The Uniform Building Inspection Report

Single Family Residence:

Prepared Exclusively for:


.
Inspection Date:

Report Number:

nspection Company:
Essential Home Inspections
Ron Bittleman
21057 N. Jocelyn Ln.,
Maricopa, AZ 85138
602-410-9538
Residential and Commercial Building Analysis
Copyright 2010 Essential Home Inspections
Essential Home Inspections
21057 N. Jocelyn Ln., Maricopa, AZ 85138
Phone: 602-410-9538
Residential and Commercial Building Analysis
Address of inspection: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Client: Paul & Marsha Martin Date: 1/5/2010
Address: Phone:
City: State/Prov.: Zip:
GENERAL INFORMATION
Selling Agent:
Company:
Phone:
E-Mail:
Present at Inspection:
Listing Agent:
Company:
Phone:
E-Mail:
Present at Inspection:
Client E-Mail:
Client Present: Approx. 30%
Structure Type: Single Family Residence
Occupancy Status: Not occupied
Approx. Sq. Ft.: 2300
Approx. Year Built: 2001
Weather Conditions: Clear
Approx. Temp.: Outside temp. = 70
Time Insp. Began: 12:30:00 PM
INVOICE
Report Number: 20100105PM
Inspection Type: Visual
Inspection Base Fee: $0.00
Per 500 sq.ft. over 1500:
Commercial per 1000 sq. ft.:
Pool:
Spa:
Pool/Spa Combo:
Re-Inspection:
Condo:
Apts.:
Escrow:
Over 20 Yrs old:
Special:
Total: $0.00
Not surePaid by: ___________________________
NOTICE: The written report, and all information
Inspector: Ron Bittleman
Lic. Number:
gathered during the inspection, is not considered
transferable to third parties. The inspection
results are intended for the exclusive use of the
client.
NOTICE: Client is responsible for payment at the time services are rendered. Any
account 30 DAYS or more PAST DUE
is subject to finance charges and/or collection proceedings. Escrow/attorney bil
ling is available for an additional fee but
does not relieve the client's responsibility for payment should the property fai
l to close.
Copyright 2010 Essential Home Inspections
Essential Home Inspections Inspection Agreement

THIS IS A LEGALLY BINDING CONTRACT -PLEASE READ IT CAREFULLY

Address:
VISUAL INSPECTION DEFINITIONS AND LIMITATIONS:
1. The Client understands and agrees that this Agreement is a part of the Inspec
tion Report and acceptance of or
payment for the Inspection Report by the Client will confirm this agreement, eve
n if Client was not present at the
inspection and/or has not signed this agreement.
2. The Client understands that this report and any information therein is intend
ed for the sole use of the Client and shall not
substitute for, replace or be used in lieu of any required Transfer Disclosure S
tatements and shall not be disclosed to any person
or persons other than the parties to the transaction for which this Inspection r
eport was ordered. Client further agrees that
dissemination of information to any third party, even with the consent of the co
mpany, is with the understanding and agreement
that any action brought by the Client or a third party becomes the responsibilit
y and liability of the Client.
3. Nothing in the Inspection Report, and no opinion of the Inspector, shall be c
onstrued as advice to the Client to
purchase, or not to purchase, the property.
4. The Visual Inspection Service is performed in accordance with the Standards o
f Professional Practice for Arizona Home Inspectors
and according to these standards, is intended to provide the Client with a bette
r understanding of the property conditions as observed
at the time of the inspection. The specific systems and components of a building
to be inspected are listed in these Standards of
Practice.
Any area which is not exposed to view, is concealed, or is inaccessible because
of soil, walls or wall coverings, floors or floor coverings,
ceilings, furnishings, cosmetic or subjective defects or any other thing, is NOT
included in this inspection.
Client agrees to assume all the risk for all conditions which are concealed from
view at the time of the inspection.

5. The following are NOT included in the inspection:


Recalls or Callbacks of any kind and from any source: Latent or concealed defect
s
Environmental hazards or conditions, including, but not limited to, toxic, react
ive, combustible, or corrosive contaminants, wildfire, odors,
noise, flood potential, electromagnetic fields, underground storage tanks, asbes
tos, radon gas, lead paint, urea formaldehyde, PCB's, water
or air quality, the proximity to toxic waste sites, or other environmental or he
alth hazards
Structural, geological, soil or hydrological stability, survey, engineering, ana
lysis or testing
Permit research or validation, code, installation or zoning violations
The examination of conditions related to animals, rodents, insects, wood destroy
ing insects, organisms, mold and mildew, or the damage
caused thereby
Radio controlled devices or low-voltage systems or relays
Security or intercom systems or central vacuum systems
Elevators, lifts or dumbwaiters
Thermostatic, time clock or photoelectric controls
Water softener or purifier systems
Furnace heat exchangers, solar heating systems, fire sprinklers and piping, hidd
en moisture, and freestanding appliances or other personal
property
Window coverings
The examination or operation of any sewage disposal system or component includin
g, but not limited to, septic tanks, cesspools, and/or any
underground system or portion thereof, or ejector pumps for rain or waste
Landscape or farm irrigation systems
The condition and/or irrigation of trees, shrubs or vegetation of any kind
Any item which is hidden from view or impractical to test
Any system or component not listed in the Standards of Professional Practice for
Arizona Home Inspectors as an observation requirement
Any system or component, condition, or application noted in the report as not in
spected, not determined, or not reported on
6. The Uniform Building Inspection Report utilizes referenced narratives corresp
onding to items listed on computer generated findings pages.
You must read the narratives in the accompanying manual corresponding to each it
em on the findings pages to have read the entire
report. The Client agrees to read the entire report. The Client agrees to immedi
ately contact the Inspection Company for copies of any pages
found to be missing from any part of the report.
7. The report, including the use of signifying letter codes, is the professional
opinion of the Inspector, based on the accessibility of the
certain fixed components surveyed. Without dismantling parts of the building and
/or its components, and without full use of all utilities, the
Inspector may extrapolate conclusions which cannot be confirmed during the inspe
ction.
8. The Inspection Company does not offer any warranty, guarantee or insurance fo
r the Client or any other person in connection with the
Inspection Report. THERE IS NO GUARANTEE, WARRANTY, EXPRESSED OR IMPLIED, OF THE
INSPECTION SERVICE OR
INSPECTION REPORT.
9. The Client agrees to submit to the Inspection Company, in written form, any c
laims or complaints prior to taking any action
thereupon. Any legal action or proceeding of any kind, whether sounding in tort
or contract, against the Inspector/Inspection
Company or its officers, agents, or employees, must be brought within one (1) ye
ar from the date of the inspection or will be deemed
waived and forever barred.
10. Any dispute, controversy, interpretation or claim including claims for, but
not limited to, breach of contract, any form of
negligence, fraud or misrepresentation arising out of, from or related to, this
contract or arising out of, from or related to the
inspection or inspection report shall be submitted to final and binding arbitrat
ion under the Rules and Procedures of the
Expedited Arbitration of Home Inspection Disputes of Construction Arbitration Se
rvices, Inc. The decision of the
Arbitrator appointed thereunder shall be final and binding and judgement of the
Award may be entered in any Court of
competent jurisdiction.
11. To the extent allowed by law, it is understood and agreed by and between the
parties hereto that the Inspector/Inspection
Company is not an insurer, that the payment for the subject inspection is based
solely on the value of the service provided by the
Inspector/Inspection Company in the performance of its limited visual inspection
and production of a written inspection report
as described herein, that it is impracticable and extremely difficult to fix the
actual damages, if any, which may result from a
failure to perform such services, and a resulting loss that the Inspector/Inspec
tion Company's and its officers,' agents,' or
employees' liability hereunder shall be limited and fixed in an amount equal to
the fee paid, as liquidated damages, and not
as penalty, and this liability shall be exclusive.
The Fee for the Visual Inspection and Report is: $

CLIENT:_____________________________________(sign)______________________________
____ Date:_________________
Essential Home Inspections, a Sole Proprietor
INSPECTION COMPANY:_____________________________________________________________
______________________
Ron Bittlman
INSPECTOR:________________________________(sign)________________________________
_ Date:___________________
This Report Has Been Prepared Exclusively For:
Property Address: Date of Inspection: Start Time: PM Report Num
ber:

Letter Code Definitions:


The letter code definitions provide the inspector's professional opinion regardi
ng the finding
significance, severity, ramifications, course of action, or path of resolution r
ecommended. If further
clarification is desired please contact your inspector.
(+)
The plus sign indicates a plus for the property.
(A)
APPEARANCE Repair or alteration usually improves component appearance and should
decrease deterioration.
(B)
BUILDING STANDARDS The finding does not conform to building standards and practi
ces in
effect at the time of construction or installation. Further study and correction
s as needed are
advised.
(C)
CAUTION Caution advised. The situation or problem could be, or could become, haz
ardous
under certain circumstances.
(D)
DAMAGED and/or DAMAGING Significant component damage and/or ongoing damage
apparent. Corrections advised.
(E)
EFFICIENCY Repair, alteration or replacement usually improves the efficiency of
the component
or system.
(F)
FAILURE Failure of a system or component. The system or component fails to opera
te or to
operate properly.
(H)
HAZARD The situation, problem or defect should be considered hazardous. Correcti
on by a
qualified licensed contractor is advised.
(M)
MONITOR Monitor the situation on a regular basis. Corrections by a qualified lic
ensed
contractor, if and when necessary, are recommended.
(N)
NOTICE Discretion advised. The significance of the situation, problem or defect
is uncertain.
Further study is advised.
(P)
PREVENTIVE MAINTENANCE Correction or modification decreases the probability of e
xcessive
deterioration.
(R)
REVIEW BY SPECIALIST It is recommended that the finding and all associated compo
nents be
reviewed and corrected as needed, by a qualified licensed contractor.
(T)
TYPICAL/COMMON Although typical or common for the age of the structure or compon
ent,
modifications may be in order.
(U)
UPGRADE RECOMMENDED Modification or addition is generally considered an upgrade
which
may improve safety or efficiency.
IMPORTANT: Findings, Components & Applications Listings:
Each section includes a list of Findings, if any, and a list of Components and a
pplications noted during the
inspection. Please note that some components and some applications require addit
ional maintenance and
consideration and that the survey of some components is limited. Some component
information contains
disclosures. Some Findings information may be far-reaching. To obtain this infor
mation you are advised to
read all narratives in the Uniform Building Inspection Report Reference Manual, r
eferenced by item
number, before purchasing the property.
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 5 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Grounds Survey Findings:


If present, vegetation, grading, drainage, driveways, patio
ground surfaces, walkways and retaining walls, stoops, steps,
non-abutting decks, visible components of grounds electrical
systems and watering systems, and other general conditions
were observed. The inspector is not required to test grounds
lighting systems or watering systems.
Significant visible deficiencies or potential concerns, if any, are
reported below.
Grounds systems or components are indicated by type or
described in the components section.
The condition of exterior faucets is addressed in this section,
though any observed leaks may be reported in the Plumbing
Section.
[+] 0970.15: No deficiencies noted in this area at the time
of the inspection.
[Note] 0980.01: The grounds was inspected and reported
on with the enclosed information.
Grading and drainage are probably the most significant
aspects of a property, simply because of the direct and
indirect damage that moisture can have on structures. All
structures are dependent on the soil beneath them for
support, but soils may vary. For this reason, it is
recommended that proper drainage away from the
foundation be provided. This can be enhanced by roofs that
have gutters and downspouts that discharge into area
drains with catch basins that carry water away to hard
surfaces. It is recommended that tree limbs and vegetation
be kept trimmed back from roof and wall surfaces.
Sprinkler systems are primarily an underground system, our
inspection is limited. It is recommended that you consult
the sellers as to the operation of the timer, and entire
system, and all associated controls before the close of
escrow if the property is equip with a system.
Grounds Components & Applications:
The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
IRRIGATION:
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 6 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

00a(1) All or part of the irrigation or sprinkler system is


automatically activated. Be aware that the inspector does
not inspect or review the operational characteristics of
irrigation or sprinkler systems.
00a(2) All or part of the irrigation or sprinkler system is
manually activated. Be aware that the inspector does not
inspect or review the operational characteristics of irrigation
or sprinkler systems.

SITE ELEMENTS, GRADING, DRAINAGE:


01c Yard drains (if visible and discovered)
01d(1) Above grade (with respect to roadway)
01k Expansive/clay type soil
Grading and drainage condition proximate to inspected
structures: Acceptable
Vegetation adversely impacting inspected structure(s):
Acceptable (No adverse conditions noted)

RETAINING WALLS:
03d Retaining wall type not listed (Unlisted retaining
wall types may include rip-rap, river stone, old tires, metal,
interlocking prefab concrete, etc.)
Retaining wall(s) general condition: Acceptable

FENCES & GATES:


04a(1) Masonry
04c(1) Wood

WALKS, DRIVES, & PARKING:


05b(1) Cement concrete walks/drives
Walks, drives, parking general condition: Acceptable
Decks, balconies, patios general condition: Acceptable

GROUNDS/PARKING LIGHTING:
06c 110/120 volt lighting/outlets
06c(1) GFCI protected outlet(s) (The inspector indicates
GFCI protection is provided at exterior outlets even though
all exterior outlets may not be so equipped.)

MISC. GROUNDS DEVICES & OUTBUILDINGS:


No misc. grounds devices noted
No outbuildings noted

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 7 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Exterior / Roof Survey Findings:


The roof, roof drainage systems, jacks, flashings, skylights,
chimneys, other roof penetrations were observed within the
limits of accessibility. The method of observation, which is
suggestive of the extent to which the roof and related
components were observed, is set forth in the components
section.
Wall cladding, flashing, trim, eaves and rake fascias (barge
rafters), all doors, a representative number of windows, and all
garage doors were observed if present. Any garage door
operators were tested for the ability to stop or reverse when
meeting normal hand resistance.
If bedroom windows have security bars, they may be required to
have release mechanisms. The release mechanisms are not
tested by the inspection company. It is strongly recommended
that you have the owner or agent demonstrate the release
mechanism on each window.
Significant visible deficiencies or potential concerns, if any, are
reported below.
Any visible deficiencies in abutting or attached decks may be
reported in the STRUCTURE section rather than here.
Visible signs of leaks or abnormal condensation (if any) on
surfaces are reported in this, and/or other pertinent, sections.
Exterior systems or components are indicated by type or
described in the components section.
[M] 1510.01: Insulated window (I.G.) appears to have lost
seal.
Seal is raised between dual pane window. Recommend
monitoring window for condensation. Noted at master
bathroom toilet area.
See Photo(s) 1510.01.
[E] 1530.06: Window cracked.
Recommend repair of window. Outside pane of window is
cracked. Noted at master bathroom shower area.
See Photo(s) 1530.06.
[Note] 1970.01: The exterior of the home was inspected
and reported on with the enclosed information.
We do not comment on coating or cosmetic deficiencies
and the wear and tear associated with the passage of time,
which would be apparent to the average person. However,
cracks in hard surfaces can imply the presence of
expansive soils that can result in continuous movement, but
this could only be confirmed by a geological evaluation of
the soil. It is important to maintain a property, including
painting or sealing walkways, decks, and other hard
surfaces, and it is particularly important to keep the house
walls sealed, which provide the only barrier against
deterioration. It is recommended that gaps and
penetrations around framing, plumbing, mechanical,
electrical penetrations, windows, doors and thresholds be
Photo: 1510.01 (1)

Photo: 1530.06 (1)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 8 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

checked and if necessary sealed for moisture and pest


protection. Therefore it is recommended to maintain the
exterior of the home on a regular basis.
Exterior wood features, such as roof eaves, fascias, beam,
door jambs and trim, around windows will need periodic
caulking and painting to preserve and to prevent moisture
inundation. Eaves,Soffits and fascias are viewed from the
ground, not all problems may be noticed. Tree limbs and
vegetation should be trimmed back from roof and wall
surfaces.
Hairline cracks in concrete and masonry are considered
normal due to concrete shrinkage. Gutters and subsurface
drains are not water tested for leakage or blockage.
Recommend observing during heavy rains. Regular
maintenance of drainage systems is required to avoid water
problems at roof and foundation.
Wall insulation type and value is not verified.
[Note] 1970.03: Concrete Tile Roof
Concrete roof tile are brittle and walking on them can
crack or break the tile. Therefore, a limited inspection was
preformed. Hair line cracks and possibly broken tile may go
unnoticed during this limited inspection. The inspector did
inspect all components that were visible from certain
vantage points with a ladder and binoculars. The condition
of roof felt paper or membrane below roof tiles is unknown
and cannot be inspected with out possible damage to the
roof coverings. The material on most pitched roofs is not
designed to be waterproof only water resistance. While the
inspector makes every effort to find all areas of concern,
some areas can go unnoticed. No guarantee or warranty is
made by this inspection whether the roof leaks at the time of
the inspection or is subject to future leaking. There may be
concealed damage. Without fully viewing, it's almost
impossible to know whether there's a serious problem. The
sellers or the occupants of the residence will generally have
the most intimate knowledge of the roof and of its history.
Therefore, it is recommended that you ask the sellers about
it, and that you either include comprehensive roof coverage
in you home insurance policy, or that you obtain a roof
certification from a licensed and insured roofing contractor.
Exterior Components & Applications:
The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 9 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Report Reference Manual, referenced by item number,


before purchasing the property.
ROOF REVIEW METHOD:
17b The roof was partially viewed due the various
reasons. Roof penetrations were not fully observed.
17e Viewed with binoculars
17f Viewed from ground

ROOF / DECK STYLES:


13a Gable
13t 4 to 6/12 pitch

ROOF/DECKFLOOR WATERPROOFING MATERIALS:


15c(1) Concrete tile
Roof covering general condition: Acceptable (Inspection
limited)

ROOF FLASHING AND PENETRATIONS:


15p Metal flashing
Roof flashing/roof penetrations general condition:
Acceptable (Inspection limited)

GUTTERS / ROOF DRAINS:


No gutters installed
Roof drainage systems general condition: Acceptable

WALL CLADDING MATERIALS (Siding), FLASHING &


TRIM:
16h(1) Stucco (all applications)
Wall cladding general condition: Acceptable
16q(2) Wall flashing partially visible
Exterior wall flashing condition: Acceptable where visible
(Inspection limited)
Exterior trim condition: Acceptable

EAVES, SOFFITS, FASCIA, PORCHES & RAILINGS


16s(10)Covered or partially visible bargeboard(s)
16s(9) Visible bargeboard(s)
Eaves, soffits and fascia general condition: Acceptable
(Inspection limited)

WINDOWS AS VIEWED FROM EXTERIOR (see Interior


Section also):
10a Multi-glaze (I.G.)
10c(1) Metal sash
10h Sliding sash
10m Single hung sash
10n Picture window(s)
Windows general condition: Questionable-1 or more

ENTRY DOORS:
12b Solid core
12c(1) Glass (large pane(s))

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 10 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Entry doors general condition: Acceptable


VEHICLE DOORS and SAFETY REVERSE DEVICES:
14a(1) Automatic opener
14a(2) Obstruction sensor
One or more garage door operators is/are equipped
with an obstruction sensor safety reverse device(s). Test
the operation on a regular basis.
14a(3) Pressure sensitive reverse mechanism
One or more garage door operators is/are equipped
with pressure sensitive safety reverse device(s). Test the
operation on a regular basis and keep the reverse pressure
properly adjusted.
The safety reverse mechanism(s), including the
pressure sensitive and the obstruction sensor type,
was/were tested by the Inspector and it/they did reverse.
Garage door operator(s) general condition: Acceptable
14b(1) Sectional
14g Metal (frame/skin)
Vehicle door(s) general condition: Acceptable
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 11 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

HVAC Survey Findings:


(Includes Air Conditioning / Fireplace(s) / Stove(s) and
Chimney(s), if present)

Within the limits of visibility, heating equipment, normal


operating controls, automatic safety controls, related chimneys,
flues, & vents were observed. If present and visible, fans,
pumps, piping, supports, dampers, related insulation, registers,
radiators, fan coil units or convectors were observed. The
inspector looked for the presence of installed heat and cooling
sources for each room.
If installed, the fireplace(s) and parts of any chimney(s) were
observed.
Significant visible deficiencies or potential concerns, if any, are
reported below.
Heating/air conditioning/fireplace systems or components, if
present, are indicated by type or described in the components
section.

[+] 2851.15: No deficiencies noted in this area at the time


of the inspection.
[Note] 2855.01: The heating/cooling system of this home
was inspected and reported on with the enclosed
information.
It is recommended that you clean or replace filter(s) on a
monthly basis to maintain a healthy environment and to
assist in the unit working properly, and since health is a
deeply personal responsibility, it's recommended to have
the air quality tested and distribution ducts cleaned as a
prudent investment in environmental hygiene, and
particularly if any family member suffers from allergies or
asthma. The operation of the HVAC system should be
verified by the seller and also checked (weather permitting
for temperature) again on the day of closing.
It is recommended to have the heating and cooling system
serviced by an licensed contractor seasonally. Heat pumps
are not tested in extreme temperature conditions to avoid
damage to unit. This home is equiped with a A/C unit in the
attic, it is recommended to periodically clean debris from
A/C catch pan and condensate drain line to avoid
condensate overflow in attic.
HVAC / Fireplace / Stove Components:
The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 12 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
HEATING EQUIPMENT LOCATION(S):
Heating equipment #1 is located in the attic.
Heating equipment #2 is located in the attic.
HEATING SYSTEM(S):
21a(1) Natural gas heating: If not presently installed, the
installation of a carbon monoxide (CO) detector in each
sleeping room is highly recommended.
21e Forced air heat
Heating equipment general condition: Acceptable
Heating automatic safety controls condition: Acceptable
(Inspection limited)
21n Visually restricted heat exchanger
HEATING EQUIPMENT THERMOSTATS / OPERATING
CONTROLS / ZONING
22b Non set-back thermostat(s)
Heating equipment operating controls condition: Acceptable
HEATING FLUE AND VENT SYSTEMS AND
COMBUSTION AIR:
Heating flue and vent systems condition: Acceptable
(Inspection limited)
Heating combustion air condition: Acceptable
24b Disposable or washable filters
Heating/cooling air filter(s)(excluding electronic or
mechanical types) condition: Acceptable
25a Heat Distribution Methods
25a(2) Ducting (forced air)
Heating distribution system condition: Acceptable
(Inspection limited)
Heat source in each room: Acceptable
APPROXIMATE AMBIENT TEMPERATURE AND
TEMPERATURE DIFFERENTIAL TEST RESULTS, IF
TAKEN:
Outside Temp. = Outside temp. = 70
Unit 1 Temperature Differential = 16 degrees AC mode
Unit 2 Temperature Differential = 18 degrees AC mode
COOLING / VENTILATION SYSTEM(S):
20b Dual-Pack / Gas-Pack (gas heat, elec. cool)
20c(1) Condenser/evaporator separate (split system)
Cooling equipment general condition: Acceptable
COOLING EQUIPMENT THERMOSTAT(S)/OPERATING
CONTROLS:
Cooling equipment operating controls condition: Acceptable
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 13 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

20h Cooling Distribution Methods


20h(1) Ducting
Cooling distribution system condition: Acceptable
(Inspection limited)
Cooling source in each room: Acceptable
FIREPLACE(S), STOVE(S):
No fireplace or stove noted
Chimney(s) general condition: Acceptable (Inspection
limited)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 14 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Plumbing Survey Findings:


The hot water systems, visible sections of interior water supply
and distribution systems, including pipes, supports, and
insulation, and functional flow (if water was on) were observed.
All water handling fixtures, faucets & valves, interior drain
systems including waste & vent systems, functional drainage (if
water was on) and sump pumps (if installed) were observed.
(Drains to clothes washers, roofs, floors, and decks were not
tested.)
If present, interior and exterior fuel storage & distribution
systems were observed.
The inspector did inspect for visible evidence of leaks and cross
connections.
The clothes dryer venting system was also visibly examined, if
accessible, though not tested (unless so stated).
Significant visible deficiencies or potential concerns, if any, are
reported below.
Visible plumbing systems or components are indicated by type
or described in the components section.
[+] 4985.15: No deficiencies noted in this area at the time
of the inspection.
[Note] 4989.01: The plumbing in the home was inspected
and reported on with the enclosed information.
The condition of waste and drain pipes is usually directly
related to their age. However, as significant portions of
drainpipes are concealed, your inspector can only infer their
condition by observing the draw at drains. Nonetheless,
blockages will occur in the life of any system, but blockages
in drainpipes, and particularly in main drainpipes.
Therefore, it is recommended that a video inspection of the
main sewer line be performed by a licensed qualified
contractor, and be used in your further inspection or repair
issues. The seller should also be asked if there have been
any problems relating to the entire plumbing and drainage
systems.
Because the main water shutoff are not operated during
inspections, we suggest verification of working condition be
made by the seller prior to close of escrow. Gas Appliances
on property. It is recommend that the that a Gas, LPG or
fuel supplier perform a "safety check" before taking
possession of the property. Water heaters, gas stoves, gas
fire places, gas clothes dryers (if applicable), and A/C
heaters are examples of such appliances that should be
checked by the gas supplier or by a licensed contractor
before the close of escrow.The supplier may use inspection
tools and/or methods not allowed by this inspection
company. Is is also recommended that a wrench, capable
of turning the main gas valve OFF in case of an emergency,
be located near the gas meter. Carbon Monoxide
detectors, it is recommended to install a (CO) Carbon
Monoxide detectors in appropriate areas with gas
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 15 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

appliances. In the interest of greater occupant safety,


consideration should be given to the installation of a carbon
monoxide detectors. Tests for gas leaks or pipe sizing are
not performed.
Plumbing Components & Applications:
The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
MAIN WATER SOURCE, SHUTOFF LOCATION, VACUUM
BREAKERS AND ANTI-SIPHON DEVICES:
45a Main water valve located at the left side of the
garage.
45f Water supply approximate size: 1"
42a Municipal water supply indicated
45d Handle type main water valve installed
45e Water pressure regulator installed
42d Hose bib anti-siphon devices

FUNCTIONAL FLOW AND FUNCTIONAL DRAINAGE:


47a Functional water flow tested
Functional flow test results: Acceptable
47b Functional drainage tested
Functional drainage test results: Acceptable

OPERATION AND CONDITION OF FIXTURES


All fixture operations and general condition: Acceptable

OPERATION AND CONDITION OF FAUCETS


All faucet operations and general condition: Acceptable

PRIMARY INTERIOR HEATING ENERGY SOURCE AND


SHUTOFF LOCATION:
44a Natural gas
Gas shutoff valve located at the right side of the home.
WATER HEATER(S):
43a(1) Natural gas water heater(s)
Water heater(s) general condition: Acceptable (Inspection
limited)

WATER HEATER AUTOMATIC SAFETY CONTROL


DEVICE(S) OBSERVED:

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 16 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

43k Temperature, pressure relief valve


Water heater automatic safety controls apparent condition:
Acceptable (Inspection limited)

WATER HEATER COMBUSTION AIR REVIEWED:


Water heater combustion air source: Acceptable

WATER HEATER LOCATION(S), APPROXIMATE AGE(S)


AND SIZE(S):
Water Heater #1 is located in the garage.
The approximate age of this water heater is 5 to 10 years.
Its approximate size is 40 gals.

APPLIANCE VENT TYPES AND CONDITION:


41a(1) Sheet-metal appliance vents
Appliance vents general condition: Acceptable

LAUNDRY FACILITIES AND VENTING:


40a Washer connections
40b Electric dryer connections
40k Dryer vent terminates at vertical exterior wall

INTERIOR WATER SUPPLY AND DISTRIBUTION PIPING:


41c Copper/brass water lines visible
Interior water supply and distribution piping general
condition: Acceptable (Inspection limited)

INTERIOR WATER SUPPLY AND DISTRIBUTION PIPING


SUPPORTS AND INSULATION:
Interior water supply pipe supports general condition:
Acceptable
Interior water supply pipe insulation general condition: None
Noted

FUEL DISTRIBUTION PIPING AND SUPPORTS:


41g Steel gas/oil lines visible
Fuel distribution piping general condition: Acceptable
(Inspection limited)
Fuel distribution piping supports general condition:
Acceptable

WASTE AND VENT PIPING SYSTEM:


41q Plastic drain lines visible
41q(1) Acrylonitrilebutadiene-styrene (ABS)
Waste and vent piping general condition: Acceptable
(Inspection limited)
SEWAGE DISPOSAL:
The Inspector did not ascertain the sewage disposal
method.

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 17 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Electrical Survey Findings:


Where visible and if installed, the service entrance conductors,
service equipment, main over-current device, main & distribution
panels, grounding equipment, amperage and voltage ratings,
branch circuit conductors, including the presence of aluminum
conductors, their overcurrent devices, and the compatibility of
the ampacities and voltages were observed.
A representative number of lighting fixtures, switches, and
receptacles (if power was on) were observed with respect to their
operation, polarity and grounding, on the interior, within 6 feet of
plumbing fixtures, in attached garages, carports, and on the
exterior.
All accessible ground fault circuit interrupters and arc fault circuit
interrupters (if power was on) were tested with the installed test
button.
Significant visible deficiencies or potential concerns, if any, are
reported below.
Visible electrical systems or components are indicated by type,
or described, in the Components Section.
[C] 5120.05: Knockout seal(s) missing from panel.
Knockout seal is missing on bottom of electrical panel.
Recommend installing seal to prevent accidental
electrocution or insect entry. This is a safety hazard,
recommend a licensed electrician make necessary repair
as soon as possible. Noted at the rear of the home.
See Photo(s) 5120.05.
[Note] 5919.01: The electrical system of the home was
inspected and reported on with the enclosed information.
In the interests of safety, your inspector(s) will regard every
electrical deficiency and recommended upgrade as a latent
hazard that should be serviced as soon as possible, and
that the entire system be evaluated and certified as safe by
an electrician. While the inspector makes every effort to
find all areas of concern, some areas can go unnoticed.
Outlets were not removed and the inspection was only
visual. Any outlet not accessible (behind the refrigerator for
example) was not inspected or accessible. Therefore, is is
essential that any recommendations that your inspector(s)
may make for service or upgrades should be completed
before the close of escrow, because an electrician could
reveal additional deficiencies or recommend some upgrade
for which we disclaim any responsibility.
Recommend testing GFI(s) on a regular basis. Bonded gas
line. The electrical system has also been bonded to the gas
lines. Appears intact where visible.
Electrical Components & Applications:
The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
Photo: 5120.05 (1)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 18 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

require additional maintenance and consideration. The survey


of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
MAIN / SUB-PANEL LOCATION(S):
Main service panel located at the right side of the home.
Service main condition: Acceptable (Inspection limited)

SERVICE DROP/SERVICE LATERAL & SERVICE PANEL:


51a Underground service lateral
Observed portions of the Service drop/Service lateral
condition: Acceptable
51m The service entrance conductor materials could not
be ascertained
Observed portions of service entrance conductors condition:
Acceptable
51e Exterior main service panel
51g Single disconnect

SERVICE AMPERAGE / VOLTAGE, ETC:


52b 110/120 volt service
52c 220/240 volt service
52d Single phase
52j The service amperage rating is 200 amps. (This was
determined by the amperage rating of the main disconnect)

DISTRIBUTION SYSTEMS:
53b Circuit breakers
Observed overcurrent protection condition: Acceptable
(Inspection limited)
53f Nonmetallic sheathed cable ("Romex")
53j Copper wires
Visible branch circuit conductors condition: Acceptable
(Inspection limited)
53k(1) Stranded aluminum wire noted in single branch
circuit(s).
Stranded aluminum wire is acceptable in single branch
circuits. This would include circuits for dryers, ovens,
ranges, AC units, etc.

A Representative Number of Lights and Switches were


Tested.
The condition of the lights and switches tested was:
Acceptable

A Representative Number of Receptacles were Tested.


The condition of the representative number of receptacles
tested was: Acceptable

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 19 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

GROUNDING METHOD, ETC.:


54b Grounded to water pipe
54c Grounded to wire/rebar in footing
54d Bonded service panel
Observed service ground condition: Acceptable
Ground fault circuit interrupter(s) condition: Acceptable
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 20 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Bathroom Survey Findings:


Bathroom electrical systems, including any venting systems (if
present) were observed (and tested if power was on). If any
deficiencies or concerns were observed, they may be reported
under the ELECTRICAL section.
Unless access was impaired, all water handling fixtures were
observed (and tested if water was on). Bathroom walls, ceilings,
floors, counters, a representative number of cabinets, and
windows were observed.
Significant visible deficiencies or potential concerns, if any, are
reported below (window deficiencies may also be reported under
the EXTERIOR or INTERIOR sections). (Some bathroom
plumbing or fixture deficiencies, if any, might be reported under
the PLUMBING section.)
Visible bathroom specific systems or components are indicated
by type or described in the components section.
[+] 6885.10: Positive photo
Nice bathroom area. Nice tiled floor.
See Photo(s) 6885.10.
[+] 6885.15: No deficiencies noted in this area at the time
of the inspection.
[Note] 6889.01: The bathroom areas of the home was
inspected and reported on with the enclosed information.
Bathrooms are high-use areas containing many elements
subject to ongoing wear and periodic malfunction,
particularly fixtures and other elements associated with the
plumbing system. Water flow and drainage evaluations are
limited to a visual assessment of functional flow and
functional drainage. The function and water tightness of
fixture overflows or other internal fixture components
generally cannot be inspected. Anticipate the possibility of
leakage or other concerns developing with normal
usage/aging or as concealed conditions are discovered with
maintenance work or upon removal of carpeting, tile,
shower enclosures, etc. Normal usage cannot be simulated
during a standard home inspection. The water tightness of
all surfaces exposed to water must be maintained on a
regular basis by caulking, grouting, or other means to the
showers, tubs, toilets, cabinets and baseboards, etc., for
moisture protection. Showers and tub enclosures are high
leakage, high maintenance areas. Leaks in these area can
occur at any time. It is recommend to regularly monitor
these areas for leaks.
Due to the potential hazards associated with electric
components located in bathroom areas, any identified
concern should be addressed immediately. Ground-fault
Circuit-interrupters (GFCI's) are recommended for all
bathroom receptacles outlets.
It is recommended to clean the bathroom exhaust fan(s) on
a regular basis. Lint buildup could cause potential fire.
Photo: 6885.10 (1)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 21 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Bath Components & Applications:


The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
BATHTUB TYPE(S):
60c Fiberglass bathtub(s)

SHOWER FLOOR TYPE(S):


60a(2) Tub/shower combination
60d Fiberglass pan insert

TUB/SHOWER WALLS:
62e Fiberglass or plastics walls
62n No tub/shower enclosure
62h(1) The tub and/or shower door(s) appeared to be safety
glaze

WASH BASIN(S):
64e(1) Cultured marble wash basin(s)
64g(1) The wash basin(s) and the countertop(s) are molded
as a single unit
64k(1) Free-standing wash basin(s)

COUNTERTOP MATERIALS:
65d Cultured marble countertop(s)

WATER CLOSET(S):
63a(1) Down-flush toilet

PLUMBING AND ACCESSORIES:


61a "Washerless" faucet(s)
61c Diverter valve(s)
61d Pop-up stopper(s)
61e Drain access available
64n Under-sink valves
VENTILATION, SUPPLEMENTAL HEATING AND
ELECTRICAL:
No supplemental bathroom heating noted
66b Exhaust fan(s)
66g GFCI Receptacle(s)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 22 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

FLOOR(S):
67b(1) Tile floor(s)
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 23 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Interior Survey Findings:


Wall, ceiling, and floor surfaces were observed. If present,
interior steps, stairways, balconies, railings, counters, and a
representative number of cabinets & doors were observed.
A representative number of windows (in terms of opening &
locking mechanisms, and operation) were observed.
If present, fire separation walls, ceilings, & doors between the
attached garage and living space or other dwellings were
observed.
Smoke alarms (if present) were examined for visible condition
and location placement (in most cases there is no requirement
for the inspector to test these).
Ceiling fans (if present) were observed (and tested if electricity
was on, and non-remote control switches were present).
Laundry room venting system, if installed, was observed (and
tested if electricity was on). For limits of inspection of central
vacuuming (if present), see inspection agreement.
Intruder alarms and internal communication systems (if present)
were not checked by the inspector.
Significant visible deficiencies or potential concerns, if any, are
reported below (however, any deficiencies in bathroom walls,
ceilings, floors, or cabinets may be addressed under the
BATHROOM section, and kitchen cabinets may be addressed
under the KITCHEN section).
Visible interior systems or components are indicated by type or
described in the components section.

The following is a message regarding mold from the United


States Environmental Protection Agency.
Molds produce tiny spores to reproduce. Mold spores waft
through the indoor and outdoor air continually. When mold
spores land on a damp spot indoors, they may begin growing
and digesting whatever they are growing on in order to survive.
There are molds that can grow on wood, paper, carpet, and
foods. When excessive moisture or water accumulates indoors,
mold growth will often occur, particularly if the moisture problem
remains undiscovered or un-addressed. There is no practical
way to eliminate all mold and mold spores in the indoor
environment; the way to control indoor mold growth is to control
moisture.
http://www.epa.gov/mold/

The client is advised to consider all findings associated with


moisture, such as, but not limited to, stains, leaks, vapor barrier
defects, exhaust fan failures, etc., as conditions conducive to the
growth of molds and other fungi, whether direct information
regarding mold is provided by the inspector or not.

[C] 7450.02: Door weather-strip faulty.


Man door weather stripping is faulty. Recommend
replacing to prevent possible fire or exhaust gas from
entering home. Also, recommend adjusting self closing
hinges to allow man door to close properly. Noted at man
door to garage.
Photo: 7450.02 (1)

Photo: 7960.10 (1)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 24 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

See Photo(s) 7450.02.

[+] 7960.10: Positive photo


Nice interior area in home. Nice Window blinds noted
throughout home.
See Photo(s) 7960.10.

[Note] 7965.01: The interior of the home was inspected


and reported on with the enclosed information.
While the inspector makes every effort to find all areas of
concern, some areas can go unnoticed. The visual
inspection did not involve moving furniture, area rugs or
carpets, empty closets or cabinets, areas behind wall
coverings, pictures, beds or under appliances or the
evaluation of window treatments, or areas obstructed from
view. If furnishings or item mentioned above are present
during the inspection, it is recommend to carefully check all
areas on your walk through. The inspector(s) cannot
ascertain the conditions during a limited visual home
inspection.
Your inspector may not comment on cosmetic deficiencies
such as the cracks that appear around windows and doors,
or which follow the lines of framing members and the
seams of drywall and plasterboard. These cracks are a
consequence of, but not limited to, movement such as
common settling and wood shrinkage and will often
reappear if not repaired correctly. Such crack can be
disputed, and are therefore best evaluated by a specialist.
Similarly, there are a number of environmental pollutants
that can contaminate a home, such as asbestos, carbon
monoxide, radon gas, formaldehyde, urea-formaldehyde,
lead based paints, and a variety of molds and fungi that
require specialized testing equipment, which is beyond our
expertise and the scope of our service. Refer to appropriate
contractor(s) for an additional opinion(s) or corrections if
necessary before the close of escrow. There are lesser
contaminates, such as odors that are typically caused by
moisture penetrating concealed slabs, or those caused by
household pets, cigarette smoke that can permeate walls,
carpets, heating and air conditioning ducts, and other
porous surfaces, which can be difficult to eradicate.
However, inasmuch as the sense of smell adjusts rapidly,
and the sensitivity to such odors is not uniform, it is
recommended that you make this determination for yourself
and particularly if your or any member of your family suffers
from allergies or asthma, schedule whatever remedial
services may be deemed necessary before the close of
escrow.
Windows in sleeping rooms must meet certain requirements
for emergency egress.
It is recommended to test smoke alarm(s) on a monthly
basis and that the batteries are replaced once per year and
replacement of smoke detectors every 7 to 10 years. It is
also recommended for people moving into homes that don't

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 25 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

know the age of the detector should replace them. When


testing the smoke alarm(s), it is only testing the audio
components, be aware that the smoke alarm(s) may not
function correctly in the event of smoke and/or fire. The
existing smoke detector(s) were not tested today, but they
are only noted as to be present. Carbon Monoxide
detectors, it is recommended to install carbon monoxide
detectors for safety in appropriate areas in the home for
early leak detection of this potentially deadly gas for
structures with gas appliances for added safety.
It is recommended to clean the laundry room exhaust fan(s)
on a regular basis.
It is also recommended to clean the lint trap on the dryer
before or after each use. Failure to do so could result in a
potential fire. The dryer exhaust ducts should be cleaned
when moving into the home and on a regular basis as an
ongoing maintenance item. Full inspection of the garage
may be limited due to storage / vehicles, recommend to
check carefully on walk through if items in garage are
present.
Double pane window are present throughout this house.
Although we do our best to locate bad seals in the windows,
this is not always possible due to the varying temperature
and weather conditions We recommend review of the
windows again on the day of closing for evidence of
moisture between the panes of glass. Be advised due to
weather conditions, temperature, cleanliness of the
windows, etc, it is extremely difficult to tell if dual-pane
window seals are intact. Unfortunately, this is not always
apparent, which is why your inspector does disclaim an
evaluation of hermetic seals. Every effort was made to
examine each window for lost seals. Please view all the
windows again at different times of the day. Ceiling fan(s).
We do not fully evaluate all speeds of the fan(s) or any
variable brightness control for the light(s), only that they are
responding to the switch. If fan has a remote control device,
it must be present at the time of the inspection to test the
fan.
Interior Components & Applications:
The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 26 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

WALLS AND CEILINGS:


70b Drywall
Interior walls and ceilings general condition: Acceptable
(Inspection limited)

FIRE SEPARATION WALLS AND CEILINGS


70q Fire separation walls and ceilings were observed
Fire separation walls and ceilings general condition:
Acceptable (Inspection limited)

FIRE SEPARATION DOOR(S)


71n Fire separation/fire resistant door(s) was/were
observed
Fire separation door(s) condition: Acceptable

EXTERIOR AND INTERIOR DOOR SYSTEMS:


71b Bypass door(s)
71e Hinged door(s)
71f Sliding glass door(s)
71h Dead bolt(s)
71k French door(s)
71m Weather stripped
71p(1) Self-closing door(s)
Interior doors and interior view of entry doors general
condition: Acceptable

WINDOWS
75a A representative number of windows were tested.
General condition of windows tested: Questionable

INTERIOR STYLES, STAIRS, ETC.:


72a Volume, vaulted or high ceilings
72f(1) Multi story
72g(1) Wood stairway/steps
Interior steps and stairways general condition: Acceptable
72j Room(s) over garage

FINISH FLOORING:
73a Carpet
73e(1) Tile (All types)
Floors general condition: Acceptable (Inspection limited)

MISC. SYSTEMS:
74a(1) Smoke alarm
Counters and cabinetry general condition: Acceptable
74h Ceiling fan(s)
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 27 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Kitchen Survey Findings:


Kitchen/break area specific water supply and distribution
systems, including visible piping, supports, and insulation were
observed where visible (and tested if water was on). Kitchen
specific electrical and venting systems were observed (and
tested if power was on).
Counters and a representative number of cabinets were
observed. Appliances have been examined within the scope of
the inspection agreement (see Inspection Agreement).
Significant visible deficiencies or potential concerns, if any, are
reported below (however, any deficiencies in electrical
receptacles and lighting may be addressed under the
ELECTRICAL section; and any wall, ceiling, and/or floor
deficiencies may be addressed under INTERIOR section).
Visible kitchen/break area specific systems or components are
indicated by type or described in the components section.
[C] 8020.13: Oven / range anti-tip device not installed.
Recommend installing an anti-tip device to the oven to
prevent possible injury.
See Photo(s) 8020.13.
[Note] 8989.01: The inspection of the kitchen was
inspected and reported on with the enclosed information.
Our comments regarding the appliances are based on the
condition they are in on the day of the inspection. Of the
items tested, it is only a short, operational test and may not
reflect normal usage, the variety of their settings or cycles,
or the operability of the particular unit in the future. The
operation of all appliances should be verified by the seller
and also checked again on the day of closing. Portable
appliances or accessories such as washer, dryer,
refrigerator, microwave and ice makers are generally
excluded. Water purifier, instant hot water maker, built in
toaster, can openers, coffee makers and blenders are not
within the scope of this inspection. The inspection of the
cabinetry is limited to functional unit conditions based on a
representative sampling: finishes and hardware issues are
not included.
It is recommended to clean, wash or replace filter(s) in the
hood exhaust or overhead microwave oven. Filters are a
regular maintenance item. Most mechanical filters are
washable, and many can be cleaned in a dishwasher.
Vegetable sprayers and extendable faucets can form a
cross connection and should not be left in sinks or other
fixtures, this is a health concern. If your home has an
vegetable sprayer or an extendable faucet, you should not
leave the vegetable sprayer or extendable faucet in sinks or
other fixtures. Ground-fault Circuit-interrupters (GFCI's) are
recommended for all kitchen receptacles outlets.
Kitchen Components & Applications:
Photo: 8020.13 (1)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 28 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

The following is a list of components, systems, and applications


noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
RANGE(S) / COOKTOP(S):
80a(2) Electric range or cooktop
80b Free-standing range

OVEN(S):
83a(2) Electric oven
83b Free-standing oven

VENTILATION:
81a Mechanical exhaust

CABINETS:
84a Modular wood cabinets

COUNTERTOP(S) AND BACKSPLASH:


86d Plastic laminate

SINK(S):
82b Stainless steel sink
82g Washerless faucet

REFRIGERATOR(S):
No refrigerator noted

LIGHTING AND ELECTRIC:


87a Counter outlets
87a(1) GFCI Protection
87c Incandescent lighting

OTHER APPLIANCES:
88d Disposal
88e Dishwasher

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 29 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Structure Survey Findings:


Visible portions of the following were observed: foundations;
structure to walls, columns, floors, roofs, overhang posts, and
columns; attached or firmly abutting decks, balconies, and
railings; ventilation techniques and applications of attic and
foundation; visible insulation and vapor retarders in unfinished
spaces; termination locations of kitchen, bathroom, and laundry
venting systems; and visible appliance flue and vent clearances
and related visible fire blocking.
The inspector did look for evidence of past or present leaks.
Significant visible deficiencies or potential concerns, if any, are
reported below.
Visible structure specific systems or components are indicated
by type or described in the components section.
[+] 9905.10: Positive photo
Good level of insulation in attic.
See Photo(s) 9905.10.
[+] 9905.15: No deficiencies noted in this area at the time
of the inspection.
[Note] 9909.01: The structure was inspected and reported
on with the enclosed information.
Due to typical design and accessibility constraints such as
insulation, storage, finished attic surfaces, roofing products,
etc., many elements and areas, including major structural
components, are often at least partially concealed from
view and cannot be inspected. Also, we do not move or
disturb any portion of the insulation, which may well obscure
water pipes, electrical conduits, junction boxes, exhaust
fans, and other components. A standard home inspection
does not include an evaluation of the adequacy of the roof
structure to support any loads, the thermal value or energy
efficiency of any insulation, the integrity of vapor retarders,
or the operation of thermostatically controlled fans. In
evaluating the type and amount of insulation on the attic
floor, we use only generic terms and approximate
measurements, and do not sample or test its composition
for a specific identification.
It is recommended that small cracks or voids in the concrete
foundation stem walls should be filled and the exposed
areas should be repainted.
Joints between dissimilar materials, such as stucco to wood,
stucco to metal flashings, stucco to window and door
frames, stucco weep screed and the concrete stem wall
etc., should be sealed and caulked for moisture and pest
protection.
Access impaired, due to the finished areas of floor ( floor
covering, etc.) in the property, we are unable to evaluate the
floor slab system. The inspector(s) cannot ascertain the
condition during a limited visual home inspection. There
may be concealed damage.
Photo: 9905.10 (1)

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 30 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Structure Components & Applications:


The following is a list of components, systems, and applications
noted during the inspection. This is a very important part of the
inspection report. Some components and some applications
require additional maintenance and consideration. The survey
of some components is limited. Some component information
contains disclosures.
Where the general condition of a component or system is
indicated, reference is to the visible and/or active components
only.
Read all narratives in the Uniform Building Inspection
Report Reference Manual, referenced by item number,
before purchasing the property.
INSPECTED STRUCTURES BUILDING TYPE:
94a Single family residence
94b(2) Home Owner's Association

APPROXIMATE ERA OF CONSTRUCTION:


91g 1996 to Present

ROOF/CEILINGS STRUCTURAL COMPONENTS:


90a(1) Truss roof system
90c Plywood/OSB roof sheathing
Roof and ceiling structural components general condition:
Acceptable where visible (Inspection limited)

FLOOR STRUCTURAL COMPONENTS:


90a(2) Truss floor system
90f Plywood/OSB subfloor
90j(1) Concrete slab floor
Floor structural components general condition: Acceptable
where visible (Inspection limited)

EXTERIOR WALLS STRUCTURAL COMPONENTS:


90t Wood framing
Exterior walls structural components general condition:
Acceptable where visible (Inspection limited)

FOUNDATION AND/OR BASEMENT STRUCTURES


WHERE VISIBLE (if basement present):
93a Concrete pier and/or perimeter foundation
93g Columns / poles / posts extrapolated description(s):

93g(5) Siding wrap on frame


93g(7) Metal
Structural posts/poles/columns general condition:
Acceptable where visible (Inspection limited)
Foundation system general condition: Acceptable where
visible (Inspection limited)
SUB-AREA OBSERVATION EXTENT AND METHOD:
This type of construction has no sub-area
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 31 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

ATTIC OBSERVATION EXTENT AND METHOD:


96b Partially viewed
96c(2) From inside attic

ATTIC ACCESS LOCATION:


An attic access is located in upstairs loft. There may be
other attic access locations not listed here.

ATTIC VENTILATION:
92a Attic ventilation
Attic ventilation adequacy: Acceptable (Inspection limited)

THE VENT DUCTS OF KITCHEN, BATH AND LAUNDRY


VENTILATION SYSTEMS, IF INSTALLED, WERE
OBSERVED TO COMPLETE THE REVIEW OF THOSE
SYSTEMS:
Kitchen ventilation adequacy: Acceptable (Inspection
limited)
Bath ventilation adequacy: Acceptable (Inspection limited)
Laundry ventilation adequacy: Acceptable (Inspection
limited)
Dryer ventilation adequacy: Acceptable (Inspection limited)

APPROXIMATE ATTIC INSULATION THICKNESS:


(In many cases, such as with flat or vaulted roof structures
without attics, the inspector cannot ascertain the thickness
of the insulation or whether any is installed. An indication of
insulation thickness does not guarantee complete coverage.
The presence of wall insulation generally cannot be
ascertained at all)
95e 9 to 12 inches (attic)
95e Thickness varies (attic)

APPROXIMATE FLOOR INSULATION THICKNESS:

INSTALLED ATTIC AND FLOOR INSULATION TYPES:


95a(2) Cellulose (loose fill)
Insulation general condition: Acceptable where visible
(Inspection limited)

VAPOR RETARDERS/BARRIERS:
Vapor retarder presence and type not fully ascertainable

Questions or concerns? Please call 602-410-9538


Essential Home Inspections Page 32 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Additional Information:
Note: Read the first page of the Uniform Building Inspection
Report Reference Manual and the Standards of Practice for
an insight into the scope of the inspection.
The inspection represents the condition of the visually
inspected areas of the property on the date of the
inspection. Component conditions may change between
the date of the inspection and the title transfer date. A
thorough walk-through prior to title transfer helps protect
against unexpected surprises, and is recommended. The
purchase of a home warranty is recommended.
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 33 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

Summary of Findings:
The condensed version is not the entire report and should
not be considered exclusive. In States requiring
summary distribution the following listed items are
considered by the inspector as inoperative, not operating
properly or as intended, health and/or safety concerns,
warranting further investigation by a specialist, or
warranting continued observation by others. In all other
States the summary may include all findings regardless
of significance.
Grounds Findings:
[+] 0970.15: No deficiencies noted in this
area at the time of the inspection.
Exterior/Roof Findings:
[M] 1510.01: Insulated window (I.G.) appears
to have lost seal.
Seal is raised between dual pane window.
Recommend monitoring window for
condensation. Noted at master bathroom
toilet area.
See Photo(s) 1510.01.
[E] 1530.06: Window cracked.
Recommend repair of window. Outside pane
of window is cracked. Noted at master
bathroom shower area.
See Photo(s) 1530.06.
HVAC & Fireplace Findings:
[+] 2851.15: No deficiencies noted in this
area at the time of the inspection.
Plumbing Findings:
[+] 4985.15: No deficiencies noted in this
area at the time of the inspection.
ElectricalFindings:
[C] 5120.05: Knockout seal(s) missing from
panel.
Knockout seal is missing on bottom of
electrical panel. Recommend installing seal to
prevent accidental electrocution or insect
entry. This is a safety hazard, recommend a
licensed electrician make necessary repair as
soon as possible. Noted at the rear of the
home.
See Photo(s) 5120.05.
Bathroom(s)Findings:
[+] 6885.10: Positive photo
Nice bathroom area. Nice tiled floor.
See Photo(s) 6885.10.
[+] 6885.15: No deficiencies noted in this
area at the time of the inspection.
Interior Findings:
[C] 7450.02: Door weather-strip faulty.
Man door weather stripping is faulty.
Recommend replacing to prevent possible fire
or exhaust gas from entering home. Also,
recommend adjusting self closing hinges to
allow man door to close properly. Noted at
man door to garage.
See Photo(s) 7450.02.
[+] 7960.10: Positive photo
Nice interior area in home. Nice Window
blinds noted throughout home.
See Photo(s) 7960.10.

Kitchen/Appliance Findings:
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 34 of 35
Copyright 2010 Essential Home Inspections
This Report Has Been Prepared Exclusively For: Paul & Marsha Martin
Property Address: 30044 N. Desert Willow Blvd, San Tan Valley, AZ 85143
Date of Inspection: 1/5/2010 Start Time: 12:30:00 PM Report Number: 20100105PM

[C] 8020.13: Oven / range anti-tip device not


installed.
Recommend installing an anti-tip device to the
oven to prevent possible injury.
See Photo(s) 8020.13.
Structure Findings:
[+] 9905.10: Positive photo
Good level of insulation in attic.
See Photo(s) 9905.10.
[+] 9905.15: No deficiencies noted in this
area at the time of the inspection.
Questions or concerns? Please call 602-410-9538
Essential Home Inspections Page 35 of 35
Copyright 2010 Essential Home Inspections