Professional Documents
Culture Documents
Supplement to Ch. 13, Indoor Environmental Modeling, of the 2013 ASHRAE HandbookFundamentals
(A)
Fig. E1
(B)
(A) Danish Pavilion at World Exposition EXPO 92 in Seville and (B) Cooling Elements in South Gable of Danish
Pavilion
The room had a complicated geometry, but two-dimensional prediction was used to get preliminary results. The focus was
especially aimed at draft in the occupied zone and the ability to obtain stratified flow with a large vertical temperature gradient, which
prevented heated air from the upper part of the room from reaching the occupied zone.
2
Figure E2 shows the results of a simulation when the occupied-zone load was 8.56 Btu/hft and the load in the upper part of the
room was 95.1 Btu/hft. Velocity in the occupied zone was restricted to 1.3 to 1.6 fps, which was high compared to that in an ordinary
room, but was acceptable in an exhibition pavilion. Thermal stratification was generated in the room, and heat emission from slides
and video equipment was maintained in the upper part of the room (Nielsen 1995).
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E3
2
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E5
Fig. E4
The buildings energy consumption was calculated by a BEPS program, which was unable to predict flow between zones 1, 2,
and 3 as a function of the pressure and temperature distribution in the zones. It was assumed, as an initial guess, that energy flow
between the zones was low and therefore unimportant.
Figure E6 shows temperature development in the three zones during a week in June (week 23) when the building was loaded
according to the reference year. The library hall (zone 1) was heated by solar radiation through skylights, and at times the hall
reached a temperature level 14.4F above that in the surrounding zones. This temperature difference induced energy flow between
the zones, making it necessary to extend the program to include information on the air movement in the open connections in the
building.
3
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E6
Flow between zones 1, 2, and 3 was found from CFD predictions of all three zones. Different situations during the reference
year were selected for this analysis. Boundary conditions for energy flow were obtained by the BEPS program, based on given values
of the heat transfer coefficient. The boundary conditions could also have been given as a temperature distribution, but it was difficult
to make an accurate prediction of the heat transfer coefficient with the wall functions in a CFD program (Chen and Jiang 1992;
Nielsen 1998).
The final solution required iteration between the BEPS and CFD programs, because a change in airflow between the three zones
changed the temperature level and energy flow in the surrounding surfaces.
Figure E7 shows the stages of iteration. The initial BEPS predictions were made without air exchange between the zones 1, 2,
and 3. Then, a CFD computation was used to determine the air exchange values, which were introduced into the BEPS program to
generate new energy flows at the zone surfaces. The CFD program then computed new air exchanges between the three zones
based on the updated energy flow inputs. Iteration continued until the difference in airflows from one iteration to the next was below
5%.
Fig. E7
Figure E8 shows temperature development in the three zones during week 23 when air exchange was considered. Airflow
between the zones decreased both the temperature differences between the zones and the temperature level in the library hall. The
4
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E8
Air quality evaluation in the library hall was also based on CFD predictions. The prediction was made for a geometry
corresponding to the halls layout, including bookcases in the occupied zone but without zones 2 and 3. The effect of these zones
was introduced by flow rates and temperatures through vertical surfaces in the hall.
Indoor air quality problems were noticed during winter because the library hall was heated by the ventilation system, and
supply air seemed to bypass the occupied zone because of buoyancy. Figure E9 shows air distribution in the hall on January 8
at 11:00 AM. The heated jets (9662 cfm, 90.5F) rose and generated radial flow below the ceiling. Air moved down in the corners
of the hall because three of the corners were without supply openings. Flow in the bottom left corner of the figure was from zone
2, which in this situation supplied air to the occupied zone at 4386 cfm and 65.5F. Flow in the top left corner of the figure was
partly cold downdraft from a glazed area in this corner, and partly induced flow from the upper part of the building. Velocity was
very low in the main part of the occupied zone, which corresponded to low ventilation efficiency in this area of the hall.
Fig. E9
Air Movement and Concentration Distribution at Floor Level (0.8 ft) in Library Hall
Moreover, a pollutant concentration distribution was predicted for a situation where the low surfaces in the hall were the sources
of a pollutant. The maximum concentration cP/cR in the occupied zone had a level of 2.05, which corresponded to a local ventilation
index p of 0.49 (cP was the concentration in the air and cR was the mean concentration in the return openings). The average
concentration in the occupied zone, coc/cR, was 1.3, which corresponded to a mean ventilation efficiency of 0.77. This was not high,
and it can be reasoned that recirculation in the ventilation system would further decrease the level of fresh air in the occupied zone.
5
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E10
For mixed ventilation, air was supplied by a single 2 by 2 ft square diffuser with a circular throw pattern and a 8 in. supply duct.
For displacement ventilation, air was supplied by two identical corner displacement diffusers that were 9 by 9 by 30 in. Both diffusers
were modeled using the momentum method summarized in ASHRAE Research Project RP-1009 (Chen and Srebric 2000).
Modeling Decisions
Symmetry was not used because the mixed ventilation case was asymmetric (because of the position of the return), and the
displacement ventilation case was symmetric only about the diagonal.
The incompressible Navier-Stokes equations were solved using the Boussinesq approximation that accounted for density variations
with temperature.
Direct heating of the air by lighting was assumed to be 50% of the total heat load, and was added uniformly to the air immediately
below the lights. The remaining reradiated heat load was added uniformly to the air immediately above the floor and table.
The LVEL k- turbulence model was used. This model uses an algebraic model (LVEL) to estimate the enhanced heat and
momentum transport near solid objects and the standard k- model in the bulk fluid.
The mixed and displacement ventilation cases contained 256,000 and 171,000 total grid cells, respectively (Figure E11). A
Cartesian grid was used, with several localized regions of finer grid located in regions of greater geometrical detail and/or steep
gradients. (The mixed-ventilation case included two nested grid regions around the diffuser.)
6
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E11
Radiation heat transfer was not accounted for; this can cause overprediction of buoyant thermal plume strength from occupants and
the amount of temperature stratification from floor to ceiling, because radiative exchange between the cool floor and the surrounding
walls is neglected. However, the example is still useful in showing many aspects of typical CFD analysis.
Results. Airflow patterns (Figure E12) reveal the fundamental differences between the two ventilation schemes. The
displacement system supplied relatively low-velocity air over a much greater area. Thus, airflow was driven primarily by buoyancy
forces associated with heat sources in the room. In contrast, the mixed ventilation system supplied relatively high-momentum airflow,
resulting in several distinct jets along the ceiling and good mixing in the room.
Fig. E12
Airflow Patterns
Because the heat load and air volume were identical in each case, the temperature difference between supply and extract was
identical (13F) as well. With iteration, the supply air temperatures required to meet the design condition were found to be 62 and
66F. Displacement ventilation produced a more stratified temperature distribution (Figure F13) and a higher return temperature,
which would have possibly yielded a higher efficiency from the air handler. Mixed ventilation produced more uniform temperatures
throughout the room.
The predicted percentage dissatisfied (PPD) (Fanger 1972; Lin et al. 1992) (Figure E14) further highlights the differences between
the two schemes. The mixed ventilation system yielded a more uniformly conditioned space, whereas the displacement ventilation
system delivered a comfortable environment only in the occupied portion of the room.
7
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E13
Fig. E14
Temperature
Figures E15 to E17 show a similar procedure for a collegiate ice rink. Figures E18 to E20 present ventilation for a
pharmaceutical laboratory. Natural ventilation for fire and smoke management is modeled in Figures E21 to E23. Figures E24 to E27
illustrate airflow paths, velocity vectors, and relative humidity for an auditorium.
8
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E15
Fig. E16
Plan View of Airflow Patterns from Supply Diffusers on Either Side of Arena in Ice Rink
9
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E17
Contours of Local Air Temperature and Predicted Percent Dissatisfied (PPD) on Vertical Plane in Ice Rink
10
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E18
Fig. E19
11
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E20
Flow Pathlines from Supply Diffuser and Plane Immediately in Front of Fume Hood
Fig. E21
12
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E22
Flow Paths from Fire Region and Contours of Smoke Concentration on Vertical Plane
13
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
14
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E24
Fig. E25
Flow Pathlines from Displacement Diffusers Shaded by Local Air Temperature in Auditorium
15
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.
Fig. E26
Fig. E27
16
ThisfileislicensedtoBrianWong(bwong@blackandmcdonald.com).ASHRAEHandbookOnlinesubscriptionisforindividualuse.CopyrightASHRAE.