Professional Documents
Culture Documents
www.schneider-electric.com
www.schneider-electric.com
Revision: Revision C
www.schneider-electric.com
Contact Information
For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider
Electric website at:
http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page
Information About Your System
As soon as you open your product, record the following information and be sure to keep your proof of purchase.
Serial Number
_________________________________
Product Number
_________________________________
Purchased From
_________________________________
Purchase Date
_________________________________
Conventions Used
The following conventions are used in this manual.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result
in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result
in moderate or minor injury.
NOTICE
NOTICE indicates a potentially hazardous situation, which, if not avoided, can result in
equipment damage.
990-4613B Revision C
iii
ANSI
BDEW
CE
CENELEC
DIN
GFDI
HVAC
IEC
NFPA
PE
PPE
PV
Photovoltaic
RMS
SELV
VAC
VDC
VDE
Related Information
You can find more information about Schneider Electric and its products and
services at www.schneider-electric.com.
iv
990-4613B Revision C
DANGER
HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Read all instructions, cautionary markings, and all other appropriate sections of this
manual before installing or maintaining the Conext Core XC Series.
This inverter is energized from multiple sources: the PV array, the AC grid, and the
external auxiliary AC source (if used). Before opening doorsa or covers:
De-energize, lock out, and tag out all sources following the procedure beginning
on page ix.
Operation of the switches in or on the inverter does not remove all power from this
inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC
source have been disconnected externally.
Before servicing, test using a meter rated at least 1000 V AC and DC, to ensure all
circuits are de-energized.
For proper circuit isolation, connect a suitably rated isolating transformer between
the output of the inverter and the utility power line connections. The transformer
must be selected and installed in accordance with this manual. The transformer
must be an isolation type having separate primary and secondary windings.
990-4613B Revision C
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH
HAZARD OF EQUIPMENT DAMAGE
Obey the manuals instructions plus all physical, electrical, and environmental
specifications shipped with the inverter.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH
In all installations, the installer must provide external disconnecting means for the
PV input, AC output, and external auxiliary AC source input wiring.
The overcurrent protection devices within the inverter are intended to provide
adequate protection for inverter circuitry only.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH
Do not install or attempt to operate the inverter if it has been dropped or has received
more than cosmetic damage during transport or shipping. If the inverter is damaged, or
suspected to be damaged, contact customer service.
WARNING
LIMITATIONS ON USE
The inverter is not intended for use in connection with life support systems or other
medical equipment or devices. The inverter can only be used in grid-interconnected PV
systems. It is not suitable for any other application areas.
WARNING
HAZARD OF CRUSH INJURY AND EQUIPMENT DAMAGE
Use caution and follow the instructions in this manual for correct lifting, moving, and
mounting of the inverter.
The inverter can easily fall over if it is moved without caution. The inverter must be
securely attached to the mounting surface after positioning.
vi
990-4613B Revision C
Safety
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Do not defeat or change the settings of the heaters located inside the inverter as these
heaters are installed to help prevent condensation inside the inverter.
CAUTION
HAZARD OF BURNS
Components become hot during normal operation. Surfaces inside of the inverter may
continue to be hot after the 15 minute duration required to discharge the internal
capacitors. After opening the cabinet doors, follow all posted warnings and use caution
before touching conductive surfaces.
CAUTION
HAZARD OF OVERHEATING AND EQUIPMENT DAMAGE
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Inverter electronics can be destroyed by electrostatic charge. Wear electrostatic
protection gear, and use anti-static tools and procedures when installing the inverter.
Failure to follow these instructions can result in damage to equipment.
990-4613B Revision C
vii
Personal Protection
Follow these instructions to help protect yourself while working with the Conext
Core XC Series.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Never work alone when installing this inverter. A team of two is required until
external sources are properly de-energized, locked out and tagged out, and
verified de-energized with a meter, according to the procedure beginning on
page ix.
Thoroughly inspect the inverter prior to energizing. Verify that no tools or materials
have inadvertently been left inside the inverter and that all guards and barriers are
properly replaced and secured.
Protective glasses
Ear protection
Padlocks and tags (for lock out and tag out of disconnects)
Check local safety regulations and applicable workplace safety procedures for
additional requirements.
viii
990-4613B Revision C
Safety
DANGER
MULTIPLE SOURCES WITH HAZARD OF ELECTRIC SHOCK, FIRE,
EXPLOSION, AND ARC FLASH
The Conext Core XC Series inverter is energized from the PV array, the AC grid, and
the external auxiliary AC source (if used). Before installing the inverter:
De-energize, lock out, and tag out all sources following the procedure beginning
on page ix.
Test using a meter rated at least 1000 V AC and DC to ensure all circuits are deenergized.
Operation of the switches in or on the inverter does not remove all power from this
inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC
source have been disconnected externally.
Additional external disconnecting means for the PV, AC, and external auxiliary AC
source (if used), capable of being locked out and tagged out, must be provided as
part of the installation to help facilitate safe installation and for certain servicing
operations.
990-4613B Revision C
ix
990-4613B Revision C
Safety
Front panel
user interface
Power stage cabinet
AC cabinet
DC cabinet
ENABLE STATE/
DISABLE STATE
switch
Inverter ON/OFF
switch
AC circuit breaker
PV disconnect
990-4613B Revision C
xi
The external sources are verified de-energized, locked out, and tagged out.
The inverter switches have all been opened, locked out, and tagged out.
This completes the LOTO procedure for the external sources and the inverter for
first-time installation of the inverter.
Note: inverter
shown with
barriers removed
Internal inverter
ON/OFF switch
PV auxiliary
circuit breaker
990-4613B Revision C
Contents
Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - v
Installation Lock-out and Tag-out Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ix
Introduction
Operator Interface Controls - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12
ENABLE STATE/DISABLE STATE Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -13
Inverter ON/OFF Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -13
Front Panel User Interface - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -15
Local vs. Remote Monitoring- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16
Setting the Communication Method - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -16
AC Circuit Breaker and PV Disconnect Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 18
Planning
Inverter Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 22
Site Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -22
Conduit Entry - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -23
Anchoring the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -24
Grounding the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -24
Installation at High Elevation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -24
Ventilation Outside a PV Shelter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -25
Exhaust Duct Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -25
Venting Recommendations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -26
PV Array Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 27
Number of PV Panels - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -27
Grounding the Array - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -27
Utility Side Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 28
Transformer Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -28
General Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -28
Medium Voltage Winding Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -29
Low Voltage Winding Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -29
Electrical Diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 210
Installation
Unloading - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 32
Removing the Conext Core XC Series from a Truck - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -33
Removing the Conext Core XC Series from the Pallet - - - - - - - - - - - - - - - - - - - - - - - - - - - - -34
Mounting and Anchoring the Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 35
Opening Access Doors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 35
General Wiring Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 36
Conductor Termination - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -36
Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -39
Specific Wiring Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 310
AC Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -310
990-4613B Revision C
xiii
313
316
317
319
321
322
323
326
Inspection
Visual Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 42
Re-installing AC and DC Barriers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
Arranging for Commissioning and Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
Specifications
System Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Electrical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Physical and Environmental Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Regulatory Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Bolt Sizes and Torque Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Dimensions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
A2
A2
A3
A4
A4
A5
xiv
990-4613B Revision C
Figures
Figure i
Figure ii
Figure iii
Figure 1-1
Figure 1-2
Figure 1-3
Figure 1-4
Figure 1-5
Figure 2-1
Figure 2-2
Figure 2-3
Figure 2-4
Figure 2-5
Figure 2-6
Figure 2-7
Figure 3-1
Figure 3-2
Figure 3-3
Figure 3-4
Figure 3-5
Figure 3-6
Figure 3-7
Figure 3-8
Figure 3-9
Figure 3-10
Figure 3-11
Figure 3-12
Figure 3-13
Figure 3-14
Figure 3-15
Figure 3-16
Figure 3-17
Figure 3-18
Figure 3-19
Figure 3-20
Figure 3-21
Figure 3-22
Figure 3-23
Figure 3-24
Figure 3-25
Figure 3-26
Figure A-1
990-4613B Revision C
xv
xvi
Tables
Table 1-1
Table 3-1
Table 3-2
Table 3-3
Table 3-4
Table 3-5
Table A-1
Table A-2
Table A-3
Table A-4
Communication features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16
Voltage ranges and transformer taps for external auxiliary AC source
(original Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -317
Voltage ranges and transformer taps for external auxiliary AC source
(newer Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -317
XT2:21 cable location for transformer tap
(original Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -319
Tap selection for internal auxiliary AC source connection
(original Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -320
Tap selection for internal auxiliary AC source connection
(newer Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -320
Electrical specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A2
Physical and environmental specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A3
AC terminal bolt size and torque values - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A4
PV terminal bolt size and torque values - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A4
990-4613B Revision C
xvii
xviii
Introduction
990-4613B Revision C
11
Exhaust
Exhaust
Exhaust
Front panel
user interface
Power stage cabinet
AC cabinet
DC cabinet
ENABLE STATE/
DISABLE STATE
switch
Inverter ON/OFF
switch
AC circuit breaker
PV disconnect
Air intake
Air intake
Air intake
Air intake
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Close the DC cabinet door as soon as you have read the display of the isolation
monitor.
Avoid longer than necessary operation with the DC cabinet door open.
12
990-4613B Revision C
DANGER
HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Turning the switch to the DISABLE STATE position will not de-energize the inverter; it only
stops power production. Externally disconnect the PV, AC, and external auxiliary AC
source to de-energize the switch terminals.
DANGER
HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Turning the switch to the OFF position will not de-energize the inverter; it only stops
power production. Externally disconnect the PV, AC, and external auxiliary AC source
to de-energize the switch terminals.
990-4613B Revision C
13
ENABLE STATE/
DISABLE STATE
switch
Inverter ON/OFF
switch
Figure 1-2 ENABLE STATE/DISABLE STATE switch and inverter ON/OFF switch
14
990-4613B Revision C
Access level
Periodic servicing
reminder
Inverter activity or
state description
Parameter
description
Event ID
PV
LVL2
6341
Online
Inverter status
line
Inverter state
Active power
463.5 kW
Parameter value
F1 return to default
parameter display
Disable via
software command
Exit current
menu
Enable via
software command
Unused
Scroll wheel
990-4613B Revision C
15
Description
Communication Method
System status
Disable
Online
Offline
Service
Offline state
event
Service state
event
Data logging
16
Select Panel Control to use the front panel user interface for
communication.
990-4613B Revision C
990-4613B Revision C
17
Operation of the switches in or on the inverter does not remove all power from this
inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC
source have been disconnected externally.
18
990-4613B Revision C
AC cabinet
DC cabinet
PV
disconnect
switch
(QF11)
AC circuit
breaker
(QF1)
AC circuit breaker
PV disconnect switch
990-4613B Revision C
19
110
990-4613B Revision C
Planning
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE
990-4613B Revision C
21
Inverter Requirements
Site Requirements
The Conext Core XC Series is designed to be installed indoors only.
Establish and maintain the following site conditions to help facilitate safe and
efficient installation, operation, and servicing of the Conext Core XC Series.
Ventilation
The inverter has open sections in the bottom of the AC and DC cabinets and
ventilation openings in the front of all cabinets. Additionally, there are exhaust
openings at the top of all cabinets. Overall pressure drop across combined
intake and exhaust must not exceed 60 Pa.
Flammability
To help reduce the risk of fire, the inverter must be mounted over non-flammable
surfaces below the inverter and extending in front of the inverter for 1 m
(39 in.). That area under and in front of the inverter must also be kept clear of
flammable materials during operation of the inverter. The inverter must be
mounted flush to the mounting surface, without openings around the bottom
perimeter of the inverter. Openings for wire entry must be filled or closed to
maintain a non-flammable barrier under the inverter.
Clearance
Accessibility
Cabling
External cabling enters the inverter from the bottom into the wiring compartments
of the AC and DC cabinets. Appropriate conduits and fittings must be used
based on local electrical codes.
IP rating
The inverter has an ingress protection rating of IP20. The installation location
must meet the physical and environmental specifications listed in Table A-2 on
page A3.
Heat load
22
The intake for the inverter is located on the front (see Figure 2-4). The intake
airflow should meet the requirements of the environmental specifications listed in
Table A-2 on page A3. If these conditions cannot be met, filtration must be
implemented external to the intake to ensure contaminants do not enter the
inverter.
990-4613B Revision C
Conduit Entry
Conduit and cable entry is from the bottom of the inverter. Figure 2-1 shows a top
view of the maximum allowable area and location in which electrical conduits can
penetrate the cabinets of the Conext Core XC Series. Conductor size must be
pre-determined when the conduit is installed and must be based on local code
requirements.
DANGER
HAZARD OF ELECTRIC SHOCK
The circuits provided for use with external communications and control equipment
are designed to provide safety isolation from neighboring hazardous circuits within
the inverter. Separate conduit entries must be provided for the communications and
control circuits and the PV circuits and all AC circuits. See Remote Communication
and Control Wiring in the Conext Core XC Series Planning and Installation Manual
for proper maintenance of safety isolation for wiring related to these circuits.
The Conext Core XC Series is not provided with a conduit mounting surface to
interface with the chassis. As such, no bonding to ground is provided for external
metal conduits and this bonding must be provided elsewhere in the installation.
Dimensions in mm
(not to scale)
990-4613B Revision C
23
Dimensions in mm
(not to scale)
24
990-4613B Revision C
Wind, including lateral wind, must not be allowed to stop outgoing air flow
while the inverter is operating.
Predict any way that wind, including lateral wind, may compromise the
venting method used, such as partially closing vents, or closing all of the
vents on one side of the PV shelter. The result of this compromise must not
exceed the allowable overall pressure drop (see Ventilation on page 22)
and must maintain the minimum airflow requirements of the inverter (see
Heat load on page 22).
Wind, including lateral wind, must not be allowed to create a back-flow of air
(carrying humidity, snow, rain, or dust) into the inverter at any time.
Overall pressure drop across combined intake and exhaust for the PV shelter
must not exceed 60 Pa.
Figure 2-3 shows the mounting locations on top of the inverter to accommodate
an exhaust duct (if one is planned to route the exhaust to the exterior of the PV
shelter). If the inverter exhaust is to be routed to the exterior of a PV shelter,
mount the exhaust duct on top of the inverter in the locations shown in Figure 2-3.
DANGER
HAZARD OF SHOCK AND AMPUTATION
Do not modify the roof panels of the inverter as doing so could expose live and moving
parts. It can also cause contamination inside the inverter and compromise the
functional design.
990-4613B Revision C
25
Venting Recommendations
You can use any configuration that meets the requirements in Ventilation Outside
a PV Shelter on page 25. One recommended venting configuration is:
Side venting with fixed and gravity louvers and a shroud (see Figure 2-4).
Shroud
Duct
Fixed louvers
Gravity louvers
Intake
airflow
26
990-4613B Revision C
PV Array Requirements
In all installations, the installer must provide disconnecting means for the PV
input. The installer is also responsible for determining any external overcurrent
protection required for these circuits, in accordance with the applicable
installation codes, the currents involved (see Appendix A, Specifications), the
wiring size used, and any other system parameters required by the installation
codes.
Number of PV Panels
To determine the number of photovoltaic panels required for the PV power plant,
use the PV planning tool or sizing tool on the Schneider Electric website
(www.schneider-electric.com).
990-4613B Revision C
27
Transformer Requirements
A custom, high-efficiency, line-frequency isolation transformer must be placed
between the inverter and the grid. This transformer is not provided and must be
supplied as a separate component.
NOTICE
EQUIPMENT DAMAGE
You must select a transformer appropriate for the overall system design. Medium
voltage (MV) isolation transformers that are connected to Conext Core XC Series
inverters must meet the technical requirements described in Transformer
Requirements.
If an overvoltage protection is required (for example, a Schneider Electric Cardewtype limiter) refer toTransformer Requirements for sizing information. For simplicity,
do not connect the overvoltage protection device to the neutral; connect it between
any one line (L1, L2, or L3) and ground. Multiple overvoltage protection devices
may be used, but are restricted to one overvoltage protection device per line.
Do not connect any point on the inverter-side winding of the isolation transformer to
ground.
General Requirements
28
The rms (root mean square) value of the voltages in relation to ground is a
maximum of 900 V.
Impedance Z (%) for the transformer must be 6%, with tolerance limits
between 4.5% and 6.5%.
The configuration of the MV transformer should take into account the local
grid frequency and should meet local and regional standards.
990-4613B Revision C
The Conext Core XC Series inverter bridge switching frequency is 3.2 kHz.
This graph is provided for informational purposes only. This should not be interpreted
as typical operation. The voltage numbers on the y-axis are for reference only.
The medium voltage windings should have a voltage level that matches the
medium-voltage grid in the region.
A tap changer should be installed on the medium voltage side to align the
output voltage with the voltage level of the medium voltage grid.
NOTICE
INVERTER DAMAGE
Do not connect any point on the inverter-side winding of the MV transformer to
ground.
Failure to follow this instruction will result in equipment damage.
990-4613B Revision C
Each low voltage winding must match the rated AC voltage of the inverter.
29
Impedance Z (%) between the low voltage windings should be 10%, with
tolerance limits between 7% and 11%.
IN
Uk
Electrical Diagram
Since installations vary widely, a sample electrical diagram of the Conext Core
XC Series is provided in Figure 2-7. Use this diagram for system planning
purposes only.
210
990-4613B Revision C
Installation
DANGER
MULTIPLE SOURCES WITH HAZARD OF ELECTRIC SHOCK, FIRE,
EXPLOSION, AND ARC FLASH
The Conext Core XC Series inverter is energized from the PV array, the AC grid, and
the external auxiliary AC source (if used). Before installing the inverter:
De-energize, lock out, and tag out all sources following the procedure beginning
on page ix.
Test using a meter rated at least 1000 V AC and DC to ensure all circuits are deenergized.
The lock-out and tag-out procedure beginning on page ix in this manual only
applies to installation of an inverter, not to servicing. If the inverter is already
installed, additional steps are needed to de-energize, lock out, tag out, and verify
internal voltages, and must only be performed by authorized service personnel.
See the Service Bulletin for Conext Core XC Series Inverter Lock-Out and Tag-Out
Procedures (document number 993-0438).
Operation of the switches in or on the inverter does not remove all power from this
inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC
source have been disconnected externally.
Additional external disconnecting means for the PV, AC, and external auxiliary AC
source (if used), capable of being locked out and tagged out, must be provided as
part of the installation to help facilitate safe installation and for certain servicing
operations.
990-4613B Revision C
31
Unloading
DANGER
HAZARD OF CRUSH INJURY AND EQUIPMENT DAMAGE
The Conext Core XC Series weighs approximately 1900 kg (4189 lb), including the
packing crate and pallet. Attempting to lift or move the inverter by other than the
recommended lifting points and methods could cause the inverter to drop
unexpectedly or fall over.
Keep all the doors closed and latched when moving the inverter.
NOTICE
EQUIPMENT DAMAGE
Before proceeding with the installation, determine the location and layout of the
components, conduit penetration locations, conductor and conduit sizing, and method
for anchoring the inverter. Make sure adequate space is provided for clearance for
ventilation and serviceability. If necessary, review Chapter 2, Planning before
proceeding.
32
990-4613B Revision C
Installation: Unloading
Extension sleeve
Minimum prong
length 66%
Fork-lift prongs
990-4613B Revision C
33
Reach under the pallet and locate the 12 bolts. These bolts attach from
the bottom so use a torque, open-ended, or box wrench with a very short
head to remove them, as shown in Figure 3-2).
DANGER
HAZARD OF CRUSH INJURY AND EQUIPMENT DAMAGE
Do not lift the inverter more than 2 ft (610 mm) with the forklift.
Do not put any part of your body underneath the raised pallet, including your
hands.
34
990-4613B Revision C
990-4613B Revision C
35
NOTICE
EQUIPMENT DAMAGE
When connecting external AC wires to the Conext Core XC Series, positive phasing
sequence must be maintained throughout the installation process.
Conductor Termination
The Conext Core XC Series has terminals and bus bars for making all wiring
connections required for inverter installation. All terminals used for making AC
and DC connections require the use of conductors with an insulation rating of
75 C (or higher). If conductors rated higher than 75 C are used, base the wire
size on the requirements for 75 C wire to help prevent excessive heating of the
bus bars, terminals, and connected devices.
AC Wiring
The AC output phase wiring connects to the AC terminals identified as XT1 (L1,
L2, and L3) in the AC cabinet. These terminals require the use of a crimp-on type
ring terminal or compression-type lug. Keep the cables close together as much
as possible and make sure that all cables pass through the same conduit fittings
and the same access point in the floor of the inverter. This allows any inductive
currents to cancel.
Each terminal has five bolts per pole and accommodates a maximum of one
cable per bolt. For the location of these terminals and wiring instruction see
Figure 3-11 on page 312. For bolt sizes torque values, see Table A-3 on
page A4. For the dimensions of the terminal lug connections, see Figure 3-4.
36
990-4613B Revision C
990-4613B Revision C
The auxiliary AC input wiring connects to the terminals identified as XT4 (1 and 2)
in the AC cabinet. These terminals require a crimp-on ferrule properly sized for
the wire and accommodate one wire per terminal. For the location of these
terminals, see Figure 3-17 on page 318. For bolt sizes and torque values, see
Table A-3 on page A4.
37
The PV input wiring connects to the PV terminals identified as PV+ and PV- in the
DC cabinet. These terminals require the use of a crimp-on type ring terminal or
compression-type lug. Keep the cables close together as much as possible and
make sure that all cables pass through the same conduit fittings and the same
access point in the floor of the inverter. This allows any inductive currents to
cancel.
Each terminal has seven bolts per pole and a maximum of one cable per bolt. For
the location of these terminals, see Figure 3-16 on page 315. For bolt sizes and
torque values, see Table A-4 on page A4. For the dimensions of the terminal lug
connections, see Figure 3-5.
38
990-4613B Revision C
Grounding
The connection point for the AC grounding conductor (also known as PE) is a
copper grounding bar with several M10 bolts located at the bottom right side of
the AC cabinet and marked with . The ground conductor size depends on the
rating or setting of the overcurrent protection provided for the circuit. Refer to
local applicable electrical installation codes for grounding requirements for your
system. The ground wire for the external auxiliary AC source can also be
terminated at this ground bar. Grounding terminals for PV array frames are
provided in the DC cabinet.
990-4613B Revision C
39
AC Wiring
To help protect personnel, barriers are installed over the AC and DC electrical
wiring compartments inside the Conext Core XC Series. To perform the initial
installation you must remove these barriers.
To remove the AC barriers:
1. Open the AC cabinet door.
2. Remove and save the five screws holding the external auxiliary AC source
barrier in place, as indicated in Figure 3-7.
3. Pull the external auxiliary AC source barrier out; do not bend the metal.
310
990-4613B Revision C
Remove and save the four plates from the floor of the AC cabinet (see Figure
3-9). You must re-install the plates after routing the cables.
Tab
Retaining
screws
990-4613B Revision C
311
L3 Phase terminal
L2 Phase terminal
Ground bar
(PE)
L1 Phase terminal
312
990-4613B Revision C
PV Array Wiring
To help protect personnel, the DC cabinet is provided with four barriers:
A large plastic barrier over the entire upper half of the cabinet.
A large steel mesh barrier over the entire lower half of the cabinet.
990-4613B Revision C
313
314
Remove and save the four plates from the floor of the DC cabinet (see Figure
3-15). You must re-install them after routing the cables.
990-4613B Revision C
Ground
bar (PE)
PV-
PV+
990-4613B Revision C
315
The transformer has multiple taps that can be selected to allow for different AC
supply voltage ranges.
Two different transformer configurations exist for the auxiliary supply transformer
(TC1). Original Conext Core XC Series inverters use auxiliary voltages of 208,
230, 315, or 400 VAC rms phase-to-phase. Newer Conext Core XC Series
inverters use auxiliary voltages of 208, 230, 300, 350, or 380 VAC rms phase-tophase.
NOTICE
COMPONENT DAMAGE
For original Conext Core XC Series inverters, auxiliary power can only be supplied
from the inverter AC output if the AC output voltage will always be in one of the
following ranges:
284 346 VAC phase-to-phase
360 440 VAC phase-to-phase
For newer Conext Core XC Series inverters, auxiliary power can only be supplied
from the inverter AC output if the AC output voltage will always be in one of the
following ranges:
270 330 VAC phase-to-phase
315 385 VAC phase-to-phase
342 418 VAC phase-to-phase
Auxiliary AC supply transformer (TC1) taps must be set correctly according to the
information in Table 3-1 or Table 3-2.
316
The external AC auxiliary source is being used, but the voltage is not
230 VAC.
990-4613B Revision C
WARNING
HAZARD OF FIRE
External over-current protection must be installed for the AC auxiliary input circuit of the
inverter.
208 ( 10%)
208
230 ( 10%)
315 ( 10%)
315
400 ( 10%)
400
For newer Conext Core XC Series inverters using external auxiliary voltages of
208, 230, 300, 350, or 380 VAC rms phase-to-phase, refer to Table 3-2.
Table 3-2 Voltage ranges and transformer taps for external auxiliary AC source
(newer Conext Core XC Series)
990-4613B Revision C
208 ( 10%)
208
230 ( 10%)
300 ( 10%)
300
350 ( 10%)
350
380 ( 10%)
380
317
XT2
318
990-4613B Revision C
XT2:20
400 V
XT2:21
315 V
XT2:22
XT2:23
208 V
3. Do not re-install the DC barriers (page 43) until all other installation steps
and the visual inspection on page 42 have been completed.
Move cable marked
XT2:21 as needed to
select voltage
Insert a screwdriver into
the hole beneath the old
location to open the clip
and release the wire.
Insert a screwdriver into
the hole beneath the new
location to open the clip.
Remove the screwdriver to
close the clip and grip the
wire.
Figure 3-19 Moving the voltage tap wire (original Conext Core XC Series)
Figure 3-20 Moving the voltage tap wire (newer Conext Core XC Series)
990-4613B Revision C
If one of these conditions cannot be met, then the auxiliary power must be
supplied from an external auxiliary AC source as described on page 316.
To configure the inverter for internal auxiliary power supplied from the AC
output:
1. Change the factory configuration by moving the conductors connected to
terminals XT2:39 and XT2:40 (external supply) over to terminals XT2:45 and
XT2:46 (internal supply). See Figure 3-21 for the location of these terminals.
Internal auxiliary supply
setting (XT2:45 and XT2:46)
Figure 3-21 XT2 terminal block settings for internal auxiliary AC source
2. Using the procedure To select the correct voltage tap for the control voltage
transformer (TC1): on page 318, adjust the tap selection on XT2 for the
auxiliary supply transformer (TC1) according to Table 3-4 (original Conext
Core XC Series inverters) or Table 3-5 (newer Conext Core XC Series
inverters).
Table 3-4 Tap selection for internal auxiliary AC source connection
(original Conext Core XC Series)
AC output voltage (VAC rms phase-to-phase)a
284 to 346
315
360 to 440
400
300 ( 10%)
300
350 ( 10%)
350
380 ( 10%)
380
320
990-4613B Revision C
DANGER
HAZARD OF ELECTRIC SHOCK
The circuits provided for use with external communications and control equipment
are designed to provide isolation from neighboring hazardous circuits within the
inverter. The communications and control circuits within the Conext Core XC Series
are floating from ground and are classified as SELV. They must be connected only
to other SELV circuits in a manner which maintains all the circuits within SELV limits
and prevents ground loops. Separate conduit entries must be provided for the
communications and control circuits and the PV circuits and all AC circuits.
Physical and electrical separation of the communications and control circuits from
non-SELV electrical circuits must be maintained both within the inverter and external
to the inverters.
The circuits for external control of active and reactive power, which must be
connected only to 4-20 mA loop circuits that are SELV.
Make sure the communication and control cables enter the cabinet away from
the PV and AC wiring and are routed and mechanically secured away from the
PV and AC wiring throughout the length of the communications and control
wiring. Maintain no less than 50 mm (2 in.) separation at all points and use the
provided cable channels.
990-4613B Revision C
321
Modbus/RS-485 Wiring
Isolation and Surge
Protection
The recommended best practice is the use of fiber optic isolation, installed as
close to the inverter as possible. This provides full isolation, removing the risk of
damaging electrical surges coupling to the inverter, and, therefore, negating the
need for additional surge protection.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Installations involving non-fiber optic cables exceeding 10 m (32 ft 9 inches) outside
of a PV Box or building structure to the communication ports of the inverter must be
able to withstand a 1.0 kV surge from line to ground. The recommended methods to
meet this requirement are listed below in order of best practices:
Galvanic isolation installed within 10 m (32 ft 9 inches) of the inverter such as,
Schneider Electric gateway devices TSXETG100 or EGX300.
The RS-485 bus is a multi-drop bus implemented as a daisy chain. The Conext
Core XC Series provides two RJ-45 connectors to the same modbus ports to
facilitate daisy chaining. Either port can be connected to the upstream or
downstream device and a standard Ethernet (straight-through) patch cable may
be used to connect the devices.
Note: Ethernet cross-over cables must not be used.
Shielding and
Grounding
322
The RJ-45 cable must use a shielded cable with the Modbus master end (not the
inverter end) connected to protective ground. On the inverter end, the male
connector must be shielded.
990-4613B Revision C
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
If the inverter has been previously energized, different lock-out and tag-out
procedure steps are needed and the installation must be performed by authorized
service personnel. See the Service Bulletin for Conext Core XC Series Inverter LockOut and Tag-Out Procedures (document number 993-0438).
1. Route the communication and control cables along the following path (see Figure 322):
a) Through the slit in the foam at the access point on the floor of the inverter.
b) Through the cable channels on the left wall of the DC cabinet.
c) Up the left side of the back wall of the DC cabinet.
2. Use cable ties to hold the cables in place to prevent contact from other field wiring
and factory bus bars.
Connection Point
External enable/disable
If using a metallic cable that routes from XT14 to a location outside the PV shelter,
ensure that the cable passes through an isolation device before exiting the box.
990-4613B Revision C
323
CAUTION
RISK OF POWER SURGES
Ensure that metallic conductors routed from XT14 to a location outside the PV shelter
have proper isolation.
Copper and other metallic conductors that are used to carry communication signals
between the Conext Core XC Series inverter and devices outside the PV shelter may
conduct power surges (from lightning or ground differentials between nodes) into the
inverter.
XT14
Leave this
jumper if you
are not going to
install an
external ENABLE/
DISABLE switch
324
990-4613B Revision C
SW2
RS-485/Modbus
Do not use
990-4613B Revision C
325
WARNING
HAZARD OF ELECTRIC SHOCK
Do not apply external power to the external ENABLE/DISABLE switch.
326
990-4613B Revision C
Inspection
DANGER
/
This inverter is energized from multiple sources: the PV array, the AC grid, and the
external auxiliary AC source (if used). Before opening doorsa or covers:
De-energize, lock out, and tag out all sources following the procedure beginning
on page ix.
Operation of the switches in or on the inverter does not remove all power from this
inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC
source have been disconnected externally.
Before servicing, test using a meter rated at least 1000 V AC and DC, to ensure all
circuits are de-energized.
Additional external disconnecting means for the PV, AC, and external auxiliary AC
source (if used), capable of being locked out and tagged out, must be provided as
part of the installation to help facilitate safe installation and for certain servicing
operations.
990-4613B Revision C
41
Visual Inspection
These procedures help verify correct installation and proper wiring of the Conext
Core XC Series. Prior to performing the following inspection steps on the Conext
Core XC Series, review all safety requirements and procedures outlined in this
manual and on any cautionary markings on the components within the system.
To inspect the installation:
1. Visually inspect all the mechanical connections. This includes both electrical
conduit fittings as well as cabinet anchoring and seismic bracing, if required.
2. Visually inspect the electrical connections and verify proper tightness of all
terminations.
3. Visually inspect the utility interconnection transformer connections. Verify that
the inverter-side winding of the transformer is not connected to ground at any
point.
NOTICE
EQUIPMENT DAMAGE
Do not connect any point on the inverter-side winding of the isolation transformer to
ground.
42
990-4613B Revision C
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Leave the PV auxiliary circuit breaker in the OFF position to maintain the locked-out and
tagged-out status of the inverter.
990-4613B Revision C
43
44
Specifications
990-4613B Revision C
A1
System Specifications
The specifications for a Conext Core XC Series are provided. The Conext Core
XC Series has only been designed for use with photovoltaic power systems that
operate within the following specifications.
Electrical Specifications
Table A-1 Electrical specifications
Specification
XC540
XC630
XC680
300 Vrms
350 Vrms
380 Vrms
III
III
III
1040 Arms
1040 Arms
1040 Arms
325 kVAr
375 kVAr
400 kVAr
37 degrees
37 degrees
37 degrees
540 kVA
630 kVA
680 kVA
621 kW
725 kW
782 kW
1000 VDC
1000 VDC
1000 VDC
1280 A
1280 A
1280 A
1600 A
1600 A
1600 A
2000 A
2000 A
2000 A
440a to 800 V
510a to 800 V
550a to 800 V
440a to 850 V
510a to 850 V
550a to 850 V
2000 VA
2000 VA
a.Valid for power factor = 1 (Q = 0). Low limit of MPP range is dynamically adjustable based on nominal phase-to-phase
AC voltage based on V_Mppt_min = 15V+ 2 x (VAC[V])2 + 4,021 x f[Hz] x Q[kVAr]
A2
990-4613B Revision C
Dimensions
Net weight
Class 1K2:
-25 C to 55 C maximum (-13 F to 131 F)
Maximum 95% relative humidity, non-condensing
Operating:
Transport:
Storage:
Class 3Z1a
Class 2Z1a
Class 1Z1a
Biological conditions
Operating:
Transport:
Storage:
Class 3B1a
Class 2B1a
Class 1B1a
Operating:
Transport:
Storage:
Class 3C1a
Class 2C1a
Class 1C1a
Operating:
Transport:
Storage:
Class 3S1a
Class 2S1a
Class 1S1a
Mechanical conditions
Operating:
Transport:
Storage:
Class 3M1a
Class 2M1a
Class 1M1a
Altitude
IP20
3000 m/h
4000 m/h
a.Environmental range ratings correlate approximately to Classes shown, as defined by EN60721 standard series.
b.Above 45 C (113 F), the inverter will derate its power output up to 50 C (122 F).
c.Depending on ambient temperature at altitude, the output power may automatically derate above 1000 m.
The installer must derate the PV and AC voltages above 2000 m.
See Application Note: Altitude Derating for Conext Core XC Series.
990-4613B Revision C
A3
Regulatory Specifications
Regulatory specifications for the Conext Core XC Series are:
CE marked for the Low Voltage Directive per EN50178 and EN 60529-1.
# of Terminals
Max #
Conductors
per Terminal
Bolt
(Hardware) Size
Torque
Requirements
Grounding (PE)
M12
60 to 70 Nm
(44 to 51.5 lb ft)
AC output/grid (XT1)
M12
60 to 70 Nm
(44 to 51.5 lb ft)
External auxiliary AC
source (XT4)
2 (L1, L2)
0.6 0.8 Nm
(5.3 7.1 lb in)
AC Terminal
Connections
Table A-4 provides acceptable bolt sizes and torque values for PV terminal
connections.
Table A-4 PV terminal bolt size and torque values
DC Terminal
Connections
PV Terminal (XT11)
A4
# of Terminals
Max #
Conductors
per Terminal
Bolt
(Hardware) Size
Torque
Requirements
2 (PV+, PV-)
M12
60 to 70 Nm
(44 to 51.5 lb ft)
990-4613B Revision C
Specifications: Dimensions
Dimensions
2085
2400
600
660
Dimensions in mm
990-4613B Revision C
A5
A6
990-4613B Revision C
Site Evaluation
Checklist
B1
Use this checklist to record details of the site configuration and to verify correct installation of the inverter before a Schneider
Electric technician is sent on site to commission the inverter.
Inspector Name & Phone Number:
Inspection Date:
Project Information
Project name:
GPS coordinates:
Site Contacts
Project manager:
Security officer:
Maintenance technician:
MV transformer operator:
Other teams that work on site (who, when, where, point of contact):
Safety
Safety protocol (e.g., boots, hard hat, etc.):
Entrance requirements (contact person, location of keys, sign in/out procedure):
1. Site Readiness
3. PV Box (contd)
Yes __
# of filters ___
No __
_____ (ddmmyy)
Yes __
Type: ______
No __
Yes __
No __
Is ducting complete?
Yes __
No __
Yes __
2. Environment
No __
Min __ C (__ F)
Max __ C (__ F)
Yes __
No __
Altitude:
AC cable type:
Copper __
Aluminum __
None __
Single __
AC cable shielding:
Shielded __
Armored __
Double __
3. PV Box
AC cable area:
___ runs/phase
DC cable type:
Copper __
Aluminum __
Armored __
Height:
DC cable shielding:
Shielded __
DC cable area:
Yes __
No __
Yes __
Copper __
Aluminum __
Type of lighting:
_______________________
Shielded __
Armored __
_______________________
Yes __
No __
Yes __
# of filters ___
No __
April 2013
B2
No __
Page 1 of 2
990-4613B Revision C
4. Communication
6. PV Array (contd)
___ Vmpp
___ Isc
Floating __
Positive grounded __
Negative grounded __
_____ baud
_____ bits
_____ parity
Yes (please
attach) __
Yes __
No __
Number of strings:
____ strings
Yes __
No __
____ modules/string
Yes __
No __
Yes __
No __
Remote
monitoring __
SCADA __
Type:______
Other _________________
Yes __
No __
Yes __
No __
OFC __
Copper __
Yes __
No __
Yes __
No __
No __
Max _____ :
_____________________
Type: ________________
Rating: _____________
Transformer rating:
_________________ kVA
Shielding: _______________
Yes __
No __
Type:
___________
___________
___________
Qty:
___
___
___
Yes __
No __
Yes __
No __
Yes __
No __
Yes __
No __
Yes __
No __
Yes __
Number of inputs:
____ inputs
Nominal LV AC output:
____ VAC
5. MV Transformer
Yes __
No __
Yes __
No __
No __
Max _____ :
Location of fuses:
PV+ __
PV - __
Both __
Yes __
No __
Yes __
No __
Yes __
No __
Yes __
No __
Type _____________
6. PV Array
Module technology:
Thin film __
Monocrystalline silicon __
Polycrystalline silicon __
Other (describe) _________
___ Voc
Page 2 of 2
990-4613B Revision C
Yes __
No __
Ref _______
Rating ____A
Qty __
Type:
___________
___________
___________
___________
___________
Qty:
___
___
___
___
___
April 2013
B3
B4
Schneider Electric
www.schneider-electric.com
For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider
Electric website at:
http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page
990-4613B Revision C
Printed in