenon of flashover and
component damage.
qualified
qualified
No.
Version2010
/ Released/Revised On 201006
Debug
Inpspection
Revised State1
149
DOC.NOHN/QEH.-0819
Conclusion
Result
CPU I
6ES74123HJ140AB0
2
Check if CPU module type of PLC is consistent with drawing design:
Type:
Module No.:
qualified
qualified
1. 6ES74070KR020AA0
2
2.220V 110V
24V
5V
3..
Check if working power level of power module conforms to drawing design:
1. type:
( 2 ) in total
2. operating voltage: 220V 110V
24V
5V
3. check if input/output voltage and indicating lamp is normal
qualified
qualified
qualified
qualified
1.
1. 6ES73211BL000AA0
(2) 6ES73217BH000AB0
2.
18
3. II
1.input module checking, type:
1. 6ES73211BL000AA0
(2) 6ES73217BH000AB0
2.number: 18
3.check if module input indicating lamp and input signal comform to drawing
qualified
qualified
1.
1. 6ES73211BL000AA0
2.
3
3.
qualified
qualified
PLC TYPE
1. CPU
2.
3.
4.
5..
1. Check if PLC CPU module indicating lamp is normal;
2.check communication with background: serial Ethernet
Version2010
/ Released/Revised On 201006
Revised State1
150
DOC.NOHN/QEH.-0819
3.check if outputs conform to outlet relay, consistent with laylout design; outlet
relay contact closing/breaking reliable action.
6ES73311KF020AB0
6
Check analog quantity acquisition module type: YES
NO
Current mode
voltage mode
Type: 6ES73311KF020AB0
( 1 )in total
NO
qualified
qualified
MT-8121T
Type:
qualified
qualified
qualified
qualified
Check if PLC communication and indicating lamp are normal; alarm window be
displayed automatically, alarm content conforms to actual alarm signal.
qualified
qualified
qualified
qualified
PLC
Check if DI signal conforms to drawing and PLC input point; data display of
monitoring pictures is correct;
qualified
qualified
qualified
qualified
qualified
qualified
Check if background monitoring system can adjust time with PLC correctly;
qualified
qualified
Check if function menu and function key are effective and available, contact
points without shift;
qualified
qualified
10
11
20 mA
1100 2100 3100 4100 5100
6100 7100 8100 9100 10100
11100 12100 13100 14100 15100
16100
qualified
qualified
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
151
DOC.NOHN/QEH.-0819
meter: YES
NO
CP-T96
0-150V
Voltmeter: YES
NO
type: CP-T96
range: 0-150V
qualified
qualified
qualified
qualified
5%
qualified
qualified
qualified
qualified
qualified
qualified
...
Input system voltage and to-be sync.voltage, check if system voltage,
frequency, to-be sync.voltage and frequency meter are indicated when
switching to manual synchronism.
qualified
qualified
qualified
qualified
CP-F96
NO
type: CP-F96
NO
CP-S96-N/110V
Type: CP-S96-N/110V
1.
2.
3. 0
30
Detection method:
1.only input voltage in to-be sync. side, and voltage and frequency pointer
deviate upward;
2. only input voltage in system side, and voltage and frequency pointer deviate
downward;
3. input the same voltage in two sides, and voltage and frequency pointer is
horizontal, phase angle pointer to about 0; if angle changes, pointer advance or
fall behind 30pointer deviation not exceeding accuracy error.
Version2010
NO
/ Released/Revised On 201006
Revised State1
152
DOC.NOHN/QEH.-0819
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
NO
DZZB-6
1
Type: DZZB-6
No.:1
2
LCD display or nixie tube indicate clearly, with sensitive button, and all kinds of
state indication is right;
5%
3
input rated voltage in input terminal, and the error of automatic synchronizm
value and circumscribed measuring instrument value is not more than 5%
NO
2
All output contact N.O./N.C.conforms to drawing, and contact output
reliable action
1
Control switch No.: YES
NO
LW39-16C-40B-211/2
LW-16C-40B-202A
LW39-16CYS-40B-505/5
1+1+5+5
Type: LW39-16C-40B-211/2
LW-16C-40B-202A
LW39-16CYS-40B-505/5
No.: 1+1+5+5
Version2010
LW39-25-Z1-2002/2
LW39-25-Z1-2002/2
/ Released/Revised On 201006
Revised State1
153
DOC.NOHN/QEH.-0819
....
/
All Control switches can operate normally, e.g.,test,synchronized on, accident
reset,
opening
increase/decrease,excitation
increase/decrease,CB
opening/closing, contact reliable closing/breaking.
qualified
qualified
NO
AD16-22D/RG23
5
Type: AD16-22D/RG23
No.:5
qualified
qualified
Check if type and voltage class conform to layout design, and lable name
correspond to drawing and actual signal, luminous evenly,
qualified
qualified
PF-500-24V
Type: PF-500-24V
No.: 3
AC/DC will be mutual standby: YES
NO
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
qualified
Type of Switching power supply: YES
NO
Alarm:
YES
NO
1
BJ-1I
1
Type: BJ-1I
No.:1
NO
NC608-4M
1
1
Type: NC608-4M
No.:1
..
2
Check if device type conforms to layout design (including communication
superviser,serial server,optical fiber communication device,etc.)
3
Check if communication with other device and background is normal
2
Regulators
Debugging time 2012-3-24
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
154
DOC.NOHN/QEH.-0819
A
Name of Panel: Energy Meter Cabinet A
I. Integrate part
Number
Test
items
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the
lamp in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test
atmospheric conditions between the live parts of the device
and non-charged metal and shell, and electrical contact
circuit with open circuit voltage of 500V megger to measure
the insulation resistance value of each grade of each
loopbetween the insulation resistance of not less than
50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency
withstand voltage test without breakdown phenomenon of
flashover and component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
155
DOC.NOHN/QEH.-0819
T1 High Side
Mian
Model number
DSSD341
0.2S
DSSD341
bidirectional
0.2S
T2 High Side
Mian
DSSD341
0.2S
DSSD341
bidirectional
0.2S
110kV line 1
Spare
DSSD341
0.5S
DSSD341
bidirectional
0.5S
Version2010
2.
3.
2.
3.
2.
3.
/ Released/Revised On 201006
Debugging
Result
Inpspection
Result
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
156
DOC.NOHN/QEH.-0819
110kV line 2
Spare
DSSD341
0.5S
DSSD341
bidirectional
0.5S
T1 High Side
Spare
DSSD341
0.5S
DSSD341
bidirectional
0.5S
T2 High Side
DSSD341
Version2010
1..
2.
3.
2.
3.
/ Released/Revised On 201006
qualified
qualified
qualified
qualified
Revised State1
157
DOC.NOHN/QEH.-0819
Spare
0.5S
DSSD341
bidirectional
0.5S
2.
3.
Regulators
Debugging time 2012-4-24
qualified
qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
158
DOC.NOHN/QEH.-0819
B
Name of panel: Energy Meter Cabinet B
I. Integrate part
Number
Test
items
Debugging
Result
Inpspection
Result
qualified
qualified
ID
Maintenance
of
lightingLighting
Switch on the work power. When open the real door, the
lamp in the panel is on; otherwise, it is off.
qualified
qualified
Panel
size and color
check
Check the panel size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.
qualified
qualified
Insulation
Resistance Test
500V
50M Between normal test
atmospheric conditions between the live parts of the device
and non-charged metal and shell, and electrical contact
circuit with open circuit voltage of 500V megger to measure
the insulation resistance value of each grade of each
loopbetween the insulation resistance of not less than
50M.
qualified
qualified
Dielectric
strength
50Hz
2000V 1
Under normal test atmospheric conditions, the
device can withstand a frequency of 50Hz, the test voltage of
2000V, the work lasted one minute power frequency
withstand voltage test without breakdown phenomenon of
flashover and component damage.
qualified
qualified
Version2010
/ Released/Revised On 201006
Revised State1
159
DOC.NOHN/QEH.-0819
Name
1G Spare
Model number
DSSD331
0.5S
DSSD331
bidirectional
0.5S
2G Spare
DSSD341
0.2S DSSD331
0.5S
DSSD341
bidirectional
0.2S DSSD331
bidirectional
0.5S
TD1 Spare
DSSD331
0.5S
DSSD331
bidirectional
0.5S
Version2010
2.
3.
2.
3.
2.
3.
/ Released/Revised On 201006
Debugging
Result
Inpspection
Result
qualified
qualified
qualified
qualified
qualified
qualified
Revised State1
160
DOC.NOHN/QEH.-0819
TD1 Spare
DSSD331
0.5S
DSSD331
bidirectional
0.5S
1..
2.
3.
Regulators
Debugging time 2012-4-24
qualified
qualified
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
161
DOC.NOHN/QEH.-0819
Number
Test
items
Debugging
Result
Inpspection
Result
qualified
qualified
Label
Maintenance
of
lightingLighting
qualified
qualified
Check the screen size and color of the body with the
design drawings are consistent, consistent with the
technical agreement.
Meet
Qualified
Version2010
/ Released/Revised On 201006
Revised State1
162
DOC.NOHN/QEH.-0819
Debugging
Result
Inpspection
Result
..
PCM825
Check if device type conforms to layout design
communication
superviser,serial
See technical (including
protocols 6.34 server,optical fiber communication device,etc.)
qualified
qualified
qualified
qualified
Model number
Name
communication
management
computer
GPS
DMP-348(DC220V)
See technical
protocols
6.2.10
Regulators
Debugging time 2012-4-26
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
163
DOC.NOHN/QEH.-0819
MTC
MTC Background Monitoring System
Scope of examination
NO.
Debugging
Result
Inpspection
Result
... I
Check out if the brand, quantity, oerating voltage and parameters of computer
and display consistent with design requirements.
qualified
qualified
qualified
qualified
Check out if double net multimachine hot back-up switch over is normal.
qualified
qualified
Checked out that communication is normal, and double net multimachine switch
over is normal.
qualified
qualified
qualified
qualified
qualified
qualified
I Protection unit
1 7UM612 7UM622 7UT612 7UT613 7SJ622 7SA611 7SD610
7SJ622 7SJ632 7SJ624 7UT635
Unit name:
7UM612 7UM622 7UT612 7UT613 7SJ622 7SA611 7SD610
7SJ622 7SJ632 7SJ624 7UT635
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal Normal
No need
Version2010
/ Released/Revised On 201006
Revised State1
164
DOC.NOHN/QEH.-0819
2
2# LCU
Name of panel: Unit 1 LCULCU1Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal
Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal
qualified
qualified
3 LCUA/B
Name of panel: Auxiliary LCULCU4Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal
Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal
qualified
qualified
4
LCUA/B
Name of panel: Switching station LCU (LCU3) Cabinet A/B
Message audit Normal
Abnormal
Telesignalisation audit Normal
Abnormal
Telemetry checkout Normal
Abnormal
Telecontrol checkout Normal
Normal
No need
Read-write constant value Normal
Normal
No need
Alarm incident Normal
Abnormal
qualified
qualified
Check out that communition and data of watt-hour meter are normal.
qualified
qualified
Regulators
Debugging time 2012-5-12
Surveyor
Checking time
Test result
Version2010
/ Released/Revised On 201006
Revised State1
165