Professional Documents
Culture Documents
341105269.doc
S
GeneralSpecificationforFixedCapacitor
BankforElectricalNetworkupto
12KV
GeneralpresentationofCP214capacitorbank
Standards
Technicalcharacteristics
Electricalcharacteristics
Operatingconditions
Factorytests
Documentssuppliedincaseofanorder
Lastupdate:20081201
SpecificationforTender
341105269.doc
Tableofcontents:
1.Generalpresentation...................................
p.3
2.Standards...
p.3
3.Technicalcharacteristics........
p.3
4.Electricalcharacteristics........
p.3
4.1Acceptableovercurrentandovervoltage.........
p.4
4.2Designvoltage,designpowerandmarking.................................
p.4
4.3Composition......................................
p.4
4.4Generallayoutandsinglelinediagram....
p.5
4.5Enclosures......................
p.5
4.6Capacitorunits.................................................
p.5
4.7Reactors.....................
p.5
4.8Connections..........
p.5
4.9Quickdischargecoils(optional).......
p.6
5.Operatingconditions.......
p.6
5.1Internalfaultprotection....
p.6
5.2Additionalprotections.....................................
p.6
6.Factorytests.........
p.6
6.1ForPROPIVARcapacitorunits........................
p.6
6.2ForCP214capacitorbanks.....................
p.7
7.Documents....................................................
p.7
8.ForCP227....................................................................................................................................p.7
9.ForCP254....................................................................................................................................p.7
Lastupdate:20081201
SpecificationforTender
341105269.doc
1.Generalpresentation
CP214isarangeofMVcapacitorbanksdesignedtobeusedinelectricalnetworksupto12kV.The
capacitorbankismadeofunpaintedaluminiumframeandpaintedsteelpanels,whichisequippedwith
PROPIVARcapacitors,HRCfusesandinrushcurrentlimitingreactors.
ThebankisarrangedindeltaconnectionandtheHRCfusesinsuretheprotectionagainstcapacitorinternal
fault.
2.Standards
TheCP214equipmentisdesigned,manufactured,andtestedaccordingtotherelevantIEC
recommendations.
Highvoltagecapacitors
IEC608711&2,BS1650,VDE0560,C222N190M1985,
Reactors
IEC289
HRCFuses
IEC282.1,IEC787
3.Technicalcharacteristics
CP214capacitorbankismadeofunpaintedaluminiumframesandpaintedsteelpanels(RAL9002).
Itisdesignedforthefollowinginstallationconditions:
indoorinstallation,
altitudelessthan1000m,
averagedailyambienttemperatureofbetween25Cand+35C,andamaximumof40C.
TheprotectiondegreeoftheenclosureisIP23.
Availableoptionsfortheenclosure:
Doorwithlockforindoortypeenclosure,
Outdoortypeenclosure(unpaintedaluminiumpanels),
Doorwithlockforoutdoortypeenclosure,(tobeusedwithoutdoortypecubicleoption).
Lastupdate:20081201
SpecificationforTender
341105269.doc
4.Electricalcharacteristics
CP214capacitorbankrangesareavailableforvoltageupto12kV,for50Hzor60Hznetwork.
Theinsulationlevelofequipmentisasfollows:
Ratedvoltage(Vdim)
(V)
Insulationlevel
(kV)
4160
6600
12000
7,2
7,2
12
Powerfreq.
voltagewithstand
(kVrms)
20
20
28
Impulsevoltage
withstand(kV
peak)
60
60
75
Thetoleranceontheratedpowerofthecapacitorbankis:0/+10%,
Capacitancevariationaccordingtotemperatureis:3,5.10-4/C
4.1Acceptableovercurrentandovervoltage
CP214capacitorbanksaredesignedfor:
1,10xUnovervoltage12hoursperday,
1,15xUnpowerfrequencyovervoltage30minutesperday,
Permanentovercurrent:1,3xIn.
4.2Designvoltage,designpowerandmarking
AccordingtoIEC60871recommendations,capacitorunitsorcapacitorbanksnameplatesshallindicatethe
maximumpowerandvoltageforwhichitisdesigned(Qdim&Vdim).
Ourcapacitorunitsandcapacitorbankshavenameplatesshowingthesedesignpoweranddesignvoltage
(QdimandVdim).Operatingvaluescanbeequalorlowerthanthesevalues(QnandVn).
Thedocumentssuppliedwithourmediumvoltageproducts(pricelists,orderforms,catalogues,)provide
reactivepowervaluesforthemostcommonnetworkvoltages.Iftherequiredvoltagedoesnotappearinthe
tables,itispossibletomakeacalculationusingtheformulae:
Lastupdate:20081201
SpecificationforTender
341105269.doc
Qn=(Vn/Vdim)xQdim
4.3Composition
EachstageofCP214capacitorbankincludesthefollowingcomponents:
4.3.1Basiccomponents:
Paintedsteelcubicle(RAL9002),IP23,forindoorinstallation,
PROPIVARcapacitorunits,(1or2units,dependingontheratedpowerofthebank)
Threesinglephaseinrushcurrentlimitingreactors,
ThreeHRCfuses.
4.3.2Thefollowingitemsareavailableasoptions:
Setoftwoquickdischargecoils
4.4Generallayoutandsinglelinediagram
4.5Enclosures
Thecapacitorbanksenclosureismadeofunpaintedaluminiumframesandpaintedsteelpanels.Thebanks
aredesignedtoincludeupto2capacitorunitsindeltaconnection.
4.6Capacitorunits
ThePROPIVARcapacitorunitsusedinCP214bankshavethefollowingcharacteristics:
Allfilmtechnology,
Lastupdate:20081201
SpecificationforTender
341105269.doc
Filledwithbiodegradabledielectricfluid,
Threephase,deltaconnected,
Fittedwiththreeepoxyresinbushings,
Fittedwithinternaldischargeresistors(75V/10min).
AccordingtoIEC60871standardrequirements,capacitorunitsincludeinternaldischargeresistorssothat
theresidualvoltageislessthan75Vwithin10minutesafterdisconnection.
4.7Reactors
Thereactorsusedaresinglephase,drytype,withaircoreandnaturalaircooling.Theratedcurrentisequal
orhigherthan1,43timesthecapacitorbanknominalcurrent.Theinductancevalueiscalculatedsothatthe
peakinrushcurrentvalueislowerthan100timesthenominalcurrentofthecapacitorbank,asperIEC
recommendation.
4.8Connections
Theconnectionsupportsaremadeofporcelainorepoxyresin.Connectionsareofbarecopperbars.
4.9Quickdischargecoils(optional)
Quickdischargecoilsallowaveryfastdischargetime(lessthan10s).
Caution:Inanycase(withoutorwithquickdischargecoils),atimedelayrelaymustbeusedtoavoid
connectionofthecapacitorbankwithinlessthan5minutesafteritsdisconnection,eitherduetoautomatic
control,protectiontripping,voltageoutage,
5.Operatingconditions
5.1Internalfaultprotection
PROPIVARcapacitorshavetobeprotectedaccordingtoRectiphaseinstructions.
OnlyHRCfusestypesandratingsrecommendedbyRectiphasecanbeusedforcapacitorprotection.
5.2Additionalprotections
Toprovideasuitableprotectionlevelfortheequipment,thecapacitorbankfeedermustincludethe
followingadditionalprotectiondevices:
Shortcircuitprotection:recommendedsettingvalues:3xIn/0,1s,
Overloadprotection:recommendedsettingvalues:1,4xIn/10s.
Importantnote:Thecircuitbreakerusedtoprotectthecapacitorbankshallhavethesuitableratingandmust
havebeenspecificallydesignedforcapacitorcurrentswitching.
Lastupdate:20081201
SpecificationforTender
341105269.doc
6.Factorytests
Thereferencevoltageusedfortestingisthedesignvoltage(Vdim).Testreportswillalsomentionthisvalue
whichisallwayshigherorequaltoservicevoltage.
EachCP214capacitorbankmanufacturedbyRectiphasepassroutinetestingbeforedelivery.Thefactory
routinetestsareperformedaccordingtoIECrelevantrecommendationsandincludethefollowing:
6.1ForPROPIVARcapacitorunits
capacitancemeasurement,
lossanglemeasurement(tg),
sealingtest,
internaldischargeresistorvaluechecking,
voltagetestbetweenterminals,
voltagetestbetweenterminalsandcontainer.
Lastupdate:20081201
SpecificationforTender
341105269.doc
6.2ForCP214capacitorbanks
phasetophasecapacitancemeasurement,
insulationmeasurement,
conformitychecking.
7.Documents
ThefollowingdocumentsarepartofRectiphasesupply:
threesetsofroutinetestcertificates(french/english),
threesetsofdrawingsanddiagrams(french/englishorfrench/spanish),
oneinstructionmanual(french/english/spanish).
8ForCP227capacitorbanks
phasetophasecapacitancemeasurement,
insulationmeasurement,
conformitychecking.
9ForCP254capacitorbanks
9.1Generalpresentation
CP254isarangeofMVcapacitorbanksdesignedtobeusedinelectricalnetworksupto36kV.The
capacitorbankismadeofunpaintedaluminiumorgalvanisedsteelframeandpanels,whichisequippedwith
PROPIVARcapacitors,SF6contactor,HRCfusesanddetuningreactors.
The bank is arranged in delta connection and the HRC fuses insure the protection against capacitor internal
fault.
Several capacitor stages are controlled by a power factor relay to make an automatic power factor correction
system.
9.2Standards
TheCP254equipmentisdesigned,manufactured,andtestedaccordingtotherelevantIEC
recommendations:
Highvoltagecapacitors
IEC608711&2,BS1650,VDE0560,C222N190M1985,
Highvoltagecontactors
IEC420,IEC470
Reactors
IEC289
HRCFuses IEC282.1,IEC787
Relays
IEC255
Lastupdate:20081201
SpecificationforTender
341105269.doc
9.3.Technicalcharacteristics
CP254capacitorbankismadeofunpaintedaluminiumorgalvanisedsteelframesandpanels.
Itisdesignedforthefollowinginstallationconditions:
indoorinstallation,
altitudelessthan1000m,
averagedailyambienttemperatureofbetween25Cand+35C,andamaximumof40C,
TheprotectiondegreeoftheenclosureisIP23.
Availableoptionsfortheenclosure:
Outdoortypeenclosure,
9.4.Electricalcharacteristics
CP254capacitorbankrangesareavailableforvoltageupto36kV,for50Hzor60Hznetwork.
Accordingtonetworkratedvoltage,theinsulationlevelofequipmentisasfollows:
Ratedvoltage(Vdim)
(V)
Insulationlevel
(kV)
15000
22000
33000
17,5
24
36
Powerfreq.
voltagewithstand
(kVrms)
38
50
70
Impulsevoltage
withstand(kV
peak)
95
125
170
Thetoleranceontheratedpowerofthecapacitorbankis:0/+10%,
Capacitancevariationaccordingtotemperatureis:3,5.10-4/C.
Lastupdate:20081201
SpecificationforTender
341105269.doc
1Acceptableovercurrentandovervoltage
CP254capacitorbanksaredesignedfor:
1,10xUnovervoltage12hoursperday,
1,15xUnpowerfrequencyovervoltage30minutesperday,
Permanentovercurrent:1,3xIn.
2Designvoltage,designpowerandmarking
AccordingtoIEC60871recommendations,capacitorunitsorcapacitorbanksnameplatesshallindicatethe
maximumpowerandvoltageforwhichitisdesigned(Qdim&Vdim).
Ourcapacitorunitsandcapacitorbankshavenameplatesshowingthesedesignpoweranddesignvoltage
(QdimandVdim).Operatingvaluescanbeequalorlowerthanthesevalues(QnandVn).
Lastupdate:20081201
10