Professional Documents
Culture Documents
The c.s.a. and the protection of the neutral conductor, apart from its current-carrying
requirement, depend on several factors, namely:
c The type of earthing system, TT, TN, etc.
c The harmonic currents
c The method of protection against indirect contact hazards according to the
methods described below
The color of the neutral conductor is statutorily blue. PEN conductor, when insulated,
shall be marked by one of the following methods :
c Green-and-yellow throughout its length with, in addition, light blue markings at the
terminations, or
c Light blue throughout its length with, in addition, green-and-yellow markings at the
terminations
Ba
ck
I1 H1
I1 H3
I2 H1
I2 H3
I3 H1
I3 H3
IN =
Ik H1
k H3
3 IH3
Fig. G65a : Triplen harmonics are in phase and cumulate in the Neutral
G45
Figure G65b shows the load factor of the neutral conductor as a function of the
percentage of 3rd harmonic.
In practice, this maximum load factor cannot exceed e.
Ba
ck
INeutral
IPhase
2.0
1.8
1.6
1.4
1.2
1.0
G46
0.8
0.6
0.4
0.2
0
i 3 (%)
0
20
40
60
80
100
Fig. G65b : Load factor of the neutral conductor vs the percentage of 3rd harmonic
Reduction factors for harmonic currents in four-core and five-core cables with
four cores carrying current
The basic calculation of a cable concerns only cables with three loaded conductors
i.e there is no current in the neutral conductor. Because of the third harmonic
current, there is a current in the neutral. As a result, this neutral current creates an
hot environment for the 3 phase conductors and for this reason, a reduction factor
for phase conductors is necessary (see Fig. G66 ).
Reduction factors, applied to the current-carrying capacity of a cable with three
loaded conductors, give the current-carrying capacity of a cable with four loaded
conductors, where the current in the fourth conductor is due to harmonics. The
reduction factors also take the heating effect of the harmonic current in the phase
conductors into account.
c Where the neutral current is expected to be higher than the phase current, then the
cable size should be selected on the basis of the neutral current
c Where the cable size selection is based on a neutral current which is not
significantly higher than the phase current, it is necessary to reduce the tabulated
current carrying capacity for three loaded conductors
c If the neutral current is more than 135% of the phase current and the cable size is
selected on the basis of the neutral current then the three phase conductors will not
be fully loaded. The reduction in heat generated by the phase conductors offsets the
heat generated by the neutral conductor to the extent that it is not necessary to apply
any reduction factor to the current carrying capacity for three loaded conductors.
ck
B a Third harmonic content
of phase current
(%)
0 - 15
15 - 33
33 - 45
> 45
Reduction factor
Size selection is based on
phase current
1.0
0.86
-
Fig. G66 : Reduction factors for harmonic currents in four-core and five-core cables
(according to IEC 60364-5-52)
Examples
Consider a three-phase circuit with a design load of 37 A to be installed using fourcore PVC insulated cable clipped to a wall, installation method C. From Figure G24,
a 6 mm2 cable with copper conductors has a current-carrying capacity of 40 A and
hence is suitable if harmonics are not present in the circuit.
c If 20 % third harmonic is present, then a reduction factor of 0,86 is applied and the
design load becomes: 37/0.86 = 43 A.
For this load a 10 mm2 cable is necessary.
c If 40 % third harmonic is present, the cable size selection is based on the neutral
current which is: 37 x 0,4 x 3 = 44,4 A and a reduction factor of 0,86 is applied,
leading to a design load of: 44.4/0.86 = 51.6 A.
For this load a 10 mm2 cable is suitable.
c If 50 % third harmonic is present, the cable size is again selected on the basis of
the neutral current, which is: 37 x 0,5 x 3 = 55,5 A .In this case the rating factor is
1 and a 16 mm2 cable is required.
G47
Ba
ck
TT
TN-C
TN-S
IT
Single-phase
(Phase-Neutral)
N
or
N (B)
or
Single-phase
(Phase-Phase)
(A)
(A)
or
or
G48
Three-phase
four wires
Sn u Sph
N (B)
or
Three-phase
four wires
Sn < Sph
N (B)
or
(A) Authorized for TT or TN-S systems if a RCD is installed at the origin of the circuit or upstream of it, and if no artificial
neutral is distributed downstream of its location
(B) The neutral overcurrent protection is not necessary:
c If the neutral conductor is protected against short-circuits by a device placed upstream, or,
c If the circuit is protected by a RCD which sensitivity is less than 15% of the neutral admissible current.
Fig. G67 : The various situations in which the neutral conductor may appear