Professional Documents
Culture Documents
a r t i c l e
i n f o
Article history:
Received 22 July 2015
Received in revised form
11 September 2015
Accepted 16 September 2015
Available online 21 September 2015
Keywords:
Natural ventilation
Wind-driven ventilation
Single-sided ventilation
Wind tunnel experiment
Tracer gas technique
a b s t r a c t
This study uses wind tunnel experiments to investigate the wind-driven ventilation for buildings with
two openings on a single wall. The exchange rates are measured by the tracer gas decay method under
different external wind speeds, directions and opening sizes. The experimental results indicate that the
time-averaged pressure difference across the openings is much larger than the uctuating pressure when
the wind direction is = 22.545 , and the ventilation rate can be predicted by the orice equation.
When the wind direction is = 0 and 67.5180 , the pressure difference across the openings is insignificant and the uctuating pressure entrains air across the openings. The exchange rate is proportional
to the root-mean-square of the pressure uctuation. Furthermore, the dimensionless exchange rate of
the shear-induced ventilation (wind is parallel to the openings) is found to be independent of the wind
speed, opening area and location. The exchange rate for buildings with an internal partition is lower
than that without a partition when the wind direction is = 090 . A semi-empirical prediction model
is proposed to calculate the exchange rate by incorporating the time-averaged pressure difference and
pressure uctuation. The application of the prediction model to compute the air change rate (ACH) is also
discussed.
2015 Elsevier B.V. All rights reserved.
1. Introduction
equation can be used to calculate the steady ow rate of winddriven ventilation through the building openings:
The air exchange between a building and the external air plays
a vital role in determining the indoor air quality and thermal environment of the building [1,2]. The frequency of air exchange can be
dened as the air change rate [3]:
I=
Q
V
(1)
2|P P | 1/2
e
i
Q = Cd A
(2)
where A is the cross-section area of the opening; Cd is the dimensionless discharge coefcient; is the density of the air; and Pe and
Pi are the exterior and interior pressures of the opening, respectively. Eq. (2) is frequently used in multi-zone models to calculate
the ventilation rate, and the typical discharge coefcients given in
the literature are in the range of 0.600.66 for sharp-edged openings in high Reynolds number ows [4,5].
However, several studies [68] have pointed out that the orice
equation cannot be used to predict the ow rate of buildings with
a single opening. The time-averaged
pressure difference across
the opening is close to zero, P 0, for buildings with a single opening, regardless of wind direction. Warren [6] used the
tracer gas technique to study wind-driven ventilation with a single opening on the windward facade. His experimental results
showed that the dimensionless exchange rate was in the range of
Q* = Q/UA = 0.0230.026 in a smooth ow (low turbulence ow),
and Q* = 0.035 in a grid-generated turbulent ow. The British
Standard [8] proposed the an empirical formula to predict the
366
Notation
cross-section area of external opening (m2 )
A
Aw
area of external wall (m2 )
Cd
discharge coefcient of opening (dimensionless)
Cp = (PPo )/0.5U2 external pressure coefcient of opening
Cprms = Prms /0.5U2 root-mean-square of internal pressure
coefcient
H
height of the building (m)
air change rate (h1 )
I = Q/V
Iu = u /UH turbulence intensity (dimensionless)
Po
reference pressure (Pa)
Pe
external pressure near the opening (Pa)
Pi
internal pressure (Pa)
root-mean-square of internal pressure (Pa)
Prms
Q
exchange rate (m3 s1 )
Q* = Q/UH A dimensionless exchange rate
r = A/Aw wall porosity ratio (dimensionless)
UH
external wind speed at building height (m/s)
air density (kg/m3 )
wind direction ( )
kinematic viscosity of air (m2 s1 )
Subscript 1, 2 opening one and opening two
Q
= 0.025
UA
(3)
Q
= 0.015
UH A
(4)
where UH is the wind speed at the building height and Aw is the area
of the external wall. However, the dimensionless exchange rate is
Q* = 0.020 when the wall porosity ratio r = 12.25%.
Larsen and Heiselberg [10] employed a full-scale model and the
tracer gas technique to study the airow rate of single-sided ventilation. Their experimental conditions included wind-driven and
buoyancy-driven ventilation under various wind directions. Their
results indicated that whether wind or buoyancy was the dominant
driving force depended on the wind direction and the ratio between
the driving forces. The prediction error of their model was in the
range of 1828%.
The above studies only investigated single-sided ventilation for
buildings with one opening. Hu et al. [11] used a Large Eddy Simulation (LES) model to simulate the wind-driven ventilation for
buildings with two openings on two opposite walls, each with one
opening. They studied two different kinds of ow conditions: (1)
Cross ventilation, where the external wind direction is normal to
the windward and leeward openings; and (2) Shear ventilation,
where the wind direction is parallel to the openings on the two lateral walls. They observed bi-directional, unsteady air ows across
the lateral openings, but did not quantify the exchange rate of the
shear ventilation.
Chu et al. [12] used wind tunnel experiments and the tracer
gas technique to investigate the shear-induced ventilation for one
and two openings. They found that the uctuating pressure dominates the shear ventilation, especially when the time-averaged
Cp1 Cp2
1 + i + 2
1/2
(5)
where Cp1 and Cp2 are the pressure coefcients near the external
openings; and 1 , 2 and i are the resistance factors of the external and internal openings, respectively. The resistance factors of
external openings 1 and 2 are equal to:
1 =
2 =
Cd2 A21
1
Cd2 A22
(6)
|P| 1/2
Q = Cd A
(7)
367
Q = Cd
kCprms
2
1/2
(12)
Fig. 1. Schematic diagram of single-sided ventilation with two openings on the same
wall.
|P| + kP
rms
Q = Cd A
1/2
(8)
where k is an empirical coefcient to quantify the inuence of uctuating pressure on the air exchange across the opening, and Prms is
the root-mean-square (rms) value of the uctuation of the internal
pressure:
n
1
2
Prms =
[P(t) P]
n
(9)
i=1
Q = Cd
|Cp | + kCprms
2
1/2
(10)
Prms
2
0.5UH
(11)
openings
is much larger than the coefcient of uctuating pressure,
Cp Cprms , the air exchange is driven by the pressure difference
Fig. 2. (a) Photograph of the model building in the test section of the wind tunnel;
(b) schematic diagram of the locations of openings and pressure taps for opening
area A1 = A2 = 40 mm 40 mm.
368
partition
wall
Wind
A1
Reference
( )
Q*
Warren [6]
British Standard [8]
Present study
Kato et al. [9]
Larsen and Heiselberg [10]
Chu et al. [12]
Present study
0
0
0
90
90
90
90
0.0230.026
0.025
0.0265
0.0150.020
0.025
0.018
0.020
A2
transient evolution of the spatially-averaged concentration C(t)
inside the model building was used to calculate the exchange rate
Q by the following equation:
Q =
Top view
Unit: mm
400
Wind
A1
partition
Ai
400
A2
360
Fig. 3. Schematic diagram of single-sided ventilation with two openings and internal partition.
ln C(t2 )/C(t1 )
t2 t1
(13)
369
0.25
0.20
Q*
0.15
0.10
0.05
Fig. 6. Schematic diagram of the separation shear layer under wind direction
= 67.5 .
0.00
0
30
60
90
120
150
180
1.0
(Deg)
Fig. 4. Dimensionless exchange rate Q* as a function of wind direction for singlesided ventilation with two openings. The external wind speed UH = 2.32 m/s, and
wall porosity ratio r = 1.0%.
0.6
(a)
1.2
0.8
0.4
Cp1
Cp2
0.8
Cpi
0.2
0.4
Cp
0.0
0
0.0
30
60
90
(Deg)
120
150
180
-0.4
-0.8
0
30
60
90
120
150
180
120
150
180
(Deg)
(b)
0.5
0.4
Cprms
0.3
0.2
0.1
0.0
0
30
60
90
(Deg)
370
Top view
(a )
Wind
(b )
A2
A1
A1
A2
0.30
(14)
where Q*m and Q*p are the measured and predicted exchange rates,
respectively. The average prediction error was 13%, and the coefcient of determination was R2 = 0.969. The accuracy was better than
the models of Larsen and Heiselberg [10] for single-sided ventilation with one opening.
0.15
Qm
0.20
Error =
Qm Qp
0.25
0.10
0.05
0.00
10
12
UH (m/s)
Fig. 9. Schematic diagram of shear ventilation with two openings (wind direction
= 90 ). (a) Two openings on two opposite walls; (b) two openings on a single lateral
wall; (c) relationship between dimensionless exchange rate Q* and external wind
speed UH for shear ventilation. The experimental condition of Larsen and Heiselberg
[10] and Kato et al. [9] is shear ventilation with a single opening.
0.25
No partition, UH = 2.32 m/s
With partition, UH = 2.32 m/s
0.20
0.15
Q*
0.10
0.05
0.00
0
30
60
90
120
150
180
(Deg)
Fig. 10. Dimensionless exchange rate Q* for buildings with or without internal partition under various wind directions. The wall porosity ratio r = 1.0%, external wind
speed UH = 2.32 m/s and 3.56 m/s.
Fig. 10 compares the dimensionless exchange rates Q* for buildings with and without an internal partition under various wind
directions. As expected, the exchange rate, Q*, without the partition was larger than that with the partition for wind direction
= 090 . However, the exchange rate, Q*, was not affected by the
internal partition when the openings were located on the leeward
side ( = 112.5180 ). In addition, the dimensionless exchange
rates of wind speed UH = 2.32 m/s and 3.56 m/s were very close.
This indicated that for buildings with an internal partition, the
371
0.3
10
Without partition
1:1
With partition
8
0.2
i/1
Qp*
4
0.1
0
0.0
0.0
0.0
22.5
45.0
67.5
0.1
90.0
1 + i + 2
(15)
0.15
1/2
Cp + kCprms
0.20
0.10
1
Q =
A1
0.3
Qm*
(Deg)
Fig. 11. Dimensionless resistance factor i / 1 of the internal partition as a function
of wind direction.
0.2
0.05
0.00
10
12
UH (m/s)
Fig. 13. Dimensionless exchange rate Q* of shear ventilation (wind direction = 90 )
for building with and without internal partition under different wind speeds.
Table 2
Air exchange rate of different opening congurations.
Conguration
Wind direction
Single opening
Two openings
w/o partition
( )
Q*
Q (m3 s1 )
ACH (h1 )
0.018
0.054
0.65
0.075
0.224
2.69
22.567.5
90
112.5180
0.183
0.087
0.056
0.550
0.261
0.167
6.60
3.13
2.00
0.041
0.122
1.46
0.093
0.048
0.050
0.279
0.145
0.152
3.35
1.74
1.82
Two openings
with partition
Exchange rate
22.567.5
90
112.5180
UH = 3.0 m/s, the interior volume was V = 300 m3 , and the opening
area A1 = A2 = 1 m 1 m (wall porosity r = 3.33% for each opening).
The computed exchange rate Q and ACH of different opening congurations were listed in Table 2. The air change rate of single opening
was only ACH = 0.65, while ACH = 6.6 when the two openings were
on the windward facade (22.567.5 ) and ACH = 2.0 when the openings were on the leeward facade (112.5180 ). As expected, the
value of ACH with the partition was lower than that without the
372
References
[1] D.W. Etheridge, M. Sandberg, Building Ventilation: Theory and Measurement,
John Wiley and Sons, England, 1996.
[2] P.F. Linden, The uid mechanics of natural ventilation, Annu. Rev. Fluid Mech.
31 (1999) 201238.
[3] H.B. Awbi, Ventilation of Buildings, 2nd ed., Taylor and Francis, 2003.
[4] C.R. Chu, Y.H. Chiu, Y.J. Chen, Y.W. Wang, C.P. Chou, Turbulence effects on the
discharge coefcient and mean ow rate of wind-driven cross ventilation,
Build. Environ. 44 (2009) 20642072.
[5] P. Heiselberg, M. Sandberg, Evaluation of discharge coefcients for window
openings in wind driven natural ventilation, Int. J. Vent. 5 (1) (2006) 4352.
[6] P.R. Warren, Ventilation through openings on one wall only, in: C.J.
Hoogendorn, N.H. Afgar (Eds.), Int. Conf. Heat and Mass Transfer in Buildings,
Dubrovnik, Yugoslavia. Energy Conservation in Heating, Cooling and
Ventilating Buildings, Hemisphere, Washington, DC, USA, 1977, pp. 189209.
[7] P.R. Warren, L.M. Parkins, Single-sided ventilation through open windows, in:
Conference Proceedings of Thermal Performance of the Exterior Envelopes of
Building, FL, USA, ASHRAE 49, 1985, pp. 209228.
[8] British Standard 5925, Code of Practice for Design of Buildings: Ventilation
Principles and Designing for Natural Ventilation, British Standards Institution,
London, UK, 1980.
[9] S. Kato, R. Kono, T. Hasama, T. Takahashi, R. Ooka, A wind tunnel experimental
analysis of the ventilation characteristics of a room with single-sided opening
in uniform ow, Int. J. Ventilation 5 (1) (2006) 171178.
[10] T.S. Larsen, P. Heiselberg, Single-sided natural ventilation by wind pressure
and temperature difference, Energy Build. 40 (2008) 10311040.
[11] C.H. Hu, M. Ohba, R. Yoshie, CFD modelling of unsteady cross ventilation ows
using LES, J. Wind Eng. Ind. Aerodyn. 96 (10/11) (2008) 16921706.
[12] C.R. Chu, R.H. Chen, J.W. Chen, A laboratory experiment of shear-induced
ventilation, Energy Build. 43 (10) (2011) 26312637.
[13] H. Wang, Q. Chen, A new empirical model for predicting single-sided,
wind-driven natural ventilation in buildings, Energy Build. 54 (2012)
386394.
[14] L. Ji, H. Tan, S. Kato, Z. Bu, T. Takahashi, Wind tunnel investigation on
inuence of uctuating wind direction on cross natural ventilation, Build.
Environ. 46 (2011) 24902499.
[15] N. Nikolopoulos, A. Nikolopoulos, T.S. Larsen, K.-S.P. Nikas, Experimental and
numerical investigation of the tracer gas methodology in the case of a
naturally cross-ventilation building, Build. Environ. 56 (2012) 379388.
[16] C.R. Chu, Y.W. Wang, The loss factors of building openings for wind-driven
ventilation, Build. Environ. 45 (10) (2010) 22732279.
[17] C.R. Chu, Y.H. Chiu, Y.W. Wang, An experiment study of wind-driven cross
ventilation in partitioned buildings, Energy Build. 42 (2010)
667673.
[18] C.R. Chu, B.F. Chiang, Wind-driven cross ventilation with internal obstacles,
Energy Build. 67 (2013) 0109.
[19] C.R. Chu, B.F. Chiang, Wind-driven cross ventilation in long buildings, Build.
Environ. 80 (2014) 150158.
[20] P. Karava, T. Stathopoulos, A.K. Athienitis, Airow assessment in
cross-ventilated buildings with operable facade elements, Build. Environ. 46
(1) (2011) 266279.
[21] M.H. Sherman, Tracer-gas techniques for measuring ventilation in a single
zone, Build. Environ. 25 (1990) 365374.
[22] N.P. Gao, J.L. Niu, M. Perino, P. Heiselberg, The airborne transmission of
infection between ats in high-rise residential buildings: tracer gas
simulation, Build. Environ. 43 (2008) 18051817.
[23] S. Van Buggenhout, A. Van Brecht, S. Eren zcan, E. Vranken, W. Van Malcot,
D. Berckmans, Inuence of sampling positions on accuracy of tracer gas
measurements in ventilated spaces, Biosys. Eng. 104 (2009) 216223.
[24] Z. Bu, S. Kato, T. Takahashi, Wind tunnel experiments of wind-driven natural
ventilation rate in residential basements with areaway space, Build. Environ.
45 (2010) 22632272.