B1 TRIFASICA
----------------------------------------------------------------------------------------------------------------------------------|
DIgSILENT
| PowerFactory
|-------------------------------
| Date:
15.2.4
| Project:
10/31/2016
3-Phase Short-Circuit
| Grid Identification
| Short-Circuit Duration
Break Time
0,10 s
1,00 s
Always Considered
Automatic
| Conductor Temperature
| c-Voltage Factor
Using Method
User Defined
No
User Defined
No
| Annex:
/ 1
----------------------------------------------------------------------------------------------------------------------------------|
rtd.V.
[kV]
Voltage
[kV]
c-
[deg] Factor
Sk"
[MVA/MVA]
Ik"
[kA/kA]
[deg]
ip
Ib
Sb
Ik
[kA/kA]
[kA]
[MVA]
[kA]
Ith
[kA] |
----------------------------------------------------------------------------------------------------------------------------------|
|B1
13,80
T1
G1
0,00
0,00
1,00
B2
1436,03 MVA
60,08 kA
-86,36
154,45 kA
46,67
1115,62
60,08
61,55 |
263,88 MVA
11,04 kA
92,01
28,38 kA
1172,28 MVA
49,04 kA
-86,00
126,08 kA
-----------------------------------------------------------------------------------------------------------------------------------
B1 MONOFASICA
----------------------------------------------------------------------------------------------------------------------------------|
DIgSILENT
| PowerFactory
|-------------------------------
| Date:
15.2.4
| Project:
10/31/2016
| Grid Identification
| Short-Circuit Duration
Break Time
0,10 s
1,00 s
Always Considered
Automatic
| Conductor Temperature
| c-Voltage Factor
User Defined
No
|
|
User Defined
|
No
|
|
| Annex:
/ 1
----------------------------------------------------------------------------------------------------------------------------------|
rtd.V.
[kV]
Voltage
[kV]
c-
Sk"
[deg] Factor
[MVA/MVA]
Ik"
[kA/kA]
[deg]
ip
Ib
Sb
EFF |
[kA/kA]
[kA]
[MVA]
[-] |
----------------------------------------------------------------------------------------------------------------------------------|
|B1
|
|
13,80
0,00
0,00
9,29
9,34
1,00
401,46 MVA
50,39 kA
-85,09
129,54 kA
50,39
401,46
0,00 |
-98,06
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00
0,00
0,89 |
97,19
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00
0,00
0,91 |
|
|
|
T1
B2
84,61 MVA
10,62 kA
96,15
27,30 kA
32,07 MVA
4,03 kA -125,66
10,35 kA
28,04 MVA
3,52 kA
9,05 kA
-44,90
|
|
|
A
316,88 MVA
G1
39,77 kA
-85,42
102,24 kA
32,07 MVA
4,03 kA -125,66
10,35 kA
28,04 MVA
3,52 kA
9,05 kA
-44,90
----------------------------------------------------------------------------------------------------------------------------------
B4 TRIFASICA
----------------------------------------------------------------------------------------------------------------------------------|
DIgSILENT
| PowerFactory
|-------------------------------
| Date:
15.2.4
| Project:
10/31/2016
3-Phase Short-Circuit
| Grid Identification
| Short-Circuit Duration
Break Time
0,10 s
1,00 s
Always Considered
Automatic
| Conductor Temperature
| c-Voltage Factor
Using Method
User Defined
No
User Defined
No
|
|
| Annex:
/ 1
-----------------------------------------------------------------------------------------------------------------------------------
rtd.V.
[kV]
Voltage
[kV]
c-
[deg] Factor
Sk"
[MVA/MVA]
Ik"
[kA/kA]
[deg]
ip
Ib
Sb
Ik
[kA/kA]
[kA]
[MVA]
[kA]
Ith
[kA] |
----------------------------------------------------------------------------------------------------------------------------------|
|B4
6,30
T2
G2
0,00
0,00
1,00
B3
791,98 MVA
72,58 kA
-88,61
188,22 kA
60,52
660,34
72,58
74,55 |
355,53 MVA
32,58 kA
92,99
84,49 kA
436,71 MVA
40,02 kA
-89,92
103,78 kA
----------------------------------------------------------------------------------------------------------------------------------
B4 MONOFASICA
----------------------------------------------------------------------------------------------------------------------------------|
DIgSILENT
| PowerFactory
|-------------------------------
| Date:
15.2.4
| Project:
10/31/2016
| Grid Identification
| Short-Circuit Duration
Break Time
0,10 s
1,00 s
Always Considered
Automatic
| Conductor Temperature
User Defined
| c-Voltage Factor
No
User Defined
No
|
|
| Annex:
/ 1
----------------------------------------------------------------------------------------------------------------------------------|
rtd.V.
[kV]
Voltage
[kV]
c-
Sk"
[deg] Factor
[MVA/MVA]
Ik"
[kA/kA]
[deg]
ip
Ib
Sb
EFF |
[kA/kA]
[kA]
[MVA]
[-] |
----------------------------------------------------------------------------------------------------------------------------------|
|B4
|
|
6,30
0,00
0,00
3,78
3,73
1,00
260,97 MVA
71,75 kA
-84,59
186,06 kA
71,75
260,97
0,00 |
-109,70
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00
0,00
0,92 |
105,60
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00
0,00
0,96 |
|
|
|
T2
B3
111,79 MVA
30,73 kA
95,27
79,70 kA
3,76 MVA
1,03 kA -145,64
2,68 kA
9,92 MVA
2,73 kA -101,59
7,07 kA
|
|
|
A
149,18 MVA
G2
41,01 kA
-84,49
106,36 kA
3,76 MVA
1,03 kA -145,64
2,68 kA
9,92 MVA
2,73 kA -101,59
7,07 kA
|
|
-----------------------------------------------------------------------------------------------------------------------------------
B7 TRFASICA
----------------------------------------------------------------------------------------------------------------------------------|
DIgSILENT
| PowerFactory
|-------------------------------
| Date:
15.2.4
| Project:
10/31/2016
3-Phase Short-Circuit
| Grid Identification
| Short-Circuit Duration
Break Time
0,10 s
1,00 s
Always Considered
Automatic
| Conductor Temperature
| c-Voltage Factor
Using Method
User Defined
No
User Defined
No
| Annex:
/ 1
----------------------------------------------------------------------------------------------------------------------------------|
rtd.V.
[kV]
Voltage
[kV]
c-
[deg] Factor
Sk"
[MVA/MVA]
Ik"
[kA/kA]
[deg]
ip
Ib
Sb
Ik
[kA/kA]
[kA]
[MVA]
[kA]
Ith
[kA] |
-----------------------------------------------------------------------------------------------------------------------------------
|B7
69,00
T3
G3
B6
0,00
0,00
1,00
B8
422,71 MVA
3,54 kA
-87,53
9,34 kA
3,39
404,70
3,54
3,66 |
346,57 MVA
2,90 kA
92,13
7,66 kA
76,18 MVA
0,64 kA
-86,00
1,68 kA
-----------------------------------------------------------------------------------------------------------------------------------
B7 MONOFASICA
----------------------------------------------------------------------------------------------------------------------------------|
DIgSILENT
| PowerFactory
|-------------------------------
| Date:
15.2.4
| Project:
10/31/2016
| Grid Identification
| Short-Circuit Duration
Break Time
0,10 s
1,00 s
Always Considered
Automatic
| Conductor Temperature
| c-Voltage Factor
User Defined
No
|
|
User Defined
|
No
|
|
| Annex:
/ 1
----------------------------------------------------------------------------------------------------------------------------------|
rtd.V.
[kV]
Voltage
[kV]
c-
Sk"
[deg] Factor
[MVA/MVA]
Ik"
[kA/kA]
[deg]
ip
Ib
Sb
EFF |
[kA/kA]
[kA]
[MVA]
[-] |
----------------------------------------------------------------------------------------------------------------------------------|
|B7
|
|
69,00
0,00
0,00
37,52
37,52
1,00
192,88 MVA
4,84 kA
-87,11
12,79 kA
4,84
192,88
0,00 |
-90,35
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00
0,00
0,87 |
89,65
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00
0,00
0,87 |
|
|
|
T3
B6
B8
167,48 MVA
4,20 kA
93,05
11,11 kA
11,95 MVA
0,30 kA
82,42
0,79 kA
13,75 MVA
0,35 kA
99,99
0,91 kA
|
|
|
G3
25,40 MVA
0,64 kA
-88,18
1,68 kA
11,95 MVA
0,30 kA
82,42
0,79 kA
13,75 MVA
0,35 kA
99,99
0,91 kA
|
|
|
A
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00 MVA
0,00 kA
0,00
0,00 kA
0,00 MVA
0,00 kA
0,00
0,00 kA
CARGA 2
-----------------------------------------------------------------------------------------------------------------------------------