Professional Documents
Culture Documents
MANUAL
CORROSION INHIBITION OF
DOWNHOLE PRODUCTION TUBING,
PROCESS PIPING AND PIPELINES
PTS 20.210
OCTOBER 1995
PREFACE
PETRONAS Technical Standards (PTS) publications reflect the views, at the time of publication,
of PETRONAS OPUs/Divisions.
They are based on the experience acquired during the involvement with the design, construction,
operation and maintenance of processing units and facilities. Where appropriate they are based
on, or reference is made to, national and international standards and codes of practice.
The objective is to set the recommended standard for good technical practice to be applied by
PETRONAS' OPUs in oil and gas production facilities, refineries, gas processing plants, chemical
plants, marketing facilities or any other such facility, and thereby to achieve maximum technical
and economic benefit from standardisation.
The information set forth in these publications is provided to users for their consideration and
decision to implement. This is of particular importance where PTS may not cover every
requirement or diversity of condition at each locality. The system of PTS is expected to be
sufficiently flexible to allow individual operating units to adapt the information set forth in PTS to
their own environment and requirements.
When Contractors or Manufacturers/Suppliers use PTS they shall be solely responsible for the
quality of work and the attainment of the required design and engineering standards. In
particular, for those requirements not specifically covered, the Principal will expect them to follow
those design and engineering practices which will achieve the same level of integrity as reflected
in the PTS. If in doubt, the Contractor or Manufacturer/Supplier shall, without detracting from his
own responsibility, consult the Principal or its technical advisor.
The right to use PTS rests with three categories of users :
1)
2)
3)
Subject to any particular terms and conditions as may be set forth in specific agreements with
users, PETRONAS disclaims any liability of whatsoever nature for any damage (including injury
or death) suffered by any company or person whomsoever as a result of or in connection with the
use, application or implementation of any PTS, combination of PTS or any part thereof. The
benefit of this disclaimer shall inure in all respects to PETRONAS and/or any company affiliated
to PETRONAS that may issue PTS or require the use of PTS.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual
arrangements, PTS shall not, without the prior written consent of PETRONAS, be disclosed by
users to any company or person whomsoever and the PTS shall be used exclusively for the
purpose they have been provided to the user. They shall be returned after use, including any
copies which shall only be made by users with the express prior written consent of PETRONAS.
The copyright of PTS vests in PETRONAS. Users shall arrange for PTS to be held in safe
custody and PETRONAS may at any time require information satisfactory to PETRONAS in order
to ascertain how users implement this requirement.
REVISION REGISTER
REVISION NO.
DATE
DETAIL OF REVISION
5/93
7/95
Initial Issue
Registered Holder
01
ETS/4
02
ETS/6
03
PET/3
04
PET/33
05
OPM/41
06
EPD/63, SIPM
07
ME/122, KSLA
08
ETS/43
09
ETS/431
10
ETS/433
11
ETS/434
12
1314
15
16
17
18
19
20
Date Distributed
TABLE OF CONTENTS
1.
INTRODUCTION
1.1
1.2
ABBREVIATION .
1.3
CROSS REFERENCES
2.1
2.2
2.3
2.3.1
2.3.2
2.3.3
2.4
2.4.1
2.4.2
2.5
2.5.1
2.5.2
2.5.3
3.
4.
REFERENCES
5.
TABLE
6.
ATTACHMENTS
1.
INTRODUCTION
1.1
1.2
1.3
ABBREVIATION
CO2
Carbon Dioxide
SRB
CGR
GLR
HHP
HP
High Pressure
H2S
Hydrogen Sulphide
CROSS-REFERENCES
Where cross-references to other parts of the main text in this procedure are made, the
referenced section number is shown in brackets. Documents referenced by this procedure are
listed under references (4).
2.
2.1
2.1 .1
Corrosion
In single-phase gas systems no aqueous phase is present and aqueous corrosion thus
cannot occur.
For downhole tubulars generally liquid condensation will occur at some point in the tubulars.
The depth where condensation occurs will vary through the life of the well, as pressures and
temperatures change. Above the point of condensation the tubulars needs corrosion control
measures. This portion of the well that is corrosive drives the corrosion control measures. The
portion of the well that is technically non-corrosive, because it is only single phase gas,
usually has to be protected to be able to protect the rest of the well, so no account can be
made of the fact that this portion is non-corrosive.
For "dry" gas export pipelines, where the gas is dried before transport to prevent formation of
gas hydrates and corrosion, however an aqueous phase may still be present unintentionally
under certain circumstances:
-
This condition will change the single-phase gas system to a two-phase gas-liquid system
(2.3).
2.1 .2
Corrosion Control
In true single phase gas systems corrosion control by inhibition is normally not required.
However, in the event that the presence of a water phase is possible for extended duration,
corrosion control measures may be required.
In downhole tubulars the single phase portion of the tubulars has inhibitor injected in order to
be able to protect the portion of the tubulars that is in two-phase flow. For dry" gas pipelines,
when the gas drying system goes out of specification some pipelines have systems installed
to inject inhibitors as a protection system in this system which is now two-phase.
2.2
2.2. 1
Corrosion
Single-phase liquid systems in production and transport systems are systems where crude oil
or gas condensate (usually containing dissolved water and gas) is produced, or where all the
liquids are fully emulsified (i.e. no free water phase).
The principal examples are:
oil wells above the bubble point pressure and where the fluids are fully emusified. Note
the depth that the well reaches the bubble point will depend on the pressures in the well
and the reservoir. The bubble point pressure could be reached at or downstream of the
wellhead, at some point in the tubulars or in the formation itself. For most mature oil wells
(i.e. PETRONAS wells) the water cut is high and the pressures are relatively low, so that
the tubulars contain 3 separate phase, oil, water and gas.
export oil lines ("trunklines"), where the gas has been separated from the oil and the
water remaining in the oil is at a low enough concentration and high enough velocity to be
fully emulsified or disposed (i.e. no free water phase). The minimum velocity to ensure no
water dropout in these situation is above a critical value of at least 1 m/s (ref. 5).
In single-phase liquid systems whenever the water content is higher than the amount which
can dissolve molecularly the water will be present as a separate phase. From a corrosion
stand point this starts to be a concern in a crude system at water cuts of > 40 % and/or at
water cuts < 40 % with liquid velocities < 1 m/s Under this condition the system should be
regarded as a two-phase liquid-liquid system (2.4). Note that the 40 % limit is believed to be
conservative and there is ongoing research to redefine this limit. Further data on the critical
water/oil ratio can be obtained by running the Wetgas7 or Flowline7 corrosion modelling
programs. The effects of emusification of the crude/water also need to be considered.
In the water injection systems, where produced water is re-injected and dissolved corrosive
gases (CO2 and/or H2S) are not completely removed, corrosion may occur. In cases where
seawater is injected to enhance oil recovery, the injected water is usually de-aerated to
remove dissolved oxygen and chemically treated with biocides to suppress SRB-induced
corrosion. If oxygen is present in the injected water (through leaks or poor de-aeration), the
corrosion rates will be extremely high and unlikely to be economically treatable with inhibition;
effort needs to be placed on first reducing the oxygen level in the water.
2.2.2
Corrosion Control
In true single-phase condensate or oil systems, there is no free water phase, hence, corrosion
control normally will not be needed. However there are few systems that are truely singlephase and these must be treated as two-phase or multi-phase systems. The conditions which
would allow water to settle out must be clearly understood, before a system can be called
"single-phase".
Injection of corrosion inhibitor into water injection systems is generally not favoured because
film forming corrosion inhibitors may block the reservoir pores. If this needs to be considered,
specific tests with reservoir cores should be carried out.
2.3
2.3.1
2.3.1.1 Corrosion
With respect to corrosion, the two-phase gas-liquid systems being considered with annulardispersed flow have an aqueous phase in contact with the steel pipe wall over the whole
circumference of the pipe, and are consequently corrosive.
2.3.2
2.3.2.1 Corrosion
In a non-vertical pipeline operating in stratified two-phase gas-liquid flow the bottom of the line
will be in contact with the aqueous phase. The top of the line will be in contact with the flowing
vapour phase of the system. In practical situations this means that the top of the line will be
wet due to water condensation. The latter may occur due to temperature gradient across the
pipe wall or due to capillary condensation of water vapour in the pores of the corrosion
products present on the pipe wall.
2.3.3
2.3.3.1 Corrosion
With respect to the occurrence of corrosion, systems operating in slug flow of gas and liquid
have to be regarded as being in single-phase liquid flow for a time fraction, t, and in stratified
flow for a time fraction, 1-t. The fraction t is determined by Eq(1) as follows:
t = f (L / v )
Eq(1)
where:
L
= length of pipeline ft
The choice will depend on the value of t in Eq(1) above. For both cases, continuous addition
of the corrosion inhibitors soluble in water or water/glycol mixtures is recommended, (Ref. 2).
Corrosion control by continuous injection of an inhibitor soluble in a hydrocarbon phase into
the system is not recommended.
2.4
2.4.1
2.4.1.1 Corrosion
For aqueous corrosion to occur the aqueous phase must be in continuous contact with the
steel wall.
which is the continuous phase, i.e. will the inhibitor reach all areas where it is required?
No definite guidelines can be given - each case must be reviewed separately. Generally for
high water cuts a water-soluble/oil dispesible corrosion inhibitor is used and for low water cuts
an oil-soluble/water dispesible corrosion inhibitor is used. There is a middle range of water
cuts where either type of inhibitor can be used.
2.4.2
2.4.2.1 Corrosion
For aqueous corrosion to occur the aqueous phase must be in continuous contact with the
steel wall.
2.5
saline water,
gas phase
In systems producing crude oil, the crude oil may act as a natural inhibitors; note however
that it is very unlikely that condensate will act as a natural inhibitor in gas production systems.
2.5.1
2.5.1.1 Corrosion
If there is separate flow of water and gas condensate or oil and the water phase is in contact
with the pipe wall the corrosion characteristics of the system can be described as for the case
of an annular dispersed two-phase gas liquid system (2.3.1).
2.5.2
2.5.3
3.
4.
5.
REFERENCES/RELATED GUIDELINES
1.
2.
Flow effects on corrosion of carbon steel by L. Van Bodegom and U. Lotz, KSLA,
Corros. Prev. Process Ind., Proc NACE Int. Symp., 1 st Meeting date 1988, page
123-138, Editor Parkins and N. Redvers, Publisher, NACE Houston Texas USA.
3.
4.
Selection and set-up of laboratory test methods for corrosion inhibitors for sweet oil
and gas production and transport, S.F. Keij, KSLA report AMGR.95.236.
5.
TABLE
1.
6.
ATTACHMENTS
1.
2.
3.
4.