Professional Documents
Culture Documents
EV MS F / 5240.46 / M
Erlangen, 21. August 1997
When a fault occurs at a voltage transformer, a circuit breaker will always respond. Whether the
feeder breaker or an upstream incoming feeder breaker clears, depends on the duty of the branch
circuit and its partitioning.
Branch
Branch
Incomer
Busbar
Busbar
Energy
flow
Energy
flow
Circuit-breaker
Cable termination
Circuit-breaker
Overcurrent relay
Line differential
relay
Compartmented cubicle
Overcurrent relay
Cable termination
Energy
flow
1) This summary extends various texts by Messrs Dorsch, Jahn and the Ritz Company.
N:\mt\5240\46\THEMEN\U-Wandler mit HH-Sicherung\HRC Fuses for Voltage Transformers.doc 30.10.00
1/3
3
The operating primary currents of voltage transformers lie in the milliampere range, whereas the
smallest rated currents of HRC fuses start at a few full amperes. Current limiting, back up fuses,
which are mostly used, first operate at currents over 10 A.
Possible operating currents I1 for voltage transformers:
10 kV maximum 100 mA
20 kV maximum 50 mA
at rated power:
HRC fuse
e.g.: IrHH = 6 A (Imin 25 A)
If a fault occurs within a voltage transformer, for example, a winding short circuit, that leads rapidly
to thermal overload. The transformer bursts and causes a fault arc which, for a single pole transformer first becomes evident as an earth fault or, for a two phase transformer, immediately as a
phase to phase short circuit. An earth fault developes within about 100 ms into a multi phase fault.
Possible faults on 1- and 2-pole voltage transformers and their effects are listed in the table on the
following page, together with the response of an HRC fuse and the effects on the switchboard.
Busbar
HRC Fuse
I1
Voltage transformer
Measuring cubicle
Measuring cubicle
with compartments
Measuring cubicle
non-compartmented
2/3
Possible faults on 1- and 2-pole voltage transformers and their effects
Nr.
Type of fault *
Current I1
HRC Fuse
separate enclosures
I1 = Ik > Imin
operates
2a
I1 = IE < Imin
I1 = IE > Imin
operates
operates
2b
3a
3b
4
operates
Fault arc: the fuse does interrupt but the arc reignites on line side live terminals.
5a
I1 < IrHH
First, fault arc in transformer enclosure due destruction of transfr., then fuse interrupts and limits
damage to transfr. Enclosure.
5b
I1 < IrHH
First, fault arc in transformer enclosure due deAfter short time transformer thermally destroyed - phase to phase short circuit - fault as No. 1 struction of transfr., then fuse interrupts and limits
damage to transformer enclosure.
- fault arc
First, fault arc in transformer enclosure due detruction of transfr., then fuse interrupts and limits damage to transformer enclosure.
I1 IrHH (<1 A)
First, fault arc in transformer enclosure due detruction of transfr., then fuse interrupts and limits damage to transfr. Enclosure.
I1 IrHH (<1 A)
First, fault arc in transformer enclosure due detruction of transfr., then fuse interrupts and limits damage to transfr. Enclosure.
* When not separately listed, there is no difference between 1 and 2-pole transformers.
I1 = Primary current
Imin = Minimum interrupt current; above this the fuse will certainly interrupt and clear.
3/3