HEAD CALCULATION FOR IRRIGATION BOOSTER PUMP

PROJECT

ROVE HOTEL AL JAFILIYA

Consultant
ARCHGROUP
HEAD CALCULATION FOR IRRIGATION
BOOSTER PUMP

Project

ROVE HOTEL
Main Contractor
M/S- SHAPOORJI PALOONJI
MIDEAST LLC.

Landscape & Irrigation contractor


AL SAYYAR TECHNICAL SERVICES

HEAD CALCULATION FOR IRRIGATION BOOSTER PUMP

IRRIGATION VALVE OPERATION SCHEDULE (PEAK REQUIREMENT)

Station
No.

1
2

Valve

DV - 1
DV -2

Size of
Valve
1"
1"

Controller's
Program
A
A

flow in
lps

Duration
(min)

0.72
0.05

60
60

Total flow
as
per
specified
duration
(litres/day)

2592
180
2772

Total run time 2 hrs


Total Water Requirement 2.6 m3/day
Maximum flow of the system: 2.6 m3 per hour (Considering water
window of 1 hr/day)

Head Loss Calculations


1. Head Loss Calculation in Main Line
Head loss of the Total Main Line Length to a Valve can be taken as Main Line
Loss for Total Head Loss Calculation.
The length of Main Line to a Valve (DV2) = m
Sl.No

Main Line

Length
in m

1
2

A -B
B C

59
8

Flow in the
Section, in lps

0.05
0.05
Total Loss

Size of the
Pipe
1.5
1.5

Head Loss in
(Mtr) from Pipe
Characteristic
Sheet
0.01
0.005
0.011

(Note; friction loss is calculated as per the DarcyWeisbach equation formula uPVC
pipe Class E)

Project

ROVE HOTEL
Main Contractor
M/S- SHAPOORJI PALOONJI
MIDEAST LLC.

Landscape & Irrigation contractor


AL SAYYAR TECHNICAL SERVICES

HEAD CALCULATION FOR IRRIGATION BOOSTER PUMP

2. Head Loss Calculation in Solenoid Valve


Head loss of the Highest Elevation end point Flow under a Valve can be taken as
Solenoid Valve Loss for Total Head Loss Calculation.
The Maximum Flow of Solenoid Valve (DV2) = 0.05 lps
Sl.No

Solenoid Valve

Flow in the
Section, in lps

Size of Valve

Head Loss in (Mtr)


from Valve
Characteristic Sheet

DV02

0.05

0.138

The length of lateral Line of Valve (DV 02) = m


Sl.No

Lateral Line

1
2
3

a b
bc
cd

Length
in m

Flow in the
Section, in lps

46
0.05
7.40
0.05
25
0.05
Total Loss

Size of the
Pipe
1
1
1

Head Loss in
(Mtr) from Pipe
Characteristic
Sheet
0.05
0.012
0.032
0.094

(Note; friction loss is calculated as per the DarcyWeisbach equation formula uPVC
pipe Class E)
3. Total Head Requirement of The IRRIGATION SYSTEM

Head Loss due to Elevation difference from the Pump Room to irrigation
System = 10.95 m.
Head loss due to Pump Room Fittings can be considered as 5.0 m.
Maximum Head Loss due to Pipe Fittings (Main line & Lateral lines) can be
considered as 3.0 m.

Project

ROVE HOTEL
Main Contractor
M/S- SHAPOORJI PALOONJI
MIDEAST LLC.

Landscape & Irrigation contractor


AL SAYYAR TECHNICAL SERVICES

HEAD CALCULATION FOR IRRIGATION BOOSTER PUMP

Total Head Loss Calculation:


Sl.N
o
1

Item Description

Head Loss

Minimum Required operating Pressure for Drip


Irrigation System
2
Head Loss in Main Line
3
Head Loss in Lateral Line
4
Head Loss in Solenoid Valve
5
Head Loss Due to the Fittings of Pump Room
6
Head Loss Due to Screen filter
7
Head Loss Due to Elevation Difference
8
Head Loss due to fittings in main line
Total Head Loss
Safety Factor @ 10%
Head Required for the Pump
Flow of the system - 2.6 m3/hr
15% safety factor - 0.39 m3/hr
Flow of pump -2.99m3/hr
The duty point of the pump should be 2.99 m3/hr @ 48 m head.

20.0 m
0.011 m
0.094 m
0.14 m
5.00 m
2.00 m
10.95 m
3.00 m
41.19 m
6.17 m
47.36 m