DDC-1

DAHU-1

Return air temperature

Fresh air temperature

Supply air temperature

Return air humidity

Fresh air humidity

Fan on/off status

Fan trip alarm

Filter clogged alarm

Damper modulating control

Fan Start/stop Control

Modulating control of cooling valve

ATC Application Handbook


Section 2
Issue Date 0500

DDC AHU Control


Free cooling application

Schematic Drawing

1
2
3
4
5
6

AI

DDC
7

BI
8
9

AO
10
11

x1

x1

x1

x1

x1

x1

x1

x1

x2

x1

x2

BO

ATC Application Handbook


Section 2
Issue Date 0500

DDC AHU Control


Free cooling application

Operation Description
For auto mode, direct digital controller, DDC (DDC-1)
provides time schedule for start/stop operation of AHU.

At free cooling operation, the motorized cooling valve (TV-1)


will be driven to fully closed position.

Duct type temperature sensor (TE-3) is installed to


sense the supply air temperature. Direct digital
controller, DDC (DDC-1) provides modulating (PI)
control for the motorized valve (TV-1), so as to maintain
the desired supply air temperature.

If the enthalpy of outdoor air is higher than that of return air or


outdoor air temperature is higher than the set point of supply
air temperature, the motorized return air damper (DA-1) will be
driven to maximum position, while the motorized outdoor air
damper (DA-2) will be driven to minimum position.

The supply air temperature set point is reset by the


return air temperature, sensed by duct type
temperature sensor (TE1), based on a reset schedule.

The controller interlocks with the supply fan status, so that on


fan shut down, the controller will be switched off, the cooling
valve will be driven to its closed position, and the dampers be
driven to fully closed position.

Duct type temperature sensors (TE-1, 2) and humidity


sensors (HE-1, 2) is installed to sense the return and
fresh air temperature and humidity. DDC calculates the
enthalpy values of return and fresh air based on the
sensed value, so as to provide free cooling control.

The differential pressure switch (DPS-1) monitors the status of


filter, when the set point is exceeded, a signal will be given to
DDC.

If the enthalpy of outdoor air is lower than that of return


air with a enthalpy differential and the outdoor air
temperature is lower than the supply air setpoint, the
motorized return air damper (DA-1) will be driven to
minimum opening, while the motorized outdoor air
damper (DA-2) will be driven to maximum opening.

Equipment List
Instr. No.

Code No.

Description

TE-1~3

TE-6311P-1

-46/104 C Duct temp. sensor

HE-1, 2

HT-9000-1D1

Duct type humidity transmitter

DPS-1

P32AC-2

0/5" W.C. differential pressure switch

DA-1, 2

M-9116-GGA-1

Modulating damper actuator, 0-10VDC 16Nm

DDC-1

DX-9100-8154

Extended Digital Controller

X-1

Y62HKL-40

Transformer, 40VA, 240/220/24V

TV-1

Refer to Valve Schedule (Section 3)

Valve & Valve Actuator with 24 VAC power supply

DAHU-1