Micafil Transformer Bushings

AirRIP/RTKF 24 550 kV

Micafil RIP bushings

Micafil brand products combine functionality, high performance


and long service life. The optimized solutions are based on
our long-term, trustworthy partnerships with customers and our
understanding of their needs. With proven components and a
variety of designs, our new AirRIP series meets customer-specific
requirements. To date, our factory in Zurich Altstetten has
delivered more than 600000 bushings. The worlds leading
transformer manufacturers and electric power utilities rely on us.
With the new Micafil AirRIP series, we will continue to live up to
our reputation.

Page
Todays technology for tomorrow

The AirRIP bushing in detail

Choice of insulator

Choice of current conductor

General information

Ordering information
AirRIP overview

9
10

AirRIP bushings 24 170 kV


Data for types with cable conductor

11

Data for types with rod conductor

15

Data for types with fixed conductor

19

AirRIP bushings 245 550 kV


Data for types with cable conductor

23

Data for types with rod conductor

27

Data for types with fixed conductor

31

Other Micafil RIP bushings

35

Todays technology for tomorrow

The AirRIP bushing in detail


 c2

Micafils AirRIP outdoor transformer bushings are the product


of a sophisticated design using a small number of components:
insulating body, main flange, insulator shell and current
c onductor. They are produced in a wide variety of d
esigns
and thus can easily fulfil specific customer requirements.
A irRIP bushings are completely dry, pressurized, explosionproof, fire-resistant and allow high application temperatures.

Outer insulation

Current conductor terminal


with de-aeration of central tube

For decades, porcelain has proved its worth as a material for


outer insulation. With the development of composite hollow
insulators in recent decades an alternative has gained market
maturity. Our customers appreciate the benefits these offer,
such as reduced weight, easier handling, and the explosion
safety characteristics of these silicone composite insulators.
We offer the AirRIP bushings both with silicone composite
insulators as well as with porcelain insulators.

Head with clamp for conductor

Dry lling MICAGEL


RIP insulating body
with capacitor control and central tube

RIP insulation
Capacitor bushings enable control of electric field distribution
in radial and axial directions by inserting conductive layers
in the insulator body. The insulating body of the Micafil RIP
(Resin Impregnated Paper) s ystem consists of wound strips
of crepe paper. Aluminium foils of graduated lengths are
wrapped at exactly calculated points.
The wrap is heated, vacuum dried, as well as impregnated
and cured under vacuum with an epoxy resin formulated by
ABB. The impregnation process requires high skills in setting
and in the control of process parameters, as well as a broad
knowledge and experience in the field of materials science
and in materials selection.
We have developed our expertise over decades and gained
market experience as first-class supplier. The result is RIP
bushings with very good thermal and chemical resistance
and high mechanical strength and stiffness.

AirRIP stands for quality and versatility


High-voltage bushings must meet the highest standards of
operational safety and minimize the risk of damage for people
and facilities. The greatly increased and growing environmental awareness requires gentle production and clean operation.
The Micafil AirRIP series meets these requirements thanks to
high-quality materials and reliable processing techniques. The
technical standard is very high and development and manufacturing processes are regularly reviewed. High product quality is ensured with comprehensive testing during production
and in the electrical testing laboratory.

Advantages of Micafil AirRIP technology

Dry bushings
In line with our product philosophy of compact design and dry
bushing, the space between the insulating body and insulator
is filled with the time-tested dry filler MICAGEL. MICAGEL is
poured in a liquid form into the bushing and after curing forms
a compressible dry filling.

4 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

Partial discharge free up to double service voltage


High temperature resistance (class E, 120C)
Low dielectric losses (tan < 0.35%)
High flexural strength, heavy load
according to IEC 60137 (2008)
Completely dry bushing, i.e., no oil spills, no explosion risk
No maintenance or constant monitoring necessary
Transport and storage is possible in all positions
Flexible design allows for adaptation to different customer
needs and transformer requirements

Porcelain or silicon composite insulator

Flange with test tap


and transformer de-aeration (DA)
DA

Tap
Bolted ange plate

Sub-section extension for current


transformers

Oil side shield

The bushing in principle


(for example: bushing for cable conductor)

Insulating body
The core of the AirRIP bushing is the insulating body of RIP
with capacitor inserts for electric field control. The production of RIP is based on time-tested and proven technology.
Complex production processes compress the material into
a compact, liquid and gas-tight insulating body, which complies with current partial discharge and temperature requirements.
To accommodate current transformers, the lower body part
can be extended in steps of 100 mm up to 600 mm. The
short oil side is consistent with our proven and balanced
dimensioning and optimizes the strength of the interface
between the insulating body and transformer oil. These
dimensions also guarantee a high level of interchangeability
with older bushing types.

Flange and insulator


The insulator is the supporting part of the bushing and takes
over the mechanical loads with the two integrated fittings,
head and flange. The flange not only holds the insulating
body, it also forms the lower fitting of the insulator. The connection to the transformer takes place via the flange plate
bolted to the flange.
With a multiple O-ring system, the transition between body
and flange is oil-and gas-tight. The aluminium alloy used for
this purpose is corrosion-resistant and mechanically robust.
This ensures safe control of the bending moments in occurring operating stresses or in bending test loads. The whole
series is designed and type-tested in accordance with the
highest bending load class of IEC 60137 (2008).
The standard flange plate bolt circles conform to currently
common dimensions. Deviations can easily be executed as
variants. The flange is equipped with a test tap and has an
opening (M12) with a closure screw that can be used to deaerate the transformer or as connector for a Buchholz relay.
Also mounted on the flange: identification tag, connection
thread M12 for the flange earthing and, with larger bushings,
eyebolts for lifting purposes.
The head of the bushing closes the bushing and carries the
current conductor fixing. The 420 kV and 550 kV bushings
have a separate shield to avoid external corona discharges.

Oil side end


The shape of the opening ensures that no shield electrodes
are required up to 73 kV. We offer shielding as a v ariant.
From 123 kV, depending on current conductor version,
either fixed shields (cable conductors) or removable shields
(rod conductor and fixed conductor) are used, which are
attached to the end of the bushing. They prevent the excessive use of transformer oil and facilitate the assembly of the
conductor insulation beneath the bushing.
Our shield electrodes are dimensioned using modern methods
and their surface is provided as standard with a high-quality
solid insulation layer.
Please note our installation recommendations.

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV5

Choice of current conductor

Choice of insulator

The choice of insulator type has no influence on the performance of the bushing.
Please note corresponding weights as well as head and shed
diameters for each insulator type.

Silicone composite insulators made of glass fibrereinforced tube with helical or straight sheds
Hydrophobicity and the ability to transfer these properties
also to foreign layers is the most important value-added
feature of these insulators. They have many advantages:
Excellent contamination behaviour due to hydrophobic
surface properties and low leakage currents
Improved safety for personnel and equipment
Lower weight
The helical shed is the outcome of intensive development
efforts of ABB. Outstanding results in tough long-term pollution tests have proven their quality (certificates on request).
Insulators with conventional straight sheds complement our
product range.

Porcelain insulators made of high-quality


electrical porcelain, brown and grey
High-quality electrical porcelain for decades an excellent,
proven material is available as always in the standard
colour brown and alternatively in light grey.

Creepage distances
All types of insulation are made with alternate shed profiles.
Creepage distances are measured for the high pollution
requirements of IEC 60 815:
Bushings Ur

class

SCD 1

USCD 2

up to 420 kV

very heavy

31 mm/kV

53.7 mm/kV

550 kV

heavy

25 mm/kV

43.3 mm/kV

1 SCD: speci c creepage distance


2 USCD: uni ed speci c creepage distance

These long creepage distances ensure optimum dielectric


strength even under extreme environmental conditions.

The rated current is the starting point for choosing the type
of conductor.
However, current levels of conductor types partially overlap
and can be selected according to individual preferences.
Please follow the respective icons when making your choice.

Low currents with cable conductor


The current is led through a multi-stranded
flexible conductor joined to the terminal of
the winding. The lead is drawn up through
the central tube of the bushing and provided
with the top connector (cable bolt) that is
fastened to the bushing head. In the standard model, the air
side terminal is a round, bare copper bolt. As an option, the
surfaces can be silver- or nickel-plated and other terminal
sizes can be selected. To avoid unnecessary contact junctions, the draw lead bolt is of a single-piece design. A triedand-tested fixing device with few parts ensures that no inadvertent displacement in axial direction or twisting is possible.
It also allows the positioning of the cable bolt to 10 mm from
nominal dimensions. The manufacturers of the transformers
must provide the conductor cable with a thin insulation in
order to keep transient voltages to the central bushing tube.
Maximum allowable drilling depth and hole diameter of
standard cable bolt
Tube
diameter d3
[mm]

Composite insulator with silicone sheds

Porcelain insulator

Helical sheds

Straight sheds

Brown

Grey

Standard 123 kV

Standard 72.5 kV

Standard

Optional

Optional 123 kV

(all voltages)

(all voltages)

Cable bolt
diameter
B [mm]

Max. hole
diameter
A [mm]

Max. hole
depth
C [mm]

40

38

35

T-20

50

45

40

T-20

65

60

55

T-20

100

95

90

T-20

Recommended Option

T = Lenght of
cable bolt diameter

C = T20 mm

De-areation hole

The rod conductor can be fitted with a joint, usually near the
flange. Various terminal shapes are available for their lower
end. Conductor installation and de-aeration of the central
tube are similar in both the version with rod conductor and
with cable conductor.
Please note: The rod conductor is a separate component
and must be selected separately.

High currents with fixed conductor


Bushings with a directly wound and nonremovable conductor are suitable for high
currents. Various terminal solutions are
available, see data tables and figures.

Current data
The type designation of the bushings contains the standard
current according to IEC 60137 (2008). The actually per missible operating currents depend on the lower part extension
L6 and are shown in the data tables.

Air side terminal


The standard air side terminal mentioned in the data tables
covers the entire current range of the bushing.
Guidelines for the dimensions of air side terminals:
Maximum permissible
 d2
Length c2
operating current (A)
1600

30

80

2500

40

125

3500

50

125

4300

60

125

5000

flat 90 105

thickness 30

In case the full current range of the bushing is not utilized as


an option one may use smaller dimensions, as long as above
rules are observed.
Medium currents with removable
rod conductor
For a better current utilization of the bushing
with central tube, it is equipped with a
removable conductor rod of copper.
In the standard model, the air side terminals
are bare. As an option, the surfaces can be silver- or nickelplated and the shapes of the terminals can be selected.

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

Overload
If overload capacity is required for the transformer according
to IEC 60076-7 (normal load cycles), the rated current of the
bushing should be chosen with at least 120 % of the transformer-rated current, in accordance with IEC 60137 (2008).

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

[kV] 109 134 180

160

52 105

80

95

140

90

105

120

160

100

105

125

72.5
123
145
170

185

115

115

130

130

230

145

145

145

145

275

170

170

170

310

200

200

200

325

210

210

210

365

230

230

230

300

300

245

460

300

510

420
550

300

230

330

Ir (A)

Ir (A)

Drawing no: 1ZCD

Ir (A)

Drawing no: 1ZCD

mm

Cable

Rod

Silicone composite Porcelain

Fixed

Silicone composite Porcelain

Linie aussen: 0.5 pt

064026

064076

24

150 n.a.

064027

064077

24

150 n.a.

064028

064078

36

200 n.a.

064029

064079

36

200 n.a.

064030

064080

36

200 n.a.

064031

064081

52

250 n.a.

064032

064082

52

250 n.a.

064033

064083

52

250 n.a.

064034

064084

72.5

350 n.a.

064035

064085

72.5

350 n.a.

064036

064086

72.5

350 n.a.

064037

064087

123

550 n.a.

064038

064088

123

550 n.a.

064039

064089

145

650 n.a.

064040

064090

145

650 n.a.

064041

064091

170

750 n.a.

064042

064092

170

750 n.a.

0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600

conductor
3 050
2 650
2 400
4 200
3 800
3 500
5 200
4 500
4 100
3 000
2 600
2 350
4 150
3 750
3 450
5 150
4 500
4 100
2 840
2 520
2 300
3 400
3 000
2 680
4 250
3 800
3 500
2 200
1 950
1 800
3 250
2 950
2 700
4 100
3 700
3 400
2 250
2 100
2 000
3 150
2 900
2 700
2 420
2 230
2 100
3 600
3 380
3 150
2 100
2 000
1 900
3 500
3 280
3 050
2 150
2 050
1 950
3 150
3 000
2 900
2 100
2 000
1 900
3 800
3 600
3 400
2 300
2 600
2 400
3 250
2 900
2 600
2 100
2 200
1 950

insulator

150 n.a.

conductor conductor insulator


1 550
2 350
064001
1 380
2 100
1 250
1 850
2 500
3 600
064002
2 200
3 200
2 100
2 850
3 750
5 000
064003
3 200
4 300
2 880
3 850
1 500
2 300
064004
1 330
2 050
1 200
1 800
2 500
3 500
064005
2 200
3 150
2 100
2 850
3 600
4 800
064006
3 120
4 200
2 840
3 800
1 550
2 250
064007
1 380
2 000
1 250
1 750
2 100
2 800
064008
1 850
2 470
1 650
2 200
2 600
3 500
064009
2 300
3 100
2 100
2 850
1 000
1 750
064010
890
1 580
800
1 430
2 000
2 650
064011
1 800
2 380
1 650
2 150
2 500
3 400
064012
2 230
3 050
2 040
2 780
920
1 670
064013
830
1 520
770
1 370
1 940
2 610
064014
1 750
2 370
1 600
2 180
1 400
2 000
064015
1 260
1 800
1 160
1 670
2 000
2 900
064016
1 840
2 720
1 730
2 550
880
1 360
064017
805
1 250
755
1 170
1 900
2 800
064018
1 800
2 620
1 700
2 450
1 030
1 650
064019
880
1 510
820
1 400
1 700
2 400
064020
1 560
2 230
1 450
2 100
1 000
1 600
064021
850
1 110
780
1 340
2 250
3 000
064022
2 100
2 800
2 000
2 600
1 100
1 800
064023
1 250
2 000
1 000
2 000
2 000
2 800
064024
1 850
2 650
1 700
2 500
1 050
1 850
064025
1 100
2 000
900
1 750

insulator

24

Rated current (A)


Lightning impulse voltage 1.2/50 s (kV)
Maximum voltage (kV)
R = RIP bushing
T = Transformer application
K = Short lower part
F = Outdoor use

Test tap
Each bushing is equipped with a
standard test tap. The test tap
is connected to the outermost capacitor foil and is always grounded
during operation. For measurement,
the cap must be unscrewed and the
supplied 4-mm plug coupling must
be inserted.
As an option we provide transition connectors for continuous
voltage measurements.

292

Routine and type tests


The standard routine tests are carried out in accordance
with IEC 60137 (2008) and the protocols are supplied; tests
according to other standards are available on request.
The type tests were performed on representative bushings in
accordance with current standards IEC 60137 (2008), and
IEEE C57.19.00 (2004) / C57.19.01 (2000). These tests cover
the entire AirRIP portfolio and were successfully passed in
the presence of an independent observer from KEMA. Protocols are supplied to customers on request.

064043

064093

064044

064094

064045

064095

064046

064096

064047

064097

064048

064098

064049

064099

064050

064100

Current conductor
Cable bolt for draw lead
Rod conductor
Fixed conductor
Air side terminal
Dimensions:
Standard
Variant 1*
Variant 2*

Customized modifications
forpt,example
in
Linie innen:as
0.35
gepunktet
flange dimensions
terminal variants
other lower part lengths
etc.
can be made available on request. We are happy to provide
information on feasibility, price and delivery time of such
customized modi fications.

Galvanization:
bare
silver-plated
nickel-plated

Removable rod conductor


Rod conductor, one-piece
Rod conductor, split
Oil side terminal:
Standard
Variant 1
Variant 2
Silicone comp. insulator
Helical sheds (123 kV )
Straight sheds

Porcelain
Brown
Grey

Flange pitch circle 


Standard
Variant 1*
Current transformer extension L6 (mm)
0
100 200 300 400 500 600

Oil side end


Standard
Variant 1*
Variant 2*

630

450

680

500

750

550

790

600

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

1 050

750

245

1 050

750

300

1 175

850

300

1 175

850

420

1 675 1 175

420

1 675 1 175

550

1 800 1 240

330
* If available

Packaging and storage


The bushings are packaged and sent in a dry and clean
state. On request, we offer long-life packaging. The bushings
can be transported and stored in any position.

The diameter of the current conductor should be at least half


of the inner tube diameter d3. Oil access in the central

245

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

insulator
064051
064052
064053
064054
064055
064056
064057
064058
064059
064060
064061
064062
064063
064064
064065
064066
064067
064068
064069
064070
064071
064072
064073
064074
064075

Data pages 1922

L6 + 20

F = Fixed conductor

d6

180

L6

kV

Data pages 1518

B = Removable conductor bar

Shield diameter d6
[kV]

SIL

kV

Quantity:
Composite insulator

Fig. 23

d6

BIL

kV

Data pages 3134

d6

Ur

Drawing no: 1ZCD 0 6 4

RTKF 170750 / 1600 B KSI

AC test voltage

Ur

Fig. 22

Our order confirmation includes drawings of the bushing and


a detailed
bushing data sheet.
Linienstrken
fr Graken

Data pages 2730

Type designation

Minimum distances A [mm] to transformer tank


Fig. 21

When ordering, please specify the following:

Type:

 c2

Recommended installation
Our bushings are designed and tested for mineral oil applications. The field strengths in oil on the lower part of the
bushing depend on the shape of the
surrounding parts, as well as on the
quality and the conditions of the
Min. R5
transformer oil. As a guideline, the
following table shows the respective
30
distances A to grounded transformer
parts under standard conditions.
They are valid for the oil side ends
(standard and variants) as per the
A
data tables. Due to limiting conditions additional insulating measures
or larger distances may be necessary. Uninsulate edges
around the bushing should be rounded to R min = 5 mm.

AirRIP overview

Data pages 1114

bushing opening and in the open space of the shield electrodes must not be obstructed.

Each AirRIP bushing meets all requirements of IEC 60137


(2008) and the electrical values under the IEEE C57.19.01
(2000).

Ordering information

Data pages 2326

General information

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

10

AirRIP bushings 24170 kV


Types with cable conductor
Bushings with cable conductor 24 170 kV

nv

12

45

15

30

22.5

30

2
 D3
 D4

Fig. 21

 D3
 D4

 d3
L16
20

L16

L16
11

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

12

c7

c7

 d5
 d6

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

 d5
 d6

1ZCD064054

RTKF 36200/2500 KSI

RTKF 36200/2500

1ZCD064005

1ZCD064055

RTKF 36200/3150 KSI

RTKF 36200/3150

1ZCD064006

1ZCD064056

RTKF 52250/1250 KSI

RTKF 52250/1250

1ZCD064007

1ZCD064057

RTKF 52250/2000 KSI

RTKF 52250/2000

1ZCD064008

1ZCD064058

RTKF 52250/2500 KSI

RTKF 52250/2500

1ZCD064009

1ZCD064059

36
36
52

RTKF 123550/800

1ZCD064013

1ZCD064063

RTKF 123550/1600 KSI

RTKF 123550/1600

1ZCD064014

1ZCD064064

RTKF 145650/1250 KSI

RTKF 145650/1250

1ZCD064015

1ZCD064065

RTKF 145650/2000 KSI

RTKF 145650/2000

1ZCD064016

1ZCD064066

RTKF 170750/800 KSI

RTKF 170750/800

1ZCD064017

1ZCD064067

RTKF 170750/1600 KSI

RTKF 170750/1600

1ZCD064018

1ZCD064068

77 / 170 34.5

22

21

52

77 / 170 34.5

22

30 105 / 250 46

95 /
42 155 / 325 69

29 105 / 250
29 105 / 250
44 160 / 350
140 /

42 155 / 325 69
140 /

44 160 / 350
140 /

42 155 / 325 69
140 /

44 160 / 350
140 /

123

71 255 / 550 92

123

71 255 / 550 92

TR
TR

84 305 / 650 138


275 /

145

29 105 / 250

95 /

140 /

145

80 / 200

95 /

30 105 / 250 46

230 /

22

95 /

30 105 / 250 46

230 /

80 / 200

75 /

95 /
52

80 / 200

75 /

95 /

1ZCD064061

RTKF 123550/800 KSI

21

60 / 150

75 /

70 /

RTKF 72.5350/2000 KSI RTKF 72.5350/2000 72.5

1ZCD064062

77 / 170 34.5

70 /

1ZCD064060

1ZCD064012

21

60 / 150

50 /

70 /

RTKF 72.5350/1000 KSI RTKF 72.5350/1000 72.5


1ZCD064010

16

50 /
36

73 185 / 450
155 /
73 185 / 450
155 /
88 310 / 650
275 /

84 305 / 650 138


275 /

88 310 / 650
275 /

170

98 355 / 750 161 102 365 / 750

170

98 355 / 750 161 102 365 / 750

325 /
325 /

TR
TR

29

30

31

32

33

34

35

36 37 38 39 40

Flange

41 42

315 /
315 /

1 500

744

210

744

210

1 116

310

1 116

310

1 116

310

1 612

460

1 612

460

1 500

1 612

460

400

2 248

630

1 200

2 248

630

2 248

630

2 800
665
1 500
2 800
665
1 200

1 500
400
1 200
665
1 500
400
1 500

3 813 1 010
3 813 1 010
4 495 1 170
4 495 1 170
5 270 1 400
5 270 1 400

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

13

46

47

48 49

s Fig

6 16 18 10

350 250 290 180 222

8 16 18 11

380 290 335 205 261 12 16 18 12


300 185 225 135 165

6 16 18 10

350 250 290 180 222

8 16 18 11

380 290 335 205 261 12 16 18 12


300 185 225 135 165

6 16 18 10

350 250 290 180 222

8 16 18 11

380 290 335 205 261 12 16 18 12


300 185 225 135 165

6 16 18 10

350 250 290 180 222

8 16 18 11

380 290 335 205 261 12 16 18 12


350 250 290 180 222

8 16 18 11

380 290 335 205 261 12 16 18 12


380 290 335 205 261 12 16 18 12
450 400 450 245 365 12 20 22 12
380 290 335 205 261 12 16 18 12
450 400 450 245 365 12 20 22 12

L
645
945
1 245
685
985
1 285
695
995
1 295
765
1 065
1 365
805
1 105
1 405
815
1 115
1 415
915
1 215
1 515
955
1 255
1 555
965
1 265
1 565
1 150
1 450
1 750
1 190
1 490
1 790
1 200
1 500
1 800
1 705
2 005
2 305
1 715
2 015
2 315
1 925
2 225
2 525
1 945
2 245
2 545
2 215
2 515
2 815
2 235
2 535
2 835

Standard

50

51

52

Variant

d2

c2 d2

c2

d5

d6

30

80 40 125

61

20

40 125 50 125

91

20

60 125 50 125 111

20

30

c7 Fig d5

d6

c7 Fig

67 109

80 21

67 109

80 21

Figure

D8

Var.

Shield length below L 16

D2

Figure

D4

300 185 225 135 165

Bushing length, without air


side terminal and lower shield

D3

Flange plate thickness

Hole diameter

D6

Number of holes

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
silicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

Height of head (maximum)

Cable bolt:
distance from the flange plate

Terminal: distance from the


flange plate (tolerance 5 mm)

Inside tube diameter

L 6 L 16 D1 d3
L2
L 4 L 5 D5 D6 D5
0 120 92 50 525 350 135 135 270 178
300 420
600 720
0 120 120 80 565 390 135 165 300 216
300 420
600 720
0 120 144 100 575 400 145 200 322 245
300 420
600 720
0 140 92 50 625 450 135 135 270 178
300 440
600 740
0 140 120 80 665 490 135 165 300 216
300 440
600 740
0 140 144 100 675 500 145 200 322 245
300 440
600 740
0 140 92 50 775 600 135 135 270 178
300 440
600 740
0 140 120 65 815 640 135 165 300 216
300 440
600 740
0 140 144 80 825 650 145 200 322 245
300 440
600 740
0 175 92 40 975 800 165 135 270 178
300 475
600 775
0 175 120 65 1 015 840 165 165 300 216
300 475
600 775
0 175 144 80 1 025 850 175 200 322 245
300 475
600 775
0 310 120 40 1 395 1 220 165 165 300 216
300 610
600 910
0 310 144 65 1 405 1 230 175 200 322 245
300 610
600 910
0 360 144 50 1 565 1 390 175 200 322 245
300 660
600 960
0 360 185 80 1 585 1 410 175 245 370 315
300 660
600 960
0 420 144 40 1 795 1 620 175 200 322 245
300 720
600 1 020
0 420 185 80 1 815 1 640 175 245 370 315
300 720
600 1 020

Core diameter

[kg]
31
34
36
50
53
56
65
69
73
38
41
43
60
63
66
77
81
85
49
51
53
72
76
79
87
92
97
63
65
68
91
95
99
110
115
120
132
136
141
156
162
167
173
179
185
245
255
264
203
209
215
282
291
300

Sealing area: max. diameter

[kg]
18
20
23
34
3 150 1 575 vh
37
40
46
3 150 1 575 vh
50
54
20
3 150 1 575 vh
22
25
36
3 150 1 575 vh
39
42
49
3 150 1 575 vh
53
57
24
3 150 1 575 vh
27
29
40
3 150 1 575 vh
44
48
52
3 150 1 575 vh
57
62
30
3 150 1 575 vh
33
35
45
4 000 2 000 vh
49
53
60
4 000 2 000 vh
65
70
62
4 000 2 000 vh
66
70
79
4 000 2 000 vh
85
90
4 000 2 000 v30 87
93
99
130
4 000 2 000 vh
139
148
5 000 2 500 v30 100
106
112
145
5 000 2 500 vh
154
163

210 3 150 1 575 vh

Sealing area: min. diameter

[N]

744

Outside flange diameter

[N]

665

Lower core length


(tolerance 5 mm)

[mm]

With silicone composite insulator

[mm]

Installation (v = vertical,
h = horizontal, from vertical)

[kA]

Cantilever operating load

[mm 2]

45

Oil side end

terminal

Pitch circle diameter

[A]
1 550
1 380
1 250
2 500
2 200
2 100
3 750
3 200
2 880
1 500
1 330
1 200
2 500
2 200
2 100
3 600
3 120
2 840
1 550
1 380
1 250
2 100
1 850
1 650
2 600
2 300
2 100
1 000
890
800
2 000
1 800
1 650
2 500
2 230
2 040
920
830
770
1 940
1 750
1 600
1 400
1 260
1 160
2 000
1 840
1 730
880
805
755
1 900
1 800
1 700

43 44

Air side

Figure

28

Shield diameter

RTKF 36200/1250

1ZCD064004

60 / 150

50 /

55 / 125 25

27

Opening

RTKF 36200/1250 KSI

14

[kV] [kV]
50 /

16

50 /
24

26

Shield diameter

1ZCD064053

25

Air side

Opening

RTKF 24150/3150

1ZCD064003

24

Length of terminal

RTKF 24150/3150 KSI

16

50 /
55 / 125 25

23

Terminal diameter

1ZCD064052

14

22

Length of terminal

1ZCD064002

24

21

Oil side

Std.

[kV] [kV] [kV] [kV]


55 / 125 25

design

20

Weights

Terminal diameter

RTKF 24150/2500

14

RTKF 72.5350/2500 KSI RTKF 72.5350/2500 72.5

50

 d5

1ZCD064051

RTKF 24150/2500 KSI

1ZCD064011

Fig. 22

 d3

 d3

 D2
 D8

 D3
 D4

Oil side end


Fig. 20

1ZCD064001

24

data

19

Current transformer extension

60

5 45

RTKF 24150/1250

18

With porcelain insulator

20
L16 5
c7

L6

20
L6

L16 5

30

RTKF 24150/1250 KSI

17

Cantilever test load, 1 min.

Ur / 3

L4 cable bolts

L 2 (5)
(L)

L4 cable bolts

the transformer lead)

16

Mechanical

Arcing distance (minimum)

insulator

15

Insulator

Creepage distance (minimum)

composite insulator

14

Thermal short-time current


Ith 2 sec.

13

Ith 2 sec. [kA] = 0.055 S [mm 2 ] if S = 1200 mm 2


Ith 2 sec. [kA] = 0.045 S [mm 2 ] if S = 2800 mm 2

With porcelain

12

Ith 2 sec. [kA] = 0.06 S [mm 2 ] if S 700 mm 2


Ith 2 sec. [kA] = 0.05 S [mm 2 ] if S = 1500 mm 2

With silicone

AC test voltage dry / wet

4 Earthing screws 2 M12 / 180

Fig. 12

11

Current

(2000)

 D1

Fig. 11

10

IEEE C57.19.01

Flange detail

Fig. 10

(2008)

L6 Current transformer extension

Flange

IEC 60137

[kV] [kV]

 D1

3 De-aeration

7 Removability (for connecting


 D6
max.

2 Test tap

6 Sealing area

 D6
max.

With copper cable section S

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

Rated max.
line-to-ground voltage

 D5

Type and drawing

System voltage

 D5

Lightning impulse voltage,


1.2/50 s

nickel-plated, silver-plated)

1
L 5 max.

L 5 max.

c2

1 Copper, bare (optional:

Lightning impulse voltage,


1.2/50 s

c2

 d2

Shield length below L 16

Legend

 d2

L 2 (5)

24
Inner diameter of the central tube ( d3)
28, 29 Maximum head and shed diameter for silicone
composite insulator
30, 31 Maximum head and shed diameter for porcelain insulator
34, 35 Sealing area
40
Bushing length L, without air side terminal and
oil side shield
41, 42 Standard terminal on air side
43, 44 Optional terminal on air side
45 48 Standard design of oil side end
49 52 Optional design of oil side end

(L)

36
Rated voltages according to IEC 60137 (2008)
710 Rated voltages according to IEEE C57.19.01 (2000)
11, 12 Maximum operating current Ir for the largest cable
cross-section, depending on the current transformer
extension L6
13
Maximum thermal short-circuit current, 2 sec., after
operation at maximum operating current
16
Bending test load, 1 min.
17, 18 Maximum cantilever operating load and permissible
installation position (v = vertical, h = horizontal,
from vertical)
21
Standard current transformer extension L6

All dimensions in mm, unless otherwise indicated

Data for bushings with cable conductor 24 170 kV

Fig. 2

AC test voltage dry / wet

Fig. 1

Rated Voltage Ur

Explanations of the table columns

80 40 125

61

20

40 125 50 125

91

20

60 125 50 125 111

20

30

80 40 125

61

20

67 109

80 21

40 125 50 125

76

20

75 134

90 21

50 125 40 125

91

20

30

51

20

67 109

80 21

40 125 50 125

76

20

75 134

90 21

40 125 50 125

91

20

30

67 109

80 21 107 160 200 22

40 125 50 125

75 134

90 21 140 180 200 22

30

75 134

90 21 107 160 200 22

80

80

80 40 125

40 125 50 125 140 180 170 22 140 180 200 22


30

80

75 134

90 21 107 160 200 22

40 125 50 125 140 180 170 22 140 180 200 22

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

14

AirRIP bushings 24170 kV


Types with rod conductor
Bushings with rod conductor 24 170 kV

40

38

2 M8

80

50

45

3 M10

110

65

60

3 M10

110

80

75

3 M12

110

100

95

6 M12

110

1ZCD064057

RTKF 52250/2500 B KSI

RTKF 52250/2500 B

1ZCD064008

1ZCD064058

RTKF 52250/3150 B KSI

RTKF 52250/3150 B

1ZCD064009

1ZCD064059

12

30

15

22.5
2

2
 D3
 D4

Oil side terminal


flat

thread

round

L16

thickness holes
n g1

L16
thread c1

d1 c1

40

38

20

2 14

50

45

20

2 18

M363 60

30 85
40

65

60

30

2 18

M423 80

50 85

80

75

30

2 18

100

95

30

4 18

30

30

Var. 1:
thread
L16

30

L16

 g1
 g1
40
85
40  d4 85
 d4

 d4
 d4

L: Bushing length, without airside terminal and lower shield,


see column 38 of the data table
AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

d1G
d1G

 d4

Var. L16
2: round

30

L16

30

c1

30

30

40
40 20
20

50 85

* See column 23 of the data table

15

L16

 g1
40
 g1
40 20
 d4
85
20
a1
 d4
85

30 85

30

L16

Oil side end


Fig. 20

30

 d4
 d4
5
5

Fig. 22

 d3

c1
c1

d1

16

125 25

16

60 / 50

24

14

55 / 50

125 25

16

60 / 50

36

21

77 / 70

170 34.5

22

80 / 75

36

21

77 / 70

170 34.5

22

80 / 75

36

21

77 / 70

170 34.5

22

80 / 75

52

30

105 / 95

250 46

29

105 / 95

52

30

105 / 95

250 46

29

105 / 95

52

30

105 / 95

250 46

29

105 / 95

RTKF 72.5350/1600 B KSI RTKF 72.5350/1600 B 72.5

42

155 / 140

325 69

44

160 / 140

42

155 / 140

325 69

44

160 / 140

42

155 / 140

325 69

44

160 / 140

123

71

255 / 230

550 92 TR

73

185 / 155

123

71

255 / 230

550 92 TR

73

185 / 155

145

84

305 / 275

650 138

88

310 / 275

145

84

305 / 275

650 138

88

310 / 275

170

98

355 / 325

750 161 TR 102

365 / 315

170

98

355 / 325

750 161 TR 102

365 / 315

1ZCD064010

1ZCD064060

RTKF 72.5350/2500 B KSI RTKF 72.5350/2500 B 72.5


1ZCD064011

1ZCD064061

RTKF 72.5350/3150 B KSI RTKF 72.5350/3150 B 72.5


1ZCD064012

1ZCD064062

RTKF 123550/1600 B KSI

RTKF 123550/1600 B

1ZCD064013

1ZCD064063
1ZCD064064

RTKF 145650/2000 B KSI RTKF 145650/2000 B


1ZCD064065

RTKF 145650/2500 B KSI RTKF 145650/2500 B


7

 d5
 d6

c1

55 / 50

1ZCD064014

10

c1

14

1ZCD064015
 d5

10
d1

 D2

24

RTKF 123550/2500 B KSI RTKF 123550/2500 B

 d3

a1

30

 D3
 D4

L16
20

Standard: flat

c7

Var. 2

L16

Var. 1

6
 D8

 D3
 D4

50

Standard

 d4

25
105

nv

 d3 *

50

L6

45

30

a1

30

4
30

60

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

[kV] [kV]

1ZCD064016

1ZCD064066

RTKF 170750/1250 B KSI

RTKF 170750/1250 B

1ZCD064017

1ZCD064067

RTKF 170750/2500 B KSI

RTKF 170750/2500 B

1ZCD064018

1ZCD064068

[A] [kA] [mm] [mm]


[N]
[N]
150 2 350
744
210 3 150 1 575
2 100
1 850
150 3 600
744
210 3 150 1 575
3 200
2 850
150 5 000
744
210 3 150 1 575
4 300
3 850
200 2 300
1 116
310 3 150 1 575
2 050
1 800
200 3 500
1 116
310 3 150 1 575
3 150
2 850
200 4 800
1 116
310 3 150 1 575
4 200
3 800
250 2 250
1 612
460 3 150 1 575
2 000
1 750
250 2 800
1 612
460 3 150 1 575
2 470
2 200
250 3 500
1 612
460 3 150 1 575
3 100
2 850
350 1 750
2 248
630 3 150 1 575
1 580
1 430
350 2 650
2 248
630 4 000 2 000
2 380
2 150
350 3 400
2 248
630 4 000 2 000
3 050
2 780
450 1 670
3 813 1 010 4 000 2 000
1 520
1 370
450 2 610
3 813 1 010 4 000 2 000
2 370
2 180
650 2 000
4 495 1 170 4 000 2 000
1 800
1 670
650 2 900
4 495 1 170 4 000 2 000
2 720
2 550
750 1 360
5 270 1 400 5 000 2 500
1 250
1 170
750 2 800
5 270 1 400 5 000 2 500
2 620
2 450

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

17

vh
vh
vh
vh
vh
vh
vh
vh
vh
vh
vh
vh
vh
vh
v30
vh
v30
vh

[kg]
27
33
39
57
72
87
66
80
94
30
37
43
64
79
94
73
87
101
37
43
49
63
74
85
87
104
120
41
46
52
73
84
95
104
121
138
80
87
94
121
134
147
114
125
135
203
224
245
122
132
141
230
250
271

[kg]
40
46
53
74
88
103
84
98
112
49
55
61
88
103
118
100
114
128
61
68
74
94
105
117
122
139
155
73
79
84
119
130
141
153
170
187
150
157
165
198
211
224
201
211
221
318
339
360
226
235
244
366
387
407

L 6 L 16 D1 d3
L 2 L 5 D5 D6 D5 D6 D3
0 120 92 50 525 135 135 270 178 300 185
300 420
600 720
0 120 120 80 565 135 165 300 216 350 250
300 420
600 720
0 120 144 100 575 145 200 322 245 380 290
300 420
600 720
0 140 92 50 625 135 135 270 178 300 185
300 440
600 740
0 140 120 80 665 135 165 300 216 350 250
300 440
600 740
0 140 144 100 675 145 200 322 245 380 290
300 440
600 740
0 140 92 50 775 135 135 270 178 300 185
300 440
600 740
0 140 120 65 815 135 165 300 216 350 250
300 440
600 740
0 140 144 80 825 145 200 322 245 380 290
300 440
600 740
0 175 92 40 975 165 135 270 178 300 185
300 475
600 775
0 175 120 65 1 015 165 165 300 216 350 250
300 475
600 775
0 175 144 80 1 025 175 200 322 245 380 290
300 475
600 775
0 310 120 40 1 395 165 165 300 216 350 250
300 610
600 910
0 310 144 65 1 405 175 200 322 245 380 290
300 610
600 910
0 360 144 50 1 565 175 200 322 245 380 290
300 660
600 960
0 360 185 80 1 585 175 245 370 315 450 400
300 660
600 960
0 420 144 40 1 795 175 200 322 245 380 290
300 720
600 1 020
0 420 185 80 1 815 175 245 370 315 450 400
300 720
600 1 020

D4

D2

D8

s Fig

225 135 165

6 16 18 10

290 180 222

8 16 18 11

335 205 261 12 16 18 12


225 135 165

6 16 18 10

290 180 222

8 16 18 11

335 205 261 12 16 18 12


225 135 165

6 16 18 10

290 180 222

8 16 18 11

335 205 261 12 16 18 12


225 135 165

6 16 18 10

290 180 222

8 16 18 11

335 205 261 12 16 18 12


290 180 222

8 16 18 11

335 205 261 12 16 18 12


335 205 261 12 16 18 12
450 245 365 12 20 22 12
335 205 261 12 16 18 12
450 245 365 12 20 22 12

Standard

Variant

Figure

L 2 (5)
20

a1

60 / 50

49 50

Shield length below L 16

RTKF 52250/2000 B

1ZCD064007

L2

* See column 23 of the data table

30

16

Var.

Shield diameter

RTKF 52250/2000 B KSI

L16 5

30

[kV]

Std.

Opening

1ZCD064056

125 25

45 46 47 48

Figure

RTKF 36200/4000 B

1ZCD064006

30

Fig. 12

Fig. 11

Fig. 10

[kV] [kV]

44

Shield length below L 16

RTKF 36200/4000 B KSI

Flange detail

Flange

55 / 50

43

Oil side end

Shield diameter

1ZCD064055

14

41 42

Opening

RTKF 36200/3150 B

1ZCD064005

[kV]

24

40

terminal

IEEE C57.19.01 (2000)

[kV] [kV]

39

Air side

Length of terminal

RTKF 36200/3150 B KSI

33 34 35 36 37 38

Terminal diameter

1ZCD064054

32

Length of terminal

RTKF 36200/2000 B

1ZCD064004

31

Terminal diameter

RTKF 36200/2000 B KSI

5 45

length e1

30

Flange

Bushing length, without air


side terminal and lower shield

1ZCD064053

29

Figure

RTKF 24150/5000 B

1ZCD064003

 18

28

Flange plate thickness

RTKF 24150/5000 B KSI

a1

27

Hole diameter

1ZCD064052

30 40

26

Number of holes

RTKF 24150/3150 B

1ZCD064002

30
 D1

c7

screws

e1

 d4

20

 d3 *

 D1

L6

L16 5

Optional splitting of the rod conductor


Determine whether the rod conductor should be split or not.
Rod conductors are split 20 mm below the base plate and
have the following characteristics:

d2

25

Sealing area: max. diameter

1ZCD064051

RTKF 24150/3150 B KSI

In = 5000 A

24

Air side

Sealing area: min. diameter

1ZCD064001

Air side

a1
20

30

23

Outside flange diameter

RTKF 24150/2000 B

(L)

30

22

Pitch circle diameter

RTKF 24150/2000 B KSI

the transformer lead)


L6 Current
transformer extension
Spaltenbreiten

(L)

L 2 (5)

 D6
max.

21

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
silicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

c2

In = 5000 A

20

Oil side

Height of head (maximum)

insulator

design

19

Terminal: distance from the


flange plate (tolerance 5 mm)

composite insulator

6 Sealing area
 c2
7 Removability (for connecting

data

18

Weights

Inside tube diameter

17

Core diameter

With porcelain

16

Mechanical

Lower core length


(tolerance 5 mm)

With silicone

15

Current transformer extension

thickness 30

4 Earthing screws 2 M12 / 180

14

Insulator

With porcelain insulator

flat 90 105

IEC 60137 (2008)

13

With silicone composite insulator

5000

3 De-aeration

L5
max.

 D6
max.

12

Current

Installation (v = vertical,
h = horizontal, from vertical)

125

11

Cantilever operating load

125

60

10

Cantilever test load, 1 min.

50

4300

Arcing distance (minimum)

3500

Creepage distance (minimum)

125

Thermal short-time current


Ith 2 sec.

40

Ith 2 sec. = 25 Ir

2500

2 Test tap

 D5

L5
max.

L2

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

80

Lightning impulse voltage,


1.2/50 s

30

Type and drawing

AC test voltage dry / wet

1600

 D5

18

105 50

nickel-plated, silver-plated)

Rated max.
line-to-ground voltage

c2

1 Copper, bare (optional:

System voltage

d2

a1
40

25

 d2

Lightning impulse voltage,


1.2/50 s

c2

30

c2

 d2

30

Max. operating current (A)

Legend

AC test voltage dry / wet

 d2

Air side terminal


Standard terminals as per columns 39/40,
variants as per columns 41/42.
Guidelines for the terminal dimensions:

All dimensions in mm, unless otherwise indicated

Data for bushings with rod conductor 24 170 kV


Fig. 4

Ur / 3

Fig. 3

Rated Voltage Ur

Determination of the rod conductor

L d2 c2 d2 c2 d5 d6 c7 Fig d5 d6 c7 Fig
645 40 125
61
20
945
1 245
685 60 125 50 125 91
20
985
1 285
695 F90 105
111
20
995
1 295
765 40 125
61
20
1 065
1 365
805 60 125 50 125 91
20
1 105
1 405
815 F90 105
111
20
1 115
1 415
915 40 125
61
20
1 215
1 515
955 50 125 40 125 76
20
1 255
1 555
965 60 125 50 125 91
20
1 265
1 565
1 150 30 80
51
20 107 160 200 22
1 450
1 750
1 190 50 125 40 125 76
20
1 490
1 790
1 200 60 125 50 125 91
20
1 500
1 800
1 705 30 80
107 160 200 22
2 005
2 305
1 715 50 125 40 125 140 180 200 22
2 015
2 315
1 925 40 125
107 160 200 22
2 225
2 525
1 945 50 125
140 180 200 22
2 245
2 545
2 215 30 80
107 160 200 22
2 515
2 815
2 235 50 125
140 180 200 22
2 535
2 835
Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

18

AirRIP bushings 24170 kV


Types with fixed conductor

Legend

20

25
105

50

L6

L2
 D3
 D4

5 45

6
 D2
 D8

 D3
 D4

 D3
 D4

14

55 / 50

125 25

16

60 / 50

24

14

55 / 50

125 25

16

60 / 50

36

21

77 / 70

170 34.5

22

80 / 75

36

21

77 / 70

170 34.5

22

80 / 75

36

21

77 / 70

170 34.5

22

80 / 75

52

30

105 / 95

250 46

29

105 / 95

52

30

105 / 95

250 46

29

105 / 95

52

30

105 / 95

250 46

29

105 / 95

RTKF 72.5350/2000 F KSI RTKF 72.5350/2000 F 72.5

42

155 / 140

325 69

44

160 / 140

42

155 / 140

325 69

44

160 / 140

42

155 / 140

325 69

44

160 / 140

123

71

255 / 230

550 92 TR

73

185 / 155

123

71

255 / 230

550 92 TR

73

185 / 155

145

84

305 / 275

650 138

88

310 / 275

145

84

305 / 275

650 138

88

310 / 275

170

98

355 / 325

750 161 TR 102

365 / 315

170

98

355 / 325

750 161 TR 102

365 / 315

RTKF 72.5350/3150 F KSI RTKF 72.5350/3150 F 72.5

Oil side

Fig. 24

Fig. 30

Fig. 31

 d5
 d6

19

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

20

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

 d4

30

40
 d4

85


18

20 40

85

20 40


18

30

30

L16

L16

L16
20
c7

30

1ZCD064087

RTKF 123550/2000 F KSI RTKF 123550/2000 F

 d3

1ZCD064086

RTKF 72.5350/4000 F KSI RTKF 72.5350/4000 F 72.5


1ZCD064037

Oil side end

1ZCD064085

1ZCD064038

1ZCD064088

RTKF 123550/3150 F KSI

RTKF 123550/3150 F

1ZCD064039

1ZCD064089

RTKF 145650/2000 F KSI RTKF 145650/2000 F


1ZCD064040

1ZCD064090

RTKF 145650/3150 F KSI

RTKF 145650/3150 F

1ZCD064041

1ZCD064091

RTKF 170750/2000 F KSI

RTKF 170750/2000 F

1ZCD064042

1ZCD064092

RTKF 170750/3150 F KSI

RTKF 170750/3150 F

1ZCD064043

1ZCD064093

[A]
150 3 050
2 650
2 400
150 4 200
3 800
3 500
150 5 200
4 500
4 100
200 3 000
2 600
2 350
200 4 150
3 750
3 450
200 5 150
4 500
4 100
250 2 840
2 520
2 300
250 3 400
3 000
2 680
250 4 250
3 800
3 500
350 2 200
1 950
1 800
350 3 250
2 950
2 700
350 4 100
3 700
3 400
450 2 250
2 100
2 000
450 3 150
2 900
2 700
650 2 420
2 230
2 100
650 3 600
3 380
3 150
750 2 100
2 000
1 900
750 3 500
3 280
3 050

[mm]

[N]

[N]

744

210 3 150 1 575 vh

744

210 3 150 1 575 vh

744

210 3 150 1 575 vh

1 116

310 3 150 1 575 vh

1 116

310 3 150 1 575 vh

1 116

310 3 150 1 575 vh

1 612

460 3 150 1 575 vh

1 612

460 3 150 1 575 vh

1 612

460 3 150 1 575 vh

2 248

630 3 150 1 575 vh

2 248

630 4 000 2 000 vh

2 248

630 4 000 2 000 vh

3 813 1 010 4 000 2 000 vh


3 813 1 010 4 000 2 000 vh
4 495 1 170 4 000 2 000 v30
4 495 1 170 4 000 2 000 vh
5 270 1 400 5 000 2 500 v30
5 270 1 400 5 000 2 500 vh

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

21

[kg]
34
44
53
72
92
112
73
89
104
39
49
58
81
101
121
81
96
111
47
56
66
77
92
107
81
95
109
49
57
64
91
106
121
96
110
124
92
101
110
172
189
206
135
148
161
187
205
224
138
149
160
212
229
247

[kg]
47
57
66
88
108
128
92
107
122
57
67
76
105
124
144
108
123
139
71
81
90
108
123
138
116
130
144
82
89
97
137
152
167
145
159
173
162
171
181
249
266
283
221
234
247
303
321
339
241
252
263
348
366
384

L 6 L 16 D1
0 120 92
300 420
600 720
0 120 120
300 420
600 720
0 120 144
300 420
600 720
0 140 92
300 440
600 740
0 140 120
300 440
600 740
0 140 144
300 440
600 740
0 140 92
300 440
600 740
0 140 120
300 440
600 740
0 140 144
300 440
600 740
0 175 92
300 475
600 775
0 175 120
300 475
600 775
0 175 144
300 475
600 775
0 310 120
300 610
600 910
0 310 144
300 610
600 910
0 360 144
300 660
600 960
0 360 185
300 660
600 960
0 420 144
300 720
600 1 020
0 420 185
300 720
600 1 020

L2

L5

D5

D6

D5

D6

D3

D4

D2

D8

s Fig

498 108 135 270 178 300 185 225 135 165

6 16 18 10

538 108 165 300 216 350 250 290 180 222

8 16 18 11

548 118 200 322 245 380 290 335 205 261 12 16 18 12
598 108 135 270 178 300 185 225 135 165

6 16 18 10

638 108 165 300 216 350 250 290 180 222

8 16 18 11

648 118 200 322 245 380 290 335 205 261 12 16 18 12
748 108 135 270 178 300 185 225 135 165

6 16 18 10

788 108 165 300 216 350 250 290 180 222

8 16 18 11

798 118 200 322 245 380 290 335 205 261 12 16 18 12
948 138 135 270 178 300 185 225 135 165

6 16 18 10

988 138 165 300 216 350 250 290 180 222

8 16 18 11

998 148 200 322 245 380 290 335 205 261 12 16 18 12
1 368 138 165 300 216 350 250 290 180 222

8 16 18 11

1 378 148 200 322 245 380 290 335 205 261 12 16 18 12
1 538 148 200 322 245 380 290 335 205 261 12 16 18 12
1 558 148 245 370 315 450 400 450 245 365 12 20 22 12
1 768 148 200 322 245 380 290 335 205 261 12 16 18 12
1 788 148 245 370 315 450 400 450 245 365 12 20 22 12

L d2 c2 d4
618 50 125 52
918
1 218
658 60 125 80
958
1 258
668 F90 105 100
968
1 268
738 50 125 52
1 038
1 338
778 60 125 80
1 078
1 378
788 F90 105 100
1 088
1 388
888 50 125 52
1 188
1 488
928 50 125 65
1 228
1 528
938 60 125 80
1 238
1 538
1 123 40 125 45
1 423
1 723
1 163 50 125 65
1 463
1 763
1 173 60 125 80
1 473
1 773
1 678 40 125 45
1 978
2 278
1 688 50 125 65
1 988
2 288
1 898 40 125 52
2 198
2 498
1 918 60 125 80
2 218
2 518
2 188 40 125 45
2 488
2 788
2 208 60 125 80
2 508
2 808

Fig

d5

d6

c7 Fig d5

d6

c7 Fig

Figure

[mm]

Figure

[kA]

Variant

Shield length below L 16

24

1ZCD064036

[kV] [kV]

48 49

Shield diameter

60 / 50

45 46 47

Opening

16

1ZCD064035

[kV]

44

Shield length below L 16

(L)

125 25

Shield diameter

1ZCD064084

c7

[kV] [kV]

43

Opening

RTKF 52250/4000 F

1ZCD064034

15

30

22.5

55 / 50

42

Oil side end

Figure

RTKF 52250/4000 F KSI

12

30

14

41

terminal

Terminal width

1ZCD064083

[kV]

24

40

terminal

Length of terminal

RTKF 52250/3150 F

1ZCD064033

[kV] [kV]

39

Oil side

Terminal diameter

RTKF 52250/3150 F KSI

nv

45

38

Air side

Standard Standard Standard

Figure

1ZCD064082

32 33 34 35 36 37

Bushing length, without air


side terminal and lower shield

RTKF 52250/2500 F

1ZCD064032

a1

31

Flange plate thickness

RTKF 52250/2500 F KSI

L16 5

L6

L16 5

20

30

30

Hole diameter

1ZCD064081

29

Flange

Number of holes

RTKF 36200/5000 F

1ZCD064031

28

Sealing area: max. diameter

RTKF 36200/5000 F KSI

30

27

Sealing area: min. diameter

1ZCD064080

26

Outside flange diameter

RTKF 36200/4000 F

1ZCD064030

25

Pitch circle diameter

RTKF 36200/4000 F KSI

24

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
silicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

1ZCD064079

23

Air side

Height of head (maximum)

RTKF 36200/2500 F

1ZCD064029

22

Terminal: distance from the


flange plate (tolerance 5 mm)

RTKF 36200/2500 F KSI

21

Core diameter

1ZCD064078

20

Oil side

Lower core length


(tolerance 5 mm)

RTKF 24150/5000 F

1ZCD064028

design

19

Current transformer extension

RTKF 24150/5000 F KSI

 18

data

18

Weights

With porcelain insulator

1ZCD064077

17

With silicone composite insulator

RTKF 24150/4000 F

1ZCD064027

a1

16

Installation (v = vertical,
h = horizontal, from vertical)

1ZCD064076

RTKF 24150/4000 F KSI

30 40

15

Mechanical

Arcing distance (minimum)

1ZCD064026

 D1

14

Creepage distance (minimum)

RTKF 24150/2500 F

13

Insulator

Thermal short-time current


Ith 2 sec.

RTKF 24150/2500 F KSI

the transformer lead)

Fig. 12

12

Current

Ith 2 sec. = 25 Ir

insulator

Flange detail

60

11

Maximum operating current


(in respect to CT extension L6)

composite insulator

L6 Current
transformer extension
Spaltenbreiten

Flange
6

10

Lightning impulse voltage,


1.2/50 s

30

30

AC test voltage dry / wet

With porcelain

d2

Fig. 11

Rated max.
line-to-ground voltage

With silicone

In = 5000 A

Fig. 10

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

4 Earthing screws 2 M12 / 180

Air side

 D1

IEC 60137 (2008)

6 Sealing area
 c2
7 Removability (for connecting

 D6
max.

L 2 (5)

 D6
max.

System voltage

3 De-aeration

L5
max.

L5
max.

Electrical characteristics

2 Test tap

 D5

 D5

Cantilever operating load

Type and drawing

AC test voltage dry / wet

nickel-plated, silver-plated)

Rated Voltage Ur

c2

c2

1 Copper, bare (optional:

Cantilever test load, 1 min.

 d2

 d2

L 2 (5)

27, 28 Maximum head and shed diameter for porcelain insulator


31, 32 Sealing area
37
Bushing length L, without air side terminal and
oil side shield
38, 39 Standard terminal on air side
40, 41 Optional terminal on air side
42, 43 Standard design of oil side terminal
4446 Standard design of oil side end
4749 Optional design of oil side end

Fig. 4

(L)

Rated voltages according to IEC 60137 (2008)


Rated voltages according to IEEE C57.19.01 (2000)
Maximum operating current Ir as a function of the
current transformer extension L6
12
Maximum thermal short-circuit current, 2 sec.,
after operation at maximum operating current
15
Bending test load, 1 min.
16, 17 Maximum cantilever operating load and permissible
installation position (v = vertical, h = horizontal,
from vertical)
25, 26 Maximum head and shed diameter for silicone
composite insulator
36
710
11

All dimensions in mm, unless otherwise indicated

Data for bushings with fixed conductor 24 170 kV

Bushings with fixed conductor 24 170 kV


Fig. 3

Ur / 3

Explanations of the table columns

30

30

31

31

31

31

30

30

31

31

31

31

30

30

30

30

31

31

30

30 107 160 200 24

30

30

31

31

30 107 160 200 24


30 140 180 200 24
30 107 160 200 24
31 140 180 200 24
30 107 160 200 24
31 140 180 200 24

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

22

AirRIP bushings 245550 kV


Types with cable conductor

Legend

RTKF 2451050/1000 KSI RTKF 2451050/1000 245 141 505 / 460


1ZCD064019

1ZCD064069

RTKF 2451050/1600 KSI RTKF 2451050/1600 245 141 505 / 460


1ZCD064020

1ZCD064070

c7

1ZCD064023

Flange

Flange detail

.25
11

1ZCD064025

nv

15

1ZCD064075

870 /

data

design

20

21 22

23

24

25

26 27

Weights Oil side

28

29

30

31

32

33

Air side

34

35

36

37 38 39 40 41 42

Flange

[kV] [kV] [kV]

[kV]

43 44 45 46 47 48
Air side

[A]
1 050 750 230 146 425 / 350 900 750 1 030
880
820
1 050 750 230 146 425 / 350 900 750 1 700
1 560
1 450
1 000
1 175 850
850
780
2 250
1 175 850
2 100
2 000
1 100
1 675 1 175
1 250
1 000
2 000
1 675 1 175
1 850
1 700
1 800 1 240 500 318
750 / 1 675 1 175 1 050
1 100
900

[mm2]
665
1 500
665
2 800
1 200
1 500
1 500
2 800
1 200
1 500
1 500

52

53 54

terminal

[mm] [mm]
[N]
[N]
[kg]
7 595 2 050 5 000 2 500 v30 190
200
209
7 595 2 050 5 000 2500 v30 272
286
301
9 300 2 370 5 000 2 500 v30 296
312
328
9 300 2 370 5 000 2 500 v30 422
444
466
13 020 3 600 5 000 2 500 v30 614
632
654
13 020 3 600 5 000 2 500 v30 782
813
845
13 750 4 000 5 000 2 500 v30 862
889
921

[kg]
L 6 L 16 D1
376
0 590 185
386
300 890
396
600 1 190
487
0 590 234
502
300 890
516
600 1 190
574
0 590 234
590
300 890
600 1 190
606
801
0 590 285
823
300 890
845
600 1 190
1 130 0200 790 285
1 148
300 1 090
1 170
600 1 390
1 423
0 790 338
1 454
300 1 090
1 486
600 1 390
1 553 0200 850 338
1 580
300 1 150
1 612
600 1 450

d3

L2
L 4 L 5 D5 D6 D5 D6 D3 D4 D2 D8 n v s Fig
L
50 2 465 2 290 175 245 370 315 450 400 450 245 365 12 20 22 12 3 055
3 355
3 655
80 2 474 2 299 184 315 428 375 480 400 450 295 365 12 20 22 13 3 064
3 364
3 664
50 2 794 2 619 184 315 428 375 480 400 450 295 365 12 20 22 13 3 384
3 684
3 984
100 2 920 2 745 200 365 479 435 520 450 500 355 415 12 20 25 13 3 510
3 810
4 110
65 4 150 3 975 200 550 479 550 520 620 680 355 580 16 22 25 14 4 940
80
5 240
80
5540
100 4 200 4 025 200 550 547 550 580 620 680 410 580 16 22 25 14 4 990
5 290
5 590
65 4 600 4 425 200 550 547 550 580 620 680 410 580 16 22 25 14 5 450
80
5 750
80
6 050

d2 c2 d2 c2 d5 d6
30 80 40 125

c7 Fig d5 d6

Figure

Shield length below L 16

Shield diameter

Variant

Opening

Standard

Figure

Var.

Shield length below L 16

Length of terminal

Figure

Bushing length, without air


side terminal and lower shield

Flange plate thickness

Hole diameter

Number of holes

Sealing area: max. diameter

Sealing area: min. diameter

Outside flange diameter

Pitch circle diameter

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
silicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

Height of head (maximum)

Cable bolt:
distance from the flange plate

Terminal: distance from the


flange plate (tolerance 5 mm)

Inside tube diameter

Core diameter

Lower core length


(tolerance 5 mm)

Current transformer extension

With porcelain insulator

With silicone composite insulator

Installation (v = vertical,
h = horizontal, from vertical)

[kV]

Thermal short-time current Ith2 sec.

[kV]

49 50 51

Oil side end

c7 Fig

95 180 130 21 140 180 200 22

30 80 40 125 140 180 170 22 140 180 200 22


30 80 40 125 134 230 200 23
40 125 50 125 176 292 230 23
30 80 40 125 176 292 230 23
40 125 50 125 176 292 230 23
30 80 40 125 176 292 230 23

Ith 2 sec. [kA] = 0.055 S [mm 2 ] if S = 1200 mm 2


s

15

750 /

1ZCD064074

19

Mechanical

* Ith 2 sec. [kA] = 0.06 S [mm 2 ] if S 700 mm 2

2 2.

30

30

750 /

1ZCD064073

RTKF 5501800/1000 KSI RTKF 5501800/1000 550 318

2. 5
2

16

12

12

1ZCD064024

560 /

1ZCD064072

RTKF 4201675/2000 KSI RTKF 4201675/2000 420 242

Fig. 14

5 45

Fig. 13

560 /

1ZCD064071

[kV]

see footnote *

L6

[kV]

With copper cable section S

20

[kV] [kV]

 D1

Maximum operating current


(in respect to CT extension L6)

the transformer lead)


L6 Current transformer extension

18

Std.

Switching impulse voltage


250/2500 s

7 Removability (for connecting


 D6
max.

17

Insulator

Shield diameter

15 16

Opening

14

Length of terminal

13

Current

Terminal diameter

12

Terminal diameter

11

Lightning impulse voltage,


1.2/50 s

insulator

L16 5

L16 5
c7

10

AC test voltage dry / wet

composite insulator

6 Sealing area

RTKF 4201675/1000 KSI RTKF 4201675/1000 420 242

Rated max.
line-to-ground voltage

5 Eyebolts 2 M16 / 180

Switching impulse voltage


250/2500 s

With porcelain

1ZCD064022

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

With silicone

AC test voltage dry / wet

4 Earthing screws 2 M12 / 180

RTKF 3001175/2000 KSI RTKF 3001175/2000 300 173

30

IEC 60137 (2008)

1ZCD064021

System voltage

3 De-aeration

RTKF 3001175/1000 KSI RTKF 3001175/1000 300 173

Fig. 12

2 Test tap
 D5

(L)
20
L6

 D1

Electrical characteristics

Cantilever operating load

Cantilever test load, 1 min.

Type and drawing

Arcing distance (minimum)

c2

Ur / 3

L4 cable bolts

 D5

 D6
max.

nickel-plated, silver-plated)

1
L5
max.

L5
max.

1 Copper, bare (optional:

Creepage distance (minimum)

 d2

L4 cable bolts

c2

 d2

L 2 (5)

26
Inner diameter of the central tube ( d3)
30, 31 Maximum head and shed diameter for silicone
composite insulator
32, 33 Maximum head and shed diameter for porcelain insulator
36, 37 Sealing area
42
Bushing length L, without air side terminal and
oil side shield
43, 44 Standard terminal on air side
45, 46 Optional terminal on air side
4750 Standard design of oil side end
5154 Optional design of oil side end

(L)

37
Rated voltages according to IEC 60137 (2008)
812 Rated voltages according to IEEE C57.19.01 (2000)
13, 14 Maximum operating current for the largest cable
cross-section, depending on the current transformer
extension L6
15
Maximum thermal short-circuit current, 2 sec.,
after operation at maximum operating current
18
Bending test load, 1 min.
19, 20 Maximum cantilever operating load and permissible
installation position (v = vertical, h = horizontal,
from vertical)
23
Standard current transformer extension L6

Fig. 6

Rated Voltage Ur

Fig. 5

All dimensions in mm, unless otherwise indicated

Data for bushings with cable conductor 245 550 kV

Bushings with cable conductor 245 550 kV

L 2 (5)

Explanations of the table columns

Ith 2 sec. [kA] = 0.05 S [mm 2 ] if S = 1500 mm 2

6
 D2

Ith 2 sec. [kA] = 0.045 S [mm 2 ] if S = 2800 mm 2

 D8
 D3
 D4

 D3
 D4

 D3
 D4

Oil side end


Fig. 23

Fig. 22
 d3

 d3

c7

L16

L16
20

L16
20

 d3

c7

c7

Fig. 21

 d5
 d6
 d5
 d6

23

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

24

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

 d5
 d6

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

25

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

26

AirRIP bushings 245550 kV


Types with rod conductor

Fig. 8

45

3 M10

110

65

60

3 M10

110

80

75

3 M12

110

100

95

6 M12

110

L16 5

L16 5

L6

 D1

Flange detail
Fig. 13

RTKF 2451050/2000 B KSI RTKF 2451050/2000 B 245 141

505 / 1 050

1ZCD064020

460 /

1ZCD064071
1ZCD064072

1ZCD064074

RTKF 5501800/2000 B KSI RTKF 5501800/2000 B 550 318


5

1ZCD064025

nv

1ZCD064075

560 / 1 175

750 230 146


850

/
560 / 1 175

850

/
750 / 1 675 1 175
/
750 / 1 675 1 175
/
870 / 1 800 1 240 500 318
/

data

design

20

21

Weights

22

23

24

25

Oil side

26

27

28

29

30

31

Air side

32

33

34

35

36 37 38 39 40

Flange

41

42

[N]

5 000 2 500 v30


5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30

[kg]
231
244
258
386
412
439
340
360
381
537
569
601
736
832
866
947
988
1 029
996
1 110
1 154

D5

D6

D5

245

370

315

315

428

375

315

428

375

365

479

435

550

479

550

550

547

550

550

547

550

D6 D3 D4 D2 D8 n v s Fig
L
450 400 450 245 365 12 20 22 12 3 055
3 355
3 655
480 400 450 295 365 12 20 22 13 3 064
3 364
3 664
480 400 450 295 365 12 20 22 13 3 384
3 684
3 984
520 450 500 355 415 12 20 25 13 3 510
3 810
4 110
520 620 680 355 580 16 22 25 14 4 940
5 240
5 540
580 620 680 410 580 16 22 25 14 4 990
5 290
5 590
580 620 680 410 580 16 22 25 14 5 450
5 750
6 050

d2

47

48

d5

d6

Figure

c2

Shield length below L 16

Standard

c2 d2

Shield diameter

Opening

Bushing length, without air


side terminal and lower shield

Figure

Flange plate thickness

Hole diameter

Number of holes

Sealing area: max. diameter

Sealing area: min. diameter

Outside flange diameter

Pitch circle diameter

Max. shed diameter


(with porcelain insulator)

Head diameter
(with porcelain insulator)

Max. shed diameter (with


silicone composite insulator)

Head diameter (with silicone


composite insulator)

Height of head (maximum)

Terminal: distance from the


flange plate (tolerance 5 mm)

Inside tube diameter

Core diameter

Lower core length


(tolerance 5 mm)

Current transformer extension

[kg]
L6
L 16 D1 d3
L2 L5
417
0
590 185 50 2 465 175
431
300
890
445
600 1 190
601
0
590 234 80 2 474 184
628
300
890
654
600 1 190
618
0
590 234 50 2 794 184
638
300
890
659
600 1 190
915
0
590 285 100 2 920 200
947
300
890
980
600 1 190
1 252 0200
790 285 65 4 150 200
1 348
300 1 090
80
1 382
600 1 390
80
1 588
0
790 338 100 4 200 200
1 629
300 1 090
1 669
600 1 390
1 687 0200
850 338 65 4 600 200
1 800
300 1 150
80
1 845
600 1 450
80

Var.

Shield diameter

[N]

46

Oil side end

Opening

[A] [kA] [mm] [mm]


750 1 650
7 595 2 050
1 510
350 /
1 400
425 / 900 750 2 400
7 595 2 050
2 230
350 /
2 100
1 600
9 300 2 370
1 440
1 340
3 000
9 300 2 370
2 800
2 600
1 800
13 020 3 600
2 000
1 800
2 800
13 020 3 600
2 650
2 500
750 / 1 675 1 175 1 850
13 750 4 000
2 000
/
1 750

With porcelain insulator

[kV]

900

With silicone composite insulator

[kV]

Installation (v = vertical,
h = horizontal, from vertical)

[kV]

44 45

terminal
Std

425 /

43

Air side

c7 Fig

40 125 30 80 140 180 200

22

40 125

140 180 200

22

40 125 30 80 134 230 200

23

50 125

176 292 230

23

40 125

176 292 230

23

50 125

176 292 230

23

40 125

176 292 230

23

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

30

16

2 2.
5

15

15

2. 5
2

30

30

.25
11

12

12

a1

1ZCD064024

30

1ZCD064073

19

Figure

460 /

1ZCD064070

18

Mechanical

Shield length below L 16

1ZCD064019

RTKF 4201675/2500 B KSI RTKF 4201675/2500 B 420 242

Fig. 14

5 45

Fig. 12

6
 D2
 D8

Oil side terminal


L16

d1 c1

30

L16

n g1

thread c1

50

45

20

2 18

M363 60

40 85

65

60

30

2 18

M423 80

30
50 85

80

75

30

2 18

100

95

30

4 18

50 85

30

Var. 1:
thread
L16

* See column 25 of the data table

30

L16

see column 40 of the data table


AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

d1G
d1G

 d4

 D3
 D4

40
40 20
20

 g1
 g1
40
85
40  d4 85
 d4

Var. L16
2: round

Oil side end


Fig. 22

Fig. 23
 d3

 d3

30
30

 d4
 d4
5
5

 d4
 d4

 D3
 D4

30

L16

30

c1

30

L: Bushing length, without airside terminal and lower shield,

L16

 g1
40
 g1
40 20
 d4
85
20
a1
 d4
85

30

30

L16

c1
c1

10

a1

 D3
 D4

L16
20

Standard: flat

c7

Var. 2
round

L16
20

Var. 1
thread

c7

Standard
flat
thickness holes

27

750 230 146

1ZCD064022

Flange

 d4

[kV] [kV] [kV]

505 / 1 050

RTKF 4201675/1600 B KSI RTKF 4201675/1600 B 420 242

* See column 25 of the data table

 d3 *

[kV]

RTKF 2451050/1600 B KSI RTKF 2451050/1600 B 245 141


1ZCD064069

[kV]

17

Cantilever operating load

the transformer lead)


L6 Current transformer extension

16

Insulator

IEEE C57.19.01 (2000)


Thermal short-time current Ith2 sec.

7 Removability (for connecting


 D6
max.

RTKF 3001175/2500 B KSI RTKF 3001175/2500 B 300 173

30

14 15

Current

Maximum operating current


(in respect to CT extension L6)

insulator

1ZCD064023

30

13

Ith 2 sec. = 25 Ir

50

12

Switching impulse voltage


250/2500 s

composite insulator

6 Sealing area

c7

length e1

11

Lightning impulse voltage,


1.2/50 s

20
L6

 D1

c7

screws

10

AC test voltage dry / wet

5 Eyebolts 2 M16 / 180

1ZCD064021

e1

 d4

Rated max.
line-to-ground voltage

With porcelain

RTKF 3001175/1600 B KSI RTKF 3001175/1600 B 300 173

20

 d3 *

System voltage

 D6
max.

With silicone

[kV] [kV]

Optional splitting of the rod conductor


Determine whether the rod conductor should be split or not.
Rod conductors are split 20 mm below the base plate and
have the following characteristics:

Switching impulse voltage


250/2500 s

125

Lightning impulse voltage,


1.2/50 s

50

AC test voltage dry / wet

3500

4 Earthing screws 2 M12 / 180

Ur / 3

125

IEC 60137 (2008)

20

80

40

L 2 (5)

30

2500

Electrical characteristics

(L)

1600

Type and drawing

3 De-aeration

L5
max.

L5
max.
L 2 (5)

c2

2 Test tap
 D5

 D5

(L)

d2

nickel-plated, silver-plated)

c2

c2

c2

Max. operating current (A)

1 Copper, bare (optional:

Cantilever test load, 1 min.

 d2

 d2

Arcing distance (minimum)

 d2

Air side terminal


Standard terminals as per columns 39/40,
variants as per columns 41/42
Guidelines for the terminal dimensions:

Legend

Creepage distance (minimum)

Fig. 7

All dimensions in mm, unless otherwise indicated

Data for bushings with rod conductor 245 550 kV

Bushings with rod conductor 245 550 kV

Rated Voltage Ur

Determination of the rod conductor

10
d1
d1

 d5
 d6

c1
c1
28

 d5
 d6

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

29

AirRIP bushings 245550 kV


Types with fixed conductor
Bushings with fixed conductor 245 550 kV
Legend

[kV]

[kV] [kV] [kV]

RTKF 2451050/2000 F KSI RTKF 2451050/2000 F 245 141

505 / 1 050

750 230 146

1ZCD064044

460 /

RTKF 2451050/3150 F KSI RTKF 2451050/3150 F 245 141

505 / 1 050

1ZCD064045

460 /

1ZCD064095
1ZCD064096

RTKF 3001175/3150 F KSI RTKF 3001175/3150 F 300 173


c7

1ZCD064047

1ZCD064097

RTKF 4201675/2500 F KSI RTKF 4201675/2500 F 420 242


1ZCD064048

Flange detail

Flange

RTKF 4201675/3150 F KSI RTKF 4201675/3150 F 420 242


1ZCD064049

Fig. 14

30

.25
11

nv

1ZCD064100

850

/
560 / 1 175

850

/
750 / 1 675 1 175
/
750 / 1 675 1 175
/
870 / 1 800 1 240 500 318
/

23

24

25

26

27

28

29

30

Air side

31

32

33

34

35 36 37 38 39

Flange

[A] [kA] [mm] [mm]


750 2 150
7 595 2 050
2 050
350 /
1 950
425 / 900 750 3 150
7 595 2 050
3 000
350 /
2 900
2 100
9 300 2 370
2 000
1 900
3 800
9 300 2 370
3 600
3 400
2 300
13 020 3 600
2 600
2 400
3 250
13 020 3 600
2 900
2 600
750 / 1 675 1 175 2 100
13 750 4 000
2 200
/
1 950

[N]

[N]

5 000 2 500 v30


5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30
5 000 2 500 v30

[kg]
263
280
297
361
385
409
378
401
425
557
591
625
807
790
821
977
1 019
1 062
1 079
1 066
1 108

[kg]
L6
L 16 D1
L2
0
449
590 185 2 438
300
466
890
600 1 190
483
0
577
590 234 2 447
300
601
890
600 1 190
624
0
656
590 234 2 767
300
679
890
600 1 190
703
0
936
590 285 2 893
300
969
890
600 1 190
1 003
1 323 0200
790 285 4 123
300 1 090
1 306
600 1 390
1 337
0
1 618
790 338 4 173
300 1 090
1 660
600 1 390
1 703
1 769 0200
850 338 4 573
300 1 150
1 757
600 1 450
1 799

L5

D5

D6

D5

148

245

370

315

157

315

428

375

157

315

428

375

173

365

479

435

173

550

479

550

173

550

547

550

173

550

547

550

Figure

Bushing length, without air


side terminal and lower shield

Flange plate thickness

Hole diameter

Number of holes

Sealing area: max. diameter

Sealing area: min. diameter

Outside flange diameter

Pitch circle diameter

Max. shed diameter


(with porcelain insulator)

Head diameter
(with porcelain insulator)

Max. shed diameter (with


silicone composite insulator)

Head diameter (with silicone


composite insulator)

Height of head (maximum)

Terminal: distance from the


flange plate (tolerance 5 mm)

Core diameter

Lower core length


(tolerance 5 mm)

Current transformer extension

With porcelain insulator

With silicone composite insulator

Thermal short-time current Ith2 sec.

[kV]

900

Maximum operating current


(in respect to CT extension L6)

[kV]

40

41

Air side

D6 D3 D4 D2 D8 n v s Fig
L
450 400 450 245 365 12 20 22 12 3 028
3 328
3 628
480 400 450 295 365 12 20 22 13 3 037
3 337
3 637
480 400 450 295 365 12 20 22 13 3 357
3 657
3 957
520 450 500 355 415 12 20 25 13 3 483
3 783
4 083
520 620 680 355 580 16 22 25 14 4 913
5 213
5 513
580 620 680 410 580 16 22 25 14 4 963
5 263
5 563
580 620 680 410 580 16 22 25 14 5 423
5 723
6 023

42

43

Oil side

terminal

terminal

Standard

Standard

44

45

46

47

Oil side end


Standard

d5

d6

Figure

22
Oil side

Shield length below L 16

design

21

Shield diameter

data

20

Weights

d2

c2

d4

Fig

40

125

52

30 140 180 200

c7 Fig
24

50

125

80

31 140 180 200

24

40

125

52

30 134 230 200

25

60

125

100

31 176 292 230

25

40

125

65
80
80

30 176 292 230


31
31

25

50

125

100

31 176 292 230

25

40

125

65
80
80

30 176 292 230


31
31

25

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

34

15

15

1ZCD064050

19

2 2.

30

30

18

Mechanical

16

12

12

1ZCD064099

RTKF 5501800/2000 F KSI RTKF 5501800/2000 F 550 318

2 2. 5

5 45

Fig. 13

1ZCD064098

560 / 1 175

750 230 146

[kV]

425 /

Ith 2 sec. = 25 Ir

1ZCD064094

[kV]

Switching impulse voltage


250/2500 s

L6

 D1

Lightning impulse voltage,


1.2/50 s

20

(L)

the transformer lead)


L6 Current transformer extension

Ur / 3

7 Removability (for connecting


 D6
max.

17

IEEE C57.19.01 (2000)

AC test voltage dry / wet

insulator

16

Insulator

Opening

14 15

Figure

13

Terminal width

12

Length of terminal

11

Terminal diameter

10

Rated max.
line-to-ground voltage

composite insulator

L16 5

L16 5

Current

System voltage

5 Eyebolts 2 M16 / 180

1ZCD064046
c7

Switching impulse voltage


250/2500 s

With porcelain

RTKF 3001175/2000 F KSI RTKF 3001175/2000 F 300 173

Lightning impulse voltage,


1.2/50 s

With silicone

AC test voltage dry / wet

4 Earthing screws 2 M12 / 180

[kV] [kV]

IEC 60137 (2008)

6 Sealing area

 D1

Fig. 12

Installation (v = vertical,
h = horizontal, from vertical)

Electrical characteristics

3 De-aeration

L5
max.

20

2 Test tap
 D5

L5
max.

L6

Type and drawing

Cantilever operating load

 D5

 D6
max.

nickel-plated, silver-plated)

Cantilever test load, 1 min.

1 Copper, bare (optional:

c2

c2

Arcing distance (minimum)

 d2

Creepage distance (minimum)

 d2

(L)

22
Standard current transformer extension L6
27, 28 Maximum head and shed diameter for silicone
composite insulator
29, 30 Maximum head and shed diameter for porcelain insulator
33, 34 Sealing area
39
Bushing length L, without air side terminal and
oil side shield
40, 41 Standard terminal on air side
42, 43 Standard oil side terminal
4447 Standard design of oil side end

L 2 (5)

Rated voltages according to IEC 60137 (2008)


Rated voltages according to IEEE C57.19.01 (2000)
Maximum operating current as a function of the
current transformer extension L6
14
Maximum thermal short-circuit current, 2 sec.,
after operation at maximum operating current
17
Bending test load, 1 min.
18, 19 Maximum cantilever operating load and permissible
installation position (v = vertical, h = horizontal,
from vertical)
37
812
13

All dimensions in mm, unless otherwise indicated

Data for bushings with fixed conductor 245 550 kV

Fig. 8

Rated Voltage Ur

Fig. 7

L 2 (5)

Explanations of the table columns

6
 D2
 D8

 D3
 D4

 D3
 D4

 D3
 D4

Oil side end

Oil side

Fig. 24

Fig. 25
 d3

Fig. 30

Fig. 31

30
 d5
 d6

31

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

32

 d5
 d6

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

 d4

30
30

85


18

20 40


18

85

20 40

c7

c7

30

L16

L16

L16
20

L16
20

 d3

40
 d4

Micafil Transformer Bushings | AirRIP / RTKF 24 550 kV

33

Other Micafil RIP bushings

ABB offers an extensive range of high-quality products.


They can be adapted to different transformer and plant
designs and thus meet the requirements of the most varied applications. In addition, our company is specialized
in tailor-made solutions including custom designs and
small series production.
Our range of products encompasses bushings for
oil-outdoor, oil-SF 6, oil-oil transformer systems as well as
outdoor-SF6 bushings for GIS. If you dont see what you need
right here, please get in touch with us we can address
your individual needs in a highly professional, flexible and
efficient manner. Our bushings are developed and approved
for mineral oil applications.

Transformer bushings, oil-outdoor

Transformer bushings, oil-SF6

Outdoor-SF6 bushings for GIS

Series: AirRIP / RTKF KSI


Silicone composite insulator available with straight
or helical sheds
Voltage range: from 24 to 550 kV
Current range: up to 5000 A

Series: GARIP / RTKG


Voltage range: from 36 to 550 kV
Current range: up to 4000 A

Series: RAKF
Porcelain or silicone composite insulator
Voltage range: from 245 to 550 kV
Current range: up to 4000 A

Transformer bushings, oil-oil

Wall bushings

Series: ORIP / RTKK


Voltage range: from 72.5 to 550 kV
Current range: up to 4000 A

Series: RMI indoor-indoor


RMF outdoor-indoor
RMFF outdoor-outdoor
Porcelain or silicone composite insulator
Voltage range: from 24 to 300 kV
Current range: up to 5000 A

Series: AirRIP / RTKF


Porcelain insulator
Voltage range: from 24 to 550 kV
Current range: up to 5000 A

Series: SeismicRIP / RTKF KSI


Silicone composite insulator
Voltage range: from 69 to 550 kV
Current range: up to 5000 A
Standard: IEEE 693 (2005)
High seismic performance level

Railway bushings
Series: HIRIP high-current RTXF
Porcelain insulator
Voltage range: up to 36 kV
Current range: up to 40 000 A

35

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

Series: RMF / RTAK porcelain insulator


Voltage range: from 15 to 36 kV
Current range: up to 2000 A

36

AirRIP / RTKF 24 550 kV | Micafil Transformer Bushings

ABB Switzerland Ltd


High Voltage Components
Badenerstrasse 780
CH-8048 Zurich/Switzerland
Phone + 41 58 586 03 33
Fax +41 58 586 04 44
E-mail: info.micafil @ch.abb.com
www.abb.com/electricalcomponents

Note
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the a greed
particulars shall prevail. ABBS witzerlandLtd
does not accept any responsibility whatsoever
for p otential errors or possible lack of information
in this document. We reserve all rights in this
d ocument and in the subject matter and illustrations
contained therein. Any reproduction, d isclosure to
third parties or u tilization of its c
ontents in w hole
or in parts is forbidden w
ithout prior written
c onsent of ABB Switzerland Ltd.
Copyright 2014 ABB
All rights reserved.

1ZCD067932AA EN 04/2014. Subject to change.