L325:P4142
Cl/Sfb
EPIC
F631:X442
(31.9)
Hh2
December 2008
Catnic
www.catnic.com
Catnic
Pontypandy Industrial Estate
Caerphilly
CF83 3GL
Telephone 029 2033 7900
Facsimile 029 2086 7796
87
87
C03:30000:UK:11/2008
87
PDA8753/05
Lintels
Pioneers of the steel lintel for more
than three generations with a
reputation for superior quality,
reliability and backed by excellence
in service.
Steel Lintels
Special Lintels
Stainless Steel Lintels
Free design service for bespoke feature lintels
Free scheduling service
Expanded Metal
Easy to use, versatile and perfectly
formed expanded metal products
benefit from our long experience of
using steel in construction.
Metal Lath
Coil Mesh
Arch formers
Wall Starter Kits
STRONGHOLD Wall Starter Kits
are a simple yet effective system
for tying new masonry walls to
existing walls.
Steelwork
A selection of steelwork beams,
columns and channels for when
loading conditions exceed our
standard range of lintels
Universal beams
Universal columns
Parallel flange channels
Steel Plasterers Beads
Precision engineered and simple to
use to create, edges, corners and
joints that are resistant to chipping,
cracking and impact damage.
Galvanised steel plaster
and render beads
Stainless steel plaster
and render beads
PVC-U Plasterers Beads
Light, rigid, non-corrosive, and
easy to use material, that offers
a cost-effective way to create,
edges, corners and joints that
are resistant to chipping,
cracking and impact damage.
Plaster and render beads
4
5
6
7
8
Service
10
11
Specification Guide
13
14
16
Steel Lintels
19
30
33
35
37
40
42
45
46
48
49
Accessories
Soffit Cladding
Arch Centres
Stop Ends
Weep Vents
External Plaster Key
65
66
67
68
69
Installation
71
73
74
76
77
78
79
80
81
82
Special Lintels
Technical Specifications
Introduction
4
5
6
7
8
Introduction
4
5
6
7
8
Catnics excellence is
internationally recognised
Catnic lintels have gained the approval of the regulatory
authorities both in the domestic and international
markets. Such wide-spread comprehensive approval is
an assurance to designers, specifiers and builders of the
reliability and state-of-the art quality of the Catnic range
Leaders in Technical Innovation
Our rigid adherence to quality
control and compliance is your
guarantee of technical superiority
Quality
Catnic are committed to quality control
and is a BSI registered company with
quality management systems in
accordance BS EN ISO 9001: 2000.
073
Material Specification
Catnics Standard lintels are
manufactured from high quality grade
galvanised steel to BS EN 10327:2004
DX51D & Z275, with a black coloured
polyester resin finish.
Catnics CXL lintels and Special lintels
are manufactured from structural grade
steel plate of grade S275 to
Independent Testing
Extensive testing was undertaken at
the following test houses:
The University of Wales,
School of Engineering
The University of Glamorgan,
Construction Centre
Ceram Building Technology,
Stoke-on-Trent
Fire Testing
Catnic lintels have been independently
tested in accordance with the relevant
parts of BS476, Methods of Determination
of the Fire Resistance of Loadbearing
Elements of Construction.
BS 5977
LICENCE No. KM07234
BSI Kitemark
Catnic steel lintels have been awarded
the BSI Kitemark license number
KM07234.
BBA Certification
Catnic steel lintels are certified by the
British Board of Agrment under
certificate number 91/2638.
Further details can be found in page 77 and full reports of relevant tests are available
on request from the Catnic Technical Services Department on 029 2033 7900.
Catnics excellence is
internationally recognised
Catnic lintels have gained the approval of the regulatory
authorities both in the domestic and international
markets. Such wide-spread comprehensive approval is
an assurance to designers, specifiers and builders of the
reliability and state-of-the art quality of the Catnic range
Leaders in Technical Innovation
Our rigid adherence to quality
control and compliance is your
guarantee of technical superiority
Quality
Catnic are committed to quality control
and is a BSI registered company with
quality management systems in
accordance BS EN ISO 9001: 2000.
073
Material Specification
Catnics Standard lintels are
manufactured from high quality grade
galvanised steel to BS EN 10327:2004
DX51D & Z275, with a black coloured
polyester resin finish.
Catnics CXL lintels and Special lintels
are manufactured from structural grade
steel plate of grade S275 to
Independent Testing
Extensive testing was undertaken at
the following test houses:
The University of Wales,
School of Engineering
The University of Glamorgan,
Construction Centre
Ceram Building Technology,
Stoke-on-Trent
Fire Testing
Catnic lintels have been independently
tested in accordance with the relevant
parts of BS476, Methods of Determination
of the Fire Resistance of Loadbearing
Elements of Construction.
BS 5977
LICENCE No. KM07234
BSI Kitemark
Catnic steel lintels have been awarded
the BSI Kitemark license number
KM07234.
BBA Certification
Catnic steel lintels are certified by the
British Board of Agrment under
certificate number 91/2638.
Further details can be found in page 77 and full reports of relevant tests are available
on request from the Catnic Technical Services Department on 029 2033 7900.
Corrosion resistance
Thermal performance
Duplex Corrosion Protection
Initially, Catnic standard lintels are manufactured from hotdipped galvanised steel to BS EN 10327: 2004 of grade DX51D
plus coating type Z275.
A coating of thermal setting polyester powder is then applied by
an electrostatic process, further protecting the lintel. High
temperature curing then produces a tough durable surface highly
resistant to impact, abrasion and damage during rough on-site
handling. This double method of protection gives Catnic lintels
inherent benefits over those offered by other manufacturers using
the more traditional pre or postgalvanised steel techniques.
Both these processes rely on just a simple coating of zinc to
provide cathodic protection. The zinc protects the steel but is
itself liable to rust with aqueous alkaline solutions leaching from
the building fabric and therefore corrode. The famous black
coating makes Catnic lintels instantly recognisable and provides
an effective barrier against moisture or chemical attack leached
from the mortar and masonry.
Steel
Post Galvanised
Steel
30 Min.
Inside face of window
head to overlap inside
face of outer wall by
30mm minimum
30 Min.
Lightweight plaster or
plasterboard
Lightweight plaster or
plasterboard
Catnic design features that help reduce cold bridging by offering the following specific benefits
Stainless Steel Lintels
Stainless Steel
Continuous
insulation
Plaster key
Accessories
Accessories such as the Catnic Cavity
Weep Vent, used at 450mm centres
above the lintel will vent interstitial
condensation which is sometimes
associated with cold bridging.
Corrosion resistance
Thermal performance
Duplex Corrosion Protection
Initially, Catnic standard lintels are manufactured from hotdipped galvanised steel to BS EN 10327: 2004 of grade DX51D
plus coating type Z275.
A coating of thermal setting polyester powder is then applied by
an electrostatic process, further protecting the lintel. High
temperature curing then produces a tough durable surface highly
resistant to impact, abrasion and damage during rough on-site
handling. This double method of protection gives Catnic lintels
inherent benefits over those offered by other manufacturers using
the more traditional pre or postgalvanised steel techniques.
Both these processes rely on just a simple coating of zinc to
provide cathodic protection. The zinc protects the steel but is
itself liable to rust with aqueous alkaline solutions leaching from
the building fabric and therefore corrode. The famous black
coating makes Catnic lintels instantly recognisable and provides
an effective barrier against moisture or chemical attack leached
from the mortar and masonry.
Steel
Post Galvanised
Steel
30 Min.
Inside face of window
head to overlap inside
face of outer wall by
30mm minimum
30 Min.
Lightweight plaster or
plasterboard
Lightweight plaster or
plasterboard
Catnic design features that help reduce cold bridging by offering the following specific benefits
Stainless Steel Lintels
Stainless Steel
Continuous
insulation
Plaster key
Accessories
Accessories such as the Catnic Cavity
Weep Vent, used at 450mm centres
above the lintel will vent interstitial
condensation which is sometimes
associated with cold bridging.
Steel
Galvanised Steel
Duplex coating
Continuous
insulation
Plaster key
Duplex Corrosion
Protection System
Many Catnic lintels employ not
just one but two methods of protection
against corrosive attack: The unique,
sophisticated Duplex Corrosion
Protection system.
Manufactured from hot-dipped
galvanised steel to BS EN 10327: 2004
of grade DX51D & Z275 with the added
protection of a black coloured polyester
resin finish. The protection system
complies fully with the chemical and
physical test requirements outlined in
Table 2 of BS 5977:PART 2:1983 and
table C.1 of BS EN845-2:2003 for lintels
effectively having their own built-in
Damp Proof Course (DPC).
The famous black coating makes
Catnic lintels instantly recognisable and
provides an effective barrier against
moisture or chemical attack leached
from the mortar and masonry.
Service
10
11
Steel
Galvanised Steel
Duplex coating
Continuous
insulation
Plaster key
Duplex Corrosion
Protection System
Many Catnic lintels employ not
just one but two methods of protection
against corrosive attack: The unique,
sophisticated Duplex Corrosion
Protection system.
Manufactured from hot-dipped
galvanised steel to BS EN 10327: 2004
of grade DX51D & Z275 with the added
protection of a black coloured polyester
resin finish. The protection system
complies fully with the chemical and
physical test requirements outlined in
Table 2 of BS 5977:PART 2:1983 and
table C.1 of BS EN845-2:2003 for lintels
effectively having their own built-in
Damp Proof Course (DPC).
The famous black coating makes
Catnic lintels instantly recognisable and
provides an effective barrier against
moisture or chemical attack leached
from the mortar and masonry.
Service
10
11
10
NEXT
Y
A
D
DELIVERY
BLE
AVAILdA
conditions
Terms an
apply
Technical support
Experienced engineers qualified in
construction enable Catnic to offer an
advisory service to anyone engaged on
building projects, regardless of size,
from a private house extension, to a
major housing development or
commercial building.
Telephone Technical
Services on
11
10
NEXT
Y
A
D
DELIVERY
BLE
AVAILdA
conditions
Terms an
apply
Technical support
Experienced engineers qualified in
construction enable Catnic to offer an
advisory service to anyone engaged on
building projects, regardless of size,
from a private house extension, to a
major housing development or
commercial building.
Telephone Technical
Services on
11
Wall Construction
Once you have determined your wall construction please refer to the lintel selector overleaf
Cavity Wall
If the construction is a cavity
wall, see the Open Back lintel
section on page 19. You will
need to know the cavity wall
dimensions to choose the
correct lintel:
the external leaf
dimension
the cavity dimension
including insulation
the internal leaf dimension
Timber Frame
For timber frame
constructions, you need
to know:
the external leaf
dimension
cavity dimension
Once you have these
dimensions, please refer to
the Timber Frame lintels
section on page 35.
Guide to Specification
2
How to select a lintel
Product Selector
Specification Clauses
13
14
16
Applied Load
All lintels are designed to carry a
specific safe working load (SWL).
13
Lintel Length
The length of lintel required is
calculated by establishing the total
width of the structural opening and
adding 150mm (200mm for CXL lintels)
end bearing allowance for each end.
12
Specification
Telephone Catnic
Technical Services on
13
Wall Construction
Once you have determined your wall construction please refer to the lintel selector overleaf
Cavity Wall
If the construction is a cavity
wall, see the Open Back lintel
section on page 19. You will
need to know the cavity wall
dimensions to choose the
correct lintel:
the external leaf
dimension
the cavity dimension
including insulation
the internal leaf dimension
Timber Frame
For timber frame
constructions, you need
to know:
the external leaf
dimension
cavity dimension
Once you have these
dimensions, please refer to
the Timber Frame lintels
section on page 35.
Guide to Specification
2
How to select a lintel
Product Selector
Specification Clauses
13
14
16
Applied Load
All lintels are designed to carry a
specific safe working load (SWL).
13
Lintel Length
The length of lintel required is
calculated by establishing the total
width of the structural opening and
adding 150mm (200mm for CXL lintels)
end bearing allowance for each end.
12
Specification
Telephone Catnic
Technical Services on
13
Product Selector
page 20
page 22
page 24
Continuous
solid infill
block
Continuous
solid infill
block
100 48
95
100 48
95
page 26
Continuous
solid infill
block
Continuous
solid infill
block
100 48
95
100
68
100
95
68
100
95
page 27
110-125mm Cavity Wall
Continuous
solid infill
block
Continuous
solid infill
block
68
95
100
88
100
95
88
95
100
Continuous
solid infill
block
Continuous
solid infill
block
88
108
95
100
108
95
100
108
100
95
128
95
100
Continuous
solid infill
block
Continuous
solid infill
block
95
100
page 28
130-145mm Cavity Wall
128
100
95
Continuous
solid infill
block
Continuous
solid infill
block
128
95
100
148
95
100
148
95
100
148
95
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
CG50/100
CH50/100
CX50/100
CG70/100
CH70/100
CX70/100
CG90/100
CH90/100
CX90/100
CG110/100
CH110/100
CX110/100
CG130/100
CH130/100
CX130/100
CG150/100
CH150/100
CX150/100
115mm Cavity
140mmCavity
Continuous
solid infill
block
Continuous
solid infill
block
page 25
90-105mm Cavity Wall 125-140mm WIL
Continuous
solid infill
block
Continuous
solid infill
block
page 29
50mm Cavity Wall
140-150mm WOL
Continuous
solid infill
block
Continuous
solid infill
block
48
125
95
48
95
125
48
125
95
68
95
125
68
95
125
68
95
125
88
125
95
213
125
95
88
95
50
130
100
70
130
100
90
265
213
6
259
240
140
213
6
133
133
213
6
236
100
133
213
6
88
90mm Cavity
133
125
70mm Cavity
133
284
309
290
315
6
334
340
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Standard Duty
Standard Duty
Extreme Duty
Extreme Duty
Extreme Duty
Extreme Duty
Extreme Duty
CG50/125
CH50/125
CX50/125
CG70/125
CH70/125
CX70/125
CG90/125
CH90/125
CX90/125
CN42C
CN99/124C
CN99/1644C
CXL240
CXL265
CXL290
CXL315
CXL340
page 34
page 36
50-75mm Cavity
35-60mm Cavity
100
48
143
100
60
88
60
100
75
100
47
75
Standard Duty
Heavy Duty
CGE50/100
CGE90/100
CN55A
CN55C
95
67
143
90
95
95
CTF5
YRY
A
D
DELIVE
219
143
Standard Duty
NEXT
h
h
h
page 38
200 & 215mm Solid Walls
CTF7
CTF9
38
100
95
100
95
95
182
Heavy Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Standard Duty
CN23B
CN23C
CN71A
CN71C
CN81B
CN81C
CN50C
CN51C
BLE
AVermAsIaLndAconditions
T
apply
page 41
102mm Exterior Solid Wall
page 43
102mm Exterior Solid Wall
page 44
140 -150mm Solid Wall
70
55
h
h
h
25
91
Light Duty
CNZ94A
CNZ94C
CNZ95C
CNZ96C
CNZ97C
94
100
95
Heavy Duty
Heavy Duty
CNZ97D
CN48C
CN49C
CN49D
25
68
98
CN92
CN102
103
140
100
Light Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
CN100
CN5XA
CN5XC
CN6XB
CN6XC
Heavy Duty
CN99/438C
CN66XC
CN99/436C
CN56XA
Accessories
Special Lintels
page 64
page 47
50-100mm Cavity Wall
Standard Arch
Lintels
Bespoke Arch
Lintels
Bay Window
Lintels
Corner Lintels
With over 10,000 variations available to choose from, theres a design to suit any
size, shape, length, breadth and depth of doorway, archway, window or aperture.
Corrosion protection
Aesthetics
Moisture Control
Moisture Control
Aesthetics
Soffit
Cladding
Arch
Centres
Stop Ends
Weep Vents
External
Plaster Key
www.catnic.com
14
15
Product Selector
page 20
page 22
page 24
Continuous
solid infill
block
Continuous
solid infill
block
100 48
95
100 48
95
page 26
Continuous
solid infill
block
Continuous
solid infill
block
100 48
95
100
68
100
95
68
100
95
page 27
110-125mm Cavity Wall
Continuous
solid infill
block
Continuous
solid infill
block
68
95
100
88
100
95
88
95
100
Continuous
solid infill
block
Continuous
solid infill
block
88
108
95
100
108
95
100
108
100
95
128
95
100
Continuous
solid infill
block
Continuous
solid infill
block
95
100
page 28
130-145mm Cavity Wall
128
100
95
Continuous
solid infill
block
Continuous
solid infill
block
128
95
100
148
95
100
148
95
100
148
95
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
CG50/100
CH50/100
CX50/100
CG70/100
CH70/100
CX70/100
CG90/100
CH90/100
CX90/100
CG110/100
CH110/100
CX110/100
CG130/100
CH130/100
CX130/100
CG150/100
CH150/100
CX150/100
115mm Cavity
140mmCavity
Continuous
solid infill
block
Continuous
solid infill
block
page 25
90-105mm Cavity Wall 125-140mm WIL
Continuous
solid infill
block
Continuous
solid infill
block
page 29
50mm Cavity Wall
140-150mm WOL
Continuous
solid infill
block
Continuous
solid infill
block
48
125
95
48
95
125
48
125
95
68
95
125
68
95
125
68
95
125
88
125
95
213
125
95
88
95
50
130
100
70
130
100
90
265
213
6
259
240
140
213
6
133
133
213
6
236
100
133
213
6
88
90mm Cavity
133
125
70mm Cavity
133
284
309
290
315
6
334
340
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Standard Duty
Standard Duty
Extreme Duty
Extreme Duty
Extreme Duty
Extreme Duty
Extreme Duty
CG50/125
CH50/125
CX50/125
CG70/125
CH70/125
CX70/125
CG90/125
CH90/125
CX90/125
CN42C
CN99/124C
CN99/1644C
CXL240
CXL265
CXL290
CXL315
CXL340
page 34
page 36
50-75mm Cavity
35-60mm Cavity
100
48
143
100
60
88
60
100
75
100
47
75
Standard Duty
Heavy Duty
CGE50/100
CGE90/100
CN55A
CN55C
95
67
143
90
95
95
CTF5
YRY
A
D
DELIVE
219
143
Standard Duty
NEXT
h
h
h
page 38
200 & 215mm Solid Walls
CTF7
CTF9
38
100
95
100
95
95
182
Heavy Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
Standard Duty
Standard Duty
CN23B
CN23C
CN71A
CN71C
CN81B
CN81C
CN50C
CN51C
BLE
AVermAsIaLndAconditions
T
apply
page 41
102mm Exterior Solid Wall
page 43
102mm Exterior Solid Wall
page 44
140 -150mm Solid Wall
70
55
h
h
h
25
91
Light Duty
CNZ94A
CNZ94C
CNZ95C
CNZ96C
CNZ97C
94
100
95
Heavy Duty
Heavy Duty
CNZ97D
CN48C
CN49C
CN49D
25
68
98
CN92
CN102
103
140
100
Light Duty
Standard Duty
Heavy Duty
Standard Duty
Heavy Duty
CN100
CN5XA
CN5XC
CN6XB
CN6XC
Heavy Duty
CN99/438C
CN66XC
CN99/436C
CN56XA
Accessories
Special Lintels
page 64
page 47
50-100mm Cavity Wall
Standard Arch
Lintels
Bespoke Arch
Lintels
Bay Window
Lintels
Corner Lintels
With over 10,000 variations available to choose from, theres a design to suit any
size, shape, length, breadth and depth of doorway, archway, window or aperture.
Corrosion protection
Aesthetics
Moisture Control
Moisture Control
Aesthetics
Soffit
Cladding
Arch
Centres
Stop Ends
Weep Vents
External
Plaster Key
www.catnic.com
14
15
Steel Lintels
Specification Clauses
Steel Lintels
Cavity Walls
Timber Frame
Cavity Walls
Product reference:
Catnic CG or CH or CX
Product reference:
Catnic CTF or CN23.
Product reference:
Catnic CNZ or CN48 or CN49
Material:
DX51D & Z275 galvanised steel
coated with Duplex Corrosion
Protection system.
Material:
DX51D & Z275 galvanised steel
coated with Duplex Corrosion
Protection system.
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Raise inner and
outer leaves of masonry together.
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Install pinch batten
and restraint clips to the timber frame
as per manufacturers instructions. Prop
and laterally restrain the lintel during
construction.
Material:
DX51D & Z275 galvanised steel
coated with Duplex Corrosion
Protection system (CN48, CN49) or
S250GD & Z600 galvanised steel (CNZ).
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. When installing the
masonry the lintels must be propped
and laterally restrained during
construction.
Product reference:
Catnic C
Material:
Austenitic Stainless Steel grade 304S15
to BS EN 10088-2-1.4301.
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Raise inner and
outer leaves of masonry together.
Other Applications
Lintel Accessories
Product reference:
Catnic CL3 or C90
Product reference:
Catnic WV colour
Installation:
Insert lintel Stop Ends to suit lintel
profiles on either end of the lintel.
Position in the nearest perpend at/or
beyond the end of the opening.
Installation:
Insert lintel Cavity Weep Vents (ref:
Catnic WV colour) at 450mm
centres. At least two per opening to be
installed.
Product reference:
Catnic RC for Rebated Cavity Wall
lintels, or FC for Standard Cavity Walls
and colour)
Product reference:
Catnic C
Material: DX51D & Z275 galvanised
steel coated with Duplex Corrosion
Protection system or DX51D Z600
galvanised steel
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Raise inner and
outer leaves of masonry together whilst
propping and laterally restraining the
lintel during construction.
16
17
Steel Lintels
Specification Clauses
Steel Lintels
Cavity Walls
Timber Frame
Cavity Walls
Product reference:
Catnic CG or CH or CX
Product reference:
Catnic CTF or CN23.
Product reference:
Catnic CNZ or CN48 or CN49
Material:
DX51D & Z275 galvanised steel
coated with Duplex Corrosion
Protection system.
Material:
DX51D & Z275 galvanised steel
coated with Duplex Corrosion
Protection system.
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Raise inner and
outer leaves of masonry together.
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Install pinch batten
and restraint clips to the timber frame
as per manufacturers instructions. Prop
and laterally restrain the lintel during
construction.
Material:
DX51D & Z275 galvanised steel
coated with Duplex Corrosion
Protection system (CN48, CN49) or
S250GD & Z600 galvanised steel (CNZ).
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. When installing the
masonry the lintels must be propped
and laterally restrained during
construction.
Product reference:
Catnic C
Material:
Austenitic Stainless Steel grade 304S15
to BS EN 10088-2-1.4301.
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Raise inner and
outer leaves of masonry together.
Other Applications
Lintel Accessories
Product reference:
Catnic CL3 or C90
Product reference:
Catnic WV colour
Installation:
Insert lintel Stop Ends to suit lintel
profiles on either end of the lintel.
Position in the nearest perpend at/or
beyond the end of the opening.
Installation:
Insert lintel Cavity Weep Vents (ref:
Catnic WV colour) at 450mm
centres. At least two per opening to be
installed.
Product reference:
Catnic RC for Rebated Cavity Wall
lintels, or FC for Standard Cavity Walls
and colour)
Product reference:
Catnic C
Material: DX51D & Z275 galvanised
steel coated with Duplex Corrosion
Protection system or DX51D Z600
galvanised steel
Installation:
Bed on mortar with a minimum 150mm
bearing at each end. Raise inner and
outer leaves of masonry together whilst
propping and laterally restraining the
lintel during construction.
16
17
18
CH & CX
Benefits
As CG plus:
Supports concrete floors
Attic truss loads
Larger span multiple truss loads
Conditions of use
Nominal 150mm end bearings
Both leaves are raised together
One course of block prior to
installation of floor/roof
Refer to Installing a cavity wall lintel
(page 71)
Note:
For a definition of these terms see the
Glossary of Technical Terms on page 82.
Steel Lintels
CG
19
30
33
35
37
40
42
45
46
Integral insulation
Maximising thermal efficiency,
minimising cold bridging
Accessories
ArchCentres, Stop Ends, Cavity Weep
Vents, Soffit Cladding (refer to page 64)
NOTE: Whilst the above information is intended to offer
general guidance regarding typical applications, it should
not be considered as comprehensive. Requirements not
fully covered by the above should be referred to our
technical services department for individual consideration.
19
18
CH & CX
Benefits
As CG plus:
Supports concrete floors
Attic truss loads
Larger span multiple truss loads
Conditions of use
Nominal 150mm end bearings
Both leaves are raised together
One course of block prior to
installation of floor/roof
Refer to Installing a cavity wall lintel
(page 71)
Note:
For a definition of these terms see the
Glossary of Technical Terms on page 82.
Steel Lintels
CG
19
30
33
35
37
40
42
45
46
Integral insulation
Maximising thermal efficiency,
minimising cold bridging
Accessories
ArchCentres, Stop Ends, Cavity Weep
Vents, Soffit Cladding (refer to page 64)
NOTE: Whilst the above information is intended to offer
general guidance regarding typical applications, it should
not be considered as comprehensive. Requirements not
fully covered by the above should be referred to our
technical services department for individual consideration.
19
Standard Duty
Standard Duty
CG50/125*
CG50/100
Standard lengths (mm)
900-1500
1800
2100
2400
2700
3000-3600
15
18
20
22
26
26
Weight (kg/m)
5.8
7.3
8.0
8.6
9.8
12.3
140
140
160
180
220
220
100
48
95
900-1200
12
17
20
26
Weight (kg/m)
6.3
7.8
9.0
12.9
140
140
180
220
125
Heavy Duty
Heavy Duty
CH50/125
h
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
10.5
13.1
13.1
157
157
157
Continuous
solid infill
block
100
48
95
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
10.7
13.4
13.4
157
157
157
CX50/100
h
900-2700
60
55
50
32
Weight (kg/m)
16.0
16.0
19.4
19.4
232
232
232
232
100
48
95
900-2700
60
55
50
32
Weight (kg/m)
16.2
16.2
19.8
19.8
232
232
232
232
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
48
95
CX50/125
Continuous
solid infill
block
Continuous
solid infill
block
125
20
95
CH50/100
48
Continuous
solid infill
block
125
48
95
21
Standard Duty
Standard Duty
CG50/125*
CG50/100
Standard lengths (mm)
900-1500
1800
2100
2400
2700
3000-3600
15
18
20
22
26
26
Weight (kg/m)
5.8
7.3
8.0
8.6
9.8
12.3
140
140
160
180
220
220
100
48
95
900-1200
12
17
20
26
Weight (kg/m)
6.3
7.8
9.0
12.9
140
140
180
220
125
Heavy Duty
Heavy Duty
CH50/125
h
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
10.5
13.1
13.1
157
157
157
Continuous
solid infill
block
100
48
95
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
10.7
13.4
13.4
157
157
157
CX50/100
h
900-2700
60
55
50
32
Weight (kg/m)
16.0
16.0
19.4
19.4
232
232
232
232
100
48
95
900-2700
60
55
50
32
Weight (kg/m)
16.2
16.2
19.8
19.8
232
232
232
232
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
48
95
CX50/125
Continuous
solid infill
block
Continuous
solid infill
block
125
20
95
CH50/100
48
Continuous
solid infill
block
125
48
95
21
Standard Duty
Standard Duty
CG70/125*
CG70/100
Standard lengths (mm)
750-1500
1650-1800
2100
2400
2700
3000-3600
15
18
20
22
26
26
Weight (kg/m)
6.0
7.5
8.1
8.7
10.0
12.5
140
140
160
180
220
220
100
68
95
750-1200
12
17
20
26
Weight (kg/m)
6.3
8.0
9.2
13.1
140
140
180
220
125
Heavy Duty
Heavy Duty
CH70/100
h
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
10.9
13.6
13.6
157
157
157
95
900-1800
32
48
45
Weight (kg/m)
11.1
13.9
13.9
157
157
157
900-2700
55
50
32
Weight (kg/m)
16.4
16.4
19.9
19.9
232
232
232
232
68
95
900-2700
55
50
32
Weight (kg/m)
16.7
16.7
20.3
20.3
232
232
232
232
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
When using the Catnic CH and CX Open Back ranges with concrete floors, always ensure
that the blockwork is built tight against the inner vertical face of the lintel, and that a mortar
joint is added to the top of the blockwork so that the floor units have an even spread over
the inner flange of the lintel. For guidance on installation refer to page 73.
22
95
Continuous
solid infill
block
60
68
Continuous
solid infill
block
125
CX70/125
Continuous
solid infill
block
60
1950-2100 2250-2400
CX70/100
95
CH70/125
Continuous
solid infill
block
100
68
125
68
95
23
Standard Duty
Standard Duty
CG70/125*
CG70/100
Standard lengths (mm)
750-1500
1650-1800
2100
2400
2700
3000-3600
15
18
20
22
26
26
Weight (kg/m)
6.0
7.5
8.1
8.7
10.0
12.5
140
140
160
180
220
220
100
68
95
750-1200
12
17
20
26
Weight (kg/m)
6.3
8.0
9.2
13.1
140
140
180
220
125
Heavy Duty
Heavy Duty
CH70/100
h
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
10.9
13.6
13.6
157
157
157
95
900-1800
32
48
45
Weight (kg/m)
11.1
13.9
13.9
157
157
157
900-2700
55
50
32
Weight (kg/m)
16.4
16.4
19.9
19.9
232
232
232
232
68
95
900-2700
55
50
32
Weight (kg/m)
16.7
16.7
20.3
20.3
232
232
232
232
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
When using the Catnic CH and CX Open Back ranges with concrete floors, always ensure
that the blockwork is built tight against the inner vertical face of the lintel, and that a mortar
joint is added to the top of the blockwork so that the floor units have an even spread over
the inner flange of the lintel. For guidance on installation refer to page 73.
22
95
Continuous
solid infill
block
60
68
Continuous
solid infill
block
125
CX70/125
Continuous
solid infill
block
60
1950-2100 2250-2400
CX70/100
95
CH70/125
Continuous
solid infill
block
100
68
125
68
95
23
Standard Duty
Standard Duty
CG90/100
CG90/125
h
750-1500
15
18
20
22
26
26
Weight (kg/m)
6.1
7.6
8.3
8.9
10.2
13.0
140
140
160
180
220
220
100
88
95
750-1200
12
17
20
26
Weight (kg/m)
6.5
8.1
9.4
13.3
140
140
180
220
125
Heavy Duty
Heavy Duty
900-1800
CH90/125
Continuous
solid infill
block
1950-2100 2250-2400
32
48
45
Weight (kg/m)
11.2
14.0
14.0
157
157
157
88
95
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
11.5
14.3
14.3
157
157
157
CX90/100
Standard lengths (mm)
SWL 1:1/19:1 (kN)
900-2700
55
50
32
Weight (kg/m)
16.9
16.9
20.5
20.5
232
232
232
232
88
95
55
50
32
Weight (kg/m)
17.2
17.2
20.9
20.9
232
232
232
232
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
When using the Catnic CH and CX Open Back ranges with concrete floors, always ensure
that the blockwork is built tight against the inner vertical face of the lintel, and that a mortar
joint is added to the top of the blockwork so that the floor units have an even spread over
the inner flange of the lintel. For guidance on installation refer to page 73.
24
88
95
Continuous
solid infill
block
60
125
900-2700
Continuous
solid infill
block
CX90/125
Continuous
solid infill
block
60
95
CH90/100
88
125
88
95
25
Standard Duty
Standard Duty
CG90/100
CG90/125
h
750-1500
15
18
20
22
26
26
Weight (kg/m)
6.1
7.6
8.3
8.9
10.2
13.0
140
140
160
180
220
220
100
88
95
750-1200
12
17
20
26
Weight (kg/m)
6.5
8.1
9.4
13.3
140
140
180
220
125
Heavy Duty
Heavy Duty
900-1800
CH90/125
Continuous
solid infill
block
1950-2100 2250-2400
32
48
45
Weight (kg/m)
11.2
14.0
14.0
157
157
157
88
95
900-1800
1950-2100 2250-2400
32
48
45
Weight (kg/m)
11.5
14.3
14.3
157
157
157
CX90/100
Standard lengths (mm)
SWL 1:1/19:1 (kN)
900-2700
55
50
32
Weight (kg/m)
16.9
16.9
20.5
20.5
232
232
232
232
88
95
55
50
32
Weight (kg/m)
17.2
17.2
20.9
20.9
232
232
232
232
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
When using the Catnic CH and CX Open Back ranges with concrete floors, always ensure
that the blockwork is built tight against the inner vertical face of the lintel, and that a mortar
joint is added to the top of the blockwork so that the floor units have an even spread over
the inner flange of the lintel. For guidance on installation refer to page 73.
24
88
95
Continuous
solid infill
block
60
125
900-2700
Continuous
solid infill
block
CX90/125
Continuous
solid infill
block
60
95
CH90/100
88
125
88
95
25
Standard Duty
Standard Duty
CG110/100
CG130/100
h
900-1500
1800
2100
2400-3600
15
18
20
26
Weight (kg/m)
11.3
11.3
11.9
16.8
167
167
183
247
900-1500
108
95
1800
2100
2400-3600
15
18
20
26
Weight (kg/m)
11.8
11.8
12.4
17.3
167
167
183
247
100
Heavy Duty
Heavy Duty
CH110/100
Standard lengths (mm)
SWL 1:1/19:1 (kN)
900-1800
2100
32
48
45
12.3
14.7
14.7
157
157
157
95
CH130/100
Continuous
solid infill
block
2400
Weight (kg/m)
128
108
95
900-1800
2100
2400
32
48
45
Weight (kg/m)
12.6
15.1
15.1
157
157
157
Continuous
solid infill
block
100
128
95
CX110/100
h
900-2700
CX130/100
Continuous
solid infill
block
60
55
50
32
Weight (kg/m)
17.3
17.3
20.8
20.8
232
232
232
232
108
95
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
26
900-2700
60
55
50
32
Weight (kg/m)
17.8
17.8
21.4
21.4
232
232
232
232
Continuous
solid infill
block
100
128
95
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
27
Standard Duty
Standard Duty
CG110/100
CG130/100
h
900-1500
1800
2100
2400-3600
15
18
20
26
Weight (kg/m)
11.3
11.3
11.9
16.8
167
167
183
247
900-1500
108
95
1800
2100
2400-3600
15
18
20
26
Weight (kg/m)
11.8
11.8
12.4
17.3
167
167
183
247
100
Heavy Duty
Heavy Duty
CH110/100
Standard lengths (mm)
SWL 1:1/19:1 (kN)
900-1800
2100
32
48
45
12.3
14.7
14.7
157
157
157
95
CH130/100
Continuous
solid infill
block
2400
Weight (kg/m)
128
108
95
900-1800
2100
2400
32
48
45
Weight (kg/m)
12.6
15.1
15.1
157
157
157
Continuous
solid infill
block
100
128
95
CX110/100
h
900-2700
CX130/100
Continuous
solid infill
block
60
55
50
32
Weight (kg/m)
17.3
17.3
20.8
20.8
232
232
232
232
108
95
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
26
900-2700
60
55
50
32
Weight (kg/m)
17.8
17.8
21.4
21.4
232
232
232
232
Continuous
solid infill
block
100
128
95
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
27
Standard Duty
CG150/100
CN42C
h
900-1500
1800
2100
2400-3600
15
18
20
26
Weight (kg/m)
12.3
12.3
12.7
17.7
167
167
183
247
148
95
750-4200
29
Weight (kg/m)
20.5
219
Heavy Duty
CH150/100
Standard lengths (mm)
2100
2400
32
48
45
Weight (kg/m)
13.1
15.6
15.6
157
157
157
Continuous
solid infill
block
100
148
95
750-4200
29
Weight (kg/m)
20.6
219
100
70
130
CN99/1644C
900-2700
Continuous
solid infill
block
750-4200
60
55
50
32
Weight (kg/m)
18.2
18.2
21.9
21.9
Weight (kg/m)
21.4
232
232
232
232
219
100
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths
3000mm - 4800mm (including 4575mm, but excluding 4500mm).
148
95
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
28
130
CX150/100
Standard lengths (mm)
50
CN99/124C
900-1800
100
29
100
90
140
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
29
Standard Duty
CG150/100
CN42C
h
900-1500
1800
2100
2400-3600
15
18
20
26
Weight (kg/m)
12.3
12.3
12.7
17.7
167
167
183
247
148
95
750-4200
29
Weight (kg/m)
20.5
219
Heavy Duty
CH150/100
Standard lengths (mm)
2100
2400
32
48
45
Weight (kg/m)
13.1
15.6
15.6
157
157
157
Continuous
solid infill
block
100
148
95
750-4200
29
Weight (kg/m)
20.6
219
100
70
130
CN99/1644C
900-2700
Continuous
solid infill
block
750-4200
60
55
50
32
Weight (kg/m)
18.2
18.2
21.9
21.9
Weight (kg/m)
21.4
232
232
232
232
219
100
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths
3000mm - 4800mm (including 4575mm, but excluding 4500mm).
148
95
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
28
130
CX150/100
Standard lengths (mm)
50
CN99/124C
900-1800
100
29
100
90
140
The SWL (safe working load) is based on the total UDL (uniform distributed load) over
maximum span using 150mm end bearings.
29
Material used
Supplied in post galvanised finish.
Lintels manufactured from a universal
beam section and 6.0mm structural
grade steel plate Grade S275 to
BSEN 10025:2004 and hot dip
galvanised after manufacture to
BSEN ISO1461:1999.
Standard increment lengths
Overall lengths are available in 50mm
increments for lengths up to 6600mm.
Optional Extra
As an optional extra, CXL lintels can
be supplied with expanded metal
mesh secured to the base plate.
Load ratios
To achieve the loading figures
shown, the lintel must be laterally
restrained and have 200mm end
bearing supports and inner to outer
load ratios between 5:1 and 19:1.
Separate DPC
A separate flexible DPC must be
installed during construction.
Note:
For alternative cavity wall constructions please contact
our Technical Services Department on 029 2033 7900.
Application:
CXL240
Standard lengths (mm) 2100-3000 3300-4800
SWL 5:1/19:1(kN)
88
83
Weight (kg/m)
41.1
41.1
Ixx (cm4)
4051
4051
Zxx (cm3)
303
303
Serviceability moment (kNm)
50
50
Allowable reaction (kN)
66
66
5100
78
41.1
4051
303
50
66
5400
71
41.1
4051
303
50
66
5700
64
41.1
4051
303
50
66
6000
56
41.1
4051
303
50
66
6300
52
41.1
4051
303
50
66
6600
47
41.1
4051
303
50
66
213
6
6
236
240
Application:
CXL265
Standard lengths (mm) 2100-3000 3300-4800
SWL 5:1/19:1 (kN)
88
83
Weight (kg/m)
42.3
42.3
Ixx (cm4)
4139
4139
Zxx (cm3)
305
305
Serviceability moment (kNm) 50.3
50.3
Allowable reaction (kN)
66
66
5100
78
42.3
4139
305
50.3
66
5400
71
42.3
4139
305
50.3
66
5700
64
42.3
4139
305
50.3
66
6000
56
42.3
4139
305
50.3
66
6300
52
42.3
4139
305
50.3
66
6600
47
42.3
4139
305
50.3
66
213
6
6
259
265
30
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 200mm end bearings.
31
Material used
Supplied in post galvanised finish.
Lintels manufactured from a universal
beam section and 6.0mm structural
grade steel plate Grade S275 to
BSEN 10025:2004 and hot dip
galvanised after manufacture to
BSEN ISO1461:1999.
Standard increment lengths
Overall lengths are available in 50mm
increments for lengths up to 6600mm.
Optional Extra
As an optional extra, CXL lintels can
be supplied with expanded metal
mesh secured to the base plate.
Load ratios
To achieve the loading figures
shown, the lintel must be laterally
restrained and have 200mm end
bearing supports and inner to outer
load ratios between 5:1 and 19:1.
Separate DPC
A separate flexible DPC must be
installed during construction.
Note:
For alternative cavity wall constructions please contact
our Technical Services Department on 029 2033 7900.
Application:
CXL240
Standard lengths (mm) 2100-3000 3300-4800
SWL 5:1/19:1(kN)
88
83
Weight (kg/m)
41.1
41.1
Ixx (cm4)
4051
4051
Zxx (cm3)
303
303
Serviceability moment (kNm)
50
50
Allowable reaction (kN)
66
66
5100
78
41.1
4051
303
50
66
5400
71
41.1
4051
303
50
66
5700
64
41.1
4051
303
50
66
6000
56
41.1
4051
303
50
66
6300
52
41.1
4051
303
50
66
6600
47
41.1
4051
303
50
66
213
6
6
236
240
Application:
CXL265
Standard lengths (mm) 2100-3000 3300-4800
SWL 5:1/19:1 (kN)
88
83
Weight (kg/m)
42.3
42.3
Ixx (cm4)
4139
4139
Zxx (cm3)
305
305
Serviceability moment (kNm) 50.3
50.3
Allowable reaction (kN)
66
66
5100
78
42.3
4139
305
50.3
66
5400
71
42.3
4139
305
50.3
66
5700
64
42.3
4139
305
50.3
66
6000
56
42.3
4139
305
50.3
66
6300
52
42.3
4139
305
50.3
66
6600
47
42.3
4139
305
50.3
66
213
6
6
259
265
30
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 200mm end bearings.
31
Application:
Eaves Lintels
133
5100
78
43.5
4222
307
50.6
66
5400
71
43.5
4222
307
50.6
66
5700
64
43.5
4222
307
50.6
66
6000
56
43.5
4222
307
50.6
66
6300
52
43.5
4222
307
50.6
66
6600
47
43.5
4222
307
50.6
66
213
6
6
284
290
Classic Box
Typical applications
Universal application caters for all loading conditions
Direct roof loading
Attic truss loads
Supports point loads eg. multiple trusses
Application:
Continuous insulation
Maximising thermal efficiency, minimising cold bridging
133
5100
78
44.6
4301
311
50.9
66
5400
71
44.6
4301
311
50.9
66
5700
64
44.6
4301
311
50.9
66
6000
56
44.6
4301
311
50.9
66
6300
52
44.6
4301
311
50.9
66
6600
47
44.6
4301
311
50.9
66
213
6
6
309
315
Application:
CXL340
Standard lengths (mm) 2100-3000 3300-4800
SWL 5:1/19:1 (kN)
88
83
Weight (kg/m)
45.8
45.8
Ixx (cm4)
4375
4375
Zxx (cm3)
312
312
Serviceability moment (kNm) 51.6
51.6
Allowable reaction (kN)
66
66
5100
78
45.8
4375
312
51.6
66
5400
71
45.8
4375
312
51.6
66
5700
64
45.8
4375
312
51.6
66
6000
56
45.8
4375
312
51.6
66
6300
52
45.8
4375
312
51.6
66
6600
47
45.8
4375
312
51.6
66
213
6
6
334
340
Eaves Lintel
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 200mm end bearings.
32
33
Application:
Eaves Lintels
133
5100
78
43.5
4222
307
50.6
66
5400
71
43.5
4222
307
50.6
66
5700
64
43.5
4222
307
50.6
66
6000
56
43.5
4222
307
50.6
66
6300
52
43.5
4222
307
50.6
66
6600
47
43.5
4222
307
50.6
66
213
6
6
284
290
Classic Box
Typical applications
Universal application caters for all loading conditions
Direct roof loading
Attic truss loads
Supports point loads eg. multiple trusses
Application:
Continuous insulation
Maximising thermal efficiency, minimising cold bridging
133
5100
78
44.6
4301
311
50.9
66
5400
71
44.6
4301
311
50.9
66
5700
64
44.6
4301
311
50.9
66
6000
56
44.6
4301
311
50.9
66
6300
52
44.6
4301
311
50.9
66
6600
47
44.6
4301
311
50.9
66
213
6
6
309
315
Application:
CXL340
Standard lengths (mm) 2100-3000 3300-4800
SWL 5:1/19:1 (kN)
88
83
Weight (kg/m)
45.8
45.8
Ixx (cm4)
4375
4375
Zxx (cm3)
312
312
Serviceability moment (kNm) 51.6
51.6
Allowable reaction (kN)
66
66
5100
78
45.8
4375
312
51.6
66
5400
71
45.8
4375
312
51.6
66
5700
64
45.8
4375
312
51.6
66
6000
56
45.8
4375
312
51.6
66
6300
52
45.8
4375
312
51.6
66
6600
47
45.8
4375
312
51.6
66
213
6
6
334
340
Eaves Lintel
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 200mm end bearings.
32
33
Open Back
CGE50/100
Standard lengths (mm)
SWL (kN)*
Weight (kg/m)
Nominal height h (mm)
900-1500 1800-2100
25
22
7.0
8.0
95
115
2400
20
10.2
115
2700
20
10.2
115
100
48
60
Benefits
CGE90/100
Standard lengths (mm)
SWL (kN)*
Weight (kg/m)
Nominal height h (mm)
900-1500 1800-2100
25
22
7.7
8.3
95
115
2400
20
10.7
115
2700
20
10.7
115
Restraint clips
Allows vertical differential movement
of timber frame.
CTF5 Lintel
100
88
60
900&1200
30
9.0
1500
30
9.0
1650-2100
25
9.0
2400&2700
20
9.0
Standard lengths are available in increments of 150mm. For lengths over 2700mm please contact Technical Services.
CN55C
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
900&1200
50
12.8
1500
50
12.8
1650-2100
40
12.8
2400&2700
30
12.8
Standard lengths are available in increments of 150mm. For lengths over 2700mm please contact Technical Services.
143
CN23 Lintel
100
75
34
35
Open Back
CGE50/100
Standard lengths (mm)
SWL (kN)*
Weight (kg/m)
Nominal height h (mm)
900-1500 1800-2100
25
22
7.0
8.0
95
115
2400
20
10.2
115
2700
20
10.2
115
100
48
60
Benefits
CGE90/100
Standard lengths (mm)
SWL (kN)*
Weight (kg/m)
Nominal height h (mm)
900-1500 1800-2100
25
22
7.7
8.3
95
115
2400
20
10.7
115
2700
20
10.7
115
Restraint clips
Allows vertical differential movement
of timber frame.
CTF5 Lintel
100
88
60
900&1200
30
9.0
1500
30
9.0
1650-2100
25
9.0
2400&2700
20
9.0
Standard lengths are available in increments of 150mm. For lengths over 2700mm please contact Technical Services.
CN55C
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
900&1200
50
12.8
1500
50
12.8
1650-2100
40
12.8
2400&2700
30
12.8
Standard lengths are available in increments of 150mm. For lengths over 2700mm please contact Technical Services.
143
CN23 Lintel
100
75
34
35
Solid Walls
CTF5
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
750-1200
4
3.8
128
1350-1500
5
4.8
128
1650-2400
7
5.6
183
2550-3000
7
7.2
183
3300-3600
9
8.0
218
3900-4800
10
9.0
256
47
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm.
95
750-1200
4
4.2
145
1350-1500
5
5.2
145
1650-2400
7
5.9
187
2550-3000
7
7.5
187
3300-3600
9
8.3
218
3900-4800
10
9.3
265
67
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm.
95
1650-2400
7
5.9
146
2550-3000
7
8.1
200
3300-3600
9
8.4
220
3900-4800
10
9.6
271
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm.
Two-piece inverted T
Benefits
Box Profile
Saves on brickwork and insulation.
Resists twisting during construction
CTF9
750-1500
5
4.7
146
Classic Box
90
Continuous insulation
Maximising thermal efficiency, minimising cold bridging
Integral plaster key
With staggered slots to side and underside of the box
profile
95
CN51 Lintel
CN23C
750-3600
10
12.8
268
3900-4800
10
16.3
268
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm (including 4575mm but excluding 4500mm).
The SWL (safe working load) is based on the total UDL (uniform distributed load) over maximum span using 150mm end bearings.
38
95
36
37
Solid Walls
CTF5
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
750-1200
4
3.8
128
1350-1500
5
4.8
128
1650-2400
7
5.6
183
2550-3000
7
7.2
183
3300-3600
9
8.0
218
3900-4800
10
9.0
256
47
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm.
95
750-1200
4
4.2
145
1350-1500
5
5.2
145
1650-2400
7
5.9
187
2550-3000
7
7.5
187
3300-3600
9
8.3
218
3900-4800
10
9.3
265
67
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm.
95
1650-2400
7
5.9
146
2550-3000
7
8.1
200
3300-3600
9
8.4
220
3900-4800
10
9.6
271
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm.
Two-piece inverted T
Benefits
Box Profile
Saves on brickwork and insulation.
Resists twisting during construction
CTF9
750-1500
5
4.7
146
Classic Box
90
Continuous insulation
Maximising thermal efficiency, minimising cold bridging
Integral plaster key
With staggered slots to side and underside of the box
profile
95
CN51 Lintel
CN23C
750-3600
10
12.8
268
3900-4800
10
16.3
268
Standard lengths are available in 150mm increments up to 3000mm, 300mm at lengths from 3000mm - 4800mm (including 4575mm but excluding 4500mm).
The SWL (safe working load) is based on the total UDL (uniform distributed load) over maximum span using 150mm end bearings.
38
95
36
37
Standard Duty
CN71A
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
CN71C
750-1500
29
9.3
143
1650-2100
27
9.3
143
2250-2700
20
9.3
143
900-1500
49
14.6
143
1650-1950
44
14.6
143
143
100
Standard Duty
CN81B
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
95
Heavy Duty
CN81C
2100-3600
29
15.1
219
2100-2700
54
18.5
219
2850-3300
47
18.5
219
3600
39
18.5
219
3900-4575
29
18.5
219
4800
26
18.5
219
219
CG Lintel installed
in solid wall
construction
100
95
CN81 Lintel
Standard Duty
CN51C
750-1800
10
9.0
91
1950-2700
12
12.7
167
182
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 150mm end bearings.
38
39
Standard Duty
CN71A
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
CN71C
750-1500
29
9.3
143
1650-2100
27
9.3
143
2250-2700
20
9.3
143
900-1500
49
14.6
143
1650-1950
44
14.6
143
143
100
Standard Duty
CN81B
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
95
Heavy Duty
CN81C
2100-3600
29
15.1
219
2100-2700
54
18.5
219
2850-3300
47
18.5
219
3600
39
18.5
219
3900-4575
29
18.5
219
4800
26
18.5
219
219
CG Lintel installed
in solid wall
construction
100
95
CN81 Lintel
Standard Duty
CN51C
750-1800
10
9.0
91
1950-2700
12
12.7
167
182
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 150mm end bearings.
38
39
Angle
C Profile
Applications
CNZ94A suitable for use over meter boxes only.
CNZ94C, CNZ95C, CNZ96C & CNZ97C suitable for
light duty loading applications
Applications
CN48C & CN49C lintels are fully built into wall construction for
use with single leaf face brick or block walls
Duplex Corrosion Protection System
Ensures optimum durability and longevity
Standard Duty
CN48C
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
CN49C
750-1800
15
7.5
154
Heavy Duty
CN49D
1950-3000
20
9.3
229
2850-3000
30
18.0
231
70
3300-4800
20
18.0
231
55
h
h
100
95
CNZ94A
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
750
8
2.7
88
1350
4
2.7
88
h
h
91
CNZ94C
CNZ96 Lintel
CN48 Lintel
CNZ95C
900-1500
5
4.4
91
CNZ96C
1650-2100
7
5.4
131
2250-2400
10
6.3
167
CNZ97C
2550-3000
15
7.5
215
94
CNZ97D
3300-3900
15
7.5
215
Lintels CNZ94C, CNZ95C, CNZ96C, CNZ97C and CNZ97D should be suitably propped and laterally restrained during construction.
Standard lengths are available in increments of 150mm at lenghts up to 3000mm, 300mm at lengths
3000mm - 3900mm.
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 150mm end bearings.
40
41
Angle
C Profile
Applications
CNZ94A suitable for use over meter boxes only.
CNZ94C, CNZ95C, CNZ96C & CNZ97C suitable for
light duty loading applications
Applications
CN48C & CN49C lintels are fully built into wall construction for
use with single leaf face brick or block walls
Duplex Corrosion Protection System
Ensures optimum durability and longevity
Standard Duty
CN48C
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
CN49C
750-1800
15
7.5
154
Heavy Duty
CN49D
1950-3000
20
9.3
229
2850-3000
30
18.0
231
70
3300-4800
20
18.0
231
55
h
h
100
95
CNZ94A
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
750
8
2.7
88
1350
4
2.7
88
h
h
91
CNZ94C
CNZ96 Lintel
CN48 Lintel
CNZ95C
900-1500
5
4.4
91
CNZ96C
1650-2100
7
5.4
131
2250-2400
10
6.3
167
CNZ97C
2550-3000
15
7.5
215
94
CNZ97D
3300-3900
15
7.5
215
Lintels CNZ94C, CNZ95C, CNZ96C, CNZ97C and CNZ97D should be suitably propped and laterally restrained during construction.
Standard lengths are available in increments of 150mm at lenghts up to 3000mm, 300mm at lengths
3000mm - 3900mm.
The SWL (safe working load) is based on the total UDL (uniform
distributed load) over maximum span using 150mm end bearings.
40
41
CN102
1050-1200
7
1.2
1050-1200
7
1.8
100
75
25
25
98
68
Standard lengths are available in increments of 150mm
Corrugated
Channel
Box
Applications
CN100
As corrugated lintel plus:
Suitable for masonry/timber floor loads.
(Note: 1800 & 2100 are not suitable for
floor loads)
Applications
CN5X & CN6X
Universal application caters for all
loading conditions
Direct floor or roof load
Supports concrete floor loads
Supports point loads
eg. steel beams etc
Optional 4 course profile for high
loads at extended lengths
Applications
CN92 & CN102
Suitable for nominal domestic loading
Integral plaster key
Lozenge shaped staggered slots to
sides of corrugated profile
CN100
Standard lengths (mm)
SWL (kN)*
Weight (kg/m)
Nominal height h (mm)
1050-1200
10
4.7
50
1350-1500
13
5.9
73
1800*
3
4.7
50
2100*
3
4.7
50
h
103
Standard lengths are available in increments of 150mm at lengths up to 1500mm, 300mm at lengths from 1800mm - 2100mm.
CN5XC
750-1500
29
7.6
143
Standard Duty
CN6XB
1650-2100
25
7.6
143
2250-2700
20
7.6
143
750-1500
49
12.3
143
1650-1950
39
12.3
143
h
Heavy Duty
CN6XC
100
2100-3600
29
12.4
219
2100-2700
49
15.7
219
2850-3300
39
15.7
219
3600
34
15.7
219
3900-4575
29
15.7
219
4800
26
15.7
219
CN92 Lintel
42
CN100 Lintel
CN5X Lintel
3000-3300
54
19.5
295
3600-3900
51
19.5
295
4200-4800
41
19.5
295
The SWL (safe working load) is based on the total UDL (uniform distributed
load) over maximum span using 150mm end bearings.
43
CN102
1050-1200
7
1.2
1050-1200
7
1.8
100
75
25
25
98
68
Standard lengths are available in increments of 150mm
Corrugated
Channel
Box
Applications
CN100
As corrugated lintel plus:
Suitable for masonry/timber floor loads.
(Note: 1800 & 2100 are not suitable for
floor loads)
Applications
CN5X & CN6X
Universal application caters for all
loading conditions
Direct floor or roof load
Supports concrete floor loads
Supports point loads
eg. steel beams etc
Optional 4 course profile for high
loads at extended lengths
Applications
CN92 & CN102
Suitable for nominal domestic loading
Integral plaster key
Lozenge shaped staggered slots to
sides of corrugated profile
CN100
Standard lengths (mm)
SWL (kN)*
Weight (kg/m)
Nominal height h (mm)
1050-1200
10
4.7
50
1350-1500
13
5.9
73
1800*
3
4.7
50
2100*
3
4.7
50
h
103
Standard lengths are available in increments of 150mm at lengths up to 1500mm, 300mm at lengths from 1800mm - 2100mm.
CN5XC
750-1500
29
7.6
143
Standard Duty
CN6XB
1650-2100
25
7.6
143
2250-2700
20
7.6
143
750-1500
49
12.3
143
1650-1950
39
12.3
143
h
Heavy Duty
CN6XC
100
2100-3600
29
12.4
219
2100-2700
49
15.7
219
2850-3300
39
15.7
219
3600
34
15.7
219
3900-4575
29
15.7
219
4800
26
15.7
219
CN92 Lintel
42
CN100 Lintel
CN5X Lintel
3000-3300
54
19.5
295
3600-3900
51
19.5
295
4200-4800
41
19.5
295
The SWL (safe working load) is based on the total UDL (uniform distributed
load) over maximum span using 150mm end bearings.
43
1050-1500
29
9.0
143
1650-2700
20
9.0
143
Stainless Steel
Continuous
insulation
Plaster key
CN66XC
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
1650-2700
54
18.0
219
2850-3300
47
18.0
219
3600
39
18.0
219
3900-4575
29
18.0
219
4800
26
18.0
219
140
CN99/436C
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
44
3000-3300
54
23.0
295
3600-3900
51
23.0
295
4200-4800
49
23.0
295
a) Non-aggressive Environment
Buildings exceeding three storeys
in a non-aggressive environment.
The material coating specification
for products in contact with or
embedded in an outer leaf of an
external cavity wall or a single leaf
external wall should be austenitic
stainless steel.
Product Range
All Catnic Stainless Steel Lintels are
manufactured from Austenitic
Stainless Steel, grade 304S15 to
BS EN 10088-2-1.4301
Other grades of stainless steel are
available on request.
All Catnic galvanised steel loading
tables apply.
All stainless steel lintel lengths are
manufactured to order, price and
delivery on application.
All standard stainless steel lintels from
Catnic are BBA approved under
Agrment Certificate No. 91/2638
Special lintels in stainless steel are
available manufactured to order.
All stainless steel lintel products are
manufactured to order.
The SWL (safe working load) is based on the total UDL (uniform distributed
load) over maximum span using 150mm end bearings.
b) Aggressive Environment
Buildings located in an aggressive
environment (e.g. coastal sites). The
material coating specification for
products in both leaves of external
walls should be austenitic stainless
steel.
Special lintel
Box lintel
45
1050-1500
29
9.0
143
1650-2700
20
9.0
143
Stainless Steel
Continuous
insulation
Plaster key
CN66XC
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
1650-2700
54
18.0
219
2850-3300
47
18.0
219
3600
39
18.0
219
3900-4575
29
18.0
219
4800
26
18.0
219
140
CN99/436C
Standard lengths (mm)
SWL (kN)
Weight (kg/m)
Nominal height h (mm)
44
3000-3300
54
23.0
295
3600-3900
51
23.0
295
4200-4800
49
23.0
295
a) Non-aggressive Environment
Buildings exceeding three storeys
in a non-aggressive environment.
The material coating specification
for products in contact with or
embedded in an outer leaf of an
external cavity wall or a single leaf
external wall should be austenitic
stainless steel.
Product Range
All Catnic Stainless Steel Lintels are
manufactured from Austenitic
Stainless Steel, grade 304S15 to
BS EN 10088-2-1.4301
Other grades of stainless steel are
available on request.
All Catnic galvanised steel loading
tables apply.
All stainless steel lintel lengths are
manufactured to order, price and
delivery on application.
All standard stainless steel lintels from
Catnic are BBA approved under
Agrment Certificate No. 91/2638
Special lintels in stainless steel are
available manufactured to order.
All stainless steel lintel products are
manufactured to order.
The SWL (safe working load) is based on the total UDL (uniform distributed
load) over maximum span using 150mm end bearings.
b) Aggressive Environment
Buildings located in an aggressive
environment (e.g. coastal sites). The
material coating specification for
products in both leaves of external
walls should be austenitic stainless
steel.
Special lintel
Box lintel
45
Special Lintels
Steelwork
When loading conditions exceed our standard
range of lintels Catnic offer a selection of
Steelwork beams, columns and channels
Width (mm)
102
102
133
146
Weight (Kg/m)
19
23
30
43
Special Lintels
Width (mm)
152
152
203
254
Weight (Kg/m)
23
30
46
73
Channels (PFC)
Height (mm)
230
Width (mm)
90
Weight (Kg/m)
32
Special Lintels
48
49
46
47
Special Lintels
Steelwork
When loading conditions exceed our standard
range of lintels Catnic offer a selection of
Steelwork beams, columns and channels
Width (mm)
102
102
133
146
Weight (Kg/m)
19
23
30
43
Special Lintels
Width (mm)
152
152
203
254
Weight (Kg/m)
23
30
46
73
Channels (PFC)
Height (mm)
230
Width (mm)
90
Weight (Kg/m)
32
Special Lintels
48
49
46
47
Special Lintels
Arches
Special Lintels
When you want to make a feature of
brickwork you may need more than a
standard lintel, so Catnic offers both
standard and innovative bespoke designs
Bespoke Designs
150
150
150
150
Clear Span
Clear Span
245
150
285
Lintel
Type
All arch lintels require a separate
DPC installed over
Standard semi-circular arches available for
domestic housing applications. For alternative
cavity and masonry widths, please contact our
Technical Services Department.
Clear Span
(mm)
Weight
(kg)
600
630
900
915
1200
11.79
12.26
16.53
16.77
21.37
CCA/600
CCA/630
CCA/900
CCA/915
CCA/1200
Application
20mm maximum
overhang
48
Lintel
Type
Clear Span
(mm)
CCB/600
CCB/630
CCB/900
CCB/915
CCB/1200
Weight
(kg)
600
630
900
915
1200
12.96
13.47
18.14
18.40
23.43
Application
20mm maximum
overhang
3
102
115-125
150
50-85
50-65
102
102
20mm maximum
overhang
3 Leaf
Outer
102
115-125
90-100
70-85
20mm maximum
overhang
Inner Leaf
102
102
49
Special Lintels
Arches
Special Lintels
When you want to make a feature of
brickwork you may need more than a
standard lintel, so Catnic offers both
standard and innovative bespoke designs
Bespoke Designs
150
150
150
150
Clear Span
Clear Span
245
150
285
Lintel
Type
All arch lintels require a separate
DPC installed over
Standard semi-circular arches available for
domestic housing applications. For alternative
cavity and masonry widths, please contact our
Technical Services Department.
Clear Span
(mm)
Weight
(kg)
600
630
900
915
1200
11.79
12.26
16.53
16.77
21.37
CCA/600
CCA/630
CCA/900
CCA/915
CCA/1200
Application
20mm maximum
overhang
48
Lintel
Type
Clear Span
(mm)
CCB/600
CCB/630
CCB/900
CCB/915
CCB/1200
Weight
(kg)
600
630
900
915
1200
12.96
13.47
18.14
18.40
23.43
Application
20mm maximum
overhang
3
102
115-125
150
50-85
50-65
102
102
20mm maximum
overhang
3 Leaf
Outer
102
115-125
90-100
70-85
20mm maximum
overhang
Inner Leaf
102
102
49
R2
H
R1
E
R3
A
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Clearspan - A (mm)*
Radius 1 - R1 (degrees)*
Timber Floor
Concrete Floor
Radius 2 - R2 (degrees)*
Radius 3 - R3 (degrees)*
Lintel Dimensions
Load
Clearspan - A (mm)*
Cavity (mm)*
Wall Construction
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Wall Construction
Application details
Cavity (mm)*
Inside Only
Timber Floor
Concrete Floor
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
50
51
R2
H
R1
E
R3
A
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Clearspan - A (mm)*
Radius 1 - R1 (degrees)*
Timber Floor
Concrete Floor
Radius 2 - R2 (degrees)*
Radius 3 - R3 (degrees)*
Lintel Dimensions
Load
Clearspan - A (mm)*
Cavity (mm)*
Wall Construction
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Wall Construction
Application details
Cavity (mm)*
Inside Only
Timber Floor
Concrete Floor
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
50
51
A
Angle
H
A
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
A (mm)*
Lintel Dimensions
Load
Clearspan - A (mm)*
Cavity (mm)*
Wall Construction
Lintel Dimensions
Inside Only
Both Sides
Load
B (mm)*
Angle (degrees)*
Cavity (mm)*
Wall Construction
None
Inside Only
Support Posts*
Application details
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
Both Sides
None
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
52
53
A
Angle
H
A
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
A (mm)*
Lintel Dimensions
Load
Clearspan - A (mm)*
Cavity (mm)*
Wall Construction
Lintel Dimensions
Inside Only
Both Sides
Load
B (mm)*
Angle (degrees)*
Cavity (mm)*
Wall Construction
None
Inside Only
Support Posts*
Application details
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
Both Sides
None
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
52
53
A
O
H
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Clearspan - A (mm)*
Lintel Dimensions
Load
Clearspan - A (mm)
Outshot - O (mm)
Wall Construction
Lintel Dimensions
Cavity (mm)*
Inside Only
Both Sides
Load
Height of rise - H (mm)*
Wall Construction
None
Cavity (mm)*
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
54
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
55
A
O
H
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Clearspan - A (mm)*
Lintel Dimensions
Load
Clearspan - A (mm)
Outshot - O (mm)
Wall Construction
Lintel Dimensions
Cavity (mm)*
Inside Only
Both Sides
Load
Height of rise - H (mm)*
Wall Construction
None
Cavity (mm)*
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
54
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
55
H
E
A
D
1
E
F
H
R
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Clearspan - A (mm)*
Radius - R (degrees)*
Timber Floor
Concrete Floor
Lintel Dimensions
Load
Clearspan - A (mm)*
Wall Construction
Load
Cavity (mm)*
Cavity (mm)*
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Timber Floor
Concrete Floor
56
Inside Only
Both Sides
None
57
H
E
A
D
1
E
F
H
R
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Clearspan - A (mm)*
Radius - R (degrees)*
Timber Floor
Concrete Floor
Lintel Dimensions
Load
Clearspan - A (mm)*
Wall Construction
Load
Cavity (mm)*
Cavity (mm)*
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Timber Floor
Concrete Floor
56
Inside Only
Both Sides
None
57
H
E
E
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Clearspan - A (mm)*
Lintel Dimensions
Load
Clearspan - A (mm)*
Wall Construction
Lintel Dimensions
Cavity (mm)*
Inside Only
Both Sides
Load
Height of rise - H (mm)*
Wall Construction
None
Cavity (mm)*
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
58
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
59
H
E
E
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Clearspan - A (mm)*
Lintel Dimensions
Load
Clearspan - A (mm)*
Wall Construction
Lintel Dimensions
Cavity (mm)*
Inside Only
Both Sides
Load
Height of rise - H (mm)*
Wall Construction
None
Cavity (mm)*
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
58
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Application details
59
with return
bearings
B
C
Angle
Angle
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Lintel Dimensions
Application details
A (mm)*
B (mm)*
A (mm)*
B (mm)*
C (mm)*
Angle (degrees)*
Timber Floor
Concrete Floor
C (mm)*
Angle (degrees)*
Timber Floor
Concrete Floor
Wall Construction
Outer leaf (mm)*
Support Posts*
Load
Cavity (mm)*
Wall Construction
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
60
Inside Only
Both Sides
Support Posts*
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Load
Cavity (mm)*
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
61
with return
bearings
B
C
Angle
Angle
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Lintel Dimensions
Application details
A (mm)*
B (mm)*
A (mm)*
B (mm)*
C (mm)*
Angle (degrees)*
Timber Floor
Concrete Floor
C (mm)*
Angle (degrees)*
Timber Floor
Concrete Floor
Wall Construction
Outer leaf (mm)*
Support Posts*
Load
Cavity (mm)*
Wall Construction
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
60
Inside Only
Both Sides
Support Posts*
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Load
Cavity (mm)*
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
61
C
Angle
Arch Span A2
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Lintel Dimensions
Application details
A (mm)*
B (mm)*
Clearspan - A1 (mm)*
Archspan - A2 (mm)*
C (mm)*
Angle (degrees)*
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
Wall Construction
Outer leaf (mm)*
Support Posts*
Load
Cavity (mm)*
Wall Construction
Load
Cavity (mm)*
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
62
Inside Only
Both Sides
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
63
C
Angle
Arch Span A2
E
* Mandatory Fields
* Mandatory Fields
Customer Address
Site Address
Customer Address
Site Address
Name*
Name
Name*
Name
Address
Address
Address
Address
Post Code
Tel*
Post Code
Tel
Post Code
Tel*
Post Code
Tel
Email*
Fax
Fax
Email*
Fax
Fax
Lintel Dimensions
Application details
Lintel Dimensions
Application details
A (mm)*
B (mm)*
Clearspan - A1 (mm)*
Archspan - A2 (mm)*
C (mm)*
Angle (degrees)*
Timber Floor
Concrete Floor
Timber Floor
Concrete Floor
Wall Construction
Outer leaf (mm)*
Support Posts*
Load
Cavity (mm)*
Wall Construction
Load
Cavity (mm)*
n/a
1000mm
1500mm
2000mm
2500mm
3000mm
62
Inside Only
Both Sides
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
Inside Only
Both Sides
None
NOTE: All times quoted as working days, include delivery, calculated from receipt of order
and approved drawing (where applicable). All products are subject to availability.
63
Material
A PVC-U pre-cut unit, supplied in
white (FC & RC) or brown (FC only).
Important note
All external wall lintels fitted with lintel
cladding must be installed with a
flexible damp proof course (DPC)
ensuring that the DPC projects beyond
the front face of the cladding.
Accessories
Catnic is committed to offer a range of high quality
accessories to enhance the performance of Catnic
steel lintels and to make their application even easier
Accessories
Soffit Cladding
Arch Centres
Stop Ends
Weep Vents
External Plaster Key
Lintel Soffit
Cladding type FC
65
66
67
68
69
Lintel Soffit
Cladding type FC
Lintel Soffit
Cladding type RC
64
65
Material
A PVC-U pre-cut unit, supplied in
white (FC & RC) or brown (FC only).
Important note
All external wall lintels fitted with lintel
cladding must be installed with a
flexible damp proof course (DPC)
ensuring that the DPC projects beyond
the front face of the cladding.
Accessories
Catnic is committed to offer a range of high quality
accessories to enhance the performance of Catnic
steel lintels and to make their application even easier
Accessories
Soffit Cladding
Arch Centres
Stop Ends
Weep Vents
External Plaster Key
Lintel Soffit
Cladding type FC
65
66
67
68
69
Lintel Soffit
Cladding type FC
Lintel Soffit
Cladding type RC
64
65
Important note
If used with Catnic soffit cladding, the
straight ends of the ArchCentre (see
cross-hatching on illustration, left), which
extend beyond the structural opening,
should be removed before proceeding to
stage vi. (see below)
Material
Vacuum formed from HIPS (Satin High
Impact Polystyrene). The underside of the
ArchCentre incorporates a minimum of 2
built-in weep vents. For longer length
spans additional weep vents are included,
at maximum spacings of 900mm.
ACA - 75mm
ACB - 150mm
ArchCentre Span
Technical requirements
NHBC Standards: Where fair faced
masonry is supported by lintels: cavity
trays or combined lintels should have
Stop Ends.
Zurich Municipal: To prevent water
running into the adjacent cavity, cavity
trays should have 75mm deep Stop
Figure 1:
Lintel Stop End type CL3 for use with
combined lintels or CH & CX lintels
Figure 2:
Lintel Stop End type C90 for use with CG
lintels and external solid lintels
Installation notes
i) Ensure the lintel surface is clean and
dry.
Lintel ArchCentre
Installation notes
i) Do not use damaged ArchCentres.
ii) Remove the ArchCentre from its protective wrapping.
iii) Check that the ArchCentre is correct for application (Refer to
the lintel specification).
iv) Ensure the ArchCentre and lintel mounting surfaces are clean
and dry.
v) Locate the unit centrally over the opening to determine the
position on the lintel. The front drip section should
be trimmed off at the bearing end to allow for thin mortar joints
and to enhance the appearance.
vi) Locate the unit on the lintel at position previously
determined, ensuring a tight fit to the edge of lintel toe.
66
ArchCentre ArchCentre
Structural
Code
Span (mm) Opening (mm) Rise (mm)
ACA0475
475
450-500
75
ACA0625
625
600-650
75
ACA0925
925
900-950
75
ACA1050
1050
1025-1075
75
ACA1225
1225
1200-1250
75
ACA1350
1350
1325-1375
75
ACA1485
1485
1460-1510
75
ACA1625
1625
1600-1650
75
ACA1700
1700
1675-1725
75
ACA1785
1785
1760-1810
75
ACB1975
1975
1950-2000
150
ACB2125
2125
2100-2150
150
ACA2250
2250
2225-2275
75
ACB2325
2325
2300-2350
150
ACB2425
2425
2400-2450
150
67
Important note
If used with Catnic soffit cladding, the
straight ends of the ArchCentre (see
cross-hatching on illustration, left), which
extend beyond the structural opening,
should be removed before proceeding to
stage vi. (see below)
Material
Vacuum formed from HIPS (Satin High
Impact Polystyrene). The underside of the
ArchCentre incorporates a minimum of 2
built-in weep vents. For longer length
spans additional weep vents are included,
at maximum spacings of 900mm.
ACA - 75mm
ACB - 150mm
ArchCentre Span
Technical requirements
NHBC Standards: Where fair faced
masonry is supported by lintels: cavity
trays or combined lintels should have
Stop Ends.
Zurich Municipal: To prevent water
running into the adjacent cavity, cavity
trays should have 75mm deep Stop
Figure 1:
Lintel Stop End type CL3 for use with
combined lintels or CH & CX lintels
Figure 2:
Lintel Stop End type C90 for use with CG
lintels and external solid lintels
Installation notes
i) Ensure the lintel surface is clean and
dry.
Lintel ArchCentre
Installation notes
i) Do not use damaged ArchCentres.
ii) Remove the ArchCentre from its protective wrapping.
iii) Check that the ArchCentre is correct for application (Refer to
the lintel specification).
iv) Ensure the ArchCentre and lintel mounting surfaces are clean
and dry.
v) Locate the unit centrally over the opening to determine the
position on the lintel. The front drip section should
be trimmed off at the bearing end to allow for thin mortar joints
and to enhance the appearance.
vi) Locate the unit on the lintel at position previously
determined, ensuring a tight fit to the edge of lintel toe.
66
ArchCentre ArchCentre
Structural
Code
Span (mm) Opening (mm) Rise (mm)
ACA0475
475
450-500
75
ACA0625
625
600-650
75
ACA0925
925
900-950
75
ACA1050
1050
1025-1075
75
ACA1225
1225
1200-1250
75
ACA1350
1350
1325-1375
75
ACA1485
1485
1460-1510
75
ACA1625
1625
1600-1650
75
ACA1700
1700
1675-1725
75
ACA1785
1785
1760-1810
75
ACB1975
1975
1950-2000
150
ACB2125
2125
2100-2150
150
ACA2250
2250
2225-2275
75
ACB2325
2325
2300-2350
150
ACB2425
2425
2400-2450
150
67
Type PKS87
Technical requirements
NHBC Standards 1995: Where fair faced
masonry is supported by lintels: weep
holes should be provided at maximum
450mm intervals. Each opening should
have at least two weep holes.
Material
BS Polypropylene in grey, beige and
terracotta to match mortar.
Important note
Cavity weep holes should be provided
over all lintels fitted with stop ends
Installation notes
i) Position in the perpendicular brick
directly above the lintel.
ii) Use a minimum of 2 per lintel at
450mm maximum centres.
Application
Suitable for use with Cougar lintels
(CG, CH, CX) timber frame lintels
(CTF5, CTF7, CTF9, CN23) and External
solid wall lintels (CN71 & CN81).
Installation
External plaster
key simply clips into place
and is secured using a full length of
adhesive bead (supplied by others).
Storage
Unless required
immediate use on site the
product should be stored in a
clean dry environment.
Installation notes
i) Ensure plaster key mounting surface
and under side of lintel is clean, dry
and free from grease and dirt.
ii) Locate plaster key centrally over
lintel (refer to illustration above to
determine the position on lintel).
iii) Apply a 6mm bead of adhesive along
the full length of plaster key in
accordance with adhesive
manufactureres instructions.
Cavity Weep Vent type WV available in
terracotta, beige and grey
68
69
Type PKS87
Technical requirements
NHBC Standards 1995: Where fair faced
masonry is supported by lintels: weep
holes should be provided at maximum
450mm intervals. Each opening should
have at least two weep holes.
Material
BS Polypropylene in grey, beige and
terracotta to match mortar.
Important note
Cavity weep holes should be provided
over all lintels fitted with stop ends
Installation notes
i) Position in the perpendicular brick
directly above the lintel.
ii) Use a minimum of 2 per lintel at
450mm maximum centres.
Application
Suitable for use with Cougar lintels
(CG, CH, CX) timber frame lintels
(CTF5, CTF7, CTF9, CN23) and External
solid wall lintels (CN71 & CN81).
Installation
External plaster
key simply clips into place
and is secured using a full length of
adhesive bead (supplied by others).
Storage
Unless required
immediate use on site the
product should be stored in a
clean dry environment.
Installation notes
i) Ensure plaster key mounting surface
and under side of lintel is clean, dry
and free from grease and dirt.
ii) Locate plaster key centrally over
lintel (refer to illustration above to
determine the position on lintel).
iii) Apply a 6mm bead of adhesive along
the full length of plaster key in
accordance with adhesive
manufactureres instructions.
Cavity Weep Vent type WV available in
terracotta, beige and grey
68
69
Ensure a nominal
150mm end bearing
at each end.*
Ensure lintel is fully bedded
on bricklaying mortar.
Structural opening
or clear span.
Inner Leaf
Installation Guides
Catnic is committed to trouble free installation
Cavity
Do
Do not
Installation
71
73
74
Outer Leaf
Ensure that timber floor joists and roof trusses have a full
block depth between them and the lintel flange on Cougar
Open Back Lintels
Refer to the Catnic How to Install a Lintel Supporting
Concrete Floors or the Steel Lintel Manufacturers
Association guidelines (available on request) when using CH
& CX Open Back Lintels to support concrete floors
Consider the use of our soffit cladding for all coastal sites
(refer to page 65)
70
71
Ensure a nominal
150mm end bearing
at each end.*
Ensure lintel is fully bedded
on bricklaying mortar.
Structural opening
or clear span.
Inner Leaf
Installation Guides
Catnic is committed to trouble free installation
Cavity
Do
Do not
Installation
71
73
74
Outer Leaf
Ensure that timber floor joists and roof trusses have a full
block depth between them and the lintel flange on Cougar
Open Back Lintels
Refer to the Catnic How to Install a Lintel Supporting
Concrete Floors or the Steel Lintel Manufacturers
Association guidelines (available on request) when using CH
& CX Open Back Lintels to support concrete floors
Consider the use of our soffit cladding for all coastal sites
(refer to page 65)
70
71
i.e. one row of blocks should be raised on the inner leaf, then
three courses of brick on the outer leaf. Wall ties should then
be installed and another row of blocks on the inner leaf
followed by three courses of brick on the outer and so on.
This process ensures that the lintel flanges are equally loaded
and helps prevent rotation.
15
125
Concrete floor
Prop if necessary
Propping
When propping, a horizontal board
should be placed along the underside
of the lintel soffit, this will prevent any
point loading, which could cause
localised deformation of the lintel.
On small openings a single prop
should be placed centrally within the
openings and wedged into place.
The prop can be removed after the
wall ties are effective. The number of
props used should be increased for
larger openings.
Continuous
solid infill block
Lintel
72
73
i.e. one row of blocks should be raised on the inner leaf, then
three courses of brick on the outer leaf. Wall ties should then
be installed and another row of blocks on the inner leaf
followed by three courses of brick on the outer and so on.
This process ensures that the lintel flanges are equally loaded
and helps prevent rotation.
15
125
Concrete floor
Prop if necessary
Propping
When propping, a horizontal board
should be placed along the underside
of the lintel soffit, this will prevent any
point loading, which could cause
localised deformation of the lintel.
On small openings a single prop
should be placed centrally within the
openings and wedged into place.
The prop can be removed after the
wall ties are effective. The number of
props used should be increased for
larger openings.
Continuous
solid infill block
Lintel
72
73
300
max
600
max
600
max
300
max
Centre of lintel
Technical Specifications
& Quality Assurances
Lintel
Length (mm)
Up to 1800
1950-3000
3300-4200
4575-4800
Number
of clips
3
5
7
9
Lintel code
CTF5, 7 & 9
CTF5, 7 & 9
CN23
Length (mm)
750-3600
3900-4800
Up to 4800
74
Nail fixing
Specifications
Clearance
Clearance
Clip fixings
50mm x 3.35mm diam. Plain head galvanised nails
38mm x No10 RD/HD sherardised wood screws
38mm x No10 RD/HD sherardised wood screws
76
77
78
79
80
81
82
75
300
max
600
max
600
max
300
max
Centre of lintel
Technical Specifications
& Quality Assurances
Lintel
Length (mm)
Up to 1800
1950-3000
3300-4200
4575-4800
Number
of clips
3
5
7
9
Lintel code
CTF5, 7 & 9
CTF5, 7 & 9
CN23
Length (mm)
750-3600
3900-4800
Up to 4800
74
Nail fixing
Specifications
Clearance
Clearance
Clip fixings
50mm x 3.35mm diam. Plain head galvanised nails
38mm x No10 RD/HD sherardised wood screws
38mm x No10 RD/HD sherardised wood screws
76
77
78
79
80
81
82
75
Quality Assurance
Lerwick
Inverness
Aberdeen
Perth
Dundee
Stirling
Glasgow
Dunbar
Edinburgh
Ayr
Londonderry
Stranraer
Newcastle
Carlisle
Enniskillen
Belfast
Alston
Workington
Middlesborough
Dungannon
Darlington
Whitby
Ripon
York
Hebben Bridge
Bangor
Manchester
Chester
Bala
Stafford
Shrewsbury
Llanidloes
Doncaster
Sheffield
Macclesfield
Birmingham
Watchet
Taunton
Exeter Sidmouth
76
BSI Kitemark
BRITISH
S
TO
The Kitemark is a BSI
certification mark,
licensed for use on a
BS 5977
LICENCE No. KM07234
product after
independent testing has been carried
out to establish conformity with the
stated standard, and satisfactory
assessment of the manufacturing
control process has taken place to
establish that such conformity may
consistently be achieved.
Exposure
zones
Grimsby
Lincoln
Skegness
Approximate wind
driven rain
(litres/m2 per spell)
Nottingham
Leicester
Norwich
Peterborough
Llandrindod Wells
Cambridge
Northampton
Hay-on-Wye
Brecon
Colchester
Gloucester Luton
Swansea
Welwyn Garden City
Swindon
Newbury
London
Bristol
Cardiff
Staines
Weston-super-Mare
Barnstaple
Hull
Skelmersdale
Colwyn Bay
Aldershot
Gatwick
Southampton
Poole
Brighton
Dover
Eastbourne
1 (sheltered)
Less than 33
2 (moderate)
3 (severe)
4 (very severe)
100 or more
NDARD
TA
Domoch
CERTIFIED
Technical Conformity
Catnic comply with the technical
requirement of:
National House-Building Council
(NHBC):
is the independent
regulatory board
and the worlds
leading warranty and insurance
provider for new homes in the UK.
Housing Association Property
Mutual (HAPM):
with appropriate
adjustment
factors lintels are rated by HAPM as
satisfying the 35 years to first
maintenance durability rating, laid
down in the HAPM Component Life
Manual.
As an accredited organisation, we
are committed to making continuous
performance improvements in key
areas, such as business efficiency
and risk management, reviewing
procedures and levels of service.
Reduce waste
77
Quality Assurance
Lerwick
Inverness
Aberdeen
Perth
Dundee
Stirling
Glasgow
Dunbar
Edinburgh
Ayr
Londonderry
Stranraer
Newcastle
Carlisle
Enniskillen
Belfast
Alston
Workington
Middlesborough
Dungannon
Darlington
Whitby
Ripon
York
Hebben Bridge
Bangor
Manchester
Chester
Bala
Stafford
Shrewsbury
Llanidloes
Doncaster
Sheffield
Macclesfield
Birmingham
Watchet
Taunton
Exeter Sidmouth
76
BSI Kitemark
BRITISH
S
TO
The Kitemark is a BSI
certification mark,
licensed for use on a
BS 5977
LICENCE No. KM07234
product after
independent testing has been carried
out to establish conformity with the
stated standard, and satisfactory
assessment of the manufacturing
control process has taken place to
establish that such conformity may
consistently be achieved.
Exposure
zones
Grimsby
Lincoln
Skegness
Approximate wind
driven rain
(litres/m2 per spell)
Nottingham
Leicester
Norwich
Peterborough
Llandrindod Wells
Cambridge
Northampton
Hay-on-Wye
Brecon
Colchester
Gloucester Luton
Swansea
Welwyn Garden City
Swindon
Newbury
London
Bristol
Cardiff
Staines
Weston-super-Mare
Barnstaple
Hull
Skelmersdale
Colwyn Bay
Aldershot
Gatwick
Southampton
Poole
Brighton
Dover
Eastbourne
1 (sheltered)
Less than 33
2 (moderate)
3 (severe)
4 (very severe)
100 or more
NDARD
TA
Domoch
CERTIFIED
Technical Conformity
Catnic comply with the technical
requirement of:
National House-Building Council
(NHBC):
is the independent
regulatory board
and the worlds
leading warranty and insurance
provider for new homes in the UK.
Housing Association Property
Mutual (HAPM):
with appropriate
adjustment
factors lintels are rated by HAPM as
satisfying the 35 years to first
maintenance durability rating, laid
down in the HAPM Component Life
Manual.
As an accredited organisation, we
are committed to making continuous
performance improvements in key
areas, such as business efficiency
and risk management, reviewing
procedures and levels of service.
Reduce waste
77
Technical Information
The Research, Development and Technology
business of Corus combines top class innovation
and cutting edge technology to deliver metals
solutions in a constantly changing world
We use up to the minute technology to expand and improve
the quality of our performance; we continually invest in and
upgrade our manufacturing processes and use the latest
methods in process analysis and design
Structural performance
The structural data published in the
loading tables included in this technical
guide, was achieved in accordance with
the requirements of BS 5977: Part
2:1983 and BS EN 845-2.2003.
Extensive testing was undertaken at the
following test houses:
The University of Wales,
School of Engineering
The University of Glamorgan,
Construction Centre
Ceram Building Technology,
Stoke-on-Trent
Safe working loads (SWL)*, as defined by
BS 5977: Part 2:1983 for cavity wall
lintels refer to uniform distributed loads
applied in the inner to outer leaf ratios:
1:1 For lintels supporting masonry
only
3:1 For lintels normally carrying timber
floors
5:1 For lintels normally carrying
concrete floors
The CH & CX lintel range refers to
uniformly distributed loads in the ratio of
19:1 when non standard or unusual
loading conditions occur.
A lintel should not exceed a maximum
vertical deflection of 0.003 x the effective
span (effective span = distance between
centre of bearings) when subjected to the
safe working load (SWL).
78
The Environment
We consider care for the environment to be essential
both in terms of our duty to society and to ensure the
continuity of our business
effective span
325
or
ultimate failure
1.6 (min)
Fire tests
Catnic lintels have been independently
tested in accordance with the relevant
parts of BS476, Methods of Determination
of the Fire Resistance of Loadbearing
Elements of Construction. Details of the
test results can be found in TRADA
(Timber Research and Development
Association) Nos. FR254, 275, 659, 863,
1662 and RF94015 and FROSI (Fire
Research Organisation) No. 5001.
Thermal performance
All Catnic cavity wall lintels contribute to
the thermal integrity of the building as
they are supplied with an insulated core.
The core of the Cougar Open Back style
lintels is fully filled with CFC & HCFC free
insulation to prevent cold voids.
Also, because Catnic cavity wall lintels
are shaped to form a built-in damp proof
course, partial fill cavity wall insulation
can extend down to the top of the lintel.
This means that the cold voids normally
associated with separate damp proof
courses are avoided, without the need
to install specially shaped insulation
batts behind the DPC.
Environmental Policy
Catnic are committed to protecting the environment by minimising the impact of our
operations and our products through the adoption of sustainable practices and through
continuous improvement in environmental performance and control. We believe that respect
for the environment is critical to the success of our business and our aim, therefore, is to
continuously improve our performance
Sustainability
Catnic, part of the Corus group of
companies, utilises steel from our
European manufacturing operations that
have achieved certification to
Environmental Management Standard
ISO14001.
Corus places great emphasis on the
contribution we make to a sustainable
society and is committed to
incorporating the principles of
sustainable development into all
aspects of our operations.
Steel itself is 100% recyclable and can
be recycled again and again, without
degradation of its properties or
performance. Steels excellent
mechanical properties, combined with
its high strength, contribute to improved
safety performance. The steel in use
today will be reused and recycled many
times in the future. More than 40% of
the worlds production of new steel is
in fact made from recycled steel without
any loss of quality. The current recycling
rate and reuse rate for steel
construction products in the UK is 94%.
Our products are durable, adaptable,
reusable and recyclable. They are
79
Technical Information
The Research, Development and Technology
business of Corus combines top class innovation
and cutting edge technology to deliver metals
solutions in a constantly changing world
We use up to the minute technology to expand and improve
the quality of our performance; we continually invest in and
upgrade our manufacturing processes and use the latest
methods in process analysis and design
Structural performance
The structural data published in the
loading tables included in this technical
guide, was achieved in accordance with
the requirements of BS 5977: Part
2:1983 and BS EN 845-2.2003.
Extensive testing was undertaken at the
following test houses:
The University of Wales,
School of Engineering
The University of Glamorgan,
Construction Centre
Ceram Building Technology,
Stoke-on-Trent
Safe working loads (SWL)*, as defined by
BS 5977: Part 2:1983 for cavity wall
lintels refer to uniform distributed loads
applied in the inner to outer leaf ratios:
1:1 For lintels supporting masonry
only
3:1 For lintels normally carrying timber
floors
5:1 For lintels normally carrying
concrete floors
The CH & CX lintel range refers to
uniformly distributed loads in the ratio of
19:1 when non standard or unusual
loading conditions occur.
A lintel should not exceed a maximum
vertical deflection of 0.003 x the effective
span (effective span = distance between
centre of bearings) when subjected to the
safe working load (SWL).
78
The Environment
We consider care for the environment to be essential
both in terms of our duty to society and to ensure the
continuity of our business
effective span
325
or
ultimate failure
1.6 (min)
Fire tests
Catnic lintels have been independently
tested in accordance with the relevant
parts of BS476, Methods of Determination
of the Fire Resistance of Loadbearing
Elements of Construction. Details of the
test results can be found in TRADA
(Timber Research and Development
Association) Nos. FR254, 275, 659, 863,
1662 and RF94015 and FROSI (Fire
Research Organisation) No. 5001.
Thermal performance
All Catnic cavity wall lintels contribute to
the thermal integrity of the building as
they are supplied with an insulated core.
The core of the Cougar Open Back style
lintels is fully filled with CFC & HCFC free
insulation to prevent cold voids.
Also, because Catnic cavity wall lintels
are shaped to form a built-in damp proof
course, partial fill cavity wall insulation
can extend down to the top of the lintel.
This means that the cold voids normally
associated with separate damp proof
courses are avoided, without the need
to install specially shaped insulation
batts behind the DPC.
Environmental Policy
Catnic are committed to protecting the environment by minimising the impact of our
operations and our products through the adoption of sustainable practices and through
continuous improvement in environmental performance and control. We believe that respect
for the environment is critical to the success of our business and our aim, therefore, is to
continuously improve our performance
Sustainability
Catnic, part of the Corus group of
companies, utilises steel from our
European manufacturing operations that
have achieved certification to
Environmental Management Standard
ISO14001.
Corus places great emphasis on the
contribution we make to a sustainable
society and is committed to
incorporating the principles of
sustainable development into all
aspects of our operations.
Steel itself is 100% recyclable and can
be recycled again and again, without
degradation of its properties or
performance. Steels excellent
mechanical properties, combined with
its high strength, contribute to improved
safety performance. The steel in use
today will be reused and recycled many
times in the future. More than 40% of
the worlds production of new steel is
in fact made from recycled steel without
any loss of quality. The current recycling
rate and reuse rate for steel
construction products in the UK is 94%.
Our products are durable, adaptable,
reusable and recyclable. They are
79
Application
Do not use damaged goods.
Refer to Installation Guides detailed
on page 70.
Disposal
When disposing of any Catnic
products or packaging, due
consideration must be given to the
environmental impact of the method
of disposal.
Material Specification
Control of Substances
Hazardous to Health
Regulations 1994 (COSHH)
All products are considered nonhazardous to health under normal
conditions of use.
Copies of COSHH sheets are
available on request
80
CNZ range
The lintels are manufactured from
galvanised steel to BS EN 10326:
2004 (continuously hot-dip coated
strip and sheet of structural steels technical delivery conditions) of grade
S250GD & Z600. All external lintel cut
edges are treated with a corrosion
resistant paint.
Stainless Steel range
The lintels are manufactured from
Austenitic Stainless Steel, grade
304s15 to BS EN 10088-2-1.4301.
Feature Lintels
CCA and CCB range
The lintels are manufactured from
3.0mm structural grade steel plate of
grade S275 to BS EN10025-2:2004
and hot-dip galvanised after
manufacture to BS EN ISO1461:1999.
CXL range
The lintels are manufactured from a
universal beam section and 6.0mm
structural grade steel plate Grade
S275 to BS EN 10025-2:2004 and
hot-dip galvanised after manufacture
to BS EN ISO1461:1999.
81
Application
Do not use damaged goods.
Refer to Installation Guides detailed
on page 70.
Disposal
When disposing of any Catnic
products or packaging, due
consideration must be given to the
environmental impact of the method
of disposal.
Material Specification
Control of Substances
Hazardous to Health
Regulations 1994 (COSHH)
All products are considered nonhazardous to health under normal
conditions of use.
Copies of COSHH sheets are
available on request
80
CNZ range
The lintels are manufactured from
galvanised steel to BS EN 10326:
2004 (continuously hot-dip coated
strip and sheet of structural steels technical delivery conditions) of grade
S250GD & Z600. All external lintel cut
edges are treated with a corrosion
resistant paint.
Stainless Steel range
The lintels are manufactured from
Austenitic Stainless Steel, grade
304s15 to BS EN 10088-2-1.4301.
Feature Lintels
CCA and CCB range
The lintels are manufactured from
3.0mm structural grade steel plate of
grade S275 to BS EN10025-2:2004
and hot-dip galvanised after
manufacture to BS EN ISO1461:1999.
CXL range
The lintels are manufactured from a
universal beam section and 6.0mm
structural grade steel plate Grade
S275 to BS EN 10025-2:2004 and
hot-dip galvanised after manufacture
to BS EN ISO1461:1999.
81
Point load
The load applied from a single member
such as a steel beam or girder truss. It
should be spread over an appropriate
area so that the limiting design values
are not exceeded.
Catnic endeavor to return enquiries at the soonest opportunity. If your enquiry is urgent please contact Technical
Services on 029 2033 7900.
Please ensure that the essential information (indicated in red) is provided, to enable a quick turnaround.
Please return on Fax: 087 0024 1809
* Mandatory Fields
Customer
Date
Name*
Customer
Site
Address*
Address
End bearing
The bearing length at lintel supports.
Post Code*
Tel*
Post Code
Tel
Email*
Fax
Fax
Internals
Meter Boxes
Replace Steelwork
Lintel Requirements*
Special
Wall Construction
OUTER
CAVITY
Width
(mm)
Type
INNER
Width Between
Type
Masonry inc. insulation
Brick
Brick
Stone
Dense block
Dense block
Lightweight block
Lightweight block
Medium block
Medium block
Timber frame
Width
(mm)
Steel frame
Is a separate damp proof course to be installed?
Yes
No
Yes
No
Special Requirements
(please tick)
Plans/dimensions
Elevations (all)
Sections (all)
Technical Services
Point load
The load applied from a single member
such as a steel beam or girder truss. It
should be spread over an appropriate
area so that the limiting design values
are not exceeded.
Catnic endeavor to return enquiries at the soonest opportunity. If your enquiry is urgent please contact Technical
Services on 029 2033 7900.
Please ensure that the essential information (indicated in red) is provided, to enable a quick turnaround.
Please return on Fax: 087 0024 1809
* Mandatory Fields
Customer
Date
Name*
Customer
Site
Address*
Address
End bearing
The bearing length at lintel supports.
Post Code*
Tel*
Post Code
Tel
Email*
Fax
Fax
Internals
Meter Boxes
Replace Steelwork
Lintel Requirements*
Special
Wall Construction
OUTER
CAVITY
Width
(mm)
Type
INNER
Width Between
Type
Masonry inc. insulation
Brick
Brick
Stone
Dense block
Dense block
Lightweight block
Lightweight block
Medium block
Medium block
Timber frame
Width
(mm)
Steel frame
Is a separate damp proof course to be installed?
Yes
No
Yes
No
Special Requirements
(please tick)
Plans/dimensions
Elevations (all)
Sections (all)
Technical Services
Notes
84
Lintels
Pioneers of the steel lintel for more
than three generations with a
reputation for superior quality,
reliability and backed by excellence
in service.
Steel Lintels
Special Lintels
Stainless Steel Lintels
Free design service for bespoke feature lintels
Free scheduling service
Expanded Metal
Easy to use, versatile and perfectly
formed expanded metal products
benefit from our long experience of
using steel in construction.
Metal Lath
Coil Mesh
Arch formers
Wall Starter Kits
STRONGHOLD Wall Starter Kits
are a simple yet effective system
for tying new masonry walls to
existing walls.
Steelwork
A selection of steelwork beams,
columns and channels for when
loading conditions exceed our
standard range of lintels
Universal beams
Universal columns
Parallel flange channels
Steel Plasterers Beads
Precision engineered and simple to
use to create, edges, corners and
joints that are resistant to chipping,
cracking and impact damage.
Galvanised steel plaster
and render beads
Stainless steel plaster
and render beads
PVC-U Plasterers Beads
Light, rigid, non-corrosive, and
easy to use material, that offers
a cost-effective way to create,
edges, corners and joints that
are resistant to chipping,
cracking and impact damage.
Plaster and render beads
Uniclass
L325:P4142
Cl/Sfb
EPIC
F631:X442
(31.9)
Hh2
December 2008
Catnic
www.catnic.com
Catnic
Pontypandy Industrial Estate
Caerphilly
CF83 3GL
Telephone 029 2033 7900
Facsimile 029 2086 7796
87
87
C03:30000:UK:11/2008
87
PDA8753/05