Professional Documents
Culture Documents
March, 2000
Tip #35 Overcurrent Protection [210-20]
Branch circuit overcurrent protection devices must be sized no less than 125 percent of the
continuous loads, plus 100 percent of the noncontinuous loads; see Section 210-19(a) for branch
circuit conductor size for continuous loads.
Tip #36 Outlet Device Rating [210-21]
Receptacle and lighting outlet devices shall have an ampere rating not less than the load and shall
comply with (a) and (b).
(a) Lampholder Ratings. Lampholders connected to a branch circuit with a rating over 20 ampere
shall be of the heavy-duty type.
WARNING: Lampholders used for fluorescent lamps are not rated heavy duty; therefore,
fluorescent lighting fixtures cannot be installed on circuits rated over 20 ampere.
(b) Receptacle Ratings and Loadings.
(1) Single Receptacle. A single receptacle installed on an individual branch circuit shall have an
ampacity not less than the rating of the overcurrent protection device. A single receptacle is one
receptacle on a strap or yoke. A duplex receptacle is a multioutlet receptacle; see Article 100.
(2) Multiple Receptacle Loading. Where connected to a branch circuit supplying two or more
receptacles or outlets, receptacles must have the load limited to 80 percent of the receptacle
rating, according Table 210-21(b)(2).
(3) Multiple Receptacle Rating. When two or more receptacles are on a single branch circuit, the
receptacles must be rated and installed on a circuit in accordance with Table 210-21(b)(3).
Tip #37 Common Area Branch Circuits [210-25]
Branch circuits in a dwelling unit are only permitted to supply only loads within or associated
with the dwelling unit.
Branch circuits for lighting, central alarm, signal, fire alarm, communications, or other needs for
public safety shall not originate from a dwelling unit panelboard. This rule reduces the likelihood
of the safety circuits being turned off by tenants, or of loss of power due to nonpayment of
electric bills.
Note: This Section is not intended to prevent the dwelling unit panelboard from supplying
circuits in locker, laundry, or garage facilities that are not safety-related.
Kitchen Countertop Receptacles, Two Circuits Required. 125 volt, 15, or 20 ampere receptacles
used for countertop surface appliances in a dwelling unit kitchen must be supplied by at least two
20 ampere circuits [210-11(c)(1) and 220-16(a)]. These small appliance branch circuits can
supply receptacles in the kitchen as well as the pantry, breakfast room, dining room, or other
similar areas where food is likely to be served.
Kitchen and Dining Countertop Receptacle Location. In kitchens and dining rooms of dwelling
units, receptacle outlets for counter spaces shall be installed according to (1) through (5) below.
GFCI protection is required for all 125 volt, 15, and 20 ampere receptacles that supply kitchen
countertop surfaces [210-8(a)(6)].
(1) Wall Counter Space. A receptacle outlet must be installed for every kitchen and dining area
counter wall space 12 inches or wider. Receptacles must be installed so that no point along the
counter wall space is more than 2 feet (measured horizontally) from a receptacle outlet.
(2) Island Countertop Space. This Section mandates only one receptacle outlet to be installed at
each island countertop that has a long dimension of 24 inches or greater, and a short dimension
of 12 inches or greater.
(3) Peninsular Countertop Space. This Section mandates only one receptacle outlet to be installed
at each peninsular countertop that has a long dimension of 24 inches or greater, and a short
dimension of 12 inches or greater.
(4) Separate Spaces. When breaks occur in countertop spaces (ranges, refrigerators, sinks, etc.),
each countertop surface is considered a separate counter for determining receptacle placement.
(5) Receptacle Outlet Location. Receptacle outlets shall be located above the countertop, but not
more than 18 inches from the countertop surface. Receptacles shall not be installed in a face-up
position in the work surfaces or countertops and they must not be located on the sides of
cabinets.
Receptacles that are rendered not readily accessible by appliances fastened in place, or
appliances in dedicated spaces (dishwasher, microwave, etc.), are not considered meeting the
receptacle outlets as required by this Section.
Exception. The receptacle outlet required for the countertop can be installed below the
countertop where necessary for the physically impaired or where there is no wall space above the
island or peninsular counter. The receptacle must be located not more than 12 inches below the
countertop surface and it cannot extends more than 6 inches measured horizontally from the
counters edge.
Tip #41 Dwelling Bathroom Receptacle Outlet [210-52(d)]
At least one receptacle outlet must be installed within 36 inches of the outside edge of each basin
and the receptacle shall be located on a wall that is adjacent to the basin location. This rule
insures that a receptacle is located next to each basin to keep equipment cords from being draped
across a sink.
Note: One receptacle outlet can be used between two basins, if the receptacle is located within 36
inches of the outside edge of each basin.
Tip #42 Dwelling Unit Outside Receptacle Outlet [210-52(e)]
One-Family Dwelling Unit. Two receptacle outlets shall be installed not more than 6feet above
grade, one at the front, and one at the back of the one-family dwelling. GFCI protection is
required for these receptacles [210-8(a)(3)].
Two-Family Dwelling Unit. Each grade level unit of a two-family dwelling must have two
receptacles outlets installed not more than 6 feet, 6 inches above grade, one at the front and one
at the back of each dwelling unit at grade level. GFCI protection is required for these receptacles
as well [210-8(a)(3)].
Note: This Section does not require a receptacle outlet to be installed for dwelling units in a
multifamily dwelling building. However, if a receptacle outlet is installed outdoors of a dwelling
unit in a multifamily dwelling it must be GFCI protected [210-8(a)(3)].
Tip #43 Dwelling Unit Laundry Area Receptacle Outlet [210-52(f)]
All dwelling units shall have at least one 20 ampere receptacle for the laundry area receptacles.
The Code does not require a separate circuit for the washing machine but it does require a
separate 20 ampere circuit for the laundry receptacle outlet(s) [210-11(c)(2)].
Exception No. 1: Multifamily Building. If in a multifamily building laundry facilities are
available to all building occupants, than a laundry circuit is not required to be installed in each of
the dwelling units.
Tip #44 Dwelling Unit Basement and Garage Receptacle Outlet [210-52(g)]
Basement Receptacles. For a one-family dwelling, at least one 125 volt, 15, or 20 ampere
receptacle outlet, in addition to any provided for laundry equipment, shall be installed in each
basement. Where a portion of the basement is finished into a habitable room(s), a 125 volt, 15, or
20 ampere receptacle outlet shall be installed in the unfinished portion of the basement.
Note: Section 210-8(a)(5) requires 125 volt, 15, or 20 ampere receptacles installed in the area of
a basement not intended as a habitable room to be GFCI protected. The combination of Section
210-52(g) and 210-8(a)(5) insures that the unfinished portion of a basement has one GFCI
protected 125 volt, 15, or 20 ampere receptacle outlet, even if a portion of the basement is
finished into a habitable room(s). This prevents an extension cord from a non-GFCI protected
receptacle to supply power to loads in the unfinished portion of the basement.
Garage Receptacles. At least one receptacle outlet must be installed at each dwelling unit garage
with electric power. Section 210-8(a)(2) requires 125 volt, 15, or 20 ampere receptacles installed
in the garage to be GFCI protected.
Note: The laundry outlet required in Section 210-52(f) is not permitted to satisfy the receptacle
outlet requirement for either the basement or garage.
Tip #45 Dwelling Unit Hallway Receptacle Outlet [210-52(h)]
One receptacle outlet shall be installed for each hallway*.
*Hallway. A hallway is a corridor that is at least 10 feet long measured along the centerline of the
hall without passing through a doorway.
Tip #46 Receptacles in Guestroom for Hotels and Motels [210-60]
Receptacle Requirements. Guest rooms in hotels, motels, and similar occupancies shall have
receptacle outlets installed in accordance with Section 210-52, such as:
Number of Receptacles. Receptacle outlets shall be installed so that no point along the floor line
in any wall space is more than 6 feet, measured horizontally, from an outlet in that space,
including any wall space 2 feet or more in width [210-52(a)].
Bathroom Receptacles. A receptacle outlet shall be installed within 36 inches of the outside edge
of each basin supplied by a 20 ampere branch circuit [210-52(d)].
Receptacle Placement. The total number of receptacle outlets shall not be less than the minimum
number that would comply with the provisions of Section 210-52(a). However, the receptacle
outlets can be located so as to be convenient for permanent furniture layout, but at least two
receptacle outlets shall be readily accessible to eliminate the need for extension cords by guests
for ironing, computers, refrigerators, etc. Receptacles installed behind a bed must be located so
that the bed does not make contact with the attachment plug, or the receptacle must be provided
with a suitable protective guard.
Tip #47 Receptacles for Rooftop, Attic, and Crawl Spaces [210-63]
Heating, air-conditioning, refrigeration equipment located on roof tops, or in attics and crawl
spaces, shall have a 125 volt, 15 or 20 ampere receptacle outlet for servicing the equipment. The
receptacle shall be installed at an accessible location within 25 feet of the equipment.
Receptacles located on the roof must be GFCI protected [210-8(b)(2)] and must not be connected
to the load side of the equipment disconnect. See Section 210-70 for the requirement of a
lighting outlet for equipment requiring service.
Exception. Receptacle outlets are not required for rooftop equipment in one- and two-family
dwellings.
The load calculation does not change when the number of receptacle outlets, specified in 220.14(J)(1) through (J)(3),
is more than the required minimum. For example, another living room, identical to the one in Figure 1, contains
twice the number of required receptacle outlets. The load for this living room is calculated exactly the same as the
load for the living room in Figure 1 (see Figure 2).
The minimum number of 15- and 20-ampere branch circuits in dwellings for lighting and general-use receptacle
outlets depends on the floor area. After finding the general lighting load in accordance with Table 220.12, divide by
the voltage of a general-purpose branch circuit (typically 120 volts). The result (in amperes) can then be divided by
either 15- or 20-ampere branch circuits. For example, a dwelling unit has outside dimensions of 55 feet by 35 feet.
To find the general lighting load, the outside dimensions must be multiplied by a unit load of 3 volt-amperes per
square foot. The minimum lighting load for this dwelling is 5,775 volt-amperes (55 x 35 x 3 = 5,775). With a voltage
of 120/240, the general lighting load is 48 amperes (5,775 120 = 48). To find the minimum number of 15-amperes,
2-wire circuits, divide 48 by 15 (48 15 = 3.2 = 4). Because this result is three and two-tenths circuits, the number
must be rounded up. At least four 15-amperes, 2-wire circuits are required (see Figure 3).
Calculate the minimum number of 20-ampere general-purpose branch circuits the same. For example, a dwelling
unit has outside dimensions of 55 feet by 35 feet. Since this dwelling is the same as the one in Figure 3, the general
lighting load is the same (48 amperes). To find the minimum number of 20-amperes, 2-wire circuits for lighting and
general-use receptacles, divide 48 by 20 (48 20 = 2.4 = 3). The minimum number of 20-ampere, 2-wire generalpurpose branch circuits for lighting and receptacles in this dwelling is three. Be careful when calculating the
minimum number of 20-ampere branch circuits. At least one 20-ampere laundry circuit and at least two 20-ampere
small-appliance branch circuits are required. While the bathroom branch circuit supplying receptacle outlets must be
rated 20 amperes, no additional load calculation is required (see Figure 4). Load calculations for small-appliance and
laundry branch circuits are covered in 220.52 and will be discussed later in this load-calculation series. Caution is
advised when installing receptacles on branch circuits in dwellings. Local jurisdictions could limit the number of
receptacle outlets permitted on 15- and 20-ampere, general-purpose branch circuits.
Although not mentioned before Part VIII of Branch-Circuit, Feeder and Service Calculations, there are areas in
another occupancy covered in 220.14(J) besides one-family, two-family and multifamily dwellings. In guest rooms
or guest suites of hotels and motels, the outlets specified in 220.14(J)(1), (J)(2), and (J)(3) are also included in the
general lighting-load calculations of 220.12. Therefore, no additional load calculation is required for these receptacle
outlets also (see Figure 5). The unit load for general lighting in for hotels and motels is 2 volt-amperes per square
foot (Table 220.12).
Although this list includes basements, the general provisions are applicable to any part of a
basement containing habitable rooms, such as a den, recreational room, play (game) room, etc.
One location not mentioned is closets. Although receptacle outlets within closets are permitted,
they are not required.
210.52(A)(1) Spacing
The amount of wall space determines the minimum number of receptacle outlets in a given
dwelling. Wall space is measured horizontally along the floor line. Although the Code spells out
requirements for the minimum number of receptacles in a dwelling, it does not limit the number
of receptacle outlets.
Receptacles must be installed so that no point measured horizontally along the floor line in any
wall space is more than 6 feet or 1.8 meters from an outlet in that space. Following the floor line
from a doorway, fireplace or similar opening, the maximum distance to a receptacle is 6 feet (1.8
meters). Sometimes this requirement is known as the 6-foot rule.
Since the maximum distance to a receptacle is 6 feet (1.8 meters), the maximum distance
between two receptacles is doubled. Therefore, the maximum distance between receptacles is 12
feet (3.6 meters).
An easy way to understand and remember the placement of receptacles in dwellings is to
imagine having a floor lamp with a 6-foot cord. Anywhere this lamp is placed around the wall, a
receptacle should be within reach (unless the space is less than 24 inches wide). No extension
should be required to supply power to this lamp.
Since a receptacle is required within 6 feet (1.8 meters) of a door opening, if the lamp is placed
next to the opening, a receptacle will be within reach. Unless the wall is less than 2 feet wide, the
6-foot rule is applicable.
210.52(A)(2) Wall Space
This section contains three sentences that clarify the term wall space. As used in this section, a
wall space is any space that is 2 feet (600 mm) or more in width. [210.52(A)(2)(1)] This
provision is straightforward. If the space is less than 2 feet (600 mms) wide, it is not considered
wall space; therefore no receptacle is required. If the space is 2 feet (600 mm) or more in width,
then it is considered wall space, and consequently a receptacle outlet is required.
For example, two bedrooms located in a dwelling unit are almost identical. In each room, a small
wall space is located between the entry door and the closet door. The wall space between the
doors in the first room measures exactly 2 feet (600 mm) wide. Since this rooms space measures
2 feet (600 mm), a receptacle outlet is required.
The wall space between the doors in the second room is only 23 inches in width. In this room, no
receptacle is required.
Although receptacles are permitted in a space less than 2 feet (600 mm) wide, they are not
required.
Note: Since these receptacles are located in bedrooms, they must be arc-fault protected. All
branch circuits supplying 125-volt, single-phase, 15- and 20-ampere outlets installed in dwelling
unit bedrooms must be protected by an arc-fault circuit interrupter listed to provide protection of
the entire branch circuit.
Wall space includes the space measured around corners, regardless of whether the corner is an
inside or outside corner. The wall space continues unless broken by a doorway, fireplace or
similar opening.
The space occupied by fixed panels (in exterior walls) is considered wall space and must be
included when determining the minimum number of receptacle outlets. Sliding panels, also in
exterior walls, are treated like doorways. Therefore, the space in front of sliding panels is not
counted as wall space. Even if a window is designed to resemble a door, the space must be
counted as wall space.
For example, a dwelling units back door is a glass panel door. A window, located on each side of
the door, is almost identical to the door. Since the windows are fixed and do not open, the space
they occupy must be counted as wall space. The space in front of windows extending from
ceiling to floor must also be counted. For example, a sunroom is surrounded by floor-to-ceiling
windows.
Although there is virtually no wall space in the sunroom, receptacle outlets must still be installed
in accordance with the general provisions. Floor receptacles can be installed if they are located
within 18 inches (450 mm) of the wall.
Sliding glass doors contain fixed and sliding panels. Most sliding glass doors are comprised of
two panels, one fixed and one sliding. While it is not necessary to count the space in front of the
sliding panel, it is necessary to count the space in front of the fixed panel.
In residential occupancies receptacles are required to be spaced at fixed intervals; this is not the
case for commercial occupancies. In commercial, industrial, institutional, etc. occupancies
receptacles are generally located only where required to supply cord-and-plug connected loads.
For this reason, unit loads are assigned to receptacles in other than residential occupancies. The
Code mandates spacing of receptacles in dwelling units to provide flexibility in the use of table
lamps, floor lamps and other appliances and to reduce the use of exterior cords; not because there
will be loads plugged into every receptacle.
In all occupancies 210.11 requires an adequate number of branch circuits for the calculated
loads. And 210.11(B) require that the calculated load be evenly divided among the branch
circuits.
Some inspection authorities have local laws or ordinances that limit the number of receptacle
outlets on 15 and 20A branch circuits in residences. I am not in favor of such a regulation, but
you should be aware of such a restriction if one exists.