You are on page 1of 59

SENTRON Switching and Protection

Devices
3WL Air Circuit Breakers
Reference Manual April 2009

Low-Voltage Controls and Distribution

SENTRON Switching and


Protection Devices
Air Circuit Breakers
4

Introduction
3WL Air Circuit Breakers

8
14
21
26
34
36
49
51

52
53
53
57
58

3WL Air Circuit Breakers/


Non-Automatic Air Circuit Breakers
up to 6300 A (AC)
General data
- Design
- Function
- Configuration
- Technical specifications
Project planning aids
- Characteristic curves
- Dimensional drawings
- Schematics
- More information
3WL Non-Automatic Air
Circuit Breakers up to 4000 A (DC)
General data
- Technical specifications
Project planning aids
- Characteristic curves
- Dimensional drawings
- Schematics
- More information

Siemens 2009

SENTRON Switching and Protection Devices Air Circuit Breakers


Introduction

Overview

Size II

Size I

Size III

Air circuit breakers


3WL air circuit breakers/non-automatic air circuit breakers
up to 6300 A (AC)

3WL non-automatic air circuit breakers


up to 4000 A (DC)

Size

I, II, III

II

630, 800, 1000, 1250,


1600, 2000, 2500, 3200, 4000,
5000, 6300

1000, 2000, 4000

3-pole, 4-pole

3-pole, 4-pole

Rated operational
voltage Ue

V AC
V DC

Up to 690/1000/1150
--

-Up to 1000

Rated ultimate
short-circuit breaking
capacity at 500 V AC

kA

Rated current In

Number of poles

Endurance

Size I

Size II

Size III

55/66

66/80/100

100/150 (3-pole),
130 (4-pole)

30/25/20
(at 300/600/1000 V DC)

15000

10000

15000

Opera20000
ting cycles
3 0

Mounting position

3 0

3 0

3 0

N S E 0 _ 0 0 0 6 2 a

N S E 0 _ 0 0 0 6 1 a

Degree of protection
With cover
Without cover
(with door sealing frame)

3 0

3 0

3 0

N S E 0 _ 0 0 0 6 2 a

N S E 0 _ 0 0 0 6 1 a

IP55
IP41

3 0

IP55
IP41

320/410

460/590

704/914

460/590

H mm

434

434

434

434

D mm

291

291

291

291

H mm

465.5

465.5

465.5

465.5

D mm

471

471

471

471

NSE0_01106a

ETU15B1)

Type

ETU25B

NSE0_01109a

Withdrawable
NSS0_00535

W mm

NSE0_01108a

Fixed
mounting

NSE0_01107a

ETU27B

ETU45B

Rating Plug

NSE0_01111a

Dimensions 3-/4-pole

ETU76B

Solid-state releases for SENTRON 3WL circuit breakers


Overload protection

Short-time delayed
short-circuit protection

--

Instantaneous
short-circuit protection

Neutral conductor protection

--

--

Ground-fault protection

--

--

Zone Selective Interlocking

--

--

--

LCD, 4-line

--

--

--

--

LCD, graphic

--

--

--

--

Communication through
PROFIBUS DP/MODBUS

--

--

--

Measurement function Plus

--

--

--

Selectable parameter sets

--

--

--

--

Parameters freely programmable

--

--

--

--

CubicleBUS

--

--

--

Standard
-- Not available
Optional
1)

ETU15B cannot be used with 3WL circuit breakers, size III.

Siemens 2009

3WL air circuit breakers/non-automatic air circuit breakers


according to UL 489 up to 5000 A, see Catalog LV 16.

SENTRON Switching and Protection Devices Air Circuit Breakers


Introduction

Switching capacity
Size

II

Type

3WL11

3WL12

Switching capacity class

III

3WL13

C
3-pole

C
4-pole

Short-circuit breaking capacity


Rated operational voltage Ue
up to 415 V AC
Icu

kA

55

66

66

80

100

100

150

130

Ics

kA

55

66

66

80

100

100

150

130

Icm

kA

121

145

145

176

220

220

330

286

Rated operational voltage Ue


up to 500 V AC
Icu

kA

55

66

66

80

100

100

150

130

Ics

kA

55

66

66

80

100

100

150

130

Icm

kA

121

145

145

176

220

220

330

286

Rated operational voltage Ue


up to 690 V AC
Icu

kA

42

50

50

75

85

85

150

130

Ics

kA

42

50

50

75

85

85

150

130

Icm

kA

88

105

105

165

187

187

330

286

--

--

--

45

50

704)
4)

704)

Rated operational voltage Ue


up to 1000 V/1150 V AC
kA

Icu

--

704)

Ics

kA

--

--

--

--

45

50

70

Icm

kA

--

--

--

--

95

105

1544)

1544)

Rated short-time withstand current Icw


of the circuit breakers3)
0.5 s

kA

50

66

66

80

100

100

100

100

1s

kA

42

50

55

66

80

100

100

100

2s

kA

29.5

35

39

46

651)/702)

80

80

80

3s

kA

24

29

32

37

501)/652)

65

65

65

Short-circuit breaking capacity Icc


of the non-automatic air circuit breakers
Up to
500 V AC

kA

50

66

66

80

100

100

100

100

Up to
690 V AC

kA

42

50

50

75

85

85

100

100

Circuit breakers with ECO switching capacity N


(Icu = Ics up to 55 kA size I/up to 66 kA size II at 500 V)

Circuit breakers with standard switching capacity S


(Icu = Ics up to 66 kA size I/up to 80 kA size II at 500 V)

Circuit breakers with high switching capacity H


(Icu = Ics up to 100 kA at 500 V)

DC

1)
2)

Size II with In max 2500 A.


Size II with In max = 3200 A and In max = 4000 A.

3)

At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.

4)

Rated operational voltage Ue = 1150 V.

Circuit breakers with very high switching capacity C


(Icu = Ics up to 150 kA (3-pole)/130 kA (4-pole)
at 500 V)
Circuit breakers with DC switching capacity
These circuit breakers are indicated in the Technical
specifications by orange backgrounds.

Siemens 2009

SENTRON Switching and Protection Devices Air Circuit Breakers


Introduction
SENTRON 3WL:
Superior individual products integrated into uniform power
distribution systems up to and including industry-specific
industrial and infrastructure solutions

6
7

8
5

25

21

10

19
22

11

23
12

24

18

13

14
20

16
15

$ Guide frame
% Main circuit connection, front, flange, horizontal, vertical
& Position indicator switch
( Grounding contact, leading
) Shutter
* COM15 PROFIBUS module or COM16 MODBUS module
+ External CubicleBUS modules
, Closing solenoid, auxiliary release
- Auxiliary conductor plug-in system
. Auxiliary switch block
/ Door sealing frame
0 Interlocking set for base plate
1 Transparent panel, function insert
2 EMERGENCY-STOP pushbutton, key operated
3 Motorized operating mechanism
6

Siemens 2009

4 Operating cycles counter


5 Breaker Status Sensor (BSS)
6 Protective devices with device holder, solid-state releases (ETU)
7 Remote reset solenoid
8 Breaker Data Adapter (BDA)
9 Four-line display
: Ground-fault protection module
; Rated current module
< Measuring function module
= Circuit breaker

NSE0_01887a

17

SENTRON Switching and Protection Devices Air Circuit Breakers


Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B solid-state release)
21

Ethernet

19
20

PROFIBUS

14

22

15

16

11

12
13

18

CubicleBUS

10
1

17

NSE0_01105h

SENTRON 3VL

12 Electronic ETU release

Electronic LCD ETU release

13 Measurement function Plus

Electronic ETU release

14 ZSI module

COM10 PROFIBUS module complete with ZSI

15 Digital output module with relay contacts

COM20 PROFIBUS module2) complete with ZSI

16 Digital output module with relay contacts, configurable

Breaker Data Adapter (BDA)

17 Analog output module

BDA Plus with Ethernet interface

18 Digital input module

Browser-capable input and output device (e.g. notebook)

19 Switch ES Power on PC

SENTRON 3WL

20 PLC e.g. SIMATIC S7

10 COM15 PROFIBUS module1)

21 SIMATIC powercontrol

11 Breaker Status Sensor (BSS)

22 PAC

1) For a MODBUS connection the COM16 module is required.


2) For a MODBUS connection the COM21 module is required.

Features
Coordinated communication concept using the PROFIBUS DP
or MODBUS, ranging from 16 A to 6300 A with SENTRON 3VL
and SENTRON 3WL
The high level of modularity of circuit breakers and accessories
allows easy retrofitting of all communication components
Significant additional benefits for the switchboard due to the
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the SENTRON 3WL
Innovative software products for parameterization, operation,
monitoring, and diagnostics of SENTRON circuit breakers,
both locally or via PROFIBUS DP, MODBUS or Ethernet/
Intranet/Internet
Complete integration of the SENTRON circuit breakers into the
Totally Integrated Power and Totally Integrated Automation
solutions

Communication:
For air circuit breakers with optional communication function
(ETU45B or ETU76B solid-state release)
see Catalog LV 1.
For accessories see Catalog LV 1.
For more information see also the Chapter "Power
Management System" and "Software for Power Distribution".

Siemens 2009

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data

Design
Circuit breaker
rated current n max (A)

Breaking capacity
cu at 500 V AC (kA) or
cc at 300 V DC (kA)

Size III

6300
5000

H
100

4000

C
150 (3p)
130 (4p)

Dimensions
Fixed-mounted,
3- /4-pole

Withdrawable
3- /4-pole

704 / 914

704 / 914

Width

434 / 434

460 / 460

Height

291 / 291

385 / 385

Depth

460 / 590

460 / 590

Width

434 / 434

460 / 460

Height

291 / 291

385 / 385

Depth

320 / 410

320 / 410

Width

434 / 434

460 / 460

Height

291 / 291

385 / 385

Depth

4000
3200

Size II

2500
2000
1600
1250

DC

30

66

80

100

1000
800

1600

Size I

1250
1000

800

55

66

630

The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door.

Overview of SENTRON 3WL circuit breakers/


non-automatic air circuit breakers

Versions
Rated currents: 630 A to 6300 A
3 sizes for different rated current ranges (see illustration
"Overview of SENTRON 3WL Circuit Breakers/Non-Automatic
Circuit Breakers")
3- and 4-pole versions
Rated operational voltage up to 690 V AC and 1000 V DC.
Special versions up to 1000 V AC and 1150 V AC available
4 different switching capacity classes in the range from 55 kA
to 150 kA for AC applications and one switching capacity
class for DC applications.
The SENTRON 3WL circuit breakers are supplied complete with
operating mechanism (manual operating mechanism with mechanical closing), solid-state release and auxiliary switches
(2 NO contacts + 2 NC contacts in the standard version), and
can be equipped with auxiliary releases.
Installation types
Fixed-mounted or withdrawable version
Ambient temperatures
The SENTRON 3WL circuit breakers are climate-proof according
to IEC 60068-2-30. They are intended for use in enclosed areas
where no severe operating conditions (e. g. dust, corrosive vapors, damaging gases) are present.
When installed in dusty and damp areas, suitable enclosures
must be provided.

Siemens 2009

NSE0_00887 o

Coordinated dimensions
The dimensions of SENTRON 3WL circuit breakers only differ in
terms of the width of the device which depends on the number
of poles and the size.
Due to the nature of the design, the dimensions of devices with
a withdrawable version are determined by the dimensions of the
guide frames, which are slightly larger.
Non-automatic air circuit breakers
A special version of circuit breaker is utilized as a non-automatic
air circuit breaker. The non-automatic air circuit breakers are designed without an solid-state release system and do not perform
any protection duties for the system.
One potential application is the use as a bus coupler in systems
with parallel feed-ins.
The versions and features can be selected according to those of
the circuit breakers.
Operating mechanisms
The circuit breakers are available with various optional operating
mechanisms:
Manual operating mechanism with mechanical closing (standard design)
Manual operating mechanism with mechanical and electrical
closing
Motorized operating mechanism with mechanical and electrical closing
The operating mechanisms with electrical closing can be used
for synchronization tasks.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Safety and reliability

Fixed-mounted circuit breakers

Horizontal
connection

Front connection with single


hole or double hole

N S E 0 _ 0 0 9 7 9 a

N S E 0 _ 0 0 9 6 9 b

N S E 0 _ 0 0 9 6 7 b

N S E 0 _ 0 0 9 6 8 b

To protect the circuit breakers and plant against unauthorized


switching as well as the maintenance and operator personnel, the
system contains many locking devices. Others can be retrofitted.

Vertical
connection

Horizontal
connection

Front connection with single


hole or double hole

Vertical
connection

N S E 0 _ 0 0 9 7 3 b

N S E 0 _ 0 0 9 7 2 b

N S E 0 _ 0 0 9 7 1 b

N S E 0 _ 0 0 9 6 7 b

N S E 0 _ 0 0 9 7 0 b

Withdrawable circuit breakers and guide frames

Flange
connection

Main circuit connections connection types

Main circuit connections


All circuit breakers are equipped with horizontal main circuit
connections on the rear for up to 5000 A as standard (horizontal
connection to busbars). Exception: Circuit breakers of size II
with max. rated current 4000 A.
Circuit breakers with a max. rated current of 6300 A and circuit
breakers size II with a max. rated current of 4000 A are equipped
with vertical main connections (for upright busbars).

Connection using
screw terminals
system (SIGUT)
(standard)

N S E 0 _ 0 0 9 7 6 b

N S E 0 _ 0 0 9 7 5 b

The following options are available, with all combinations of top


and bottom connections possible:
Accessible from the front, single hole (for vertically installed
busbars)
Accessible from the front, double hole (holes according to
DIN 43673) (for vertically installed busbars)
At the rear, vertical (for vertically installed busbars)
Connecting flange (for direct connection to guide frame up to
4000 A).
Screwless
connection method
(tension springs)
(optional)

Connection options for auxiliary circuit connections

Auxiliary circuit connections


The type of connection for the auxiliary switches depends on the
type of installation:
Withdrawable version: The internal auxiliary switches are connected to the male connector on the switch side. When fully inserted, the connector makes a connection with the sliding
contact module (see "Design", graphic "Guide Frame") in the
guide frame. Various adapters can then be used to complete
the wiring (see the graphic "Connection Options for Auxiliary
Circuit Connections").
Fixed mounting: In this case the auxiliary supply connectors
are engaged directly onto the circuit breaker. The connectors
are equipped with coding pins that prevent them being mistakenly interchanged.
Operator panel
The operator panel is designed to protrude from a cut-out in the
door providing access to all control elements and displays with
the control cabinet door closed.
The operator panels for all circuit breakers (fixed-mounted/withdrawable versions, 3-/4-pole) are identical. The operator panel
ensures degree of protection IP41.

Other safety features include:


Infeed from above or below, as required
Locking of the guide frame with the circuit breaker removed,
as standard
Locking of the withdrawable circuit breaker against movement, as standard
High degree of protection with cover IP55
Mechanical reclosing lockout after overload or short-circuit
release as standard
The circuit breaker is always equipped with the required number of auxiliary supply connectors
Standard version
SENTRON 3WL circuit breakers are equipped with the following
features as standard:
Mechanical ON and OFF pushbutton
Manual operating mechanism with mechanical closing
Switch position indicator
Ready-to-close indicator
Memory status indicator
Auxiliary switch 2 NO + 2 NC
Rear horizontal main circuit connections for fixed-mounted and
withdrawable versions up to 5000 A, and rear vertical main circuit connections for 6300 A applications and size II with 4000 A
For 4-pole circuit breakers, the fourth pole (N) is installed on
the left and is 100 % loadable with the rated current
Contact erosion indicator for the main contacts
Auxiliary circuit plug-in system with SIGUT screw terminals
Delivery inclusive of all auxiliary circuit connectors to internal
features including coding device for the prevention of incorrect installation of auxiliary supply connectors for fixed-mounted circuit breakers
Mechanical "tripped" indicator for solid-state release system
Mechanical reclosing lockout after tripping operation
Operator panel cannot be taken off with the circuit breaker in
the ON position
Additional features of the withdrawable version:
Main contacts:
Laminated receptacles in the guide frame, penetration blades
on the withdrawable circuit breaker
Position indicator in the operator panel of the withdrawable
circuit breaker
Captive manual crank handle for moving the withdrawable
circuit breaker
Guide frame with guide rails for easy moving of the withdrawable circuit breaker
The withdrawable circuit breaker can be locked to prevent it
being pushed out of position
The withdrawable circuit breaker cannot be moved when it is
in the ON position
Coding of the rated current between the guide frame and the
withdrawable circuit breaker
Standards
SENTRON 3WL circuit breakers comply with:
IEC 60947-1, IEC 60947-2
EN 60947-1, EN 60947-2
Climate-proof according to IEC 60068-2-30
Versions according to UL 489 also available, see Catalog LV 16.
For further specifications, see Appendix.
Siemens 2009

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Withdrawable short-circuit, grounding, and bridging
units
Portable positively-driven grounding and short-circuit devices
are used for the disconnected system sections to verify isolation
from the supply at the workplace.

An energy storage device for shunt releases allows the circuit


breaker to be opened even if the control voltage is no longer
available.
Undervoltage releases

Withdrawable grounding units allow simple and comfortable


grounding. They are simply inserted into the guide frames in
place of the corresponding withdrawable circuit breakers. This
ensures that these devices are always first connected with the
grounding electrode and then with the components to be grounded.

The undervoltage release causes the circuit breaker to be


opened if the operational voltage falls below a certain value or is
not applied. The circuit breaker cannot be closed manually or by
means of an electrical ON command if the undervoltage release
is not connected to the operational voltage. The undervoltage release has no delay as standard. A delay can be set by the customer in the range between td < 80 ms and td < 200 ms.

The grounding terminals are fitted to the side of the switch enclosure and establish the connection when inserted into the guide
frame.

In addition, an undervoltage release with a delay in the range


from 0.2 to 3.2 s is available.

Short-time current of the


grounding terminal

kA 15 (500 ms)

Rated operational voltage

1000 (690 for size I)


EN 61230

Standards

All withdrawable terminals are short-circuited and grounded on


delivery.
Qualified electricians can easily convert it to a withdrawable
bridging unit by following the enclosed instructions.
In addition, the withdrawable unit can be adapted to various rated currents of a size.
Withdrawable short-circuit and grounding unit
The withdrawable short-circuit and grounding unit consists of a
breaker enclosure with penetration blades which are connected
with the short-circuiting link.
Depending on the version, the short-circuiting links are arranged
at the top or bottom. The grounding and short-circuit connections are established when the device is inserted.
It must be ensured that the side to be short-circuited and grounded is not live. For this reason it is recommended that the withdrawable unit is only wound in when the door is closed.
Withdrawable bridging unit
The withdrawable bridging unit consists of a breaker enclosure
in which all disconnection components and the operating mechanism have been replaced with simple connections between
the upper and lower contacts.
Auxiliary releases
Up to two auxiliary releases can be installed at the same time.
The following are available:
1 shunt release
or 1 undervoltage release
or 2 shunt releases
or 1 shunt release
+ 1 undervoltage release
Signal switch for auxiliary releases
One signaling contact is used for each auxiliary release to determine the positions of the auxiliary releases.
Shunt releases
When the operational voltage is connected to the shunt release,
the circuit breaker is opened immediately. The shunt release is
available in the versions 5 % ON period for overexcitation and
100 % ON period for permanent excitation. This means that it is
also possible to block the circuit breaker against being jogged
into closing.

10

Siemens 2009

Closing solenoid
The closing solenoid is used to close the circuit breaker electrically by means of a local electrical ON command or by a remote
unit.
Motorized operating mechanisms
The operating mechanism is used to load the storage spring automatically.
The operating mechanism is activated if the storage spring has
been unloaded and the control voltage is available.
It is switched off automatically after loading. This does not affect
manual operation of the storage spring.
Indicators, signals, and control elements
Motor shutdown switch
Control switch for switching off the motorized operating mechanism (automatic loading).
Operating cycles counter
The motorized operating mechanism can be supplied with a 5digit operating cycles counter. The display is incremented by "1"
as soon as the storage spring is fully loaded.
Resetting the manual tripped signal
When the circuit breaker has tripped, this is indicated by the
protruding red mechanical tripped indicator on the ETU. When
the mechanical tripped indicator is activated, the tripping solenoid and tripped signal are reset. If this display is to be reset remotely, the reset button can be equipped with a reset solenoid.
This option allows the circuit breaker to be reset both manually
and electrically.
Automatic resetting of reclosing lockout
When the ETU is activated, reclosing of the circuit breaker is prevented until the release is either electrically or manually reset. If
the "Automatic resetting of reclosing lockout" option is used, the
pre-tensioned circuit breaker is ready to close immediately after
tripping. Resetting the manual tripped indicator is not included
in this option.
Tripped signal switch
If the circuit breaker has tripped due to an overload, short-circuit, ground fault or extended protection function, the tripped signal switch can indicate this. This signal switch is available as
an option. If the circuit breaker is used for communication, this
option is supplied as standard.
Ready-to-close indicator switch
The SENTRON 3WL circuit breakers are equipped with an optical ready-to-close indicator as standard. In addition, the readyto-close status can be transmitted by means of a signal switch
as an option. If the switch is used for communication, the signal
switch is supplied as standard.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Circuit breakers
(1 )

(2 8 )

(2 )

(2 7 )

(3 )

(2 6 )

(4 )
(2 5 )

(5 )

(2 4 )

(6 )

(2 3 )

(1)

Arc chute

(2)

Carrying handle

(3)

Labeling plate

(4)

Motor shutdown switch (option) or


"Electrical ON" (option)

(5)

Name plate for circuit breaker

(6)

Memory status indicator

(7)

"Mechanical ON" button

(8)

Rated current indication

(9)

Positioning pictogram

(10) Operating cycles counter (option)


(11) Hand-operated lever
(12) Crank handle

(7 )

(2 2 )

(13) Withdrawable unit drive shaft


(14) Equipment plate

(2 1 )

(15) Ground terminal

(8 )
(2 0 )

(9 )

(1 9 )

(1 0 )
(1 1 )

(1 8 )

(16) Position indicator


(17) Table for ground-fault protection
(18) Safety lock for crank handle (option)
(19) Mechanical unlocking of crank handle
(option)
(20) Solid-state release
(21) Rated current module

(1 7 )

(1 2 )
(1 3 )

(1 6 )

(1 4 )
(1 5 )
N S E 0 _ 0 0 9 6 5 b

(22) "Mechanical OFF" button or


"EMERGENCY-STOP" mushroom
pushbutton (option)
(23) Ready-to-close indicator
(24) Switch position indicator
(25) "Tripped" indicator (reset button)
(26) "Secure OFF" locking device (option)
(27) Operator panel
(28) Male connector for auxiliary circuit
connections

Guide frames

(1 )
(2 )

(3 )

(1 8 )

(4 )

(1 7 )

(5 )

(1 6 )
(1 5 )

(1)

Arc chute cover


(option)

(2)

Blow-out openings

(3)

Opening for crane hook

(4)

Shutter (option)

(5)

Locking device (shutter) (option)

(6)

Type plate for guide frame

(7)

Isolating contacts

(8)

Ground terminal 14 mm

(9)

Locking device for racking rail

(10) Locking device against movement when


control cabinet door is open (option)
(11) Door interlocking for guide frame (option)
(12) Racking rail

(6 )

(13) Factory-set rated current coding

(7 )

(15) Equipment-dependent coding (option)

(14) Sliding contact for breaker grounding


(option)
(16) Shutter actuator (optional)
(17) Position indicator switch (optional)

(1 4 )
(8 )

(1 3 )

(18) Sliding contact module for auxiliary


conductors (number depends on
equipment)

(1 2 )
(9 )

(1 1 )
(1 0 )

N S E 0 _ 0 0 9 6 6 b

Siemens 2009

11

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Locking devices

Sealing devices

Locking device in OFF position

Sealing cap for "Electrical ON" button

This function prevents closing of the circuit breaker and complies to the specifications for main switches to EN 60204
(VDE 0113) - disconnector unit. This lockout only affects this circuit breaker.

The "Electrical ON button" is equipped with a sealing cap as


standard.

If the circuit breaker is replaced, closing is no longer prevented


unless the new circuit breaker is also protected against unauthorized closing.

The locking set contains covering caps which can be sealed.

To activate the locking device, the circuit breaker must be


opened. The locking device is disabled when the circuit breaker
is closed. The lock is only activated when the key is removed.
The safety key can be removed only in the "OFF" position.

Sealing cap for "Mechanical ON" and "OFF" button


Sealing device for solid-state releases
The transparent cover can be sealed. The parameter setting
sections are covered to prevent unauthorized access. Openings
allow access to the query and test button.
Locking mechanisms

Locking device for "Electrical ON"


(see graphic "Circuit breakers")

Locking mechanism against movement for withdrawable circuit


breakers when the control cabinet door is open

This prevents unauthorized electrical closing from the operator


panel. Mechanical closing and remote closing remain possible.
The lock is only activated when the key is removed.

The crank handle is blocked when the control cabinet door is


open and cannot be removed. The withdrawable circuit breaker
cannot be moved. The lock only affects the inserted crank
handle.

Locking device for "Mechanical ON"


(see graphic "Circuit breakers")
This prevents unauthorized mechanical closing. The mechanical
ON button can only be activated if the key is inserted (key operation). Closing with the "Electrical ON" button and remote closing remain possible. The lock is only activated when the key is
removed.
"Secure OFF" circuit breaker-independent locking device
against unauthorized closing
This special switch-independent function for withdrawable circuit breakers prevents closing and fulfills the specifications for
main switches to EN 60204 (VDE 0113) disconnector unit. Unauthorized closing remains impossible even after the circuit
breaker has been exchanged.
To activate the lock, the circuit breaker must be opened. The locking device is disabled when the circuit breaker is closed. The
lock is only activated when the key is removed. The safety key
can be removed only in the "OFF" position.
Locking device for crank handle
Prevents removal of the crank. The circuit breaker is protected
against movement. The lock is only activated when the key is
removed.
Locking device for "Mechanical OFF"
Prevents unauthorized mechanical opening from the operator
panel. The "Mechanical OFF pushbutton" can only be activated
if the key is inserted (key operation). Remote opening remains
possible. The lock is only activated when the key is removed.
Locking device for hand-operated lever
The hand-operated lever can be locked with a padlock. The storage spring cannot be loaded manually.
Locking device against resetting the "tripped" indicator
A lockable cover prevents manual resetting of the "tripped" indicator after overcurrent tripping. This locking device is supplied
together with the transparent cover for solid-state releases.

12

Siemens 2009

Locking of the control cabinet door


The control cabinet door cannot be opened if
The fixed-mounted circuit breaker is closed (the blocking
signal is transmitted via the Bowden wire) or
The withdrawable circuit breaker is in the connected position.
Blocking mechanism using "Mechanical ON" and "OFF" buttons
The "Mechanical ON" and "OFF" buttons are covered with a cap
which only allows actuation with a tool. These covering caps are
part of the locking set.
Optional equipment for guide frames
Shutters
The sealing strips of the shutter seal the laminated contacts of
the guide frame when the withdrawable circuit breaker is removed and therefore implement touch protection.
The sealing strips can be manually opened using the strip
levers.
The position of the sealing strips can be locked in various positions using padlocks for securing against tampering.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Rated current coding unit between circuit breaker and guide
frame
Withdrawable circuit breakers and guide frames are equipped
with a rated current coding unit as standard.
This ensures that only circuit breakers whose penetration blades
are suited to the laminated contacts of the guide frame can be
inserted into a guide frame (see diagram below).

Equipment-dependent coding
Withdrawable circuit breakers and guide frames can be retrofitted with an equipment-dependent coding unit.
This allows different designs of circuit breakers and guide frames to be uniquely assigned. If the circuit breaker and guide
frame have been assigned different codes, the circuit breaker
cannot be inserted.
36 different coding options can be selected.

The guide frame can be equipped with position indicator switches. These can be used to determine the position of the circuit
breaker in the guide frame.

N S E 0 _ 0 1 0 3 2 a

N S E 0 _ 0 1 0 3 1 a

Position indicator switch for guide frames

(1 )

Two versions are available:


Option 1
Connected position
1 CO contact,
test position
1 CO contact,
disconnected position 1 CO contact.
Option 2
Connected position
3 CO contacts,
test position
2 CO contacts,
disconnected position 1 CO contact.

(4 )
(2 )
(5 )

(3 )

(1) Guide frame, interior of l/h side; interior of r/h side similar
(2) Coding pin on racking rail in guide frame
(3) Racking rail
(4) Withdrawable circuit breaker, r/h side; l/h side similar
(5) Coding pin on guide frame

Rated current coding unit between circuit breaker and guide frame

Positions of the withdrawable circuit breaker in the guide frame


Display

Position indicator

Maintenance position

(2 )

(1 )

CONNECT

Main circuit

Auxiliary circuit

Control cabinet
door

Shutters

Disconnected

Disconnected

Open

Closed

Disconnected

Disconnected

Closed

Closed

Disconnected

Connected

Closed

Closed

Connected

Connected

Closed

Open

TEST

(4 )
N S E 0 _ 0 1 0 3 3 a

DISCON

NSE01037

Disconnected position

CONNECT

(3 )

TEST

N S E 0 _ 0 1 0 3 4 a

Test position

DISCON

NSE01038

CONNECT

TEST

DISCON

N S E 0 _ 0 1 0 3 5 a

Connected position

NSE01039

CONNECT

TEST

DISCON

N S E 0

(1) Auxiliary circuit

(2) Main circuit

0 1 0 3 6 a

NSE01040

(3) Control cabinet door

(4) Shutter

Phase barriers

Door sealing frame and cover

The plant engineering company can manufacture phase barriers


made of insulating material for the arcing fault barriers. The rear
panel of the fixed-mounted circuit breakers or guide frames are
equipped with guide grooves.

SENTRON 3WL circuit breakers have degree of protection IP20


as standard. However, if the switchgear is to be equipped with a
higher degree of protection, a door sealing frame with IP41 and
a cover with IP55 are available.

Arc chute cover


The arc chute cover is available as optional equipment for the
guide frame. It protects switchgear components which are located directly above the circuit breaker.

Siemens 2009

13

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data

NSE0_00880b

NSE0_00881b

NSE0_00882b

Function

R
R

s d

s d

J
i

s d

N S E 0 _ 0 0 9 5 2 b

N S E 0 _ 0 0 9 5 1 b

N S E 0 _ 0 0 9 5 0 c

ETU15B

ETU25B

ETU27B

Functions of the solid-state releases


Basic protection functions
Overload protection

Short-time delayed short-circuit protection

--

Instantaneous short-circuit protection

Neutral conductor protection

--

--

Ground-fault protection

--

--

N-conductor protection can be switched on/off

--

--

N-conductor protection adjustable

--

--

--

Instantaneous short-circuit protection can be switched on/off

--

--

--

Additional functions

Non-delayed short-circuit protection can be switched on/off

--

--

--

Thermal image can be switched on/off

--

--

--

Load monitoring

--

--

--

Short-time delayed short-circuit protection switchable to I2t

--

--

--

Instantaneous short-circuit protection adjustable

--

--

Overload protection switchable to I4t

--

--

--

Overload protection can be switched on/off

--

--

--

Selectable parameter sets

--

--

--

Parameterization through rotary coding switches (10 steps)

Parameterization through communication (absolute values)

--

--

--

Parameterization through user interface of ETU (absolute values)

--

--

--

Parameterization and display

Parameterization of the extended protection functions

--

--

--

LCD alphanumerical

--

--

--

Graphic LCD

--

--

--

--

--

--

Measurement function
Measurement function Plus

Communication
CubicleBUS

--

--

--

Communication through PROFIBUS DP

--

--

--

Communication through MODBUS

--

--

--

Communication through Ethernet

--

--

--

Standard

-- Not available

Optional

Detailed information about the functions of the solid-state releases is given in the following.

14

Siemens 2009

s d

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data

ETU76B

Rating Plug

NSE0_00883b

NSE0_00886c

12

IR

IR

tR

tR

Ig
tg

Isd
t sd
Ii

NSE0 00953a

Ig
tg

Isd
t sd
Ii

NSE0 00953a

ETU45B

ETU76B

--

--

--

--

--

--

--

Siemens 2009

15

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Solid-state releases (ETU)
The solid-state release is controlled by a microprocessor and
operates independently of an auxiliary voltage. It enables systems to be adapted to the different protection requirements of
distribution systems, motors, transformers and generators.

Tripped indicator/
Reset button

Communication capabilities

LCD alphanumeric
with 15
inclination
and rotatable
through 180

The international standard PROFIBUS DP or MODBUS can be


used to transmit data such as current values, switching states,
reasons for tripping etc. to central computers.
Data acquisition and energy management are possible in conjunction with the Plus measurement function.
A new internal circuit breaker data bus allows switchboard panel
communication between the circuit breaker and secondary devices in the circuit breaker section:
Actuation of analog displays
Facility to test the communication build-up with circuit
breakers
Display of tripping state and tripping reasons
Input module for reading in further switchgear panel signals
and for transmission of these signals to the PROFIBUS DP or
MODBUS
Various output modules for displaying measured values

Rated current
module/
rating plug

Slide switch
for switchable
overload
characteristic
curve

Ground-fault
protection module (retrofittable)

This means that it is not only possible to monitor the device remotely, but also to transmit current values from the entire system
and perform switching operations remotely.
I2t and I4t characteristic curve for overload protection
The best protection for the whole switchgear is achieved by setting the tripping characteristic curve to an optimum value. In order to achieve optimal discrimination for upstream fuses or medium voltage protection systems, the inclination of the
characteristic curve can be selected for the overload range.

Example of configuration for ETU45B

The overload protection L (long time protection) for the solidstate releases ETU45B and ETU76B allows the characteristic
curve to be switched between I2t and I4t.
The I4t characteristic improves discrimination for downstream
circuit breakers and fuses.
Solid-state releases ETU
Modularity has also been strictly emphasized during the development of the solid-state releases. These are some of the
modules which can be easily retrofitted at any time:
Ground-fault protection module
Communication
Measurement function
Display
Rated current module (Rating Plug)
This allows quick adaptation to new local mains specifications.
In addition, innovative functions have been included in the ETUs.
Rated current module/Rating Plug
The rated current module is an exchangeable module which allows the user to reduce the rated device current so as to adapt
it optimally to the plant; e. g. if a new plant section is taken into
operation. The rated current module must be selected to fit the
rated current of the plant.

16

Siemens 2009

Measurement function Plus

Selectable parameters
In the case of quick changes of power supply conditions,
e. g. for switchovers from transformer to generator operation or
if a section of the supply is disconnected when the shift
changes, SENTRON 3WL allows the relevant protection parameters to be quickly adapted to the new conditions.
The ETUs contain two independent tripping characteristic curves (parameter sets). The switchover is completed within
200 ms and is performed with the help of an external signal.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU15B solid-state release
Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release

Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator

Indicator: overcurrent
release activated
Indicator: fault in
overcurrent release

Indicator: overload alarm


Rotary switch for setting
value, overload release

Rotary switch for setting


value, instantaneous
short-circuit release

Sealing ring

Simple building and


system protection without time-selective coordination up to 4000 A.
Not to be used for size III.
Features:
Adjustable overload protection
with I2t characteristic curve
with preset delay time
tR = 10 seconds at 6 IR
Instantaneous short-circuit protection adjustable in the range
2 ... 8 In
Overload display
Protection function is set by
means of the rotary coding
switch

NSE0_00954b

For technical details see the table


"Functional overview of the
solid-state release system"
under "Technical specifications".
Test socket

ETU25B solid-state release


Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release

Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator

Indicator: overcurrent
release activated
Indicator: overload alarm

ETU25B
Indicator: fault in
overcurrent release

Rating Plug

Rated current module


Rotary switch for setting
value, overload release

Indicator: cause of release

Rotary switch for setting


value, instantaneous
short-circuit release
Short-circuit protection
fixed setting

Rotary switch for delay,


short-circuit release

NSE0_00955b

Query pushbutton
Test pushbutton

Sealing ring

Clear pushbutton
Test socket

Classical building, motor and system protection with time-selective


coordination for up to 6300 A
Features:
Adjustable overload protection
with I2t characteristic curve
Delay time tR =
10 seconds at 6 IR
Short-time delayed short-circuit
protection adjustable in the
range 1.25 ... 12 In and
Instantaneous short-circuit
protection preset
to 20 In, max. 50 kA
Can be adapted at any time to
the required plant currents
through retrofittable rated current module, thus ensuring overload protection in the range from
100 A to 6300 A
Overload display
Indicates the reason for tripping
by means of an LED
Test facility for the release
Protection functions are
set by means of the
rotary coding switch
For technical details see the table
"Functional overview of the
solid-state release system"
under "Technical specifications".

Siemens 2009

17

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
ETU27B solid-state release
Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release

Classical building, motor and system protection with time-selective


coordination for up to 6300 A
Features:

NSE0_00956c

Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator

Indicator: overcurrent
release activated

ETU27B

Indicator: overload alarm

OFF ON

The same as ETU25B but also


Reversible neutral conductor
protection
Permanently integrated groundfault protection. Calculation of
the ground-fault current through
vectorial summation current
formation

N-conductor protection
on/off
Indicator: fault in
overcurrent release

Rating Plug

Rated current module


Rotary switch for setting
value, overload release

Indicator: cause of release

Rotary switch for setting


value, instantaneous
short-circuit release

Rotary switch for delay,


short-circuit release

Short-circuit protection
fixed setting
Rotary switch for setting
value, earth-fault protection

For technical details see the table


"Functional overview of the
solid-state release system"
under "Technical specifications".

Sealing ring
OFF

Rotary switch for delay,


earth-fault protection

Query pushbutton
Test pushbutton

Clear pushbutton
Test socket

ETU45B solid-state release


Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Scroll up

Option: alphanumeric display

Indicators:
Overcurrent release
activated
Overload alarm

Scroll down
Indicator: fault in
overcurrent release

COMMUNICATION
EXPANDED

ETU45B
OFF ON

Rated current module

Rating Plug

Rotary switch for setting


value, overload release

Test pushbutton
Query pushbutton

Thermal memory on/off


N-conductor protection on/off
Setting value
N-conductor overload
Transfer of overload
characteristic 2 t / 4t

Rotary switch for delay,


short-circuit release
Indicator: cause of release
Sealing ring
Option: earth-fault module

SI
g

Indicator: earth-fault alarm


Indicator: earth-fault tripped
Rotary switch for delay,
earth-fault protection t g /
Clear pushbutton
Test socket

NSE0_00957b

Low-cost all-round system for intelligent buildings and all types of industrial applications
"CubicleBUS integrated"
Features:

Rotary switch for delay,


overload release
12

Rotary switch for setting


value, short-circuit
protection

Rotary switch for setting


value, earth-fault
protection
Rotary switch for setting
value, earth-fault alarm

1
1
1
1
1

Rotary switch for setting


value, instantaneous
short-circuit release

Selector for
earth-fault protection

Application:

Option: safety lock


prevents pressing of
reset button after
overcurrent release

tg

The same as ETU25B but also


Adjustable time-lag class
for overload protection
Selectable characteristic for overload and
short-delayed short-circuit range (current
discrimination) for more accurate discrimination adaptation to upstream fuses and
protective devices
Thermal image as restart protection for tripped motor outgoing feeders
Reversible and adjustable neutral conductor protection
Modular ground-fault protection module
with alarm and tripping functions which can
be adjusted separately
Communication interface,
measurement function Plus, optional connection of external modules or for
retrofitting
Storage of events and causes for tripping
for detailed fault analysis
Extended protection function possible with
measurement function
Optional high-contrast display with viewing
angle adjustment option
The protection functions can be set by
means of a rotary coding switch or slide
switch
For technical details see the table
"Functional overview of the
solid-state release system"
"Technical specifications".

18

Siemens 2009

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
ETU76B solid-state release
Application:
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator

Option: safety lock


prevents pressing of
reset button after
overcurrent release

ETU76B

The multi-talent with graphical


display for system analysis
"CubicleBUS integrated"
Features:

Indicators:
Overcurrent release
activated
Overload alarm
COMMUNICATION
EXPANDED

Graphical display

Indicator: fault in
overcurrent release

Indicator: cause of release

Rating Plug

Control keys for setting


he release parameters

Rated current module

Indicators:
Ground-fault alarm
Ground-fault tripped

Option: earth-fault module


Fields for noting
setting values

Fields for noting


setting values

Test pushbutton

Clear pushbutton

Query pushbutton

Test socket
NSE0_00960b

The same as ETU45B but also


including
Two protection parameter sets
which can be stored separately
in the release (switchover is performed by means of external signal)
With overload protection which
can be deactivated for operation
in modern drive technology
Adjustable delay of
delayed short-circuit protection
up to 4000 ms
Neutral conductor protection adjustable up to IN = 200 % In
Setting of protection functions by
means of Breaker Data Adapter
(BDA) or via communications interface
Graphical display of all
parameters and events/
curve trends
Graphics display with high contrast, backlit display, and sleep
mode
For technical details see the table
"Functional overview of the
solid-state release system"
under "Technical specifications".

Ground-fault releases "G" sense fault currents that flow to ground


and that can cause fire in the plant. Multiple circuit breakers connected in series can have their delay times adjusted so as to provide graduated discrimination.

Ground-fault protection
Selector for
ground-fault
detection
1

Rotary switch
for setting
value,
ground-fault
protection

g TRIP

ALARM

A
B
C
D
E

OFF

ALARM

TRIP

Indicators:

Ground-fault
alarm

GFM AT 45B

Ground-fault
tripped

1 2J g

(s)

.5
.4
.3
.2
.1

Rotary switch
for setting
value, groundfault protection delay

NSE0_00962a

Rotary switch
for setting value
ground-fault alarm

When setting the parameters for the solid-state release it is possible to choose between "alarm" and "trip" in the event that the
set current value is exceeded. The reason for tripping is indicated by means of an LED when the query button is activated.

.1
.2
.3
.4
.5

J g/1

The ETU45B and ETU76B solid-state release versions can be retrofitted with a ground-fault protection module. This ground fault
protection function is integrated in ETU27B solid-state releases.

GFM AT 45B ground-fault module


Field for
noting
transfer
ground-fault
detection

ALARM

1 g=

Fields for
noting setting
values

Ground-fault
alarm

GFM AT 55B-76B

Ground-fault
tripped

ALARM

A
1 2J

TRIP

TRIP

1 g=

Indicators:

J g=
NSE0_00964a

ms
Fields for
noting setting
values

GFM AT 55B-76B ground-fault module

Siemens 2009

19

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Measurement method

Setting

Vectorial summation current formation (measurement method 1)

How the module is set depends on the measurement method


used (see above):

The three phase currents and the N conductor current are


measured directly.

Measurement method 1: in position

The solid-state release determines the ground-fault current by


means of vectorial summation current formation for the three
phase currents and the N conductor current.

Measurement method 2: in position

Direct measurement of the ground-fault current


(measurement method 2)

Ground-fault protection with I2t characteristic curve

A standard current transformer with the following data is used for


measurement of the ground-fault current: 1200 A/1 A, Class 1
(the internal load of SENTRON 3WL is 0.11 ). The current transformer can be installed directly in the grounded neutral point of
a transformer.

With the exception of the ETU27B solid-state release, all


versions of the ground-fault modules are supplied with an I2t
characteristic curve which can be activated.

SENTRON WL
T5

L1
L2
L3
N
PE
NSE 00946

3-pole circuit breakers, current transformers in the N conductor

SENTRON WL

L1
L2
L3
N

T6
PE

T6: 1200 A/1 A

NSE 00947

3-pole circuit breakers, current transformers in the grounded neutral


point of the transformer

SENTRON WL

L1
L2
L3
N

T6

T6: 1200 A/1 A

PE
NSE 00948

4-pole circuit breakers, current transformers in the grounded neutral


point of the transformer

20

Siemens 2009

This setting can be implemented for the solid-state release version ETU76B with Menu/Comm.

Selection criteria for SENTRON 3WL circuit breakers


Basic criteria for selecting circuit breakers are:
Max. short-circuit current at place of installation of circuit breaker I k max.
This value determines the short-circuit breaking capacity
or short-circuit current carrying capacity of the circuit breaker.
It is compared with the value Icu, Ics, Icw of the circuit breaker
and essentially determines the size of the circuit breaker.
See illustration "Overview of SENTRON 3WL Circuit
Breakers/Non-Automatic Air Circuit Breakers".
Rated current In which is to flow through the branch circuit.
This value must not be larger than the maximum rated current
for the circuit breaker.
The rated current for the SENTRON 3WL is set with the rated
current module. See "Design", illustration "Overview of
SENTRON 3WL Circuit Breakers/Non-Automatic Air Circuit
Breakers".
Ambient temperature
for the circuit breaker.
This is usually the control cabinet internal temperature.
Design of the circuit breaker
Minimum short-circuit current
which flows through the switching device. The release must
still detect this value as a short-circuit and must respond by
tripping.
Protection functions of the circuit breaker.
These are determined by the selection of the
corresponding solid-state release, see the table
"Functions of the solid-state releases" under "Functions".

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
SENTRON 3WL for DC applications
This version of the 3WL non-automatic air circuit breaker is suitable for direct current applications. The external protective device DIGmat S100 provides adjustable overload and shortcircuit protection for the SENTRON 3WL non-automatic air circuit
breaker.
This is based on the measuring chain of a shunt resistor and the
DIGmat S100 tripping unit. Shunt resistors are available for
1000 A, 2000 A and 4000 A (special ranges on request). They
are in accordance with DIN 43703 and have a class accuracy
of 0.5.
A measuring-circuit voltage of 60 mV DC is picked off for rated
current In.
The measuring-circuit voltage is a linear image of the primary
current.

DIGmat S100

The DIGmat S100 tripping unit monitors the image of the primary
current thus supplied and compares it with the tripping characteristic curve set on the device. The parameter settings on
the DIGmat S100 apply also for DC feedbacks.
Reversing duty is possible therefore.

Short-circuit protection:
Setting range Ii = 1.25 IR up to max. 4 In
If the set value is exceeded, tripping occurs in less than
50 ms.
In
IR
tR
Ii

The tripping characteristic curve is determined and described


by the following variables:
Overload protection:
Setting range IR = 0.4 ... 1.0 In
The curve has a I2t characteristic.
The tripping time tR is selectable between 2 and 10 s, with tR
defined for 6 IR.

=
=
=
=

Rated current of the circuit breaker


Set current value of the adjustable overload release
Assigned tripping time of the overload trip
Instantaneous tripping current of the adjustable shortcircuit releases

The components are available only from the company


mat Maschinen- und Anlagentechnik
(for address see "Appendix" => "External Partners").

Configuration
Mutual mechanical circuit breaker interlocking

The bending radii of the Bowden wire must be greater than


500 mm.
The sum of all bending angles along the Bowden wire must not
exceed 640.
In a vertical arrangement of circuit breakers to be interlocked,
the interlocking mechanisms must be in line.
Circuit breakers to be interlocked must be arranged so that
Bowden cables can be optimally installed in compliance with
the conditions mentioned in the above points.
The installed Bowden wire must be fixed (with cable ties or the
like) before the interlock is adjusted.
Select the width of switchgear cubicle to allow enough freedom of movement for adjusting the interlock!
Openings and cut-outs in system elements must be designed
so that Bowden wires are not changed in direction or obstructed when they are passed through.

The module for mutual mechanical interlocking can be used for


one or two SENTRON 3WL circuit breakers and can be adapted
easily to the corresponding versions. The fixed-mounted and
withdrawable circuit breaker versions are fully compatible and
can therefore be used in a mixed configuration in an installation.
This also applies to 3WN6 circuit breakers.
The circuit breakers can be mounted alongside each other or
one above the other, whereby the distance of the circuit breakers
is determined solely by the length of the Bowden wire (lengths:
2 m/3 m/4.5 m). Interlock signals are looped through using the
Bowden wires. Interlocking is only effective in the connected position in the case of withdrawable circuit breakers. The mechanical endurance of the Bowden cables is 10 000 operating cycles.
Minimum requirements must be fulfilled in the switchgear for the
interlocking to function:
Bowden wires must be installed as far as possible in a straight
line with minimum bending.
Mutual mechanical interlocking of circuit breakers examples
Mutual interlocking of two
circuit breakers

Interlocking between three


circuit breakers

Mutual interlocking of three


circuit breakers

S1

S2

S1
S2

NSE01041

NSE01042

S3

S1
S1
NSE01043

S2

S2

Interlocking of three circuit


breakers, two of them mutual

S3

S1

S3
S2

S3
NSE01044

NSE01045

Siemens 2009

21

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Communication-capable circuit breakers

PLC e.g. SIMATIC S7


data acquisition and
processing

PC with Switch ES Power


SENTRON 3WL/3VL parameterization
and visualization tool through
PROFIBUS DP

Analog output module

Digital input module

Analog output module

Digital input module

NSE0_01820a

BDA
BDA Plus

ETU
Measurementfunction Plus

Digital output module


Relay, configurable

BSS

Digital output module


Relay

COM15

Zone Selective
Interlocking module

Output device
e.g. notebook
with browser

Ethernet/
Intranet/
Internet

Communication with PROFIBUS DP

Configuration and
display software

MODBUS Master
PLC or monitoring software

MODBUS

BDA
BDAPlus

ETU
Measurement
function Plus

NSE0_01894

BSS

Digital output module


Relay, configurable

COM16

Digital output module


Relay

Output device
e.g. notebook
with browser
Zone Selective
Interlocking module

Ethernet/
Intranet/
Internet

Communication with MODBUS

The requirements for power distribution in terms of communication capability, data transparency, flexibility and integration are
constantly increasing. An integrated and modular communication architecture was designed for the SENTRON 3WL to ensure
that it can satisfy these requirements.
The core component of this architecture is the CubicleBUS,
which links together all of the intelligent components within the
SENTRON 3WL and enables the easy and safe connection of
other additional external components to the circuit breaker. The
CubicleBUS is already incorporated and pre-connected in all
complete circuit breakers with ETU45B and ETU76B releases.

22

Siemens 2009

The high level of modularity of the system allows communication


functions to be retrofitted at any time (e. g. the measurement
function). Similarly, the upgrade of a non-communication-capable SENTRON 3WL (e .g. changeover from ETU25B to
ETU45B with CubicleBUS) can be carried out easily on site in
the plant. All modules connected to the CubicleBUS can directly
access the existing source data of the circuit breaker, which guarantees the quickest possible access to information and response to events.
Furthermore, additional external modules (including digital inputs/outputs, analog outputs) can be connected to the
CubicleBUS to provide cost-effective solutions for the automation of further devices in the switchgear.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
SENTRON 3WL communication-capable circuit breakers
Function

Solid-state
release version
ETU45B ETU76B

Breaker Status
Sensor

PROFIBUS
communication
port

Measu
rement
function
Plus

Analog
output
module
s

Digital
output
module
s

Digital ZSI
input
modul
module es
s

Breaker
Data
Adapter

Breaker
Data
Adapter Plus

Functions of the communication-capable SENTRON 3WL circuit breakers


Indication of measured values in release (current
only)

Indication of measured values in release


(U, I, P, S, Q, p.f., etc.)

Indication of measured values (current only),


parameter, diagnostic values etc. on display

--

Indication of measured values (U, I, P, S, Q, p.f., etc.),


parameters, diagnostic values etc. in release

--

Output of measured values (current only)


to rotary coil instruments in control cabinet door

Output of measured values (U, I, P, S, Q, p.f., etc.) to


rotary coil instruments in control cabinet door

Output of digital signals


(e. g. reason for tripping, alarm signals, status)
through contacts

Automatic changeover between


parameter sets A and B

--

Read in digital signals and forward to


PROFIBUS/MODBUS

Transmission of switch information


on HTML basis locally to a PC

Transmission of switch information


on HTML basis through Ethernet

Short-time grading control for


S tripping and G protection

Local display of harmonic analysis and waveform


memory

--

Local storage of harmonic analysis and waveform


memory and transmission through PROFIBUS

Read out protection parameters through PROFIBUS

Read out and adjust protection parameters through


PROFIBUS

--

Required
Function can optionally be taken over by more than one release.

Not necessary for this function, optionally combinable


--

Function not available

Function can optionally be taken over by one of these modules.

Siemens 2009

23

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter
All SENTRON 3WLs with ETU45B, ETU76B (CubicleBUS integrated)

Transmittable circuit breaker data


BSS
Order code (Order No. of circuit breaker + "Z")

BDA BSS

F01
+"BDA/BDAPLUS"
Order No.

Order No.

COM15/COM16

F02/F12

Potential applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into
higher-level visualization systems are possible
e. g. in PCS7, Power Management Systems, WinCC (incl. add-ons like the text message radio server)

--

Transmission of circuit breaker data and software (i. e. HTML pages with data) to a local output
device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into
higher-level visualization systems)
e. g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers

--

Utilization of the functionality of all CubicleBUS modules


e. g. configuration of the configurable digital output module, status check of the digital input modules,
diagnostics

Transmittable circuit breaker data without integrated measurement function


Device identification
Communication address, Order No., circuit breaker in delivery status, circuit breaker parameters
(size, number of poles, rated current module etc.), identification numbers, release type,
Free text for plant code and comments

1)

Operating statuses
On/off status message, storage spring, tripped, readiness
Switching position (connected, test and disconnected position, removed) for withdrawable circuit breakers,
PROFIBUS/MODBUS write protection on/off, free user input

--1)
--1)

Control commands
Switch circuit breaker on/off, switch free user output on/off
Reset tripped signal
Delete event and history memory
Reset the min./max. measured values, reset the maintenance information

--1)

--1)

History
Read out the event protocol, read out the release protocol

--1)

Maintenance information
Number of tripping operations L, S/I and in total, contact wear
Number of operating cycles under load and in total, number of operating hours

--1)

Event signals
Tripped signal with details of the tripping current
Alarm signals (e. g. overload) with incoming/outgoing information
All of the named event signals with time stamp

--1)
--1)

Parameterization of the protection functions


Reading out of the protection function parameters
Settings for the protection function parameters can be changed by means of communication
Parameter set switchover possible (set A to set B and back)

2)
2)

2)
2)

Measured values
Phase currents, each with min./max. value
Temperature in the circuit breaker with min./max. value
Temperature in the control cabinet with min./max. value
All of the named measured values with time stamp

--1)
--1)
--1)

--

Measurement function
Plus
Order code F01+ ... or F02+ ...

F05

Additional transmittable circuit breaker data with integrated measurement function


Additional event signals
Threshold value alarms (e. g. over/underfrequency, over/undervoltage)

Parameterization of the extended protection functions and setpoints (threshold values)


Reading out the parameters of the extended protection functions
Settings for the extended protection function parameters can be changed
Reading out and adjusting threshold values

Additional measured values


Voltages, power, energy, power factor, frequency, each with min./max. value
Harmonic analysis
Recording of currents and voltages for configurable events in the curve form memory

1) Data only available in conjunction with the COM15 module (BUS connection not required).
2) Only possible with ETU76B.

24

Siemens 2009

Available
-- Not available

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
CubicleBUS modules
Digital output modules with rotary coding switch
6 items of binary information concerning the state of the circuit
breaker (reasons for tripping and warnings) can be output via
this module to external signaling devices (e. g. LED, horn) or be
used for the selective shut-down of other system components
(e. g. frequency converters).
Digital output modules are available in versions with and without
a rotary coding switch. On modules with a rotary coding switch
it is possible to choose between two signaling blocks each with
6 defined assignments and to set an additional response delay.
All the digital output modules are available as a version with relay outputs (CO contacts, up to 12 A). Up to two modules of this
type can be connected to one SENTRON 3WL.

Analog output module

Digital input modules


With the digital input module, up to 6 additional binary signals
(24 V DC) in the circuit breaker environment can be connected
to the system. It is thus possible for example to send messages
concerning the state of a switch disconnector or a control cabinet door to the PROFIBUS DP/MODBUS.
With the digital input module on the CubicleBUS it is also possible for the two different protection parameter sets held in the
ETU76B solid-state releases to be switched over automatically in
a few milliseconds. It is thus possible, for example, to automatically change the parameters of a coupling switch should the
transformer infeed fail.

Digital output module with rotary coding switch

One module each of this type can be used for holding the six
items of digital information and for automatically switching over
the parameters.

Digital output modules, configurable


The configurable output module is available for higher-performance solutions. With this module, random events on the
CubicleBUS can be switched directly to one of six available outputs or three of these outputs can be assigned with up to six
events. In other words, up to six events can be placed on one
physical output with OR operation. Either BDA/BDA Plus or
Switch ES Power is used for configuring.
A relay variant is also available here the same as for the output
modules with rotary coding switch. Only one module of this type
is possible per SENTRON 3WL.
Digital input module

ZSI modules (short-time grading control)


The use of ZSI modules is recommended when Siemens circuit
breakers are arranged in several staggered levels but full grading with the smallest possible delay is to be assured nevertheless.

Digital output module, configurable

The circuit breakers are interconnected by these modules. In


case of a short-circuit, each affected circuit breaker asks the circuit breakers directly downstream whether the short-circuit has
also occurred in the next, lower level. The short-circuit is exactly
localized as the result, and only the next upstream circuit breaker in the energy flow direction is switched off.

Analog output modules


The analog output module can be used to output the following
measured values to analog indicators in the control cabinet
door:
IL1, IL2, IL3, IN or
UL12, UL23, UL31, UL1N or
PL1, PL2, PL3, Stot or
p.f.1 , p.f.2 , p.f.3, I % or
favg, ULLavg, Ptot, p.f.avg
Four 4-20-mA/0-10-V interfaces are available for this. The
measured values to be output are selected with a rotary coding
switch. By using the analog output module it is possible to do
without additional converters and their conventional installation/wiring in the main current path. Up to two modules of this
type can be connected to one SENTRON 3WL.

ZSI module (short-time grading control)

Siemens 2009

25

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data

Technical specifications
Size

II

Type

3WL11

3WL12

Switching capacity class

III

3WL13

C
3-pole

C
4-pole

Short-circuit breaking capacity


Rated operational voltage Ue
up to 415 V AC
Icu

kA

55

66

66

80

100

100

150

130

Ics

kA

55

66

66

80

100

100

150

130

Icm

kA

121

145

145

176

220

220

330

286

Rated operational voltage Ue


up to 500 V AC
Icu

kA

55

66

66

80

100

100

150

130

Ics

kA

55

66

66

80

100

100

150

130

Icm

kA

121

145

145

176

220

220

330

286

Rated operational voltage Ue


up to 690 V AC
Icu

kA

42

50

50

75

85

85

150

130

Ics

kA

42

50

50

75

85

85

150

130

Icm

kA

88

105

105

165

187

187

330

286

Rated operational voltage Ue


up to 1000 V/1150 V AC
Icu

kA

--

--

--

--

45

50

704)

704)

Ics

kA

--

--

--

--

45

50

704)

704)

4)

1544)

kA

Icm

--

--

--

--

95

105

154

Rated short-time withstand current Icw


of the circuit breakers3)
0.5 s

kA

50

66

66

80

100

100

100

100

1s

kA

42

50

55

66

80

100

100

100

2s

kA

29.5

35

39

46

651)/702)

80

80

80

3s

kA

24

29

32

37

501)/652)

65

65

65

Short-circuit breaking capacity Icc


of the non-automatic air circuit breakers
Up to 500 V AC

kA

50

66

66

80

100

100

100

100

Up to 690 V AC

kA

42

50

50

75

85

85

100

100

Circuit breakers with ECO switching capacity N


(Icu = Ics up to 55 kA size I/up to 66 kA size II at 500 V)

Circuit breakers with standard switching capacity S


(Icu = Ics up to 66 kA size I/up to 80 kA size II at 500 V)

Circuit breakers with high switching capacity H


(Icu = Ics up to 100 kA at 500 V)

DC

Circuit breakers with very high switching capacity C


(Icu = Ics up to 150 kA (3-pole)/130 kA (4-pole)
at 500 V)
Circuit breakers with DC switching capacity
These circuit breakers are indicated in the Technical
specifications by orange-colored backgrounds.

26

Siemens 2009

1) Size II with In max 2500 A.


2) Size II with In max = 3200 A and In max = 4000 A.
3) At a rated voltage of 690 V the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.
4) Rated operational voltage Ue = 1150 V.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
I
II
... 3WL11 10 3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
... 1000
... 1000
... 690

1250
1250
... 690

1600
1600
... 690
1000

800
800
...
690/1000
1000

1000
1000
...
690/1000
1000

1250
1250
...
690/1000
1000

1600
1600
...
690/1000
1000

2000
2000
...
690/1000
1000

1000

1000

12
4
2.5
Yes
B

12
4
2.5
Yes

12
4
2.5
Yes

12
4
2.5
Yes

12
4
2.5
Yes

12
4
2.5
Yes

12
4
2.5
Yes

12
4
2.5
Yes

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

1000
1000
1000

1250
1250
1210

1600
1600
1490

800
800
800

1000
1000
1000

1250
1250
1250

1600
1600
1600

2000
2000
2000

2000

2000

2000

2000

2000

2000

2000

2000

100
195

105
205

150
350

40
85

45
95

80
165

85
175

180
320

35
38
80
73
73
501)

35
38
80
73
73
501)

35
38
80
73
73
501)

35
34
100
73
73
501)

35
34
100
73
73
501)

35
34
100
73
73
501)

35
34
100
73
73
501)

35
34
100
73
73
501)

10 000
20 000
10 000
--20 000

10 000
20 000
10 000
--20 000

10 000
20 000
10 000
--20 000

10 000
15 000
7500
1000
500
15 000

10 000
15 000
7500
1000
500
15 000

10 000
15 000
7500
1000
500
15 000

10 000
15 000
7500
1000
500
15 000

10 000
15 000
7500
1000
500
15 000

60
--80

60
--80

60
--80

60
20
20
80

60
20
20
80

60
20
20
80

60
20
20
80

60
20
20
80

3 0

3 0

3 0

3 0

h m a x .
= 1 m m

Size
Type
Rated current In at 40 C, at 50/60 Hz
Main conductor
A
N conductor (only on 4-pole versions)
A
V AC
Rated operational voltage Ue at 50/60 Hz
(for 1000 V version see Catalog LV 1, "Options")
V AC
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
Main current paths
kV
Auxiliary circuits
kV
Control circuits
kV
Isolating function acc. to EN 60947-2
Utilization categories
Permissible ambient temperature
C
During operation (in operation with LCD max. 55 C)4)
During storage (special conditions for LCDs must be
C
observed)
A
Permissible load
Up to 55 C (Cu bare)
A
At rear horizontal main circuit Up to 60 C (Cu bare)5)
A
connections
Up to 70 C (Cu black
5)
painted)
V
Rated rotor operational voltage Uer
Power loss at In
With 3-phase symmetrical load
Fixed-mounted circuit breakers
W
Withdrawable circuit breakers
W
Operating times
ms
Make-time
ms
Opening time
2)
ms
Electrical make-time (through closing solenoid)
Electrical opening time (through shunt release)
ms
ms
Electrical opening time (instant. undervoltage release)
ms
Opening time due to ETU, instant. short-circuit release
Endurance
Mechanical (without maintenance)
Oper. cycles
Mechanical (with maintenance)3)
Oper. cycles
Electrical (without maintenance)
Oper. cycles
1000 V version, electrical (without maintenance) Oper. cycles
1150 V version, electrical (without maintenance) Oper. cycles
Oper. cycles
Electrical (with maintenance)3)
Switching frequency
690 V version
1/h
1000 V version
1/h
1150 V version
1/h
Minimum interval between tripping operation by solid-state
ms
release and next making operation of the circuit breaker (only
with autom. mechanical resetting of the lockout device)
Mounting position

and/
or
N S E 0 _ 0 0 0 6 1 a

Degree of protection
Main conductor
minimum
cross-sections
Auxiliary conductors (Cu)
Max. number of
auxiliary conductors
cross-section (solid/stranded)

Position indicator switches


Weights 3-pole
4-pole

Copper bars,
bare
Copper bars,
painted black
Standard connection =
strain-relief clamp
Without end sleeve
With end sleeve acc. to
DIN 46228 Part 2
With twin end sleeve
Optional connection =
tension spring
Without end sleeve
With end sleeve acc. to
DIN 46228 Part 2
Tension spring terminals
Fixed-mounted circuit
breakers
Withdrawable circuit
breakers
Guide frames
Fixed-mounted circuit
breakers
Withdrawable circuit
breakers
Guide frames

N S E 0 _ 0 0 0 6 2 a

N S E 0 _ 0 0 9 2 7 a

IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
2
2
1
1
2
2
Units 1
2
40 10
50 10
50 10
60 10
40 10
50 10
mm 60 10
Units 1
2
2
1
1
2
2
mm2 60 10
40 10
50 10
50 10
60 10
40 10
50 10

3
50 10
3
50 10

2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
1 0.5 mm2 (AWG 20) ... 1 2.5 mm2 (AWG 14)
kg 43
43
43
56
56

56

56

56

kg 45

45

45

60

60

60

60

60

kg 25
kg 50

25
50

25
50

31
67

31
67

31
67

31
67

31
67

kg 54

54

54

72

72

72

72

72

kg 30

30

30

37

37

37

37

37

1) Opening time on instantaneous short-circuit release with


ETU15B = 85 ms.
2) Make-time through closing solenoid for synchronization purposes
(short-time excited) 50 ms.

3) Maintenance means: replace main contact elements and arc chutes (see
Operating Manual).
4) Use of releases from 20 C.
5) ETU76B with graphics display can be used up to max. 55 C.

Siemens 2009

27

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Size

II

Type

3WL12 25

Rated current In at 40 C, at 50/60 Hz


Main conductor
N conductor (only on 4-pole versions)

III

A 2500
A 2500

3WL12 32

3WL12 40

3WL13 40

3WL13 50

3WL13 63

3200
3200

4000
4000

4000
4000

5000
5000

6300
6300

Rated operational voltage Ue at 50/60 Hz


(for 1000 V version see Catalog LV 1, "Options")

V AC ... 690/1000

... 690/1000

... 690

... 690/1000

... 690/1000

... 690/1000

Rated insulation voltage Ui

V AC 1000

1000

1000

1000

1000

1000

kV 12
kV 4
kV 2.5

12
4
2.5

12
4
2.5

12
4
2.5

12
4
2.5

12
4
2.5

Yes

Yes

Yes

Yes

Yes

Isolating function acc. to EN 60947-2

Yes

Utilization categories

B (except switching capacity class DC)

Permissible ambient temperature


During operation (in operation with LCD max. 55 C)4)
During storage (special conditions for LCDs must be observed)
6)

Up to 55 C (Cu bare)
Up to 60 C (Cu bare)5)
Up to 70 C (Cu black painted)5)
Rated rotor operational voltage Uer
Permissible load

Power loss at In
With 3-phase symmetrical load
Fixed-mounted circuit breakers
Withdrawable circuit breakers
Operating times
Make-time
Opening time
Electrical make-time (through closing solenoid)2)
Electrical opening time (through shunt release)
Electrical opening time (instantaneous undervoltage release)
Opening time due to ETU, instantaneous short-circuit release
Endurance
Mechanical (without maintenance)
Mechanical (with maintenance)3)
Electrical (without maintenance)
1000 V version, electrical (without maintenance)
1150 V version, electrical7) (without maintenance)
Electrical (with maintenance)3)

C 25/+70
C 40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

25/+70
40/+70

A 2500
A 2500
A 2280

3200
3020
2870

3950
3810
3600

4000
4000
4000

5000
5000
5000

5920
5810
5500

V 2000

2000

2000

2000

2000

2000

W 270
W 520

410
710

750
925

520
810

630
1050

900
1600

35
34
100
73
73
501)

35
34
100
73
73
501)

35
34
100
73
73
50

35
34
100
73
73
50

35
34
100
73
73
50

10000
15000
4000
1000
500
15000

10000
15000
4000
1000
500
15000

5000
10000
2000
1000
1000
10000

5000
10000
2000
1000
1000
10000

5000
10000
2000
1000
1000
10000

1/h 60
1/h 20
1/h 20

60
20
20

60
20
20

60
20
20

60
20
20

60
20
20

ms 80

80

80

80

80

80

ms 35
ms 34
ms 100
ms 73
ms 73
ms 501)

Oper. cycles 10000


Oper. cycles 15000
Oper. cycles 7500
Oper. cycles 1000
Oper. cycles
500
Oper. cycles 15000

Switching frequency
690 V version
1000 V version
1150 V version7)
Minimum interval between tripping operation by solid-state
release and next making operation of the circuit breaker (only
with automatical mechanical resetting of the lockout device)

3 0

Mounting position

3 0

3 0

3 0

and/
or
N S E 0 _ 0 0 0 6 1 a

h m a x .
= 1 m m

Rated impulse withstand voltage Uimp


Main current paths
Auxiliary circuits
Control circuits

N S E 0 _ 0 0 0 6 2 a

N S E 0 _ 0 0 9 2 7 a

IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover

Degree of protection
Units
mm2
Units
mm2

2
100 10
2
100 10

3
100 10
3
100 10

4
120 10
4
100 108)

4x
100 x 10
4
100 10

6x
100 x 10
6
100 10

Main conductor
minimum
cross-sections

Copper bars,
bare
Copper bars,
painted black

Auxiliary conductors
(Cu)
Max. number of
auxiliary conductors
cross-section
(solid/stranded)

Standard connection = strain-relief clamp


Without end sleeve
With end sleeve acc. to DIN 46228 Part 2
With twin end sleeve

2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)

Optional connection = tension spring


Without end sleeve
With end sleeve acc. to DIN 46228 Part 2

2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)


2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)

4-pole

Fixed-mounted circuit breakers


Withdrawable circuit breakers
Guide frames
Fixed-mounted circuit breakers
Withdrawable circuit breakers
Guide frames

2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)

1 0.5 mm2 (AWG 20) ... 1 2.5 mm2 (AWG 14)

Position indicator swit- Tension spring terminals


ches
Weights 3-pole

kg
kg
kg
kg
kg
kg

59
63
39
71
76
47

1) Opening time on instantaneous short-circuit release with


ETU15B = 85 ms.
2) Make-time through closing solenoid for synchronization purposes
(short-time excited) 50 ms.
3) Maintenance means: replace main contact elements and arc chutes (see
Operating Manual).

28

Siemens 2009

6x
120 x 10
6
120 10

64
68
45
77
82
54

4)
5)
6)
7)
8)

85
121
52
103
146
62

82
88
60
99
106
84

82
88
60
99
106
84

90
96
70
108
108
119

Use of releases from 20 C.


ETU76B with graphics display can be used up to max. 55 C.
4000 A, size II in fixed-mounted version, 3-pole.
Size III: data for very high switching capacity.
Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 x 120 x 10 mm.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size

I to III

Type

3WL1

Manual operating mechanism with mechanical closing


Closing/
Charging storedenergy feature

N 230
9

Max. force required to operate the hand lever


Required number of strokes on the hand lever

Manual operating mechanism with mechanical and electrical closing


Charging storedenergy feature
Closing solenoid
(CC)

Operating range

0.85 ... 1.1 Us

Extended operating range for battery operation

At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC

Power consumption

AC/DC

Minimum command duration at Us for the closing solenoid

0.7 ... 1.26 Us

VA/W 15/15
ms 60
1 A TDz (slow)/1 A

Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic

Manual/motorized operating mechanism with mechanical and electrical closing


For data see above.

Manual operating
mechanism
Motor

Operating range

0.85 ... 1.1 Us

Extended operating range for battery operation

At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC

Power consumption of motor

AC/DC

VA/W 135/135
s 10

Time required to charge the stored-energy mechanism at 1 Us

For data see above.

Closing solenoid
For motor and
closing solenoid

0.7 ... 1.26 Us

Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic;
Motor and closing solenoid for the same rated control supply voltages
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic (for different
rated control supply voltages)

At Us = 24 ... 30 V
At Us = 48 ... 60 V
At Us = 110 ... 125 V DC/
110 ... 127 V AC
At Us = 220 ... 250 V DC/
208 ... 240 V AC

2 A TDz (slow)/1 A

2A
2A
1A
1A

Solid-state release signals


Protection functions according to
EN 60947;
current indication 10 %;
Measurement function
base quantities 1 %;
Measurement function
derived quantities 4 %

Measuring accuracy of the solid-state release

Auxiliary releases
Undervoltage
releases
UVR (F3) and
UVR-td (F4)

Response values

Pickup
Dropout

0.85 Us
(circuit breaker can be closed)
0.35 ... 0.7 Us
(circuit breaker is tripped)
0.85 ... 1.1

Operating range
Extended operating range for battery operation

At 24 V DC, 30 V DC,
48 V DC, 110 V DC,
220 V DC

Rated control supply voltage Us

Instantaneous
AC 50/60 Hz
DC

V 110 ... 127/208 ... 240/380 ... 415


V 24/30/48/60/110/220 ... 2501)

Delayed
AC 50/60 Hz
DC

V 110 ... 127; 208 ... 240; 380 ... 415


V 48; 110 ... 125; 220 ... 250

Power consumption (pickup/uninterrupted duty)


Opening time of circuit breaker at Us = 0
- Version UVR (F3)
Instantaneous
With delay
- Version UVR-td (F8)
With delay, td = 0.2 to 3.2 s
Reset through additional NC contact direct switching off
Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
Miniature circuit breaker with C characteristic

AC
DC

0.85 ... 1.26

VA 20/5
W 20/5
ms 200
ms 80
ms 200
s 0.2 ... 3.2
ms 100
1 A TDz (slow) 1 A

1) 24 V and 30 V only with undervoltage release UVR (F3).

Siemens 2009

29

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data

Size

I to III

Type

3WL1

Auxiliary releases
Shunt release (ST)
(F1, F2)

For continuous command


(100 % ON period), locks
out on momentary-contact commands

- Response value

> 0.7 Us
(circuit breaker is tripped)

pickup

0.85 ... 1.1 Us

- Operating range
- Extended operating range
for battery operation

At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC

- Rated control supply voltage Us

AC 50/60 Hz
DC

- Power consumption

AC/DC

V 110; 230
V 24; 30; 48; 60; 110; 220
VA/W 15/15
ms 60

- Minimum command duration at Us


- opening time of circuit breaker at
Us = 100 %

5 % ON period

AC/DC

ms 80

- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational
class)/ miniature circuit breaker with C characteristic

1 A TDz (slow)/1 A

- Response value

> 0.7 Us
(circuit breaker is tripped)

Pickup

0.85 ... 1.1 Us

- Operating range
- Extended operating range
for battery operation

At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC

- Rated control supply voltage Us

AC 50/60 Hz
DC

- Power consumption

AC/DC

- Opening time of circuit breaker at


Us = 100 %

VA/W 15/15
ms 25

AC/DC

ms 50
1 A TDz (slow)/1 A

- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
- Rated control supply voltage Us

AC 50/60 Hz
DC

V 110; 230
V 110; 220
0.85 ... 1.1 Us

- Operating range
- Power consumption

0.7 ... 1.26 Us

V 110 ... 127; 208 ... 240


V 24; 48; 110 ... 125; 220 ... 250

- Minimum command duration at Us

With stored energy


feature consisting of
shunt release and capacitor storage device

0.7 ... 1.26 Us

AC/DC

VA/W 1/1

- Storage time at Us/


recharging time at Us

maximum 5 min/minimum 5 s

- Opening time of circuit breaker,


short-circuit protection

As with "for continuous


command"

Remote reset solenoid for mechanical tripped indicator (F7)


0.85 ... 1.1 Us

- Operating range

Remote reset solenoid for


mechanical tripped indicator (F7)

- Extended operating range


for battery operation

At 24 V DC, 48 V DC
110 V DC
220 V DC

- Power consumption

AC/DC

0.7 ... 1.26 Us

VA/W 50/50

- Minimum command duration at Us for the remote


reset solenoid

ms 60

- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic

2 A TDz (slow)/1 A at 24 V DC
and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V

Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui

V AC/DC 500

Rated operational voltage Ue

V AC/DC 500
kV 4

Rated impulse withstand voltage Uimp


Switching capacity

Alternating current
50/60 Hz

Direct current

Short-circuit protection

30

- Rated operational voltage Ue


- Rated operational current
Ie /AC-12
Ie/AC-15
- Rated operational voltage Ue
- Rated operational current
Ie/DC-12
Ie/DC-13

Largest permissible DIAZED fuse (gL operational class)


Largest permissible miniature circuit breaker with C characteristic

Siemens 2009

V 24 ... 230
A 10
A 4
V 24

48

A 10
A 8

8
4

380/400

500

10
3

10
2

110

220

3.5
1.2

10 A TDz, 10 A Dz
10 A

1
0.4

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Size

I to III

Type

3WL1

Ready-to-close signaling switch (S20) (acc. to DIN VDE 0630)


Switching capacity

Short-circuit protection

Alternating current

- Rated operational voltage Ue


- Rated operational current Ie

V 250
A
8

Direct current

- Rated operational voltage Ue


- Rated operational current Ie

V 125
A
0.4

Largest permissible DIAZED fuse (gL operational class)

250
0.2

2 A Dz (quick)

Tripped signal switch (S24) and signal switch for auxiliary releases (S22, S23) (acc. to DIN VDE 0630)
Switching capacity

Alternating current

- Rated operational voltage Ue


- Rated operational current Ie/AC-12

V 250
A
8

Direct current

- Rated operational voltage Ue


- Rated operational current Ie/DC-12

V 24
A 6

125
0.4

Short-circuit protection

Largest permissible DIAZED fuse (gL operational class)

6 A Dz (quick)

Tripped signal switch

Signal duration after tripping

Until manual or electrical


remote reset (option)

250
0.2

Position indicator switch on guide frame


Type of contact

Signal:

- "Circuit breaker in connected


position"
- "Circuit breaker in test position"
- "Circuit breaker in disconnected
position"
AC 50/60 Hz
DC

Rated insulation voltage Ui

- Ie/AC-12

V 440
V 250

- Ie/DC-13

24 V 10 A, 110/127 V 10 A,
220/240 V 10 A, 320/440 V 10 A
220/240 V 4 A,
320/440 V 3 A,
24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
24 V 3.0 A, 220/240 V 0.1 A

- A 300 (AC)

120 V 6 A, 240 V 3 A

- R 300 (DC)

125 V 0.22 A, 250 V 0.11 A

- Ie/AC-15
- Ie/DC-12

Short-circuit protection

1 CO
1 CO
1 CO

kV 4

Rated impulse withstand voltage Uimp


Rated operational
current Ie

or

V 250

Rated operational voltage Ue


Switching capacity

3 CO
2 CO
1 CO

Largest permissible DIAZED fuse (gL operational class)


Largest permissible miniature circuit breaker with C characteristic

8 A TDz (slow)
8 A TDz (slow)

Siemens 2009

31

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


General data
Protection functions
Parameterization by

ETU15B
D

ETU25B
D

ETU27B
D&S

-0.5-0.55-0.6-0.65-0.70.75-0.8-0.85-0.9-1
--

-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--

-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--

10 s fixed
------------

10 s fixed
--at tsd = 20 ms (M)
---
-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--

10 s fixed
--at tsd = 20 ms (M)

-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--

--
-2-3-4-5-6-7-8
------

--
-Fixed for Ii 20 In, max. 50
kA
------

--
-Fixed for Ii 20 In, max. 50
kA
Fixed mounted
-
-

--

--

--

-----

-----

A-B-C-D-E
-100-200-300-400-500 ms
--

---

---

---

--

--

--

---

---

---

---

---

---

--

--

--

---------

------

----

--------------

--------------

--------------

Functional overview of the solid-state release system


Overload protection
Function can be switched on/off
Setting range IR = In ...

L
R

N
s d
s d

i
N S E 0 _ 0 0 8 8 8 b

Switchable overload protection


(I2t- or I4t-dependent function)
Setting range for time-lag class tR at I2t
Setting range for time-lag class tR at I4t
Thermal image can be switched on/off
Phase failure sensitivity
Neutral conductor protection
Function can be switched on/off
N conductor setting range IN = In ...
Short-time delayed short-circuit protection
Function can be switched on/off
Setting range Isd = In ...
Setting range for delay time tsd
Switchable short-time delayed short-circuit protection
(I2t-dependent function)
Setting range for delay time tsd at I2t
Zone Selective Interlocking function
Instantaneous short-circuit protection
Function can be switched on/off
Setting range Ii = In ...

Ground-fault protection
Tripping and alarm function
Tripping function can be switched on/off
Alarm function can be switched on/off
Detection of the ground-fault current through summation
current formation with internal or external neutral cong
ductor transformer
Detection of ground-fault current through external
current transformer
g
Setting range of the operating current Ig for release
Setting range of the operating current Ig for alarm
N S E 0 _ 0 0 8 8 9 a
Setting range of the delay time tg
Switchable ground-fault protection characteristic
curve (I2t-dependent function)
Setting range for delay time tg at I2t
Zone Selective Interlocking ground-fault protect. func.
Parameter set switchover
Switchable between parameter set A and B
LCD
Alphanumeric LCD (4-line)
Graphical LCD (24 V, ext. power supply required)
Communication
CubicleBUS integrated
Communication-capable through PROFIBUS DP
Measurement function
Measurement-function capable with measurement
function Plus
LED display
Solid-state release active
Alarm
ETU fault
L-release
S-release
I-release
N-release
NSE00890
G-release
G-alarm
Release through extended protection function
Communication
Signals from signal switches with external CubicleBUS modules (relays)
Overload warning
Load shedding, load receiving
Leading signal overload trip 200 ms
Temperature alarm
Phase unbalance
Instantaneous short-circuit release
Short-time delayed short-circuit release
Overload trip
Neutral conductor release
NSE00891
Ground-fault protection release
Ground-fault alarm
Auxiliary relay
ETU fault

Delay time figures given in ms.


M = Motor protection, corresponds to 20 ms.
D = Rotary coding switch
D & S = Rotary coding and slide switch
K = Communication
M/K = Menu/communication

32

Siemens 2009

Available
-- Not available
Optional

For the setting range of the operating current Ig see page 33.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
Protection functions
Parameterization by

ETU45B
D& S

ETU76B
M/K

Functional overview of the solid-state release system

-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1

Overload protection
Function can be switched on/off
Setting range IR = In ...

Switchable overload protection


(I2t- or I4t-dependent function)
Setting range for time-lag class tR at I2t
2-3.5-5.5-8-10-14-17-21-25-30 s
Setting range for time-lag class tR at I4t
1-2-3-4-5 s
Thermal image can be switched on/off

Phase failure sensitivity


At tsd = 20 ms (M)
Neutral conductor protection

Function can be switched on/off

N conductor setting range IN = In ...


0.5 ... 1
Short-time delayed short-circuit protection

Function can be switched on/off

Setting range Isd = In ...


1.25-1.5-2-2.5-3-4-6-8-10-12
Setting range for delay time tsd
M-100-200-300-400 ms
Switchable short-time delayed short-circuit protection

2
(I t-dependent function)
2
Setting range for delay time tsd at I t
100-200-300-400 ms
Zone Selective Interlocking function
By CubicleBUS-Modul
Instantaneous short-circuit protection

Function can be switched on/off

Setting range Ii = In ...


1.5-2.2-3-4-6-8-10-12-0.8 x Ics
Ground-fault protection
Module can be retrofitted
Tripping and alarm function

Tripping function can be switched on/off

Alarm function can be switched on/off


-Detection of the ground-fault current through summation cur-
rent formation with int. or ext. neutral conductor transformer
Detection of ground-fault current through external

current transformer
Setting range of the operating current Ig for release
A-B-C-D-E
Setting range of the operating current Ig for alarm
A-B-C-D-E
Setting range of the delay time tg
100-200-300-400-500 ms
Switchable ground-fault protection characteristic curve

(I2t-dependent function)
2
Setting range for delay time tg at I t
100-200-300-400-500 ms
Zone Selective Interlocking ground-fault protect. function
By CubicleBUS-Modul
Parameter set switchover
Switchable between parameter set A and B
-LCD
Alphanumeric LCD (4-line)

Graphical LCD (24 V, external power supply required)


-Communication
CubicleBUS integrated

Communication-capable through PROFIBUS DP

Measurement function
Measurement-function capable with measurement function

Plus
LED display
Solid-state release active

Alarm

ETU fault

L-release

S-release

I-release

N-release

G-release
(only with ground-fault prot. module)
G-alarm
(only with ground-fault prot. module)
Release through extended protection functions

Communication

Signals from signal switches with external CubicleBUS modules (relays)


Overload warning

Load shedding, load receiving

Leading signal overload trip 200 ms

Temperature alarm

Phase unbalance

Instantaneous short-circuit release

Short-time delayed short-circuit release

Overload trip

Neutral conductor release

Ground-fault protection release


(only with ground-fault prot. module)
Ground-fault alarm
(only with ground-fault prot. module)
Auxiliary relay

ETU fault

Setting range of the operating current Ig


Size I and size II
Size III
A
B
C
D
E

100 A
300 A
600 A
900 A
1200 A

400 A
600 A
800 A
1000 A
1200 A

Increment size for adjustment of M


From ... to
Increment
From ... to
size
0 ... 1
0.1
1000 ... 1600
1 ... 100
1
1600 ... 10000
100 ... 500
5
10000 ... max
500 ... 1000
10

0.4 ... 1

2 ... 30 s
1 ... 5 s

(on/off)

0.2 ... 2

1.25 In ... 0.8 Icw


M-80 ... 4000 ms

100 ... 400 ms


By CubicleBUS-Modul

1.5 In ... 0.8 Ics


Module can be retrofitted

A ... E
A ... E
100 ... 500 ms

100 ... 500 ms


By CubicleBUS-Modul

(only with ground-fault prot. module)


(only with ground-fault prot. module)

(only with ground-fault prot. module)


(only with ground-fault prot. module)

Increment
size
50
100
1000

For continuation of legend


see page 32.

Siemens 2009

33

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids

Characteristic curves

0,4 ... 1,0 x

1000

100

10
sd min

1,25 ... 12 x

0 ... 0,4 s

100

10000
R min

R max

0,4 ... 1,0 x

1000

n
N

100

10
sd min

sd max

1,25 ... 12 x

sd max

0 ... 0,4 s

sd min

i > 20 x n
max. 50 kA

0,01

100

0,1

10

100
/

SENTRON 3WL circuit breaker with ETU27B solid-state release,


LSIN characteristic curve
10000

Opening time

[s]

NSE0_01521

1000

SENTRON 3WL circuit breaker with ETU15B solid-state release

10000

Opening time [s]

10
/

0,1

SENTRON 3WL circuit breaker with ETU25B solid-state release,


LSI characteristic curve

100
g min

0,1

i > 20 x n
max. 50 kA

NSE0_01527

[s]
Opening time

0,01

10

i max
n

0,1

0,01

10

i min

2 ... 8 x

sd min

10

sd max

0,1

0,1

100

sd max
n

R max

0,5 ... 1,0 x n

NSE0_01519

R max

R min

1000

g max

1000

NSE0_01523

Opening time [s]

R min

NSE0_01520

10000

10000

Opening time [s]

Every solid-state release type and every setting has its own characteristic curve. Only a selection is shown in the following. The
characteristic curves each show the largest and smallest setting
range of SENTRON 3WL circuit breakers with 1000 A rated current at 500 V rated voltage with various releases. In order to obtain a complete tripping characteristic, the relevant parts of the
characteristics have to be combined.
The characteristic curves show the behavior of the solid-state release when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after switch on and the solid-state release is therefore
not yet enabled, the opening time is extended, depending on the
level of the overcurrent by up to 15 ms. In order to determine the
break-times of the circuit breakers, approximately 15 ms must
be added to the opening times shown for the arcing time.2)
Refer to the following legend for tolerances.
The characteristic curves shown apply to ambient temperatures
at the circuit breaker between 5 and +55 C. The release can
be operated at ambient temperatures of 20 to +70 C. An extended tolerance band can apply at these temperatures.

sd

1,25 ... 12 x

100
2

sd =

const

10

100 ... 1200 A1)


1

g max

0,1 ... 0,5 s

sd =

0,1

g min

const

sd =

const

0,1 ... 0,4 s

0,1
0,02 ... 0,4 s

0,01
100

1000

10000

100000
A

0,01
0,1

10

100
/

SENTRON 3WL circuit breaker with ETU27B solid-state release,


G characteristic curve

SENTRON 3WL circuit breaker with ETU45B solid-state release,


S characteristic curve

Tolerances for the set currents


L: tripping operations between 1.05 and 1.2 x IR
S: 0 %, +20 %
I: 0 %, +20 %
G: 0 %, +20 %

1) Sizes I and II: 100 ... 1200 A


Size III: 400 ... 1200 A.

Tolerances for the tripping times


L: 20 %, +0 % for I2t characteristic curve
S: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
I: < 50 ms
G: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms

34

Siemens 2009

2) With single-pole loading in the lowest rated current range, the response
times of the short-circuit release can be extended by approx. 10 % and
the tripping times by approx. 15 % compared to the characteristic curve.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids

Opening time [s]

0,4 ... 1,0 x

1000

= const

n
2

= const

100
R
2 ... 30s for 2
1 ... 5s for 4

10

NSE0_01525a

Opening time [s]

1000

100
g

10

= const

100 ... 1200 A1)

1
g

0,1 ... 0,5 s

0,1

0,01
100

1000

10000

100000
A

SENTRON 3WL circuit breaker with ETU45B and ETU76B solid-state


release, G characteristic curve
10000

1000

NSE0_01526a

10000

Opening time [s]

10000

NSE0_01522a

Every solid-state release type and every setting has its own characteristic curve. Only a selection is shown in the following. The
characteristic curves each show the largest and smallest setting
range of SENTRON 3WL circuit breakers with 1000 A rated current at 500 V rated voltage with various releases. In order to obtain a complete tripping characteristic, the relevant parts of the
characteristics have to be combined.
The characteristic curves show the behavior of the solid-state release when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after switch on and the solid-state release is therefore
not yet enabled, the opening ime is extended, depending on the
level of the overcurrent by up to 15 ms. In order to determine the
break-times of the circuit breakers, approximately 15 ms must
be added to the opening times shown for the arcing time.2)
Refer to the following table for tolerances.
The characteristic curves shown apply to ambient temperatures
at the circuit breaker between -5 and +55 C. The release can be
operated at ambient temperatures of -20 to +70 C (ETU76B
with graphics display up to +55 C). An extended tolerance
band can apply at these temperatures.

sd

1,25 x

100

n ... 0,8

cw

10
2

1
sd =

1
0,1

sd =

const

const
0,1 ... 0,4 s

0,02 ... 4 s

0,1
0,01
0,1
0,01
0,1

10
n

SENTRON 3WL circuit breaker with ETU45B and ETU76B solid-state


release, L characteristic curve
NSE0_01524a

Opening time [s]

10000

1000

100

10

i
n ... 0,8

cw

SENTRON 3WL circuit breaker with ETU76B solid-state release,


S characteristic curve

Further characteristic curves are shown in the manual and the


planning and configuring tool SIMARIS deSign, or ask your
Siemens contact person.
Tolerances for the set currents
L: tripping operations between 1.05 and 1.2 IR
S: 0 %, +20 %
I: 0 %, +20 %
G: 0 %, +20 %

cs

0,01
0,1

1
/

Tolerances for the tripping times


L: 20 %, +0 % for I2t characteristic curve
S: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms
I: < 50 ms
G: 0 %, +60 ms or -0 %, 10 % for tripping times greater than 600 ms

1
1,5 x

10
/ n

100
/

0,1

10
/ n

1
/

cs

SENTRON 3WL circuit breaker with ETU45B and ETU76B solid-state


release, I characteristic curve

1) Sizes I and II: 100 ... 1200 A


Size III: 400 ... 1200 A.
2) With single-pole loading in the lowest rated current range, the response
times of the short-circuit release can be extended by approx. 10 % and
the tripping times by approx. 15 % compared to the characteristic curve.

Siemens 2009

35

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids

Dimensional drawings
External current transformers for N conductor without copper
connection pieces

Voltage transformer for SENTRON 3WL


277

Size I, 3WL9 111-0AA21-0AA0


125

6 0
8

8 ,9

2 2

4 0

For mounting on
35 mm standard
mounting rail

1 3 ,1

N S E 0 _ 0 1 3 7 5

99

2 2
8 1
9 6 ,8

R
NSE0_01103a

1 6

External current transformers for N conductor with copper


connection pieces

1 8

3 6

Current transformers for overload protection in the


N conductor

5 1

7 0
8 3

Size II, 3WL9 111-0AA22-0AA0

Size I, 3WL9 111-0AA31-0AA0


2 7

6 5 ,5

N S E 0 _ 0 1 3 7 6

4 1

5 4
1 1 5
1 3 1

1 5

1 3 ,5

1 7 0

9 7

1 6 1
R 1 5

3 1 0

3 1

5 0 ,5

3 0

N S E 0 _ 0 1 3 7 7

4 5

Size II, 3WL9 111-0AA32-0AA0


3 0

Size III, 3WL9 111-0AA23-0AA0

1 0 7
1 2 3

5 5
8 3

5 1

8 8
9 5
1 1 3

N S E 0 _ 0 0 6 0 6 b

9 1

1 3 0
6 8
5 1

2 4

4 4

1 3 ,5

5 1

9 1

Door cut-out for operator panel

1 7 0

1 3 0
6 8
5 1

2 4

4 4

1 6 0
1 8 4

Door cut-out with edge protector


N S E 0 _ 0 0 6 0 7 b

2 9 5

9 0
1 1 3

Inner dimensions with mounted


edge protector

1 3 1

3 0

3 0

3 1 0

3 0

5 2
2 4 0

1 3 ,5

9 1

N S E 0 _ 0 0 1 6 4 c

1 7 0

1 3 0
6 8
5 1

2 4

4 4

3 4 0

Size III, 3WL9 111-0AA33-0AA0

Option with/without door interlocking


3 1 4

1 2 3
1 2 0
5 ,5

4 0
3 )
R 5

R 5
2 )

5 ,5

Dimensions for option with door interlocking

1 8 0

1 4 0

4 0

6 5

1 7 5

3 5 0

1 8 5

N S E 0 _ 0 0 6 1 0 c

3 0 0

1 4 0

1 6 0
1 8 4

N S E 0 _ 0 0 6 0 8 b

Door cut-out for operator panel using the door sealing frame

1 2 0

5 ,5

2) Center SENTRON 3WL operator panel


3) 8 mounting holes for door sealing frame
4) 3 mounting holes for door interlocking

36

Siemens 2009

1 1 ,5

1) Mounting surface
1 )

1 2
2 1

4 )
4 0

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
CubicleBUS module

Breaker Data Adapter (BDA)

3WL9 111-0AT2.-0AA0

3WL9 111-0AT28-0AA0

70

3WL9 111-0AT33-0AA0
81,9
45,5

38
19

16(B

153

16(B

94

47,5

86

30

Siemens 2009

37

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Door cut-out for operator panel using protective cover IP55
400
395
NSE0_01030b

NSE0_01029c

Protective cover, IP55

4 x R5
4 x 5,5
72
340-350

85

70

68

435

72

295-300

Switch mounting level


341
Mounting surface for switch or
guide frame

Safety clearances from grounded parts


Rated operational voltage Above
auxiliary connector
V/AC
mm
751)
751)

Lateral
Rear
(each side)
mm
mm

500
690

50

Size I, withdrawable version,


with arc chute cover
500
690

0
0

0
0

751)
751)
180

0
0

0
0

500
690
1000

100

Size II, withdrawable version,


with arc chute cover
500
690

0
0

02)
02)

0
0

0
0
0

0
0
0

751)
751)
180

501)
501)
100

Size III, withdrawable version,


with arc chute cover
500
690

0
0

0
0
0

0
0
0

45
200
150

20
50

20
125

500
690

150
300

20
50

14
14

500
690

14
14

100
100

14
14

500
690
1000

250
600
430

50
100
100

20
140
125

500
690
1000

250
600
350

50
100
100

14
30
14

50
225

14
14

20
100
100

20
125
125

20
100
100

14
14
14

50
200

14
14

Size II, withdrawable version,


with arc chute cover

02)
2)
0

0
0

0
0
0

0
0
0

500
690

14
14

Size III, fixed-mounted version


500
690
1000

75
500
430

Size III, withdrawable version,


without arc chute cover
0
0
0

0
0
0

500
690
1000

50
500
350

Size III, withdrawable version,


with arc chute cover

02)
2)
0

0
0

0
0
0

0
0
0

DC non-automatic air circuit breakers


300
600
1000

150
300

Size II, withdrawable version,


without arc chute cover

Size III, withdrawable version,


without arc chute cover
500
690
1000

500
690

Size II, fixed-mounted version

Size III, fixed-mounted version


500
690
1000

Lateral
Rear
(each side)
mm
mm

Size I, withdrawable version,


with arc chute cover

Size II, withdrawable version,


without arc chute cover
501)
501)

Rated operational voltage Above


auxiliary connector
V/AC
mm

Size I, withdrawable version,


without arc chute cover

Size II, fixed-mounted version


500
690
1000

148

Size I, fixed-mounted version


0
0

Size I, withdrawable version,


without arc chute cover
501)
1)

Circuit-breaker
mounting level

Safety clearances from live parts

Size I, fixed-mounted version


500
690

17

313

500
690

14
14

1) Value for plate; 0 mm for struts and grids.


2) 40 mm (size II: 70 mm) for plates which cover the lateral openings in the
guide frame.

All safety clearances above the circuit breaker refer to the upper
edge of the auxiliary connector - not to the upper edge of the arc
chute! See dimensional drawings on pages 39 to 47, parts 4)
and 5).

38

Siemens 2009

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 1600 A, fixed-mounted version, 3- and 4-pole

4 7
N S E 0 _ 0 0 6 1 2 c

13,5

55

55

90

55

55

80

40

4 7

90

NSE00616b

421

11)

NSE0_00614e

80

76

5,5
45
150
210
230

106

90

90 60

6)

40
14

150

275

3)

327,5
461,5

N S E 0 _ 0 0 6 1 5 c

33,5

3)

11)

35

8 2

60,5

60 90

26

123,5

9)

8)

541,5
516

55

421

275
440,5

437,5

14)

55

3)

Front connection (double hole)


according to DIN 43673
1) 2)

55

15
10

270
300
390

55

13,5

35

5)

4)

NSE0_00611a

Optional connection variants


Front connection (single)

NSE00613b

Standard version
Horizontal connection

8 2

60 90

90

90

127

Vertical connection
35

90
55

3 5

1 1 )

NSE00619

13,5

6 0

11)

NSE00617a

N S E 0 _ 0 0 6 1 8 c

1 2 7 ,5

M8

3)

3 0

7)

2 6 7 ,5

3)

7)

139
320
410

58

1 3 ,5

1 1 3 ,5
1 2 8 ,5

60

90

90

90

NSE00620

3)

60

90

90

90

4-pole version

9) Key operation.

1) Mounting space for removal of the arc chutes.

11) Terminal face.

2) Arc quenching space.

14) Space for electrical auxiliary circuit connections.

3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the


system.
4) Auxiliary connector with SIGUT screw terminals.

Rated
a
circuit breaker
current

5) Auxiliary connector with spring-loaded connection.

6) Dimension to inside surface of the closed cabinet door.

Up to 1000

7) Fixing points for mounting the circuit breaker in the system.

1250 ... 1600

10

10

10

11

451

34

541

15

15

15

461

39

551

8) "Secure OFF" locking device.

For safety clearances to grounded parts and to live parts see


page 38.
Siemens 2009

39

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Size I, up to 1600 A, 3- and 4-pole, withdrawable version

NSE00622a

62,5

382,5
367,5
327

2)

62,5

8 0

38

60

6 9
8 0

2 8 7
3 )
150
165

9 0

9 0

9 0

4-pole version
2) For guide frame without arc chute cover, arc quenching space facing grounded or
non-conductive surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) SENTRON 3WL in connected position.
8) SENTRON 3WL in test position.
9) SENTRON 3WL in disconnected position.
10) Fixing holes 10 mm.
11) Terminal face.

287
69

90

10)

Rated circuit breaker current


A

Up to 1000
1250 ... 1600

10
15

10
15

10
15

For safety clearances to grounded parts and to live parts see


page 38.
For flange connections see following page.

40

6 9

NSE00628a

NSE0_00630a

90

3 5 0

30
267,5
127,5

NSE00627a

25

3)

15
90

9 0

N S E 0 _ 0 0 6 2 9 a

13,5

9 0

9 0

2 6 0

1 5

55

1 5

11)

350
260

10)

5 5

4 0

169,5

Vertical connection

11)

68

5 5

N S E 0 _ 0 0 6 2 6 b

6)

13,5

139
270
320
410

3 5 0

4 0

45
58
88,5
121,5
140,5

5 5

9 0

3 7 3

34

220

38

55

10)

2 6 0
5 5

9 0

1 1 )

76

a
40

27
42

9 0

493

327,5

a
519
460

275
150
31

14

55

1 5

1 3 ,5
NSE00625a

7) 8)
9)

3)

55

6 9

169,5

Front connection (double hole)


according to DIN 43673

55

1 1 )

1 4

NSE0_00624c

5 5

3 )

2 6

11

5 5

2 8 7

3 7 3
123,5
30
55

3 5 0

3 5

1 3 ,5

403

465,5

13
210
300

10)

2 6 0
5 5

5 5

N S E 0 _ 0 0 6 2 3 b

NSE0_00621a

275
468,5

5)

3 5

320
270
4)

Optional connection variants


Front connection (single)

2 8 7

Standard version
Horizontal connection

Siemens 2009

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size I, up to 1600 A, withdrawable version, 3- and 4-pole

14
M

3 5 0
5 5

5 5

1 2

2 6

2 8 7

5 9

3 3

NSE00631

2 6 0
5 5

5 5

N S E 0 _ 0 0 6 3 2 a

Flange connection

6 9

1 4 2 ,5

121

5 9

2 8 2 ,5

3 )

1 5

9 0

9 0

9 0

3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the


system.

For safety clearances to grounded parts and to live parts see


page 38.
For more connection options see previous page.

Siemens 2009

41

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Optional connection variants
Front connection (single)

275
440,5

90

90

40

40

421

8 2

12)

40

Front connection (double hole)


according to DIN 43673

2)

4 7

90

130

90
40

90

13,5

327,5
461,5

3)

11)

14

275

40

76
45

150
210
230

6)

106
127

80

5,5

150
a

90

40

130

NSE00638c

N S E 0 _ 0 0 6 3 7 d

a
621
541,5
516
451,5

3)

NSE0_00636e

130

80

14)

421

13) 1)

90

26

10

570

85

270
440

11)

35

3)

123,5

437,5

90

35

90

4 7

5)

N S E 0 _ 0 0 6 3 4 d

4)

NSE0_00633a

NSE00635c

Standard version
Horizontal connection

90 130

130

130

13,5

8 2

11)

3)

11)

130

Rated circuit
breaker
current

130

Up to 2000

10

10

10

11

451

34

541

2500

15

15

20

461

39

551

3200/4000

30

30

20

461

39

551

For safety clearances to grounded parts and to live parts see


page 38.
For flange connections see following page.

Siemens 2009

90

130

130

130

4-pole version

42

113,5
128,5

1) Mounting space for removal of the arc chutes.


2) Arc quenching space, "690 V" circuit breaker facing grounded or non-conductive
surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
12) Circuit breaker upper edge, only 1000 V circuit breaker.
13) Arc quenching space, 1000 V circuit breaker facing grounded or non-conductive
surfaces.
14) Space for electrical auxiliary circuit connections.

3)

130

35

NSE00640b

NSE00642

90

30

134,5

NSE0_00639f

128

NSE00641

3)

7)
9

139
460
590

98

13,5

7)

30

30

290

90

35

30

90

130

13,5

Vertical connection, up to 3200 A


130

130

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Vertical connection 4000 A

1)

13,5
NSE0_01868

541,5
461,5
345,5
79,5
100
30

30

2)
85 Nm

4011)
142
162

10
20
200

130

200

1) Mounting space for removal of the arc chutes.


2) Arc quenching space, "690 V" circuit breaker facing grounded or nonconductive surfaces.
11) Terminal face.

For safety clearances to grounded parts and to live parts see


page 38.
For more connection options see previous page.

Siemens 2009

43

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Size II, up to 3200 A, withdrawable version, 3- and 4-pole
Optional connection variants
Front connection (single)
62,5
9 0

4 0

4 0

9 0

9 0

1 3 ,5

1 1 )

55

6 9

2 6

1 3 ,5

13,5

3 7 3

NSE00649a

400
90

6 9
8 0
5 5 4 5

1 3 0

1 3 0

1 3 0

3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.


4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) SENTRON 3WL in connected position.
8) SENTRON 3WL in test position.
9) SENTRON 3WL in disconnected position.
10) Fixing holes, diameter 10 mm.
11) Terminal face.
12) Guide frame upper edge only 1000 V AC version.
13) Arc quenching space, 1000 V circuit breaker facing grounded or non-conductive
surfaces.

11)

138
95

530
90

90

NSE0_00652b

90

1 1 )

4-pole version
2) For guide frame 690 V, without arc chute cover, arc quenching space facing grounded or non-conductive surfaces.

30

139
270
460
590

9 0

4 0

6)

38

30

45
58
88,5
121,5
140,5

220

9 0

5 3 0

3 )

4 0
40
31

27
42

9 0

1 3 0

8 0

4 0

NSE00647b

493

c
169,5

76

10)

4 0

4 0 0
9 0

1 3 0

1 4

3)

275
150

8)
9)

327,5

9
620
520
460

62,5

13)
2)
12)
7)

14

4 5 ,1
1 3 0

5 5

Front connection (double hole)


according to DIN 43673

382,5
367,5
327

NSE0_00646f

10)

3 5

270
350

34

480

518,5

10)

c
169,5

N S E 0 _ 0 0 6 4 8 c

11

123,5

40

2 8 7

3 )
3 7 3

403

465,5

275
468,5

NSE00644b

NSE0_00643b

5 3 0

4 0 0
9 0

N S E 0 _ 0 0 6 4 5 c

5)

3 5

4)

2 8 7

Standard version
Horizontal connection

69

287

3)

10)

55 45

130

130

10)

130

For safety clearances to grounded parts and to live parts see


page 38.

Up to 2000

10

10

10

2500

15

15

20

For vertical connection and flange connection see following


page.

3200/4000

30

30

20

Rated circuit breaker current


A

44

Siemens 2009

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole
Vertical connection,
up to 3200 A

5 3 0

4 0 0
b

NSE00650a

30
30

11)
38

N S E 0 _ 0 0 6 5 1 a

100

6 9

135

290

2 8 7

3 )

5 5 4 5

157
172

1 3 0

1 3 0

1 3 0

NSE0_01869

30
109,5

315,5

100

30

Vertical connection 4000 A

4,6

4011)
177
197

55

45
200

10
20
200

130

1 2

9 0

5 3 0
N S E 0 _ 0 0 6 5 4 a

4 0 0

4 0

5 9

2 6

3 3

NSE00653

Flange connection

6 9

1 4 2 ,5

5 9

2 8 2 ,5

2 8 7

3 )

121
4 5

1 3 0

1 3 0

1 3 0

4-pole version
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
11) Terminal face.

For safety clearances to grounded parts and to live parts see


page 38.
For more connection options see previous page.

Siemens 2009

45

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Size III, up to 6300 A, fixed-mounted version, 3- and 4-pole

160

47

5)

12

205

NSE00656c

160

160

50

3)

421

130

20
82

11

270
680

890

160

50

11)

26

451

123,5

437,5

275
440,5

13,5

210

210

210

35

4)
NSE0_00655a

35

Optional connection variants


Front connection (single)

NSE00657c

Standard version
Horizontal connection

Front connection (double hole)


according to DIN 43673
1)

1 3 ,5

4 7

1 6 0

1 6 0

N S E 0 _ 0 0 6 6 0 c

5 4 1

3 )

8 0
76

45

150
210
230

1 1 )

1 4

327,5
461,5

3 4

275

35

1 6 0
5 0 5 0

5,5

2 0

2 1 0

2 1 0

8 2

6)

106
127

2 1 0

1 3 0

4 0

150
30
NSE0_00658e

N S E 0 _ 0 0 6 5 9 d

30
621
541,5
516
451,5

3)

1 6 0
5 0 5 0

8 0

4 0

2)
12)
14)

4 2 1

13)

Vertical connection
210
15

130

107

15
30

160

210

35

30

210

20
10

NSE00663

11)

914

139
704

248

NSE0_00661e

M10

13,5

40

142
162

NSE00662a

3)

3)
40

94,5
120

7)

330,5

11)

13,5

7)

85

210

210

210

NSE00664a

3)

130

210

210

210

130

4-pole version
1) Mounting space for removal of the arc chutes.
2) Arc quenching space, "690 V" circuit breaker facing grounded or
non-conductive surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
12) Circuit breaker upper edge, only 1000 V circuit breaker.

46

Siemens 2009

13) Arc quenching space, 1000 V circuit breaker facing grounded or


non-conductive surfaces.
14) Space for electrical auxiliary circuit connections.

For safety clearances to grounded parts and to live parts see


page 38.

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids

27
42

45
58
88,5
121,5
140,5

220

20
169,5

2 1 0

8 5

4 0

34

76

10)

5 9 0

5 7

6)

38
630
160

260
217

13,5

840
160

160

69

287

NSE0_00674a

160

210

210

Rated circuit breaker current

210

40
40
5

210
210
245

6 9

N S E 0 _ 0 0 6 7 3 b

2 8 7
24
177
197

6 9

NSE00671a

914

2 1 0

8 0 0

8 4 0

6 3 0
7 0 4

2 0
1 0

2 1 0

330,5
94,5
124,5

11)

139
270
704

NSE00672a

38
11)

13,5

30

30

30

2 8 7
6 9

1 6 0

1 1 )

Vertical connection, up to 6300 A

4000
5000
6300

1 6 0

8 0

40
31

14

30

57 85

5 0

1 4

30

275
150

493
327,5

30
620
520
460

3)

8 4 0

8 0

8)
9)

7)
9

8 0 0

6 3 0
1 6 0

1 6 0

5 0

4 0

62,5

2 1 0

2 1 0

5 9 0

2 8 7

13)
2)
12)

2 1 0

8 5
5 7

3 7 3

NSE0_00668d

20
169,5

Front connection (double hole)


according to DIN 43673 up to
4000 A

382,5
367,5
327

N S E 0 _ 0 0 6 6 7 c

1 3 ,5
3 7 3

403

10)
57

1 1 )

3 5

160

1 6 0

5 0

2 6

270
590

NSE00669b

800

11

10)

1 6 0

5 0

518,5

10)

8 4 0

6 3 0
1 6 0

1 6 0

123,5

465,5

275
468,5

NSE00666b

NSE0_00665b

62,5

5)

1 3 ,5

4)

Optional connection variants


Front connection (single hole),
up to 4000 A

N S E 0 _ 0 0 6 7 0 c

Standard version
Horizontal connection up to 5000 A

3 5

Size III, up to 6300 A, withdrawable version, 3- and 4-pole

5 7

a
b

5 9 0

2 1 0
8 0 0

9 1 4

4-pole version
2) For guide frame 690 V, without arc chute cover, arc quenching space facing grounded
or non-conductive surfaces.
3) Grooves (4 mm wide, 5 mm deep) for
supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) SENTRON 3WL in connected position.
8) SENTRON 3WL in test position.
9) SENTRON 3WL in disconnected position.
10) Fixing holes, diameter 10 mm.
11) Terminal face.
12) Guide frame upper edge only 1000 V guide frame.
13) Arc quenching space, 1000 V circuit breaker facing grounded or non-conductive
surfaces.

For safety clearances to grounded parts and to live parts see


page 38.
For flange connections see following page.

Siemens 2009

47

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Size III, up to 6300 A, withdrawable version, 3- and 4-pole

6 3 0
7 0 4
1 6 0

1 6 0

1 6 0

5 7 8 5

121

5 9
5

6 9

2 8 2 ,5
1 4 2 ,5
2 6

2 8 7

5 9

M
3 3

1 2

1 6 0

8 4 0
N S E 0 _ 0 0 6 7 6 a

NSE00675

Flange connection, up to 4000 A

3 0
2 1 0

5 9 0

2 1 0

2 1 0

8 0 0
9 1 4

For safety clearances to grounded parts and to live parts see


page 38.
For more connection options see previous page.

48

Siemens 2009

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids

Schematics
Terminal assignment diagram
Internal wiring

optional
Accessories
(Auxiliary switch S1, S2 = Standard)

Terminals

External wiring
L+
L

e.g. current transformer in the


star point of power transformer
or a summation current
transformer 1200 A /1A

Remote reset bell alarm & tripped indicator F7

13

G transformer S2

12

G transformer S1

11

N sensor S2

10

N sensor S1

ext. voltage transformer Com

L1

ext. voltage transformer L3

L2

ext. voltage transformer L2

L3

ext. voltage transformer L1

0 V DC

24 V DC

BUS +

BUS

7
6
5

Signaling contact at the 1 st auxiliary release

4
3

S23
Signaling contact at the 2nd auxiliary release

Open
+ OUT
F1, 2

1 2 3 4 5 6 7 8 9

/COM16
(Option F02/F12)

L+

Internal

External

10

Local electric close S10

Y1

11
"Spring charged" signal S21

Close
+

12

Termination resistor,
if not external CB-module!

Free
+

13

24 V DC input

DPWrite Free
Enable

14

Short terminals if no N-sensor

IN

Not available with communication connection "F02" or F12.


COM15/COM16 module is at position "-X7".

14

Trip signalling switch S24


(position after tripping)

1st auxiliary release F1 "ST"

14

L+

13

12

S1 "NO"

11
10

S1 "NC"

Closing solenoid

L+

6
5

"Ready to close" signal S20

S2 "NO"

3
2

S2 "NC"

F4 only "quick OFF"

14

F4 only "quick OFF"

13
12

2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td"

11
10

S3 "NO" or S7 "NO"

9
8

S3 "NC" or S7 "NO"

7
6

S4 "NO" or S8 "NO"

Charging motor
opt. motor main switch S12

5
4
NSE0_00605 o

S4 "NC" or S8 "NO"

EMERGENCY STOP
or short terminals
L+
c
L

(sw)

(br)

3
2
1

L+
L

Siemens 2009

49

3WL Air Circuit Breakers

3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)


Project planning aids
Example of an overall circuit diagram for SENTRON 3WL
(3WL1. .......4GN4Z C11+ C22 + K07)
Manual/motorized operating mechanism with stored-energy feature with electrical ON button (option C11), with ready-to-close
signaling switch (optionl C22), with LSING solid-state release,
L1
(L+)

release
contact

with "UVR" undervoltage release (F3), with "ST" shunt release


(F1), with tripped signal switch (option K07), with auxiliary switch
4 NO + 4 NC.

L1
(L+)

OFF

version

electr.
ON

-X5.6
-X5.4

-X5.10
-X5.8

-X6.4
-X6.2

-X6.12
-X6.10

ETU

-S10

-A1

1
3

-X6.6

-X7.12
-X7.14

-X5.12

-X6.14

-X6.7

-X7.9

-X5.2

ON

S
I
N N
G

-S11
-S24

-S20

-F5

-F3

-A1
-S1/-S2
-S3/-S4
-S7 (optional)

F1

-S8 (optional)

F2
F3

M1
Q1

S1 & S2
S3 & S4

1
S24

F5

Y1
A1

T1
T2
T3
T4

NSE0_01559c

50

Siemens 2009

-X5.5
-X5.3

-X5.9

Solid-state release ETU


1st auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block, S7 (2 NO) can be used
if there is no S3 - S3 and S7 have
the same terminal assignment/mounting space
2nd auxiliary switch block, S8 (2 NO) can be used
if there is no S4 - S4 and S8 have
the same terminal assignment/mounting space
3WL1. ..-.....-...2
3WL1. ..-.....-...4
3WL1. ..-.....-...7
3WL1. ..-.....-...8

F4

-X5.7

* Short terminals, if no N sensor

Function diagram of
SENTRON 3WL circuit breaker

S20

-X6.3
-X6.1

2
4

-X8.9

N
(L-)

-X8.10

-X6.5

-X7.13

-X5.11

-X6.13

-X6.8

NSE0_01558b

-T3

-F1

-X5.1

N
(L-)

-T2

-X6.9

-S12

U<

-X6.11

-Y1

mech.
OFF

-S4

-S3

-T1

M
mech.
ON

-S2

-S1

-Q1

QS

L
S
I
N N
G

-S10
-S11
-S12

(2 NO + 2 NC) S1+S2
(4 NO + 4 NC) S1+S2+S3+S4
(6 NO+ 2 NC) S1+S2+S7+S8
(5 NO + 3 NC) S1+S2+S3+S8

-S20
-S24

Electrical ON button
Internal motor shutdown switch (if spring is tensioned)
Motor shutdown switch
(no automatic tensioning of spring)
Ready-to-close signaling switch
Tripped signal switch

-F1
-F3
-F5

1st auxiliary release, shunt release


2nd auxiliary release, undervoltage release
Tripping solenoid

-M
-P
-QS
-Q1
-T1/-T2/-T3
-X5/-X6/-X7/-X8
-Y1
-R

Motor for "charging energy store"


Stored-energy mechanism
Actuator lever for "stored-energy mechanism"
Main contacts
Current transformers
Terminals
Closing solenoid
Indicator and reset button for solid-state release

-X8.9/-X8.10

Connection option: external neutral conductor


transformer

3WL Air Circuit Breakers


3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
Project planning aids
Example of the mode of operation of Zone Selective
Interlocking functionality in power distribution

SENTRON 3WL
3
4
5
6

5
6
1
2
3
4
ZSI module

SENTRON 3WL
3
4
5
6
ZSI
module

SENTRON 3WL
3
4
5
6
ZSI
module

ZSI
module

SENTRON 3WL
3
4
5
6

ZSI
module

SENTRON 3WL

SENTRON 3WL
ZSI
module

SENTRON 3VL

NSE0_01898

3
4
5
6

NSE0_01897

ZSI
module

SENTRON 3WL
3
4
5
6

SENTRON 3WL
3
4
5
6
ZSI
module

ZSI
module

SENTRON 3WL
3
4
5
6

Connection diagram for a Zone Selective Interlocking functionality with


multiple infeed and several outgoing units with SENTRON 3WL circuit
breakers

SENTRON 3VL and SENTRON 3WL circuit breakers used in various


staggered levels

ZSI module

SENTRON 3WL
3
4
5
6
ZSI
module

5
6
1
2
3
4

ZSI
module

SENTRON 3WL
3
4
5
6

NSE0_01899

SENTRON 3WL

SENTRON 3WL
3
4
5
6
ZSI
module

ZSI
module

SENTRON 3WL
3
4
5
6

Zone Selective Interlocking functionality: Connection using a coupling


switch, use of SENTRON 3WL circuit breakers

More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron

Siemens 2009

51

3WL Air Circuit Breakers

3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)


General data

Technical specifications
Size

II

Type

3WL12 10

Rated current In at 40 C
Main conductor

A ... 1000

3WL12 20

3WL12 40

2000

4000

Rated operational voltage Ue


(1000 V version, see Catalog LV 1, order code "A05")

V DC ... 600/1000

... 600/1000

... 600/1000

Rated insulation voltage Ui

V DC 1000

1000

1000

kV 12
kV 4
kV 2.5

12
4
2.5

12
4
2.5

Yes

Yes

25/+75
40/+70

25/+75
40/+70

2000
2000
2000
1950

4000
3640
3500
3250

W 280

770

1640

Rated impulse withstand voltage Uimp


Main current paths
Auxiliary circuits
Control circuits
Isolating function acc. to EN 60947-2

Yes

Permissible ambient temperature


Operation
Storage
Permissible load
At rear horizontal main circuit
connections
(Cu painted black)

C 25/+75
C 40/+70

Up to 40 C
Up to 55 C
Up to 60 C
Up to 70 C

A
A
A
A

Power loss at In for symmetrical loads


Withdrawable circuit breakers

1000
1000
1000
1000

Operating times
Make-time
Opening time

ms
ms

35
34

35
34

35
34

Electrical make-time (through activation solenoid)1)


Electrical opening time (through shunt release)

ms 100
ms 73

100
73

100
73

Electrical opening time (instantaneous undervoltage release)

ms

73

73

73

Oper. cycles 10 000


Oper. cycles 15 000
Oper. cycles
6000
Oper. cycles
1000
Oper. cycles 15 000

Switching frequency
600 V version
1000 V version

1/h 60
1/h 20

10 000
15 000
4000
1000
15 000

60
20

60
20
3 0

3 0

3 0

Mounting position

10 000
15 000
6000
1000
15 000

h m a x .
= 1 m m

Endurance3)
Mechanical (without maintenance)
Mechanical (with maintenance)2)
Electrical (without maintenance)
1000 V version
Electrical (with maintenance)2)

3 0

and/
or

Auxiliary conductors (Cu)


Max. number of
auxiliary conductors
cross-section
(solid/stranded)

N S E 0 _ 0 0 9 2 7 a

N S E 0 _ 0 0 0 6 2 a

N S E 0 _ 0 0 0 6 1 a

IP20 without cabinet door, IP41 with door sealing


frame, IP55 with cover

Degree of protection

Standard connection = strain-relief clamp


2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14)
Without end sleeve
With end sleeve acc. to DIN 46228 Part 2 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16)
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
With twin end sleeve
Optional connection = tension spring
2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14)
Without end sleeve
With end sleeve acc. to DIN 46228 Part 2 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)

Weights 3-pole

Fixed-mounted circuit breakers


Withdrawable circuit breakers
Guide frames

kg 56
kg 60
kg 31

56
60
31

64
68
45

4-pole

Fixed-mounted circuit breakers


Withdrawable circuit breakers
Guide frames

kg 67
kg 72
kg 37

67
72
37

77
82
54

1) Make-time through activation solenoid for synchronization purposes


(short-time excited) 50 ms.

2) Maintenance means: replace main contact elements and arc chutes (see
Operating Manual).
3) Further technical specifications on request.

Size

II

Type

3WL12

Switching capacity class

DC

Short-circuit breaking capacity


Up to 220 V DC
Up to 300 V DC
Up to 600 V DC
Up to 1000 V DC

Icc
Icc
Icc
Icc

kA
kA
kA
kA

35
30
25
20

kA
kA
kA
kA

-351)/302)/253)/204)
---

Rated short-time withstand current Icw


0.5 s
1s
2s
3s
1) At Ue = 220 V DC.

3) At Ue = 600 V DC.

2) At Ue = 300 V DC.

4) At Ue = 1000 V DC.

52

Siemens 2009

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids

Characteristic curves
R=

1000

= 0.4

= 1.0

0.4 ... 1.0 n


2 ... 10 s at 6
= 1.25 R ... 4

R=

R=

100

MIN
1.25

I=

0,1

I=

0,01
0,1

10 s [B]
2 s [A]

10
1

R
n

1.5

MAX
4 n

I=

NSE0_01578

[s]

10000

10
n

DIGmat S100 characteristic curve

Dimensional drawings
DIGmat S100
257
250

DIG S100

3,5

R1

AUTO
MAN

PEAK

DIAG

MAIN

MENUE

271

DIGmat S100

NSE0_01575

R2

122
115

ON

NSE0_01576

136

AUTO

DIGmat S100 drilling pattern

Siemens 2009

53

3WL Air Circuit Breakers

3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)


Project planning aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Optional connection variants
Front connection (single)

275
440,5

90

90

35

90
40

40

421

26
40

Front connection (double hole)


according to DIN 43673

2)
12)
15)
14)

90

130

90
40

90

13,5

NSE00638c

421

327,5
461,5

3)

11)

14

275

106
127

40

76

45

150
210
230

80

5,5

150
a

90

40

130

602
541,5
516
451,5
447

130

80

4 7

3)

NSE0_02003

90

8 2

1)

N S E 0 _ 0 0 6 3 7 d

16) 17)

10

570

85

270
440

11)

35

3)

123,5

437,5

90

4 7

5)

N S E 0 _ 0 0 6 3 4 d

4)

NSE0_00633a

NSE00635c

Standard version
Horizontal connection

6)

90 130

130

130

13,5

8 2

11)

3)

11)

130

Rated circuit
breaker
current

130

Up to 2000

10

10

10

11

451

34

541

4000

30

30

20

461

39

551

Siemens 2009

90

130

130

130

4-pole version

54

113,5
128,5

1) Mounting space for removal of the arc chutes.


2) Arc quenching space, "690 V" circuit breaker facing grounded or non-conductive
surfaces.
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit breaker in the system.
11) Terminal face.
12) Circuit breaker upper edge, only 1000 V circuit breaker.
14) Space for electrical auxiliary circuit connections.
15) Arc quenching space, 300 V circuit breaker facing grounded or non-conductive
surfaces.
16) Arc quenching space, 600 V circuit breaker facing grounded or non-conductive
surfaces.
17) Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.

3)

130

35

NSE00640b

NSE00642

90

30

134,5

NSE0_00639f

128

NSE00641

3)

7)
9

139
460
590

98

13,5

7)

30

30

290

90

35

30

90

130

13,5

Vertical connection
130

130

For safety clearances to grounded parts and to live parts see


page 38.

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole
Optional connection variants
Front connection (single)
62,5
9 0

4 0

4 0

9 0

9 0

1 3 ,5

3 )

55

7)

6 9

1 3 ,5

9 0

9 0

5 3 0
4 0

8 0

9 0

1 3 0

3 )

27
42

1 1 )

45
58
88,5
121,5
140,5

220

1 4

6 9
8 0
4 0

76

10)

5 5 4 5

1 3 0

1 3 0

1 3 0

6)

4-pole version
2) For guide frame 690 V, without arc chute cover, arc quenching space facing grounded or non-conductive surfaces.

30

3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.


4) Auxiliary connector with SIGUT screw terminals.
5) Auxiliary connector with spring-loaded connection.

38

13,5

11)
NSE00649a

6) Dimension to inside surface of the closed cabinet door.


7) SENTRON 3WL in connected position.
8) SENTRON 3WL in test position
9) SENTRON 3WL in disconnected position.

138
95

10) Fixing holes, diameter 10 mm.


11) Terminal face.
12) Guide frame upper edge only 1000 V AC version.
15) Arc quenching space, 300 V circuit breaker facing grounded or non-conductive
surfaces.

530
90

90

16) Arc quenching space, 600 V circuit breaker facing grounded or non-conductive
surfaces.

NSE0_00652b

90

4 0

NSE00647b

327,5
518,5

14

400
90

c
169,5

3)

40
31

275
150

8)
9)

4 0

4 0 0
9 0

1 3 0

3 7 3

651
520
496
460

62,5

16) 17)
2)
15)
12)

NSE0_02084

139
270
460
590

4 5 ,1
1 3 0

5 5

Front connection (double hole)


according to DIN 43673

382,5
367,5
327

30

2 6

10)

3 5

270
350

493

480

34

10)

c
169,5

N S E 0 _ 0 0 6 4 8 c

11

123,5

40

2 8 7

1 1 )

3 7 3

403

465,5

275
468,5

NSE00644b

NSE0_00643b

5 3 0

4 0 0
9 0

N S E 0 _ 0 0 6 4 5 c

5)

3 5

4)

2 8 7

Standard version
Horizontal connection

17) Arc quenching space, 1000 V circuit breaker (with high arc chute) facing grounded or
non-conductive surfaces.

69

287

3)

10)

55 45

130

130

10)

130

For safety clearances to grounded parts and to live parts see


page 38.

Up to 2000

10

10

10

4000

30

30

20

For vertical connection and flange connection see following


page.

Rated circuit breaker current


A

Siemens 2009

55

3WL Air Circuit Breakers

3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)


Project planning aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole

30
30

11)
38

NSE00650a

Vertical connection
4 0 0
b

5 3 0
N S E 0 _ 0 0 6 5 1 a

2 8 7

100

6 9

135

290

3 )

157
172

5 5 4 5

1 3 0

1 3 0

1 3 0

1 2

9 0

5 3 0
4 0

5 9

2 6

3 3

4 0 0

N S E 0 _ 0 0 6 5 4 a

NSE00653

Flange connection

6 9

1 4 2 ,5

5 9

2 8 2 ,5

2 8 7

3 )

121
4 5

1 3 0

1 3 0

1 3 0

4-pole version
3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the
system.
11) Terminal face.

For safety clearances to grounded parts and to live parts see


page 38.
For more connection options see previous page.

56

Siemens 2009

3WL Air Circuit Breakers


3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Project planning aids

Schematics
L1

AC230

N
PE

DC24

AC230

X1.2 X1.1

X5.2 X5.1

DIGmat S100
Auxiliary power
Emergency STOP
+

X4.i1+

DC24

X4.i1-

X2.1 +
Digital input

X4.i2+

Shunt
(60mV)

X2.3 -

X4.i2Automatic RESET
Digital output
X4.01 X4.01 X4.02 X4.02 X4.03 X4.03 X4.04 X4.04
+

-K1

Automatic / Reset

NSE0_01577a

Excitation / Alarm

12
11
12
11

-K2

14

14
-Q01

-X6.14 -X5.12
SENTRON
3WL
-F1
-F3
-X6.13 -X5.11
-Q01 2

Schematics of the DIGmat S100 and the SENTRON 3WL non-automatic


air circuit breaker

Application examples
Rated operational
voltage

Required series
breaks at rated voltage

For 3-pole non-automatic air circuit brea- For 4-pole non-automatic air circuit breakers
kers
(operational currents up to 4000 A/conducting path)
(operational currents up to 4000 A/
conducting path)

Up to 300 V + 10 %

1-pole,
2 parallel conducting
paths,
only with groundedneutral system

2-pole

1-pole,
3 parallel conducting paths,
only with grounded-neutral
system

2-pole
2 parallel conducting
paths

2-pole,
only with groundedneutral system

1-pole,
2 parallel conducting paths,
only with grounded-neutral
system

2-pole

1-pole,
only with groundedneutral system

2-pole,
only with grounded-neutral
system

1-pole,
only with groundedneutral system

Over 300 V + 10 %
Up to 600 V + 10 %

Over 600 V + 10 %
Up to 1000 V + 10 %
(version for 1000 V
required, order with "-Z"
and order code A05)

The connection to the circuit breakers is not dependent on direction and polarity; the circuit diagrams can be adapted
accordingly.
If the parallel or series connections are made directly to the
connecting bars, for thermal reasons the continuous load on the
circuit breakers must only be 80 % of the permissible operational

current. If the parallel or series connection is made at a distance


of 1 m from the connecting bars, the circuit breaker can be used
at full operational current load.

Grounded-neutral system

Load
Siemens 2009

57

3WL Air Circuit Breakers

3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC)


Project planning aids

More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron

58

Siemens 2009

Get more information


Low-Voltage Controls and Distribution
www.siemens.com/lowvoltage

Siemens AG
Subject to change without prior notice
Industry Sector
Low Voltage Controls and Distribution
Postfach 4848
90026 NRNBERG
Siemens AG 2009
GERMANY

www.siemens.com/automation

You might also like