You are on page 1of 2

Liquid-Tuff Flexible Liquidtight Conduit

Industrial

LIQUID-TUFF
UL Liquidtight Flexible Non-Metallic Conduit Type A Orange
Type LFNC-A
Description
Layered Type A construction per NEC 356.2(1)
Nylon reinforced braid between two layers of PVC for
strength and flexibility
Flame retardant compound
Sunlight resistant
Oil resistant
Mild acid resistance
Non-conductive raceway

Temperature Rating
80C/176F Dry
60C/140F Wet
60C/140F Oil resistant

References & Ratings


UL 1660 E123464
NEC 356, 390.15, 501.10(B)(2), 502.10(A)(2), 503.10(A)(2), 511.7(A)(1),
620.21, 645.5(D)(2), 680.21, 680.23, 680.25, and 680.42
CSA C22.2 No. 227.2.1 File LL69271

Applications
Constant flexing and motion applications
Signage and outdoor lighting over 1000 volts per
600.32 (A) (1)
Hazardous locations per NEC 501
Industrial and commercial applications
Physical protection from abrasion of the conductors inside
Indoor or outdoor locations

Product Dimensions/
Bend Radius

Ordering Information
Product
Code

Trade
Size
(inches)

Trade
Size
(mm)

Coil
Length
(feet)

Reel
Length
(feet)

Approx.
Weight/
100 feet
(pounds)

6501-30-00
6502-30-00
6502-60-00
6503-30-00
6504-30-00
6504-45-00
6505-24-00
6506-24-00
6507-24-00

3/8
1/2
1/2
3/4
1
1
114
112
2

12
16
16
21
27
27
35
41
53

100'
100'

100'
100'

50'
50'
50'

1000'

500'

14
16
16
18
29
29
40
83
140

Wall
Thickness

Internal
Diameter
(min/max)
inches

External
Diameter
(min/max)
inches

Bend
Radius
(inches)

0.035
0.035
0.035
0.035
0.035
0.035
0.040
0.040
0.040

0.475/0.515
0.610/0.650
0.610/0.650
0.805/0.845
1.020/1.065
1.020/1.065
1.360/1.405
1.575/1.630
2.035/2.090

0.745/0.785
0.900/0.940
0.900/0.940
1.140/1.180
1.400/1.450
1.400/1.450
1.790/1.835
2.035/2.090
2.595/2.650

2
3.25
3.25
4.25
6.5
6.5
8
9
11.1

NOTE: All dimensions and weights are subject to normal manufacturing tolerances.

www.kaf-tech.com

17
11

Liquid-Tuff Flexible Liquidtight Conduit

Industrial

LIQUID-TUFF
UL Liquidtight Flexible Non-Metallic Conduit Type A Orange
Type LFNC-A
Scope
This specification covers Kaf-Tech LIQUID-TUFF Layered Liquidtight
Flexible Non-Metallic Conduit, designed for use in wet, dry or oily
locations as a flame resistant, Non-Metallic raceway for power, control
and communications cables where repetitive motion and constant
flexing is required. It is intended for applications where abrasion and
physical abuse may occur. It complies with Article 356 of the NEC
regarding layered conduit Type LFNC-A. The product is UL Listed for
80C (176F) in a dry location, 60C (140F) in a wet location and 60C
(140F) in a oily location. It is also UL Listed through 2-inch trade sizes
for outdoor use and sunlight resistance. This Liquidtight Flexible NonMetallic Conduit is manufactured and tested in accordance with
Harmonized Underwriters Laboratories Inc. Standard UL 1660. The
product carries the UL Listing Mark, CSA Certification, and CSA
Harmonized Certification.

LIQUID-TUFF - TYPE LFNC - A

Reference Standards
UL 1660/
CSA C22.2 No. 227.2.1

Construction
Liquidtight Flexible Non-Metallic Conduit Type LFNC-A is a layered
raceway of circular cross section with a smooth flexibly polyvinyl
chloride (PVC) inner layer with a reinforcing layer covered with a
flexible polyvinyl chloride (PVC) jacket. The wall thicknesses and
dimensions of the layered conduit shall comply with Table1 of
harmonized UL 1660/CSA C22.2 No. 227.2.1 of UL 1660 which is
summarized in Table 1. Color: Orange

Standard for Liquidtight Flexible


Non-Metallic Conduit

File References

UL E123464, CSA 69271

NEC Articles:

356, 390.15, 501.10(B)(2), 502.10(A)(2),


503.10(A)(2), 511.7(A)(1), 620.21(A)(d),
645.5(D)(2), 680.21, 680.23, 680.25,
and 680.42

Grounding
A separate Grounding conductor is required by both the National
Electrical Code and Canadian Electrical Code for all trade sizes.

Markings
The outer surface of the conduit shall be clearly marked with a legible
print legend in accordance with harmonized UL 1660/CSA C22.2 No.
227.2.1.

Performance Tests
The completed LIQUID-TUFF Liquidtight Flexible Non-Metallic Conduit
Type A shall meet all of the performance requirements contained in UL
1660 outlined in Appendix A.

Appendix A
UL Performance Tests

Table 1
Conduit Size
Trade
Size, In. Metric

18

Inside
Diameter, In.
Min. Max.

Outside
Min.
Min. Wall
Diameter, In. Bend
Weight Thickness
Min. Max. Radii, In. lbs/100ft Inches

3/8

(12)

0.475 0.515

0.745 0.785

2.0

14

.035

1/2

(16)

0.610 0.650 0.900 0.940

3.25

16

.035

3/4

(21)

0.805 0.845

1.180

4.25

18

.035

(27)

1.020 1.065 1.400 1.450

6.5

29

.035

114

(35)

1.360 1.405 1.790 1.835

8.0

40

.040

112

(41)

1.575 1.630 2.035 2.090

9.5

83

.040

(53)

2.035

11.1

140

.040

2.090

www.kaf-tech.com

1.140

2.595

2.650

Physical Properties
Original Tensile and Elongation
Air Oven Aging Test
Oil Immersion Test
Deformation
Tension
Flexibility (Room and Low Temperature)
Vertical Flame
Room Temperature Impact
Secureness of Fittings
Mechanical Water Absorption
Moisture Penetration Test
Durability of Ink
Sunlight Resistance
Crush Test