Professional Documents
Culture Documents
Leo Niekamp'(Member)
Abstract
An iterative process of computing harmonic voltage profile on a
power system transmission network is presented. A method
based upon the frequency domain analysis is utilised in
conjunction with the fundamental load flow computations. The
concept of conventional reactive power and the distortion power
are incorporated in order to determine interaction between the
power system and harmonic generating sources. The model of
the transmission system considered lends itself to the
determination of the standing wave pattern and can be used in
identifying the points of maxima and minima on the transmission
line besides the two end points. A phase shifting model of
transformer is presented for the harmonic analysis. Three
examples of power transmission systems are taken to illustrate use
of the algorithm. Included in the example test cases are a five
bus example system reported by Heydt[11, IEEE-RBTS[2]
reported by Billinton et al. and a reduced six bus power
transmission system of SaskPower [3].
1699
Bus admittance matrix so formed will take care of the phase shift
at each harmonic frequency. Harmonic currents injected due to
the magnetising demand are considered as current sources shown
in Figure 1.
.P
q,
e =
hc Eki?in(kWt+CXk).
(1)
k=l
n
i =
IkSin(kWt+CXk-dk).
(2)
1- --1
k=l
n
P = CEkIkCos(dk).
(3)
Figure 1:
k=l
n
S2 =
EiCIj.
k=l
S2 =
fl +
(4)
j=l
Q2
D2.
(5)
1700
only and one pi model is sufficient for the whole line. In order
to obtain voltage profile and still keep the accuracy of the model,
it is decided to represent the transmission line by a number of
cascaded equivalent pi networks. To keep the order of the
system to a reasonable value, it was arbitrarily decided to create
half as many cascaded equivalent pi model as the harmonic order.
Therefore, there is one equivalent pi model for lst, and 2nd
harmonic order; two for 3rd and 4th harmonic order; three for
5th and 6th harmonic order and so on.
Foregoing discussion on the model of the transmission line is
valid only for the balanced condition. Balanced condition exists
particularly in the transmission system due to balanced loading
and symmetrical transposition of the transmission line. However,
at high frequencies, assumption of balanced condition may not
hold true if the length of one transposed cycle is smaller than the
smallest wavelength[l6] of interest. For example, if the speed of
light is taken as a limiting velocity on the transmission line, then
a balanced model of the transmission line can be used to study
frequencies up to 30 KHz if the transposed length is 10 kilometre
or less and up to 15 KHz if transposed length is 20 kilometre or
less and so on.
L - - s \ w
V2/P,
Figure 2:
2.4.
1
-
3. Algorithm
For harmonic analysis of the system, the methodology chosen is
based upon the non-linear frequency domain analysis[20]. Given
an initial estimate of the current waveform of the converter, the
harmonic bus voltages are determined from the system
admittance matrix equation, i.e. [I] = [Y][V]. A new estimate of
the current waveform of the converter is obtained from the new
bus voltages including the harmonic voltages. This cycle is
repeated until convergence in the magnitude of the harmonic
voltages on all nodes in the power system is obtained. The
convergence criterion is the change in harmonic bus voltages
with each step of calculation. Each frequency is dealt with
independently, since the delay angle of the converter is assumed
to be fiied during the computation cycle.
1701
--
6:
0.4
Q-B-e--e--R-43-3
-0.2
.cl
68
--.-
.-.-+b-.----.-m
Bus 4
BUS 5
-1
0.2
\.,;l.OSO&
Bus 2
LL
PU
BUS A
'12.45 kV
kV XOMISAL
. I I,.o
+ j.01
IZ.QQ%
x
,E9 kV/25 kV
I +-
Figure 4:
0.-
5>
(BUS 3)
0.a
0.001
I-
Y
$
o.o(u
0.M
O.lI01
O.OO0
0.0
0.2
u.4
0.0
0.)
1.u
1.a
RECTIFIER
P=25
MW
Bus No.
Fundamental
voltage.
Figure 3:
1
2
3
4
5
(-i P.u.)
Computed Results
20 MW, 20 WAR
0.8
06
am
Figure 5:
+ j.0:
0.4
The single line diagram of the five bus power system is shown in
Figure 3. The ac/dc converter at bus 4 of the system is a line
commutated converter operating at a delay angle of 22.5 degrees.
Buses 3, 4, and 5 have capacitor compensation for power factor
correction.
Bus 3
X'= 0.0001
= -11.0 p. U.
1-
Table 1:
105.0
106.88
110.38
108.88
131.88
Fifth
Fundamental
harmonic
voltage.
voltage.
0.006
0.383
0.625
0.762
0.197
105.00
106.81
110.43
109.05
131.95
Fifth
harmonic
voltage.
0.0057
0.3787
0.6182
0.7617
0.1946
In f i f t h
harmonic
voltage.
5
1
1
1
1
1702
2 x 4 0 UW
1x20
uw
1x10
nw
UllS 3
DUS 5
( 2 0 UWI
BUS 6
(20
nw1
Iterative method
Bus No.
Fifth harmonic
voltage
Fifth harmonic
voltage
1
2
3
4
0.003
0.224
0.365
0.444
0.115
0.006
0.383
0.625
0.762
0.1946
1703
Legend
Bus 1
U
Bus 2
Bus 3
0 B
15
20
'
'
25
' I
'
'
'
' I
Bus 5
Bus 6
' '
'
35
30
'
Line
No.
40
Figure 7:
Line
Name
1
2
3
4
5
6
Line
Length
BZR
B3R
ClW
P2C
R4C
QlW
P o s i t i v e Sequence
Impedance (per u n i t )
(U)
182.8
182.8
158.5
174.4
21.4
104.6
0.0210
0.0210
0.0172
0.0151
0.0023
0.0913
X
0.1212
0.1212
0.1428
0.1134
0.0181
0.2851
B
0.4506
0.4506
0.2909
0.437
0.0362
0.0585
Bus No.
Bus 2
Bus 3
Bus 4
1-1
Bus 5
Generator
No.
Connected
Bus Name
ED
1
2
3
Negative Sequence
Impedance (per u n i t )
R
X
0.000603
0.000897
0.002160
PR
QE
0.037343
0.054236
0.096514
0.985
15
25
20
30
35
40
Load
No.
1
2
3
4
5
6
Connected
Bus Name
Lord i n per u n i t
Real
Reactive
ED
PR
PE
0.798
0.250
2.709
0.608
0.419
2.65
CON
WOL
RG
0.177
0.100
0.680
0.0545
0.075
0.54
__
-egend
.-0
E a
Line 1-2
Line 1-3
i4
Line 4-2
In
'
'
"
20
'
"
'
'
40
"
'
60
'
'
'
'
"1
80
100
P2C(4)
1704
5. Conclusion
2.53
Legend
'[
.,,
, ,
.,
.c
Wolverine (WOL)
I
f
n 0
-,
Regina (RG)
12
16
20
(OE]
Condie (CON)
28
24
2 2.6,
10
I
I
2.2
Q)
ST 1.8
Legend
t
0
' 1.4
.-0
c
P
I Line
BD-RC
Line CON-RC
Line CON-WC
1
0
Line CON-PR
A Line OE-WO\
s0
In
.
0
20
2
40
1
60
,
80
100
1705
15.
16.
17.
18.
19.
20.
6. References
1
2.
3.
4.
5.
6.
7.
9.
10.
11.
12.
13.
14.
1706
Discussion
Y. Baghzouz (University of Nevada, Las Vegas, NV): The authors are to
be commended for their contribution in the area of harmonic penetration
studies. They presented an algorithm based on what is referred to as the
extended current injection method which was introduced in Ref. [lo].
Comments on the items that follows will be greatly appreciated.
The algorithm of Ref. [lo] is numerically stable and converges very
rapidly (within 4 or 5 iterations); however, the results may not be very
accurate since it does not check the energy balance at the converter
terminals as pointed out by the authors. It would be interesting to compare
(through an example) the quality of the results and the computational effort
of the extended current injection method and the algorithm presented by
the authors.
When modeling network elements, it was pointed out that the transformer model presented in [13] was used. However, this reference concludes that there is no generalized formula for the frequency variation of
the shunt elements. Furthermore, the fundamental-frequency shunt
impedance and harmonic currents caused by core nonlinearity vary with
the transformer voltage. It is not clear how these factors are taken into
account in the harmonic penetration program reported generalized.
In order to determine the points of maximum heating and insulation
stress along transmission lines, the authors used a number of cascaded
*-networks that is equal to half of the harmonic order. Such a model may
result in unacceptable computation time, especially when higher frequency
harmonics are considered in the analysis. Efficient algorithms are available
for computing maximum rms currents and peak voltages along transmission lines under both balanced [A] and unbalanced [B] conditions. These
algorithms require only the knowledge of the harmonic voltages and
currents at the receiving end of the line.
Finally, it is not clear how the authors defined the voltage distortion
factor. It appears that they defined this quantity as unity minus the
commonly used definition of distortion factor, i.e.,
2.
where V , and V,, are the rms fundamental and n-th harmonic voltages.
The above definition, however, does not conform with the vertical scale of
Fig. 8.
References
[A] Y. Baghzouz and 0. T. Tan, Computation of Maximum RMS
[B]
Current and Peak Voltage on Transmission Lines Under Nonsinusoidal Conditions, IEEE Transactions on Power Delivery, Vol.
PWRD-1, NO. 3, July, 1986, pp. 266-72.
Y . Baghzouz and 0. T. Tan, Maximum Heating and Insulation
Stress on Untransposed Transmission Lines with Unbalanced Harmonic Distortion, IEEE Transactions on Power Delivery, Vol.
PWRD-2, No. 1, Jan., 1987, 256-61.
DFv
vl/J(
... v,>
= 1,2,
For the test reported in section 4.2.1, the 5th, 7th, llth,
and 13th harmonic voltages at Bus 2 are 0.070, 0.0340,
0.030, 0.024 per unit respectively for a converter load of
16.5 MW. With fundamental voltage of 1 per unit at
Bus 2, the voltage distortion factor is 0.9963 as shown in
Figure 8.
Finally we would like to draw attention of the reader to a
typographical mistake. Table 1 gives the results computed by
the authors and documented results presented in reference [l],
[[7] and [SI instead of [l], [3] and [SI as reported in the paper.
Manuscript received J u l y 2, 1991