-1-
15
05
17
EEPROM error
EEPROM data loss
16
54
26
Low pressure switch
The pressure switch act when
abnormal
the unit is working
17
50
15
Compressor overheat
Detected temperature of
discharge line is higher than
120C.
18
0C
23
Fault in operation mode
Indoor units operate in different
modes.
-2-
4B
18
Diagnostic code 2
DC: Diagnostic code on wired controller
PL: Power lamp flash times/LED on PCB flash times
DC PL
Failure description
Reasons
E0 10
E1
E2
E3
E4
E5
E6
E9
-3-
Treatment
due to the signal,
resumable
due to the
signal,resumable
due to the
signal,resumable
due to the
signal,resumable
due to the
signal,resumable
Need to be checked,
reset
need to be checked,
reset
due to the
signal,resumable
Need to be checked,
reset
due to the
signal,resumable
Diagnostic code 4
Used for H MRV wireless indoor units
Flash times
Indoor failure description
Timer lamp
flash 1 time
Timer lamp
flash 2 times
Timer lamp
flash 3 times
Timer lamp
flash 4 times
Timer lamp
flash 5 times
Timer lamp
flash 6 times
Timer lamp
flash 7 times
Timer lamp
flash 8 times
Timer lamp
flash 10 times
Timer lamp
flash 11 times
Diagnostic code 5
Used for AU242FHA*A
FT : Number of flashes by fault indicator
FT
Location
Description
TE circuit of defrost
The detected sensor value is below 20H
1
temperature
(open-circuit) or above 1000H (short-circuit)
sensor, outdoor unit
for 60 seconds. The fault is fixable.
TA circuit of
The detected sensor value is below 20H
2
ambient
(open-circuit) or above 1000H (short-circuit)
temperature sensor
for 60 seconds. The fault is fixable.
TS circuit of suction
The detected sensor value is below 20H
3
line temperature
(open-circuit) or above 1000H (short-circuit)
sensor
for 60 seconds. The fault is fixable.
TD circuit of
After 3 minutes of compressor operation, the
discharge line
detected sensor value is below 20H (open4
temperature sensor circuit) or above 1000H (short-circuit) for 60
seconds. Fixable when below 80C.
TC circuit of central
The detected sensor value is below 20H
temperature
(open-circuit) or above 1000H (short-circuit)
5
sensor, outdoor unit
for 60 seconds.
condenser
Over-current
An alarm is given five seconds after the
current limit is exceeded. Where there are 3
6
alarms within 30 minutes, the fault code is
displayed. The fault is not fixable.
IPM protection
IPM over-current, short-circuit, overtemperature and under-voltage. When the
9
fault occurs three times within 30 minutes,
an alarm is given and the fault is not fixable.
Base board
857 EEPROM data access error, 11 flashes.
10
EEPROM error
The fault is not fixable.
11
Discharge line
temperature
Is it fixable
Check the sensor
Check the sensor
Check the sensor
See trouble
shooting
See trouble
shooting
Reinstall the
PC`B, or change
indoor PCB
Test the
discharge temp.
12
857-to-809
transmission error
High pressure
switch circuit
13
Check the
EEPROM
installation, or
change PCB
Test the high
pressure switch is
open circuit or
not, check the
high pressure
Diagnostic code 6
Used for AU482FIA*A
DR : Digital readout from outdoor PCB
DR
Location
Description
TE circuit of defrost
The detected sensor value is
temperature sensor,
below 20H (open-circuit) or
01
outdoor unit
above 1000H (short-circuit)
for 60 seconds. The fault is
fixable.
TA circuit of ambient The detected sensor value is
temperature sensor
below 20H (open-circuit) or
02
above 1000H (short-circuit)
for 60 seconds. The fault is
fixable.
TS circuit of suction
The detected sensor value is
line temperature
below 20H (open-circuit) or
03
sensor
above 1000H (short-circuit)
for 60 seconds. The fault is
fixable.
After 3 minutes of compressor
TD circuit of
discharge line
operation, the detected
temperature sensor
sensor value is below 20H
04
(open-circuit) or above 1000H
(short-circuit) for 60 seconds.
Fixable when below 80C.
TC circuit of central
The detected sensor value is
temperature sensor,
below 20H (open-circuit) or
05
outdoor unit
above 1000H (short-circuit)
condenser
for 60 seconds.
Over-current
An alarm is given five
seconds after the current limit
06
is exceeded. Where there are
3 alarms within 30 minutes,
the fault code is displayed.
-6-
Is it fixable
Temp. sensor is open-circuit
or short-circuit for 2min or
longer.( R25=10K)
Temp. sensor is open-circuit
or short-circuit for 2min or
longer.( R25=10K)
Temp. sensor is open-circuit
or short-circuit for 2min or
longer.( R25=10K)
discharge temp. sensor is
open-circuit or short-circuit
for 2min or longer.( R80
=50K)
Temp. sensor is open-circuit
or short-circuit for 2min or
longer.( R25=10K)
check the high(lower than
2.4MPa) and low
pressure(higher than
0.15MPa).
Compressor Failure;
08
Overload protector
circuit of inverter
compressor
IPM protection
09
10
Base board
EEPROM error
Discharge
temperature
protection (TD)
11
13
Pressure switch
circuit
Suction temperature
protection (TS)
16
19
20
Discharge line
temperature
protection at low
frequency (TD)
846-to-857
transmission error
21
22
23
857-to-846
transmission error
Indoor unit-to-846
transmission error
846EEPROM/857E
EPROM error
Diagnostic code 7
Used for AU48NFIA*A
FT : Error lamp flashes
DR : LED display on the 0010451601
INF : If sent to indoor unit?
Malfunction description
FT
DR
INF
Normal
On
Normal
Yes
E.4.
E.1.
E.3.
E.2.
E.5.
Defrosting temperature
sensor abnormal
Ambient temperature
sensor abnormal
Suction temperature
sensor abnormal
Discharging
temperature sensor
abnormal
Coil temperature
sensor abnormal
Yes
Yes
Yes
Yes
Current sensor
abnormal
Overload protection
IPM protection
10
Yes
O.C.
Yes
P O.C.
no
Yes
C.T.
O.L.
P O.L.
E.P.
P E.P.
P E.E.
Yes
no
Yes
no
no
-8-
Remarks
O.D.
Yes
P O.D.
no
11
12
13
14
O.P.
L.U.
Yes
Yes
P L.U.
O.U.
Yes
P O.U.
15
O.H.
16
P I.A.
17
P C.T.
18
P r.E.
Yes
no
no
no
-9-
- 10 -
- 11 -
- 12 -
no
yes
Is high side pressure switch
activated? (If not, DC voltage is 0V.)
no
Replace PCB
yes
Is the high side pressure detected by
the gage higher than threshold
value? The threshold value is
indicated on the switch
no
yes
if outdoor stop valves of gas pipe
and liquid pipe are open totally
no
yes
yes
Repair pipe
no
Does indoor fan work properly during
cooling cycle? Does outdoor fan work
properly during heating cycle?
no
yes
Is indoor filter or heat
exchanger dirty?
yes
Cleaning
no
Check if system is overfed according
to equalized pressure in halt.
yes
no
Is reading of discharging pressure
gage oscillatory?
no
yes
There is air in system.
Evacuate and recharge
- 13 -
yes
Is low side pressure switch
activated? (If not, DC voltage is 0V.)
no
Replace PCB
yes
Is the low side pressure detected by
the gage lower than threshold value?
The threshold value is indicated on
the switch
no
yes
if outdoor stop valves of gas pipe
and liquid pipe are open totally
no
yes
yes
Repair pipe
no
Does indoor fan work properly during
cooling cycle? Does outdoor fan work
properly during heating cycle?
no
yes
Is indoor filter or heat
exchanger dirty?
yes
Cleaning
no
Measure equalized pressure and time to
reach equalization to see if the system has
leakage. Lack of refrigerant? Is capillary
blocked?
no
Bad operation codition, such as ultra low
outdoor temperature
- 15 -
- 16 -
No
Reconnect the
plug
Yes
No
- 17 -
Readout: E3
Readout: E4
N/A
No
Yes
Reconnect
Yes
Change
PCB
No
Replace the sensor
4.
Models with wired controller
Readout: E5
Description: Transmission error between indoor unit 846 chip and 808 chip.
What to do: Replace the mainboard.
- 18 -
Readout: E7
No
Reconnect
Yes
- 19 -
Replace the
mainboard
Remove the
short wire
Readout: E8
Description: Transmission error between wire controller and indoor unit mainboard
Reconnect
Yes
No
Replace indoor
unit mainboard
Yes
No
- 20 -
Readout: N/A
10 flashes
Yes
No
.
Replace the fan
- 21 -
Readout: E9
Description: Transmission error with outdoor unit (an alarm will be given 4 minutes after
the appliance is started.)
- 22 -
N/A
Description: Fault with 12V supply of heavy current board in expansion valve
N/A
- 23 -
no
Reset address
yes
Are communication terminals of
indoor and outdoor units
securely connected?
no
Reconnect
yes
Is shielded wire
used for
communication?
no
yes
Are communication wire
and power cable set
separately?
no
wiring Separately
yes
Is there external signal
interference?
yes
Eliminate interference
no
Is indoor mainboard poorly
welded?
yes
no
Are communication resistance and
capacitor of indoor PCB correct? See
NOTE
no
yes
Check outdoor mainboard
0010450351. Make necessary
replacement
- 24 -
no
reconnect
yes
Are resistance and
temperature characteristics of
sensor normal?
no
change sensor
yes
check if PCB is defective, if
yes,replace
3.EEPROM failure
start
Is EEPROM in mainboard
inversely connected or in
poor contact?
no
re-set
replace PCB
- 25 -
no
yes
Are connectors in
good condition?
no
yes
check if running current is above 23A?
no
replace
yes
1. Is output voltage among U, V and W balanced?
2. Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
no
yes
no
Is pressure acceptable?
yes
Is compressor in good
condition?
no
yes
Is rectifier in good condition?
yes
Is electrolytic capacitor
for filtration in good
condition?
yes
Check mainboard and make
necessary replacement
- 26 -
yes
no
Is 10-pin connector between IPM
and mainboard short-circuit or in
poor contact?
yes
Replace cable
no
Is output voltage of rectifier
acceptable (310VDC at 220V. Less
than 250V when running at high
frequency.)
no
Replace rectifier
yes
Check point: CN2 in mainboard.
Is four-way supply voltage less than
13.5V (normal value: 13.5-16.5VDC)
yes
Replace PCB
no
Is compressor in good condition?
no
yes
yes
Is power module too hot?
no
Is current up to
protection limit of
power module?
yes
no
1.Is output voltage among U, V and W balanced?
2.Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
no
yes
Check mainboard and make
necessary replacement
- 27 -
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
yes
no
no
yes
Is discharging temperature
sensor in good condition?
yes
no
replace PCB
Check fan motor and capacitor
yes
Is filter or heat exchanger dirty?
yes
cleaning
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
no
Is piping twisted or deformed? Is piping
clogged with weld?
no
yes
Adjustment or
replacement
no
When TD is high, is refrigerant injection
circuit in good condition? Is injection
capillary in good condition?
no
1.Check coil and valve body of
electromagnetic valve.
2.Check injection capillary.
- 28 -
Replace TD sensor
no
no
yes
Is pressure value detected by
pressure gage above 3MPa?
no
yes
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
no
Open stop valve
yes
Is piping twisted or deformed?
no
yes
Repair or
replacement
- 29 -
no
Reset address
yes
Are communication terminals of
indoor and outdoor units
securely connected?
no
Reconnect
yes
Is shielded wire
used for
communication?
no
yes
Are communication wire
and power cable set
separately?
no
wiring Separately
yes
Is there external signal
interference?
yes
Eliminate interference
no
Is indoor mainboard poorly
welded?
yes
no
Are communication resistance and
capacitor of indoor PCB correct? See
NOTE
no
yes
Check outdoor mainboard
0010450351. Make necessary
replacement
- 30 -
no
reconnect
yes
Are resistance and
temperature characteristics of
sensor normal?
no
change sensor
yes
check if PCB is defective, if
yes,replace
Is EEPROM in mainboard
inversely connected or in
poor contact?
no
re-set
replace PCB
- 31 -
no
yes
Are connectors in
good condition?
no
yes
no
yes
Change PCB
no
yes
1. Is output voltage among U, V and
W balanced?
2. Disconnect all terminals. Is
resistance between P and N; P and
U, V, W; N and U, V, W acceptable?
yes
Is pressure acceptable?
no
yes
no
yes
Is electrolytic capacitor
for filtration in good
condition?
no
no
yes
Check mainboard and make
necessary replacement
- 32 -
yes
yes
Is 10-pin connector between IPM
and mainboard short-circuit or in
poor contact?
yes
Replace cable
no
Measure + and - terminals of
electrolytic capacitor. Is output voltage
of rectifier acceptable (310VDC at
220V.)
no
Replace rectifiter
yes
Check point: CN12 in mainboard.
Is four-way supply voltage less than
13.5V (normal value: 13.5-16.5VDC)
yes
no
no
yes
Is power module too hot?
yes
no
Is current up to protection yes
limit of power module?
no
1.Is output voltage among U, V and W balanced?
2.Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
no
yes
Check mainboard and make
necessary replacement
- 33 -
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
yes
Is actual discharging temperature detected
by thermometer too high?
no
Repair outdoor EEV
no
yes
Is discharging temperature
sensor in good condition?
yes
no
replace PCB
Check fan motor and capacitor
yes
Is filter or heat exchanger dirty?
yes
cleaning
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
no
Is piping twisted or deformed? Is piping
clogged with weld?
no
yes
Adjustment or
replacement
no
When TD is high, is refrigerant injection
circuit in good condition? Is injection
capillary in good condition?
no
1.Check coil and valve body of
electromagnetic valve.
2.Check injection capillary.
- 34 -
Replace TD sensor
no
yes
Is high pressure switch activated?
no
replace PCB
yes
Is pressure value detected by
pressure gage above 3MPa?
no
yes
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
no
Open stop valve
yes
yes
Repair or
replacement
no Check fan motor
or indoor EEV
yes
yes
cleaning
- 35 -
yes
no
Replace PCB
yes
Is pressure valve detected by
pressure guage lower than
0.05MPa?
no
yes
If outdoor stop valves of gas pipe
and liquid pipe are open totally
no
yes
Is piping twisted or deformed?
no
no
Do outdoor fan and PMV work
properly during cooling cycle? Do
indoor fan and EEV work
properly during heating cycle?
no
yes
If the filter and heat exchanger
are dirty
yes
Cleaning
yes
If refrigerant circuit is leak? or
lack of refrigerant?
yes
Check leakage point, evacuate
and recharge
- 36 -
no
reconnect
yes
Is overload protector
open-circuit?
no
yes
Is resistance of
compressor winding
acceptable?
no
Replace compressor
yes
If compressor current and discharge
pressure are acceptable, the problem
is not related to refrigeration system.
Check if piping is clogged, ambient
temperature is high or heat
exchanger is soiled
- 37 -
no
reconnect
yes
if compressor is
running?
no
yes
Is compressor current
acceptable? Is DC voltage
between both ends of CN4
acceptable?
no
Is connection between
filter board CN1 and
mainboard CN4 normal?
yes
Check connection of mainboard
CN4 and make necessary
replacement
yes
Replace filter
- 38 -
no
reconnect
yes
no
Communication normal
Reset address
yes
Are communication terminals of
indoor and outdoor units
securely connected?
no
Reconnect
yes
Is shielded wire
used for
communication?
no
yes
Are communication wire
and power cable set
separately?
no
wiring Separately
yes
Is there external signal
interference?
yes
Eliminate interference
no
Is indoor mainboard poorly
welded?
yes
no
Are communication resistance and
capacitor of indoor PCB correct? See
NOTE
no
yes
Check outdoor mainboard. Make
necessary replacement
- 39 -
no
Reconnect
yes
Are resistance and temperature
characteristics of sensor
acceptable?
no
Replace sensor
yes
Check PCB and replace
3.EEPROM failure
no
yes
Is fault corrected after
JP301 is reset?
yes
Normal
no
If chip is broken?
yes
Replace chip
no
Is it normal after replacing chip?
no
Check PCB and replace
- 40 -
no
yes
Are connectors in
good condition?
no
yes
Is actual compressor current detected
by ammeter or test board (0010451601)
above protection limit 16.9A?
no
yes
1. Is output voltage among U, V and
W balanced?
2. Disconnect all terminals. Is
resistance between P and N; P and
U, V, W; N and U, V, W acceptable?
no
yes
Is pressure acceptable?
no
yes
no
no
yes
Is electrolytic capacitor
for filtration in good
condition?
no
yes
Check mainboard and make
necessary replacement
- 41 -
yes
yes
Is 9-pin connector between IPM
and low voltage board short-circuit
or in poor contact?
yes
Replace cable
no
Check point: + and - pins of CN201 in
power source board. Is output voltage
of rectifier acceptable (530VDC at
380V)
no
Replace rectifiter
yes
Check point: CN12 in mainboard.
Is four-way supply voltage less than
13.5V (normal value: 13.5-16.5VDC)
yes
no
if the compressor is normal no
yes
Is power module too hot?
yes
no
Is current up to protection yes
limit of power module?
no
1.Is output voltage among U, V and W balanced?
2.Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
no
yes
Is there any damaged component
in power module driver?
no
yes
Check low voltage and make
necessary replacement
- 42 -
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
no
yes
Is actual discharging temperature detected
by thermometer too high?
no
Is discharging temperature
sensor in good condition?
yes
yes
no
replace PCB
Check fan motor and capacitor
yes
Is filter or heat exchanger dirty?
yes
cleaning
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
no
Is piping twisted or deformed? Is piping
clogged with weld?
no
yes
no
When TD is high, if SV2 by pass circuit
can work normally
no
Check coil and valve body of
electromagnetic valve.
- 43 -
Adjustment or
replacement
Replace TD sensor
no
yes
Is high pressure switch activated?
no
replace PCB
yes
Is pressure value detected by
pressure gage above 3MPa?
no
yes
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
no
Open stop valve
yes
yes
Repair or
replacement
yes
yes
Is filter or heat exchanger dirty?
cleaning
no
Is system overfed? Is there air in system?
Is reading of discharging pipe pressure
guage oscillatory?
yes
Evacuate and recharge
- 44 -
yes
no
Replace PCB
yes
Is pressure valve detected by
pressure guage lower than
0.05MPa?
no
yes
If outdoor stop valves of gas pipe
and liquid pipe are open totally
no
yes
Is piping twisted or deformed?
no
no
Do outdoor fan and PMV work
properly during cooling cycle? Do
indoor fan and EEV work
properly during heating cycle?
no
yes
If the filter and heat exchanger
are dirty
yes
Cleaning
yes
If refrigerant circuit is leak? or
lack of refrigerant?
yes
Check leakage point, evacuate
and recharge
- 45 -