You are on page 1of 5

electrical-engineering-portal.

com

http://electrical-engineering-portal.com/electrical-safety-standards-for-lvmvhv-part-3

Electrical Safety Standards for LV/MV/HV (Part-3)

Electrical Safety Standards for LV/MV/HV part 3 (On photo transmission tower in India)

Continued from part 2 Electrical Safety Standards for LV/MV/HV (Part-2)

Content
Standard: Northern Ireland Electricity (NIE), 6/025 ENA
Code: Indian Electricity Rules / Central Electricity Authority
1. Right of Way Clearance (As per GETCO Standard)
2. Minimum clearances between Electrical Lines crossing each other
3. Permissible Min ground Clearance of Electrical Line
4. Clearance for Telephone line Crossings Power Line
5. Vertical Clearance between Electrical Line and railway tracks
6. Clearance from Buildings to low, medium & high voltage lines

7. Clearance above ground at the lowest conductor


8. Vertical Clearance at Middle of Span
9. Safety Clearance from Live Part in Outdoor Substation
10. Lying of Telecommunication Cables with Power Cables (>33 kV)
11. Safe approach limits for people

Code: Indian Electricity Rules / Central Electricity Authority


Right of Way Clearance (As per GETCO Standard)
KV

Min ROW

66 KV

18 Meter

132 KV

27 Meter

220 KV

35 Meter

400KV

52 Meter (Single Circuit)

400 KV

48 Meter (Double Circuit)

Go to Content

Minimum clearances between Electrical Lines crossing each other


Voltage

66 KV

132 KV

220 KV

400 KV

66 KV

2.4 Meter

3 Meter

4.5 Meter

5.4 Meter

132 KV

3 Meter

3 Meter

4.5 Meter

5.4 Meter

220 KV

4.5 Meter

4.5 Meter

4.5 Meter

5.4 Meter

400 KV

4.5 Meter

5.4 Meter

5.4 Meter

5.4 Meter

Go to Content

Permissible Min ground Clearance of Electrical Line


KV

Ground Clearance

Over National Highway

66 KV

6.1 Meter

8.0 Meter

132 KV

6.1 Meter

8.6 Meter

220 KV

7.0 Meter

9.8 Meter

400KV

8.8 Meter

10.8 Meter

Go to Content

Clearance for Telephone line Crossings Power Line


KV

Clearance (Min)

66 KV

2.4 Meter

132 KV

2.7 Meter

220 KV

3.0 Meter

Go to Content

Vertical Clearance between Electrical Line and railway tracks


KV

Clearance (Min)

66 KV

14 Meter

132 KV

14.6 Meter

220 KV

15.4 Meter

400 KV

17.9 Meter

Go to Content

Clearance from Buildings to low, medium and high voltage lines


Voltage

Description

Distance

Low &
Medium
Voltage

Flat roof, open balcony, verandah roof ,When the line passes above the
building a vertical clearance from the highest point

2.5 Meter

Low &
Medium
Voltage

Line passes adjacent to the building a horizontal clearance from the


nearest point

1.2 Meter

Low &
Medium
Voltage

Line passes above the building a vertical clearance

2.5 Meter

Low &
Medium
Voltage

Line passes adjacent the building a Horizontal clearance

1.2 Meter

11 KV to 33
KV

Line passes above or adjacent to any building or part of a building

3.7 Meter

Above 33
KV

Line passes above or adjacent to any building or part of a building

3.7+(0.3 for every


additional 33 KV )

Up to 11 KV

The horizontal clearance between the nearer conductor and any part of
such building

1.2 Meter

11 KV to 33
KV

The horizontal clearance between the nearer conductor and any part of
such building

2.0 Meter

Above 33
KV

The horizontal clearance between the nearer conductor and any part
ofsuch building

2.0 + (0.3 for every


additional 33 KV )

Go to Content

Clearance above ground at the lowest conductor


Voltage

Description

Distance

Low & Medium


Voltage

Across a street

5.8 Meter

High Voltage

Across a street

6.1 Meter

Low & Medium


Voltage

Along a street

5.5 Meter

High Voltage

Along a street

5.8 Meter

Low & Medium


Voltage

Elsewhere than along or across any street

4.0 Meter

High Voltage

Elsewhere than along or across any street

5.2 Meter

33 KV & EHV

Clearance above ground(Add 0.3 Meter for every 33 KV Volts in 5.2


Meter)

Min 6.1
Meter

Go to Content

Vertical Clearance at Middle of Span


Span

Vertical Clearance (At Middle of Span)

200 Meter

4.0 Meter

300 Meter

5.5 Meter

400 Meter

7.0 Meter

500 Meter

8.5 Meter

Go to Content

Safety Clearance from Live Part in Outdoor Substation


KV

Safety Working Clearance

12 KV

2.6 Meter

36 KV

2.8 Meter

72.5 KV

3.1 Meter

145 KV

3.7 Meter

220 KV

4.3 Meter

400KV

6.4 Meter

800 KV

10.3 Meter

Go to Content

Lying of Telecommunication Cables with Power Cables (>33 kV)


Cable

Min. Distance

Power cable of voltage exceeding 33 kV shall be laid

Min 1.2 Meter depth

Underground telecommunication cable shall be with underground power cable


of voltage exceeding 33 kV.

Min 0.6 Meter Separate from


Power Cable

Go to Content

Safe approach limits for people


Voltage

214V to 415
KV

11KV

33KV

66KV

132KV

275KV

Person using manually operated


tool

1.3 Meter

2.0
Meter

3.0
Meter

4.0
Meter

5.0 Meter

6.0 Meter

Person using power operated tool

3.0 Meter

3.0
Meter

3.0
Meter

4.0
Meter

5.0 Meter

6.0 Meter

Go to Content