Project:
Customer:
Document:

AUGMENTATION OF REEFER YARD S


JAWAHARLAL NEHRU PORT TRUST
Short Circuit Calculation
630208-EE022/sckt
calculations/R0

Document Number :

VCB
33KV

Old HT Board

VCB

Cable 1

33 kV

New HT Board

VCB
Cable 2

33/0.433 kV
4000 kVA

New Trafo

33/0.433 kV
2000 kVA

ACB
0.433kV
ACB

ACB

Cable 3

APFC

TION OF REEFER YARD SUB-STATION E6A


AL NEHRU PORT TRUST
t Calculation
Revision :

Parameters
Rated System Voltage
Source Fault Level
Source Fault MVA
Voltage factor

Impedance

ZQ

Resistance

RQ

Reactance

XQ

Cable 1
No. of runs
Route Length
Cable Resistance
Cable Reactance
Net Cable Resistance

RC1

Net Cable Reactance


Total Impedance
Symmetrical S/C Current (rms) at 33 kV
SWGR Bus

Cable 4

Old Trafo

XC1
Isc

Cable 2
No. of runs
Route Length
Cable Resistance
Cable Reactance
Net Cable Resistance

RC2

Net Cable Reactance

XC2

Power Transformer - 1
Rated Capacity

ST1

Rated Primary Voltage

VP1

Rated Secondary Voltage

VT1

Rated Secondary Current

IT1

% Impedance

uT1

Full Load Cu Loss

QT1

Transformer Impedance

ZT1

Transformer Resistance

RT1

Transformer Reactance

XT1

The reactance & resistance calculated for HV Section must be recalc


the voltage ratio of the transformer.
N1
Square of the voltage Ratio
Equivalent resistance up to Power Trafo

RT1

Equivalent reactance up to Power Trafo

XT1

Busduct
Neglected for the purpose of calculation
ACB
Equivalent resistance up to 0.433kV PCC Bus

R1

Equivalent reactance up to 0.433kV PCC Bus

X1

Total Impedance
Symmetrical S/C Current (rms) at 0.433 kV
PCC Bus

Isc

Cable 3
No. of runs
Route Length
Cable Resistance
Cable Reactance
Net Cable Resistance

RC3

Net Cable Reactance

XC3

Equivalent resistance up to APFC Bus


Equivalent resistance up to APFC Bus
Total Impedance
Symmetrical S/C Current (rms) at APFC bus

Isc

33000
26.3
500

UoM
Volts
kA
MVA

Remarks
Main Board Fault Level

1.1

For MV System up to 35 kV (In Accordance


with IEC 60909)

1.05

For 415 V System (In Accordance with IEC


60909)

2.396

0.479

2.347

3x185
2
0.025
0.1270
0.1160
0.001588

kM
/km
/km

0.001450
2.398

8.74

kA

3x185
1
0.04
0.1270
0.1160
0.0051

kM
/km
/km

0.0046

MVA

RQ = 0.2 ZQ (In Accordance with IEC 60909)

As per requirement
Estimated Route length
Taken from Polycab Datasheets

Estimated Route length


Taken from Polycab Datasheets

33

kV

0.433

kV

5333.5

Amp

7.15

28500

As per CBIP Guidelines

0.003351

(uT / 100)*(VT2 / ST)

0.000334

(Q / (3 * IT2)

0.003335

(ZT2 - RT2)

V Section must be recalculated for the LV network via multiplication by square of


0.000172
0.00042

(RQ + RC1 + RC2) * N1 + RT1

0.00374

(XQ + XC1 + XC2) * N1 + XT1

If this impedenace is included, then the


fault level will reduce further

0.00042
0.00374
0.00376

73.08

kA

3x300
9
0.025
0.0769
0.0711
0.000214

Cable Up to APFC Panel

/km
/km

0.000198

0.00063

(X1 + XC3 + XC4 ) * N2 + XT2

0.00394
0.00399

(R1 + RC3 + RC4 ) * N2 + RT2

65.83

kA

Taken from KEI Datasheets

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 6.6 kV BUS COUPLER FEEDER AT 6


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)
2.0

Full load current


CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range
INVERSE (51)
i) Current setting (PHLPTOC)
ii) Time Setting (PHLPTOC)
HIGH SET (50)
i) Current setting (PHIPTOC)
ii) Time Setting (PHIPTOC)
Earth-Fault (51N)
i) Current Setting (EFLPTOC)
ii) Time Setting (EFLPTOC)
Earth - Fault High Set (50N)
i) Current Setting (EFIPTOC)
ii) Time Setting (EFIPTOC)
Check Synchronizing (25)
i) Operation acuuracy

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 6.6 kV BUS COUPLER FEEDER AT 6

ii) Reset time


iii) Reset ratio
iv) Operate time accuracy
e)
4.0
4.1

Nominal Current
RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)

Current setting adopted

51

PHLPTOC

** Note 1: Please refer Fault current calculations ( L & T Doc No: O12117-E-BM-CS-DD-8014)

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 6.6 kV BUS COUPLER FEEDER AT 6

FAULT AT ITS OWN TERMINAL


c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

PHLPTOC
4.2
a)

b)
4.3
a)

b)

INSTANTANEOUS ELEMENT
Current Setting

50

Setting Adopted
Time Delay
EARTH FAULT ELEMENT

PHIPTOC
50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

US COUPLER FEEDER AT 6.6 kV HT Board @ Main CHP SS-3

6600

31700

0.850

2187.00

2500

REF 630

ABB

Normal Inverse

0.05-5 In

0.05-15 s

0.1-40 In

20ms - 200s

0.01-5Ino

0.05-15 s

0.1-40 In

20ms - 200 s

At the frequency f=fn

** (Refer Note 1)

5P20

0.02
0.14

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

US COUPLER FEEDER AT 6.6 kV HT Board @ Main CHP SS-3


Volatage :

1.0 % or 0.002 x Un

Frequency : 10 mHz
phase angle : 2
:

< 50 ms

Typical 0.96

90 ms/ 0 ms

1.2 * Full Load load current /CT Ratio

1.2*2187/2500

1.050

1.10

BM-CS-DD-8014)

In

Approved
NH

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

3 X 660 MW Lalitpur STPP, CHP

:
:
:
:
:
:

Relay Setting calculations


O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

US COUPLER FEEDER AT 6.6 kV HT Board @ Main CHP SS-3

Fault current /(CT Ratio * PS)

31700/(2500/1*1.1)

11.5

0.14
PSM^0.02 - 1

(for PSM>20,PSM=20)

2.79

Desired Operating time


Relay Operating time at TMS=1.0

0.85 / 2.79

0.304

LV Rated fault Current/CTR


31700/2500
12.680
13
0.18
S

0.10 times of Full load current/CTR

0.10*2187/2500

0.08748

0.1

In

0.14

Approved
NH

CHP SS-3

Approved
NH

CHP SS-3

Approved
NH

CHP SS-3

Approved
NH

DESIGN BASIS FOR RELAY SETTINGS


1.1

In a radial circuit, where there are more than one section in series, there is no difference in current between a fault at the end of one se
necessary to add time discrimination, with the time settings increased towards the source.

1.2

After calculating the short circuit currents at different buses, herein above, the settings of the relays are worked out starting from the lo

1.3

As per standards, in the Over current relay operating zones upto 10 times the plug setting, an error of 7% in the operating time is allow
error of 12% is permitted. According to the MV breaker manual, the opening time of the MV breakers is 60 ms at 100% interrupting ca
considered for proper discrimination between relays.

1.4

Conventionally, a fixed selective interval of 0.35 second is used between successive relays. However considering the following time fac
wherever, possible.(Refer IEEE-242 Table 15.1 page 602)

1.5

It is preferable to discriminate between relays on primary and secondary side of the transformer to distinguish between the faults on LV
constraint vis--vis availability of other protection, switchgear short circuit withstand time, etc., then this discrimination time may be re

1.6

The instantaneous element of the Over-current relay on the HV side of the transformer will be set at 1 time the current, which will flow

1.7

Wherever large motors are present, the incomer relays will be de-sensitised for the current, which will flow during the starting of these
current relays.
All the motors above 75 kW and above are represented in ETAP SLD and motors less than 75 kW are shown as Lump load

1.8
1.9
2

Relay setting are computed for normal bus configuration where there is minimum loading, hence it is not required to be performed for d
be more than than minimum bus configuration.
Relay cordination for IDMT relays is considered for IEC-standard inverse curve

2.1
2.2
2.3
2.4

Short circuit Study


Short circuit analysis is performed using ETAP 11.1.1 with IEC 60909 standarad, considering maximum shortcircuit current in thre phase
Voltage tolerances are as per IS 12360
Short circuit MVA at the 33 kV incoming is obtained from "Power system study" performed by ABB Ltd vadodara of 525 MVA.
VVVF, VFD driven motors are not considered for shortcircuit calculation as they are not regenrative .Hence there will not be any contrib

2.5
2.6

Capacitor feeder are kept open during short circuit analysis


Fault impedance is considered as zero as we have considered 3 Phase bolted fault, However in practical conditions the fault current will
point and fault point.

Reference standard used IEEE-242-2001

GN BASIS FOR RELAY SETTINGS

urrent between a fault at the end of one section and a fault at the beginning of the next one; consequently, it is

e relays are worked out starting from the load end upto upstream towards the source.

n error of 7% in the operating time is allowed and in the operating zones between 10 to 20 times Plug setting, an
breakers is 60 ms at 100% interrupting capacity. Hence, the relay error time and breaker opening time must be

However considering the following time factors, a minimum discrimination time of 250 ms is adopted in this report,

mer to distinguish between the faults on LV & HV side. In case, operating time of the upstream relays become a
c., then this discrimination time may be reduced / sacrificed.

e set at 1 time the current, which will flow for a short circuit on the LV side.

which will flow during the starting of these motors. This will be achieved by adjusting the plug setting of the over
kW are shown as Lump load

ence it is not required to be performed for different case studies as the short circuit current from different motors will

Short circuit Study


maximum shortcircuit current in thre phase bolted fault.

y ABB Ltd vadodara of 525 MVA.


nrative .Hence there will not be any contribution from these motors during fault at connected bus.

in practical conditions the fault current will be further reduced due to the presence of impedance between source

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-1

415

39760

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-1

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

39760/(3200/1*0.96)

12.9

:
:

0.14
PSM^0.02 - 1
0.07

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


12.425
12.425
12.425
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-1

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-1

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-1

(for PSM>10,PSM=10)

Approved
PRM

C-1

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tra


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tra

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tra

i) V> Measurement Mode


ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tra


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.064

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tra


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tra

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer outgoing

6600

:
:

17880
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer outgoing Non-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
IEC
E
0.025-1
Inverse,
0=Disabled
UK LT
,1=DT,2=I
Inverse,
EC
UK S
Inverse,3=I
Rectifier,
EC
V
RI, IEEE
Inverse,4=I
M Inverse,
0.05-32In
EC
EV
IEEE
Inverse,5=
Inverse,
UK
IEEELTE
0Inverse,6=
to 100 US
Inverse,
UK
Inverse, US
Rectifier,7
ST Inverse
=RI,8=IEE
Measured
EM
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Prepared
JS

Checked
PGT

Relay setting of 6.6 kV transformer outgoing

:
:
:
:
:
:
:
:

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17880/(200/1*0.96)

93.1

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

LARSEN & TOUBRO LTD

GROUP 1 OVERCURRENT SETTINGS


i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input

LARSEN & TOUBRO LTD

i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

4.0

RELAY SETTING

4.1

SETTINGS FOR IDMT OC-51


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting
Setting Adopted
ii) Time Delay

50

LARSEN & TOUBRO LTD

4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

50N

LARSEN & TOUBRO LTD

iv) TMS Required

LARSEN & TOUBRO LTD

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:
:
:

:
:

:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:

:
:
:

:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:

:
:

:
:
:
:
:
:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
I>1 TMS

:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

415

43750

0.07

2782.41

2000.00

KVA

3200

From ETAP

Note: Load current is calcu

5P20

MICOM-P14
Schneider
Normal Inverse
* Setting range are taken from Relay Manual

a
b

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

Prepared
JS
PMCC-2

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured

Checked
PCP

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

Prepared
JS
PMCC-2

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Checked
PCP

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

1.1 * Full Load load current /CT Ratio


0.96
0.96

In

Fault current /(CT Ratio * PS)


43750/(3200/1*0.96)
14.2

0.14
PSM^0.02 - 1
2.57

(for PSM>10,PSM=10)
S

Desired Operating time


Relay Operating time at TMS=1.0
0.07 / 2.57
0.027
Rated fault Current/CTR
13.671875
13.672
13.672
0.10

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

0.10 times of Full load current/CTR


0.09
0.09
0.09

In

0.1

0.1

0.10*CT primary current


320.00
Iearthfault/CT ratio
0.1
37530

Fault current /(CT Ratio * PS)


37530/(3200/1*0.1)
117.3
0.14
PSM^0.02 - 1
2.27

(for PSM>10,PSM=10)
S

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

Desired Operating time


Relay Operating time at TMS=1.0
0.1 / 2.27
0.044

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

Prepared
JS
PMCC-2

25.10.2016

0
Checked
PCP

Approved
PRM

Load current is calculated considering 2 MVA

0.02
0.14

Approved
PRM

Approved
PRM

SM>10,PSM=10)

Approved
PRM

SM>10,PSM=10)

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

LARSEN & TOUBRO LTD

GROUP 1 OVERCURRENT SETTINGS


i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input

LARSEN & TOUBRO LTD

i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

4.0

RELAY SETTING

4.1

SETTINGS FOR IDMT OC-51


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting
Setting Adopted
ii) Time Delay

50

LARSEN & TOUBRO LTD

4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

50N

LARSEN & TOUBRO LTD

iv) TMS Required

LARSEN & TOUBRO LTD

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:
:
:

:
:

:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:

:
:
:

:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:

:
:

:
:
:
:
:
:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

:
:
I>1 TMS

:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-2

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

415

43750

0.07

2782.41

2000.00

KVA

3200

From ETAP

Note: Load current is calcu

5P20

MICOM-P14
Schneider
Normal Inverse
* Setting range are taken from Relay Manual

a
b

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

Prepared
JS
PMCC-2

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured

Checked
PCP

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

Prepared
JS
PMCC-2

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Checked
PCP

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

1.1 * Full Load load current /CT Ratio


0.96
0.96

In

Fault current /(CT Ratio * PS)


43750/(3200/1*0.96)
14.2

0.14
PSM^0.02 - 1
2.57

(for PSM>10,PSM=10)
S

Desired Operating time


Relay Operating time at TMS=1.0
0.07 / 2.57
0.027
Rated fault Current/CTR
13.671875
13.672
13.672
0.10

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

0.10 times of Full load current/CTR


0.09
0.09
0.09

In

0.1

0.1

0.10*CT primary current


320.00
Iearthfault/CT ratio
0.1
37530

Fault current /(CT Ratio * PS)


37530/(3200/1*0.1)
117.3
0.14
PSM^0.02 - 1
2.27

(for PSM>10,PSM=10)
S

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-2

Desired Operating time


Relay Operating time at TMS=1.0
0.1 / 2.27
0.044

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

Prepared
JS
PMCC-2

25.10.2016

0
Checked
PCP

Approved
PRM

Load current is calculated considering 2 MVA

0.02
0.14

Approved
PRM

Approved
PRM

SM>10,PSM=10)

Approved
PRM

SM>10,PSM=10)

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

i) V> Measurement Mode


ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

17930
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
IEC
E
0.025-1
Inverse,
0=Disabled
UK LT
,1=DT,2=I
Inverse,
EC
UK S
Inverse,3=I
Rectifier,
EC
V
RI, IEEE
Inverse,4=I
M Inverse,
0.05-32In
EC
EV
IEEE
Inverse,5=
Inverse,
UK
IEEELTE
0Inverse,6=
to 100 US
Inverse,
UK
Inverse, US
Rectifier,7
ST Inverse
=RI,8=IEE
Measured
EM
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:
:

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17930/(200/1*0.96)

93.4

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

LARSEN & TOUBRO LTD

GROUP 1 OVERCURRENT SETTINGS


i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

ii) I2>Direction

iii) I2>current set


iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input

LARSEN & TOUBRO LTD

i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

4.0

RELAY SETTING

4.1

SETTINGS FOR IDMT OC-51


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting
Setting Adopted
ii) Time Delay

50

LARSEN & TOUBRO LTD

4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

50N

LARSEN & TOUBRO LTD

iv) TMS Required

LARSEN & TOUBRO LTD

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

:
:
:
:
:

:
:

:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

:
:
:

:
:

:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

:
:
:

:
:

:
:
:
:
:
:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:
:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

:
:
I>1 TMS

:
:

Project
Title

L & T Doc No

Date
Revision
Prepared
JS
PMCC-1 Incomer-3

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-1 Incomer-3

415

39800

0.07

2782.41

2000.00

KVA

3200

From ETAP

Note: Load current is calcu

5P20

MICOM-P14
Schneider
Normal Inverse
* Setting range are taken from Relay Manual

a
b

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

Prepared
JS
PMCC-1 Incomer-3

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured

Checked
PCP

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

Prepared
JS
PMCC-1 Incomer-3

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Checked
PCP

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-1 Incomer-3

1.1 * Full Load load current /CT Ratio


0.96
0.96

In

Fault current /(CT Ratio * PS)


39800/(3200/1*0.96)
13.0

0.14
PSM^0.02 - 1
2.66

(for PSM>10,PSM=10)
S

Desired Operating time


Relay Operating time at TMS=1.0
0.07 / 2.66
0.026
Rated fault Current/CTR
12.4375
12.438
12.438
0.10

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-1 Incomer-3

0.10 times of Full load current/CTR


0.09
0.09
0.09

In

0.1

0.1

0.10*CT primary current


320.00
Iearthfault/CT ratio
0.1
37530

Fault current /(CT Ratio * PS)


37530/(3200/1*0.1)
117.3
0.14
PSM^0.02 - 1
2.27

(for PSM>10,PSM=10)
S

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

25.10.2016

0
Checked
PCP

Prepared
JS
PMCC-1 Incomer-3

Desired Operating time


Relay Operating time at TMS=1.0
0.1 / 2.27
0.044

PATLIPUTRA GRINDING UNIT

:
Relay Setting calculations
:

Prepared
JS
PMCC-1 Incomer-3

25.10.2016

0
Checked
PCP

Approved
PRM

Load current is calculated considering 2 MVA

0.02
0.14

Approved
PRM

Approved
PRM

SM>10,PSM=10)

Approved
PRM

SM>10,PSM=10)

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) v>1 Function


iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

17980
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
0=Disabled
IEC
E
0.025-1
,1=DT,2=I
Inverse,
EC
UK SLT
Inverse,3=I
Inverse,
EC
UK V
Inverse,4=I
Rectifier,
EC
E
RI, IEEE
Inverse,5=
M Inverse,
0.05-32In
UK
IEEELTV
Inverse,6=
Inverse,
0IEEE
to 100
UK
E
Rectifier,7
Inverse, US
=RI,8=IEE
Measured
Inverse, US
E
STMInverse
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse
Phase-Phase or Phase-neutral

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:

Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17980/(200/1*0.96)

93.6

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

415

39830

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

39830/(3200/1*0.96)

13.0

:
:

0.14
PSM^0.02 - 1
0.07

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


12.446875
12.447
12.447
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-2

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-2

(for PSM>10,PSM=10)

Approved
PRM

C-2

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) v>1 Function


iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

18080
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
0=Disabled
IEC
E
0.025-1
,1=DT,2=I
Inverse,
EC
UK SLT
Inverse,3=I
Inverse,
EC
UK V
Inverse,4=I
Rectifier,
EC
E
RI, IEEE
Inverse,5=
M Inverse,
0.05-32In
UK
IEEELTV
Inverse,6=
Inverse,
0IEEE
to 100
UK
E
Rectifier,7
Inverse, US
=RI,8=IEE
Measured
Inverse, US
E
STMInverse
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse
Phase-Phase or Phase-neutral

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:

Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

18080/(200/1*0.96)

94.2

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

415

42000

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

42000/(3200/1*0.96)

13.7

:
:

0.14
PSM^0.02 - 1
0.07

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


13.125
13.125
13.125
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-2

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-2

(for PSM>10,PSM=10)

Approved
PRM

C-2

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

415

47400

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

47400/(3200/1*0.96)

15.4

:
:

0.14
PSM^0.02 - 1
0.06

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


14.8125
14.813
14.813
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-2

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-2

(for PSM>10,PSM=10)

Approved
PRM

C-2

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) v>1 Function


iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

17890
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
0=Disabled
IEC
E
0.025-1
,1=DT,2=I
Inverse,
EC
UK SLT
Inverse,3=I
Inverse,
EC
UK V
Inverse,4=I
Rectifier,
EC
E
RI, IEEE
Inverse,5=
M Inverse,
0.05-32In
UK
IEEELTV
Inverse,6=
Inverse,
0IEEE
to 100
UK
E
Rectifier,7
Inverse, US
=RI,8=IEE
Measured
Inverse, US
E
STMInverse
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse
Phase-Phase or Phase-neutral

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:

Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17890/(200/1*0.96)

93.2

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

415

39740

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

39740/(3200/1*0.96)

12.9

:
:

0.14
PSM^0.02 - 1
0.07

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


12.41875
12.419
12.419
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-2

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-2

(for PSM>10,PSM=10)

Approved
PRM

C-2

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) v>1 Function


iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

17890
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
0=Disabled
IEC
E
0.025-1
,1=DT,2=I
Inverse,
EC
UK SLT
Inverse,3=I
Inverse,
EC
UK V
Inverse,4=I
Rectifier,
EC
E
RI, IEEE
Inverse,5=
M Inverse,
0.05-32In
UK
IEEELTV
Inverse,6=
Inverse,
0IEEE
to 100
UK
E
Rectifier,7
Inverse, US
=RI,8=IEE
Measured
Inverse, US
E
STMInverse
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse
Phase-Phase or Phase-neutral

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:

Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17890/(200/1*0.96)

93.2

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

415

39890

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

39890/(3200/1*0.96)

13.0

:
:

0.14
PSM^0.02 - 1
0.07

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


12.465625
12.466
12.466
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-2

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-2

(for PSM>10,PSM=10)

Approved
PRM

C-2

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) v>1 Function


iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

17890
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
0=Disabled
IEC
E
0.025-1
,1=DT,2=I
Inverse,
EC
UK SLT
Inverse,3=I
Inverse,
EC
UK V
Inverse,4=I
Rectifier,
EC
E
RI, IEEE
Inverse,5=
M Inverse,
0.05-32In
UK
IEEELTV
Inverse,6=
Inverse,
0IEEE
to 100
UK
E
Rectifier,7
Inverse, US
=RI,8=IEE
Measured
Inverse, US
E
STMInverse
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse
Phase-Phase or Phase-neutral

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:

Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17890/(200/1*0.96)

93.2

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

4.0

RELAY SETTING

LARSEN & TOUBRO LTD

4.1

SETTINGS FOR IDMT (51)


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=0.025

4.2

INSTANTANEOUS ELEMENT(50)
i) Current Setting
Setting Adopted
ii) Time Delay

4.3

EARTH FAULT ELEMENT(50N)


i) Earth fault setting

Earth fault setting Adopted

LARSEN & TOUBRO LTD

ii) Operating time ( Definite time characteristic )

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

415

39890

0.07

2782.41

2000.00

KVA

3200

MICOM-P141

Schneider

Normal Inverse
* Setting range are taken from Relay Manual

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

:
:
:

1.1 * Full Load load current /CT Ratio


0.96
0.96
In

Fault current /(CT Ratio * PS)

39890/(3200/1*0.96)

13.0

:
:

0.14
PSM^0.02 - 1
0.07

:
:
I3>current set
I3>time delay

IN2>Current

:
:

Rated fault Current/CTR


12.465625
12.466
12.466
0.10
S

:
:
:

0.10 times of Full load current/CTR


0.09
0.09

0.09

In

Project

Title

SK Mines

Relay Setting calculations


L & T Doc No

Date

Revision

1/3/2017
0
Checked
PCP

Prepared
JS
Relay settings of PMCC-2

IN2> time delay

0.1

Relay Setting calculations

Checked
PCP

Approved
PRM

C-2

From ETAP
For Minimum TMS of the relay
Note: Load current is calculated considering 2000 KVA

5P20

a
b
* Setting range are taken from Relay Manual

0.02
0.14

Relay Setting calculations

Checked
PCP

C-2

(for PSM>10,PSM=10)

Approved
PRM

C-2

Relay Setting calculations

Checked
PCP

Approved
PRM

rent is calculated considering 2000 KVA

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load current LV Side


Full load current HT Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

ii) v>1 Function


iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.03

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 6.6 kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 6.6 kV transformer-2 outgoing

6600

:
:

17890
0.170

A
0.433kv O/C Relay operating time+ time grading

39760

:
:

2782.50
174.96

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoingNon-

:
:
:

:
:
:
:
:
:

:
:

directional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
0=Disabled
IEC
E
0.025-1
,1=DT,2=I
Inverse,
EC
UK SLT
Inverse,3=I
Inverse,
EC
UK V
Inverse,4=I
Rectifier,
EC
E
RI, IEEE
Inverse,5=
M Inverse,
0.05-32In
UK
IEEELTV
Inverse,6=
Inverse,
0IEEE
to 100
UK
E
Rectifier,7
Inverse, US
=RI,8=IEE
Measured
Inverse, US
E
STMInverse
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse
Phase-Phase or Phase-neutral

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

:
:
:
:
:
:
:

Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

1.1 * Full Load load current /CT Ratio

0.96

0.96
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*0.96)
13.0

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

2.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.064

Fault current /(CT Ratio * PS)

17890/(200/1*0.96)

93.2

0.14
PSM^0.02 - 1

0.15

:
:

3250.000
1749.602
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.087480114

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 6.6 kV transformer-2 outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Motor rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0
4.1

RELAY SETTING
SETTINGS FOR THERMAL OVER LOAD (49)
Ambient temperature(Tamb)
Internal FLC
Protection unit scaling factor (PU)
Safe stalling time
Weighing factor (p)
Time constant multiplier (Kc)
Prior alarm a
Restart Inhibit level

4.2

Motor start Supervision


Motor start-up A
Motor start -up time
Lock rotor time
Operation

4.3

Motor stall protection


Operation
Start value
operation delay time

4.4

Negative sequence protection


Pickup value
Operating curve type
Operating delay time

4.5

Over current setting


Over Current Setting
i) I>1 current setting

ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

50N

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
540 kW motor out going feeder

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:
:
:
:
:
:
:
:

:
:
:
:
:

:
:

:
:
:

:
:
:

:
:

:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:
:

:
:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
540 kW motor out going feeder

6600
16560
0.07
56.00
540.00

100
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

50
FLC x (1-[(Tamb-40)/100]
50.4
[IN1/INM]x[INR/IN2]
1.79
12 seconds
50%
Tcooling/Theating
6
90%
40%

Locked rotor current/CT ratio


4.032
7 sec
14 sec
On

On
4.032
8

0.13
Inverse curve
3000 mS

1.1 * Full Load load current /CT Ratio


0.62
0.62

Fault current /(CT Ratio * PS)


16560/(100/1*0.62)
267.1

0.14
PSM^0.02 - 1
2.27
Desired Operating time

Relay Operating time at TMS=1.0


0.07 / 2.27
0.031

130 % of Motor starting current


524.16
5.242
5.242
0.10

0.10 times of Full load current/CTR


0.06
0.06
0.06
0.7

0.7

0.10*CT primary current


10.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(100/1*0.1)
62.5
0.14

PSM^0.02 - 1
2.27
Desired Operating time
Relay Operating time at TMS=1.0
0.7 / 2.27
0.309

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A

From ETAP

S
A

Note: From motor data sheet

KW

5P10

a
b

0.02
0.14

Refer Relay manual

Refer Motor data sheet

Refer Motor catalogue


Refer Data sheet
Refer Data sheet

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)

V
S

V
S

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Motor rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0
4.1

RELAY SETTING
SETTINGS FOR THERMAL OVER LOAD (49)
Ambient temperature(Tamb)
Internal FLC
Protection unit scaling factor (PU)
Safe stalling time
Weighing factor (p)
Time constant multiplier (Kc)
Prior alarm a
Restart Inhibit level

4.2

Motor start Supervision


Motor start-up A
Motor start -up time
Lock rotor time
Operation

4.3

Motor stall protection


Operation
Start value
operation delay time

4.4

Negative sequence protection


Pickup value
Operating curve type
Operating delay time

4.5

Over current setting


Over Current Setting
i) I>1 current setting

ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM

50N

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
2850kW motor out going feeder

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:
:
:
:
:
:
:
:

:
:
:
:
:

:
:
:

:
:
:

:
:
:

:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
2850kW motor out going feeder

6600
15630
0.07
304.90
540.00

350
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

50
FLC x (1-[(Tamb-40)/100]
274.41
[IN1/INM]x[INR/IN2]
1.15
7 seconds
50%
Tcooling/Theating
5.05
90%
40%

Locked rotor current/CT ratio


6.27
7 sec
On

On
6.27
4 sec

0.24*In/CT Ratio
0.21
Inverse curve
3000 msec

1.1 * Full Load load current /CT Ratio


0.96
0.96

Fault current /(CT Ratio * PS)


15630/(350/1*0.96)
46.5

0.14
PSM^0.02 - 1
2.27

Desired Operating time


Relay Operating time at TMS=1.0
0.07 / 2.27
0.031

130 % of Motor starting current


2853.864
8.154
8.154
0.10

0.10 times of Full load current/CTR


0.09
0.09
0.09
0.7

0.7

0.10*CT primary current


35.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(350/1*0.1)
17.9

0.14
PSM^0.02 - 1
2.36
Desired Operating time
Relay Operating time at TMS=1.0
0.7 / 2.36
0.297

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A

From ETAP

S
A

Note: From motor data sheet

KW

5P20

a
b

0.02
0.14

Refer Relay manual


Refer Relay manual
Refer Motor data sheet

Refer Relay manual

Refer Motor catalogue


For Rehtostat starting same can be observed at site
Refer Data sheet

It should be greater than motor starting time and less than safe stalling time

Refer relay manual

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ess than safe stalling time

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Motor rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0
4.1

RELAY SETTING
SETTINGS FOR THERMAL OVER LOAD (49)
Ambient temperature(Tamb)
Internal FLC
Protection unit scaling factor (PU)
Safe stalling time
Weighing factor (p)
Time constant multiplier (Kc)
Prior alarm a
Restart Inhibit level

4.2

Motor start Supervision


Motor start-up A
Motor start -up time
Lock rotor time
Operation

4.3

Motor stall protection


Operation
Start value
operation delay time

4.4

Negative sequence protection


Pickup value
Operating curve type
Operating delay time

4.5

Over current setting


Over Current Setting
i) I>1 current setting

ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM

50N

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
375 kW motor out going feeder

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:
:
:
:
:
:
:
:

:
:
:
:
:

:
:
:

:
:
:

:
:
:

:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
375 kW motor out going feeder

6600
16980
0.07
40.50
375.00

50
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

50
FLC x (1-[(Tamb-40)/100]
36.45
[IN1/INM]x[INR/IN2]
1.23
15 seconds
50%
Tcooling/Theating
4
90%
40%

Locked rotor current/CT ratio


5.83
15 sec
On

On
5.83
4 sec

0.24*In/CT Ratio
0.19
Inverse curve
3000 msec

1.1 * Full Load load current /CT Ratio


0.89
0.89

Fault current /(CT Ratio * PS)


16980/(50/1*0.89)
381.6

0.14
PSM^0.02 - 1
2.27

Desired Operating time


Relay Operating time at TMS=1.0
0.07 / 2.27
0.031

130 % of Motor starting current


379.08
7.582
7.582
0.10

0.10 times of Full load current/CTR


0.08
0.08
0.08
0.7

0.7

0.10*CT primary current


5.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(50/1*0.1)
125.0

0.14
PSM^0.02 - 1
2.27
Desired Operating time
Relay Operating time at TMS=1.0
0.7 / 2.27
0.309

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A

From ETAP

S
A

Note: From motor data sheet

KW

5P20

a
b

0.02
0.14

Refer Relay manual


Refer Relay manual
Refer Motor data sheet

Refer Relay manual

Refer Motor catalogue


For Rehtostat starting same can be observed at site
Refer Data sheet

It should be greater than motor starting time and less than safe stalling time

Refer relay manual

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ess than safe stalling time

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Motor rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0
4.1

RELAY SETTING
SETTINGS FOR THERMAL OVER LOAD (49)
Ambient temperature(Tamb)
Internal FLC
Protection unit scaling factor (PU)
Safe stalling time
Weighing factor (p)
Time constant multiplier (Kc)
Prior alarm a
Restart Inhibit level

4.2

Motor start Supervision


Motor start-up A
Motor start -up time
Lock rotor time
Operation

4.3

Motor stall protection


Operation
Start value
operation delay time

4.4

Negative sequence protection


Pickup value
Operating curve type
Operating delay time

4.5

Over current setting


Over Current Setting
i) I>1 current setting

ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM

50N

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
200 kW motor out going feeder

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:
:
:
:
:
:
:
:

:
:
:
:
:

:
:
:

:
:
:

:
:
:

:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
200 kW motor out going feeder

6600
16410
0.07
22.50
200.00

50
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

50
FLC x (1-[(Tamb-40)/100]
20.25
[IN1/INM]x[INR/IN2]
2.22
15 seconds
50%
Tcooling/Theating
4
90%
40%

Locked rotor current/CT ratio


3.24

On

On
3.24
4 sec

0.24*In/CT Ratio
0.11
Inverse curve
3000 msec

1.1 * Full Load load current /CT Ratio


0.5
0.50

Fault current /(CT Ratio * PS)


16410/(50/1*0.5)
656.4

0.14
PSM^0.02 - 1
2.27

Desired Operating time


Relay Operating time at TMS=1.0
0.07 / 2.27
0.031

130 % of Motor starting current


210.6
4.212
4.212
0.10

0.10 times of Full load current/CTR


0.05
0.05
0.05
0.7

0.7

0.10*CT primary current


5.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(50/1*0.1)
125.0

0.14
PSM^0.02 - 1
2.27
Desired Operating time
Relay Operating time at TMS=1.0
0.7 / 2.27
0.309

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A

From ETAP

S
A

Note: From motor data sheet

KW

5P20

a
b

0.02
0.14

Refer Relay manual


Refer Relay manual
Refer Motor data sheet

Refer Relay manual

Refer Motor catalogue


For Rehtostat starting same can be observed at site
Refer Data sheet

It should be greater than motor starting time and less than safe stalling time

Refer relay manual

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ess than safe stalling time

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Motor rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0
4.1

RELAY SETTING
SETTINGS FOR THERMAL OVER LOAD (49)
Ambient temperature(Tamb)
Internal FLC
Protection unit scaling factor (PU)
Safe stalling time
Weighing factor (p)
Time constant multiplier (Kc)
Prior alarm a
Restart Inhibit level

4.2

Motor start Supervision


Motor start-up A
Motor start -up time
Lock rotor time
Operation

4.3

Motor stall protection


Operation
Start value
operation delay time

4.4

Negative sequence protection


Pickup value
Operating curve type
Operating delay time

4.5

Over current setting


Over Current Setting
i) I>1 current setting

ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT


i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

50N

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
900 kW motor out going feeder

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:
:
:
:
:
:
:
:

:
:
:
:
:

:
:
:

:
:
:

:
:
:

:
:

I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:
:
:

:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
900 kW motor out going feeder

6600
16960
0.07
103.90
900.00

150
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

50
FLC x (1-[(Tamb-40)/100]
93.51
[IN1/INM]x[INR/IN2]
1.44
8 seconds
50%
Tcooling/Theating
5.05
90%
40%

Locked rotor current/CT ratio


4.99
8 Sec
On
On
4.99
4 sec

0.24*In/CT Ratio
0.17
Inverse curve
3000 msec

1.1 * Full Load load current /CT Ratio


0.76
0.76

Fault current /(CT Ratio * PS)


16960/(150/1*0.76)
148.8

0.14
PSM^0.02 - 1
2.27
Desired Operating time
Relay Operating time at TMS=1.0
0.07 / 2.27

0.031

130 % of Motor starting current


972.504
6.483
6.483
0.10

0.10 times of Full load current/CTR


0.07
0.07
0.07
0.7

0.7

0.10*CT primary current


15.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(150/1*0.1)
41.7
0.14
PSM^0.02 - 1
2.27

Desired Operating time


Relay Operating time at TMS=1.0
0.7 / 2.27
0.309

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A

From ETAP

S
A

Note: From motor data sheet

KW

5P20

a
b

0.02
0.14

Refer Relay manual


Refer Relay manual
Refer Motor data sheet

Refer Relay manual

Refer Motor catalogue


For Rehtostat starting same can be observed at site
Refer Data sheet

It should be greater than motor starting time and less than safe stalling time

Refer relay manual

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ess than safe stalling time

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical Bus Coupler AT PMCC-1


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)
2.0

Full load current


CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range
INVERSE (51)
i) Current setting (PHLPTOC)
ii) Time Setting (PHLPTOC)
HIGH SET (50)
i) Current setting (PHIPTOC)
ii) Time Setting (PHIPTOC)
Earth-Fault (51N)
i) Current Setting (EFLPTOC)
ii) Time Setting (EFLPTOC)
Earth - Fault High Set (50N)
i) Current Setting (EFIPTOC)
ii) Time Setting (EFIPTOC)

e)
4.0

Nominal Current
RELAY SETTING

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical Bus Coupler AT PMCC-1


4.1

INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)

Current setting adopted

51

PHLPTOC

** Note 1: Please refer Fault current calculations ( L & T Doc No: O12117-E-BM-CS-DD-8014)

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical Bus Coupler AT PMCC-1

FAULT AT ITS OWN TERMINAL


c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

4.2
a)

b)
4.3
a)

b)

INSTANTANEOUS ELEMENT
Current Setting

50

Setting Adopted
Time Delay
EARTH FAULT ELEMENT

PHLPTOC

PHIPTOC
50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

ical Bus Coupler AT PMCC-1

415

39840

0.45

2226

2500

REF 615 H

ABB

Normal Inverse

0.05 - 5.00 x In

0.05 - 15.00

1.00 - 40.00 x In

40 - 200000 ms

0.010 - 5.000 x In

0.05 - 15.00

1.00 - 40.00 x In

20 - 200000 ms

** (Refer Note 1)

5P20

0.02
0.14

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

ical Bus Coupler AT PMCC-1

1.2 * Full Load load current /CT Ratio

1.2*2226/2500

1.068

1.07

17-E-BM-CS-DD-8014)

In

Approved
NH

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

ical Bus Coupler AT PMCC-1

Fault current /(CT Ratio * PS)

39840/(2500/1*1.07)

14.9

0.14
PSM^0.02 - 1

(for PSM>20,PSM=20)

2.52

Desired Operating time


Relay Operating time at TMS=1.0

0.45 / 2.52

0.1784

LV Rated fault Current/CTR


39840/2500
15.936
16
0.1
S

0.10 times of Full load current/CTR

0.10*2226/2500

0.08904

0.1

In

0.08

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER AT MCC-1 @


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)
2.0

Full load current


CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range
INVERSE (51)
i) Current setting (PHLPTOC)
ii) Time Setting (PHLPTOC)
HIGH SET (50)
i) Current setting (PHIPTOC)
ii) Time Setting (PHIPTOC)
Earth-Fault (51N)
i) Current Setting (EFLPTOC)
ii) Time Setting (EFLPTOC)
Earth - Fault High Set (50N)
i) Current Setting (EFIPTOC)
ii) Time Setting (EFIPTOC)

e)
4.0

Nominal Current
RELAY SETTING

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER AT MCC-1 @


4.1

INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)

Current setting adopted

51

PHLPTOC

** Note 1: Please refer Fault current calculations ( L & T Doc No: O12117-E-BM-CS-DD-8014)

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER AT MCC-1 @

FAULT AT ITS OWN TERMINAL


c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

4.2
a)

b)
4.3
a)

b)

INSTANTANEOUS ELEMENT
Current Setting

50

Setting Adopted
Time Delay
EARTH FAULT ELEMENT

PHLPTOC

PHIPTOC
50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

NCOMER FEEDER AT MCC-1 @ WT-SS-1

415

39840

0.250

1250

1250

REF 615 H

ABB

Normal Inverse

0.05 - 5.00 x In

0.05 - 15.00

1.00 - 40.00 x In

40 - 200000 ms

0.010 - 5.000 x In

0.05 - 15.00

1.00 - 40.00 x In

20 - 200000 ms

** (Refer Note 1)

5P20

0.02
0.14

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

NCOMER FEEDER AT MCC-1 @ WT-SS-1

1.2 * Full Load load current /CT Ratio

1.2*1250/1250

1.2

1.2

17-E-BM-CS-DD-8014)

In

Approved
NH

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

NCOMER FEEDER AT MCC-1 @ WT-SS-1

Fault current /(CT Ratio * PS)

39840/(1250/1*1.2)

26.6

0.14
PSM^0.02 - 1

(for PSM>20,PSM=20)

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.25 / 2.27

0.1103

LV Rated fault Current/CTR


39840/1250
31.872
20
0.06
S

0.10 times of Full load current/CTR

0.10*1250/1250

0.1

0.1

In

0.04

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical Bus Coupler AT MCC-1


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)
2.0

Full load current


CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range
INVERSE (51)
i) Current setting (PHLPTOC)
ii) Time Setting (PHLPTOC)
HIGH SET (50)
i) Current setting (PHIPTOC)
ii) Time Setting (PHIPTOC)
Earth-Fault (51N)
i) Current Setting (EFLPTOC)
ii) Time Setting (EFLPTOC)
Earth - Fault High Set (50N)
i) Current Setting (EFIPTOC)
ii) Time Setting (EFIPTOC)

e)
4.0

Nominal Current
RELAY SETTING

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical Bus Coupler AT MCC-1


4.1

INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)

Current setting adopted

51

PHLPTOC

** Note 1: Please refer Fault current calculations ( L & T Doc No: O12117-E-BM-CS-DD-8014)

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical Bus Coupler AT MCC-1

FAULT AT ITS OWN TERMINAL


c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

4.2
a)

b)
4.3
a)

b)

INSTANTANEOUS ELEMENT
Current Setting

50

Setting Adopted
Time Delay
EARTH FAULT ELEMENT

PHLPTOC

PHIPTOC
50 N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

pical Bus Coupler AT MCC-1

415

39840

0.10

1250

1250

REF 615 H

ABB

Normal Inverse

0.05 - 5.00 x In

0.05 - 15.00

1.00 - 40.00 x In

40 - 200000 ms

0.010 - 5.000 x In

0.05 - 15.00

1.00 - 40.00 x In

20 - 200000 ms

** (Refer Note 1)

5P20

0.02
0.14

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

pical Bus Coupler AT MCC-1

1.2 * Full Load load current /CT Ratio

1.2*1250/1250

1.2

1.2

17-E-BM-CS-DD-8014)

In

Approved
NH

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

pical Bus Coupler AT MCC-1

Fault current /(CT Ratio * PS)

39840/(1250/1*1.2)

26.6

0.14
PSM^0.02 - 1

(for PSM>20,PSM=20)

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.1 / 2.27

0.0441

LV Rated fault Current/CTR


39840/1250
31.872
20
0.04
S

0.10 times of Full load current/CTR

0.10*1250/1250

0.1

0.1

In

0.02

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER TO STACKE


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)
2.0

Full load current


CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range
INVERSE (51)
i) Current setting (PHLPTOC)
ii) Time Setting (PHLPTOC)
HIGH SET (50)
i) Current setting (PHIPTOC)
ii) Time Setting (PHIPTOC)
Earth-Fault (51N)
i) Current Setting (EFLPTOC)
ii) Time Setting (EFLPTOC)
Earth - Fault High Set (50N)
i) Current Setting (EFIPTOC)
ii) Time Setting (EFIPTOC)

e)
4.0

Nominal Current
RELAY SETTING

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER TO STACKE


INVERSE ELEMENT
a)

Over Current Setting (Calculated)

b)

Current setting adopted

51

PHLPTOC

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER TO STACKE


4.1

FAULT AT ITS OWN TERMINAL

a)

Current setting at Fault current

b)

Relay Operating time at TMS=1.0

c)

TMS Required

4.2
a)

b)
4.3
a)

b)

INSTANTANEOUS ELEMENT
Current Setting

50

Setting Adopted
Time Delay
EARTH FAULT ELEMENT

PHLPTOC

PHIPTOC
51N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

V INCOMER FEEDER TO STACKER MCC

415

20868

0.20

1043.43 A

1250

REF 615 H

ABB

Normal Inverse

0.05 - 5.00 x In

0.05 - 15.00

1.00 - 40.00 x In

40 - 200000 ms

0.010 - 5.000 x In

0.05 - 15.00

1.00 - 40.00 x In

20 - 200000 ms

5P20

0.02
0.14

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

V INCOMER FEEDER TO STACKER MCC

1.2 * Full Load load current /CT Ratio

1.2*1043/1250

1.0017

In

Approved
NH

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

V INCOMER FEEDER TO STACKER MCC

Fault current /(CT Ratio * PS)

20868/(1250/1*1)

16.7

0.14
PSM^0.02 - 1

(for PSM>20,PSM=20)

2.42

Desired Operating time


Relay Operating time at TMS=1.0

0.2 / 2.42

0.0827

LV Rated fault Current/CTR


33615/2500
16.6944
17
0.04
S

0.10 times of Full load current/CTR

0.10*1250/1250

0.08347

0.1

In

0.02

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER TO RECLAIM


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)
2.0

Full load current


CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range
INVERSE (51)
i) Current setting (PHLPTOC)
ii) Time Setting (PHLPTOC)
HIGH SET (50)
i) Current setting (PHIPTOC)
ii) Time Setting (PHIPTOC)
Earth-Fault (51N)
i) Current Setting (EFLPTOC)
ii) Time Setting (EFLPTOC)
Earth - Fault High Set (50N)
i) Current Setting (EFIPTOC)
ii) Time Setting (EFIPTOC)

e)
4.0

Nominal Current
RELAY SETTING

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER TO RECLAIM


INVERSE ELEMENT
a)

Over Current Setting (Calculated)

b)

Current setting adopted

51

PHLPTOC

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Typical 415V INCOMER FEEDER TO RECLAIM


4.1

FAULT AT ITS OWN TERMINAL

a)

Current setting at Fault current

b)

Relay Operating time at TMS=1.0

c)

TMS Required

4.2
a)

b)
4.3
a)

b)

INSTANTANEOUS ELEMENT
Current Setting

50

Setting Adopted
Time Delay
EARTH FAULT ELEMENT

PHLPTOC

PHIPTOC
50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

INCOMER FEEDER TO RECLAIMER MCC

415

27824

0.20

1391.25 A

1600

REF 615 H

ABB

Normal Inverse

0.05 - 5.00 x In

0.05 - 15.00

1.00 - 40.00 x In

40 - 200000 ms

0.010 - 5.000 x In

0.05 - 15.00

1.00 - 40.00 x In

20 - 200000 ms

5P20

0.02
0.14

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

INCOMER FEEDER TO RECLAIMER MCC

1.2 * Full Load load current /CT Ratio

1.2*1250/1250

1.04343

1.05

In

Approved
NH

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Prepared
UKB/DVKM

Approved
NH

INCOMER FEEDER TO RECLAIMER MCC

Fault current /(CT Ratio * PS)

27824/(1600/1*1.05)

16.6

0.14
PSM^0.02 - 1

(for PSM>20,PSM=20)

2.42

Desired Operating time


Relay Operating time at TMS=1.0

0.2 / 2.42

0.0825

:
:
:

LV Rated fault Current/CTR


33615/2500
17.3901
18
0.04
S

0.10 times of Full load current/CTR

0.10*1250/1250

0.08695

0.1

In

0.02

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Prepared
UKB/DVKM

945 KW (Typical ) Motor Feeder Calculatio


Motor Data
1)
2)
3)
4)
5)
6)
7)
8)
9)

Rating
Rated Voltage
Frequency
Starting Method
Full Load Current (In)
Starting Current
Locked Rotor Current
Starting time
Stall time

:
:
:
:
:
:
:
:
:

945 KW
6.6 kV
50 Hz
DOL
96
600 % In
600%
2 Sec @ 100 % RV
Hot : 20
Cold : 25

Type
Make
Curve
Setting Range

:
:
:

REM 615 C
ABB
Standard Inverse

Relay Data
1)
2)
3)
4)

Current Setting
A)

INVERSE (51)
i) Current Setting(51P)

B)

ii) Time setting(51P)


HIGH SET (50)
i) Current Setting (50P)
ii) Time setting (50P)

C)

Earth - Fault High Set (50G)


i) Current Setting (50G)
ii) Time setting (50G)

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Prepared
UKB/DVKM

D)

Negative Sequence Protection (46M)


Definite Time
i) Current Setting (46M)
ii) Time setting (46M)

E)

Locked Rotor Protection (51LR)


i) Current Setting
ii) Time setting

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Prepared
UKB/DVKM

Phase CT Details
1)
2)

Primary
Secondary

CBCT Details
1)
2)

Primary
Secondary

Calculations
1) 51

Pickup

2) 50

High Set Curent Setting

Time delay

3) 50N

High Set earth fault Settting

Time delay

4) 46

Definite time current setting


Definite time setting

5) 51LR

Current Setting
Time Delay

LARSEN & TOUBRO LIMITED


EDRC - CHENNAI

Project
Title
L & T Doc No
BIDCO Doc No
Date
Revision
Prepared
UKB/DVKM

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

UKB/DVKM

r Feeder Calculations

Sec
Sec

0.05-5 In

0.8-10 s

0.1-40 In

40 ms - 200 s

0.1-40 In

40 ms - 200 s

Approved
NH

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

UKB/DVKM

0.01-0.5 In

100 ms - 120 s

0.01-10 In

100 ms - 120 s

Approved
NH

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

UKB/DVKM

:
:

125
1

A
A

:
:

50
1

A
A

:
:

1.1*FLC/CTR
1.1*96/125
0.84

1.3*Starting Current/CTR

5.99
1.3*6*96/125
0.05 S

:
:

0.05*FLC/CBCT ratio
0.05*96/50
0.096

0.05 S

:
:

0.1 In
3S

:
:

4.6 In
0.5 S

Approved
NH

UKB/DVKM

:
:
:
:
:
:

3 X 660 MW Lalitpur STPP, CHP


Relay Setting calculations
O12117-E-BM-CS-DD-8150
BE-LAL-EEV-102-R-0011
42738
2
Checked
HRP/GM

Approved
NH

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0

RELAY SETTING

4.1

SETTINGS FOR IDMT OC-51


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT

50N

i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
6.6kV Incomer

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:

:
:
:

:
:

:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
6.6kV Incomer

6600
11210
0.40
1749.55
20.00

2000
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

1.1 * Full Load load current /CT Ratio


0.96
0.96

Fault current /(CT Ratio * PS)


11210/(2000/1*0.96)
5.8

0.14
PSM^0.02 - 1

3.90
Desired Operating time
Relay Operating time at TMS=1.0
0.4 / 3.90
0.103

Rated fault Current/CTR


5.605
5.605
5.605
0.20

0.10 times of Full load current/CTR


0.09
0.09
0.09
0.7

0.7

0.10*CT primary current


200.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(2000/1*0.1)
3.1

0.14
PSM^0.02 - 1
6.07
Relay Operating time at TMS=1.0
0.7 / 6.07
0.115

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

Desired Operating time

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PCP

Approved
PRM

V
A
S
A

From ETAP
Down stream breaker operating time+ time grading
Note: Load current is calculated considering 20 MVA

MVA

5P20

0.02
0.14

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ting time+ time grading

lculated considering 20 MVA

LARSEN & TOUBRO LTD

Relay setting of 33kV tran


1.0

SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal (6.6kV bus)


Desired Operating time

c)

Fault current - Downstream

d)

Full load currentHV Side


Full load current LV Side

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range*
Group 1 settings

i) I>1 Function
i) I>1 Current setting
ii) I>1 TMS

i) I2> Function

LARSEN & TOUBRO LTD

Relay setting of 33kV tran

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)

LARSEN & TOUBRO LTD

Relay setting of 33kV tran

i) V> Measurement Mode


ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay

LARSEN & TOUBRO LTD

Relay setting of 33kV tran


4.0
4.1

RELAY SETTING
INVERSE ELEMENT

a)

Over Current Setting (Calculated)

b)
c)

Current setting adopted


Fault current reflected to HV side

c)

Current setting at Fault current

d)

Relay Operating time at TMS=1.0

e)

TMS Required

51

I1>current settings

I>1 TMS

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.064

4.2

INSTANTANEOUS ELEMENT
fault Considered for settings
case 2 Inrush current

50

LARSEN & TOUBRO LTD

Relay setting of 33kV tran


a)

Current Setting

b)

Setting Adopted I3> Set


Time Delay I3>time delay

4.3
a)

b)

4.4

EARTH FAULT ELEMENT

50N

Earth fault setting

Earth fault setting Adopted

EFIPTOC

Operating time ( Definite time characteristic )

EFIPTOC

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

LARSEN & TOUBRO LTD

Relay setting of 33kV tran

iv) TMS Required

I>1 TMS

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS

Approved
PRM

Relay setting of 33kV transformer outgoing

6600

:
:

2350
0.500

A
0.433kv O/C Relay operating time+ time grading

11240

:
:

349.92
1749.60

A
A

200
0=Disabled A

,1=DT,2=I
1
A
EC S
Inverse,3=I
EC V
Inverse,4=I
:
MICOM P141
EC E
Inverse,5=
:
Schneider
UK LT
:
Normal
Inverse
Inverse,6=
UK
* Setting range are taken from Relay Manual
Rectifier,7
=RI,8=IEE
EM
Inverse,9=I
Disabled,
:
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
:
0.05-4
Inverse,11=
Inverse,
:
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
:
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE V
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse, US
Inverse, US

5P20

a
b

0.02
0.14

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 33kV transformer outgoing

:
:
:

:
:
:
:
:
:

:
:

Nondirectional
Directional
Fwd
Disabled,
Directional
DT, IEC S
Rev
Inverse,
0.08-4In
IEC V
Inverse,
IEC
E
0.025-1
Inverse,
0=Disabled
UK LT
,1=DT,2=I
Inverse,
EC
UK S
Inverse,3=I
Rectifier,
EC
V
RI, IEEE
Inverse,4=I
M Inverse,
0.05-32In
EC
EV
IEEE
Inverse,5=
Inverse,
UK
IEEELTE
0Inverse,6=
to 100 US
Inverse,
UK
Inverse, US
Rectifier,7
ST Inverse
=RI,8=IEE
Measured
EM
Inverse,9=I
Disabled,
EEE V
DT, IEC S
Inverse,10
Inverse,
=IEEE E
IEC
V In
0.05-4
Inverse,11=
Inverse,
0.025-1.2 s
US
IEC E
Inverse,12
Inverse,
=US ST
UK LT
Inverse,13
Inverse,
=User
UK
curve
Rectifier,
1,14=User
RI, IEEE
curve
M Inverse,
2,15=User
IEEE
V
0.08-4In
curve
Inverse,
3,16=User
IEEE E
curve 4
Inverse,
0-200 US
Inverse, US
ST Inverse

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Prepared
JS

Checked
PGT

Relay setting of 33kV transformer outgoing

:
:
:
:
:
:
:
:

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

Approved
PRM

Project

PATLIPUTRA GRINDING UNIT

Title

L & T Doc No

Relay Setting calculations


:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 33kV transformer outgoing

1.1 * Full Load load current /CT Ratio

9.62

9.62
2500

In
A

:
:
:

Fault current /(CT Ratio * PS)


2500/(200/1*9.62)
1.3

0.14
PSM^0.02 - 1

From ETAP

(for PSM>20,PSM=20)

26.66
:

Desired Operating time


Relay Operating time at TMS=1.0

0.019

Fault current /(CT Ratio * PS)

2350/(200/1*9.62)

1.2

0.14
PSM^0.02 - 1

2.24

:
:

3250.000
17496.000
(10 x flc)

A
A

(for PSM>20,PSM=20)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 33kV transformer outgoing
:

1.3 x fault current relfected in 6.6kV/CTR


1.3 x 3408/250
21.125
20

0.1

0.10 times of Full load current/CTR

0.10*139.97/175

0.8748

0.1

In

0.5

0.5

:
:
:

0.10*CT primary current

:
:

Iearthfault/CT ratio
0.1
625
A

Fault current /(CT Ratio * PS)

625/(200/1*0.1)

31.3

20.00

0.14
PSM^0.02 - 1

(for PSM>10,PSM=10)

Approved
PRM

Project

Title

L & T Doc No

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

:
:

Date
Revision

: 14-1-2016
0
:
Checked
PGT

Prepared
JS
Relay setting of 33kV transformer outgoing

2.27

Desired Operating time


Relay Operating time at TMS=1.0

0.5 / 2.27

:
:

0.221

Approved
PRM

Approved
PRM

0.433kv O/C Relay operating time+ time grading

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

Approved
PRM

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)
c)

Fault current - Own terminal


Fault currebt at far end of bus
Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0

RELAY SETTING

4.1

SETTINGS FOR IDMT OC-51


Over Current Setting (Calculated)
i) I>1 current setting

ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

FAULT AT ITS OWN TERMINAL (Direct fault)


c)

Current setting at Fault current

d)

Relay Operating time at TMS=0.662

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT

50N

i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4
SETTINGS FOR IDMT
51N

Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM
iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting

59

Select over voltage setting


Time setting 59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
33kV TiE ICOG

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:

:
:
:

:
:

:
I>1 TMS

:
:
:

:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:
:
:
:
:
I>1 TMS

:
:
:

:
:

:
:
:

:
:
:
:
:
Prepared
JS
33kV TiE ICOG

33000
31800
25500
1.50
279.93
16.00

350
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

1.1 * Full Load load current /CT Ratio


0.88
0.88

Fault current /(CT Ratio * PS)


31800/(350/1*0.88)
82.8

0.14
PSM^0.02 - 1

2.27
Desired Operating time
Relay Operating time at TMS=1.0
1.5 / 2.27
0.662

Fault current /(CT Ratio * PS)


31800/(350/1*0.88)
103.2

0.14
PSM^0.02 - 1
1.50

Rated fault Current/CTR


72.8571428571
72.857
72.857
1.00

0.10 times of Full load current/CTR


0.08
0.08
0.08
1

1.3

0.10*CT primary current


35.00
Iearthfault/CT ratio
0.1
33290
Fault current /(CT Ratio * PS)
33290/(/350*0.1)
951.1
0.14
PSM^0.02 - 1
2.27
Relay Operating time at TMS=1.0
1.3 / 2.27
0.573

0.90*6600
5940
99
1

1.05*6600

Desired Operating time

6930
115.5
1

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A
S
A

From ETAP
Down stream breaker operating time+ time grading(0.50+0.25)
Note: Load current is calculated considering 2.5MVA

MVA

5P10

0.02
0.14

In

(for PSM>10,PSM=10)

(for PSM>20,PSM=20)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ting time+ time grading(0.50+0.25)

lculated considering 2.5MVA

LARSEN & TOUBRO LTD

GROUP 1: OVERCURRENT
MENU TEXT

RECOMMEND SETTING

I>1 Function

IEC S Inverse

I>1 Direction

Non-directional

I>1 Current Set

0.96

I>1 TMS

0.097

I>2 Function

DT

I>2 Direction

Non Directional

I>2 Current Set

13.55

I>2 Time Delay

0.1

I>3 Status

Disabled

GROUP 1: EARTH FAULT


MENU TEXT

RECOMMEND SETTING

IN>1Input

Measured

IN>1Input

IEC S Inverse

I>1 Direction

Non-directional

I>1 Current Set

0.1

I>1 TMS

0.044

I>2 Function

DT

I>2 Direction

Non Directional

I>2 Current Set

0.09

I>2 Time Delay

0.1

I>3 Status

Disabled

GROUP 1: Voltage Protection

MENU TEXT

RECOMMEND SETTING

Under Voltage
V< meas't mode

Phase-phase

V<1 Function

DT

V<1 voltage set

99

V<1 time delay

V<2 status

Disabled

Under Voltage
V< meas't mode

Phase-phase

V>1 Function

DT

V>1 voltage set

115.5

V>1 time delay

V>2 status

Disabled

Project
Title
L & T Doc No
Date
Revision
Prepared
JS

PMCC-settin

SETTING T

MINIMUM
-

0.08*In
0.025

0.08*In
0.025
Enabled, Disabled

MINIMUM
Measured
-

0.08*In
0.025

0.08*In
0.025
Enabled, Disabled

MINIMUM

10V
0

60V
0

GRINDING UNIT

Checked
PGT

MCC-setting chart
SETTING TABLE:

SETTING RANGE
MAXIMUM

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inv


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev

4*In
1.2

SETTING RANGE
MAXIMUM
Derived

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inv


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

SETTING RANGE
MAXIMUM

Phase-phase phase-Neutral
Disabled, DT ,IDMT
120V
100
Enabled, Disabled

Phase-phase phase-Neutral
Disabled, DT ,IDMT
185V
100
Enabled, Disabled

Approved
PRM

STEP SIZE

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE
1

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

N/A

1V
0.01S
N/A

N/A

1V
0.01S
N/A

LARSEN & TOUBRO LTD

Project

PATLIPUTRA GRINDING UNIT

Title

Relay Setting

L & T Doc No
Date
Revision

14.1.2016
0

Prepared

Checked
PGT

JS

Approved
PRM

HV SIDE Xmer SETTING


SETTING TABLE:
GROUP 1: OVERCURRENT
MENU TEXT

RECOMMEND SETTING

SETTING RANGE
MINIMUM

I>1 Function

IEC S Inverse

I>1 Direction
I>1 Current Set
I>1 TMS
I>2Status

Non-directional
0.96
0.19
Disabled

0.08*In
0.025
Enabled, Disabled

I>3 Function

DT

I>3 Direction
I>3 Current Set
I>3Time Delay
I>4 Status
GROUP 1: EARTH FAULT
MENU TEXT

Non Directional
20
0.35
Disabled
RECOMMEND SETTING

SETTING RANGE
MINIMUM

IN>1Input

Measured

Measured

IN>1Input

Measured

I>1 Direction
I>1 Current Set
I>1 TMS

Non-directional
0.1
0.154

0.08*In
0.025

I>2 Function

DT

I>2 Direction
I>2 Current Set
I>2 Time Delay
I>3 Status

Non Directional
0.1
0.35
Disabled

GROUP 1: Voltage Protection


MENU TEXT

RECOMMEND SETTING

0.08*In
0.025
Enabled, Disabled

0.08*In
0.025
Enabled, Disabled

SETTING RANGE
MINIMUM

MAXIMUM
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inverse, IEEE V
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
32*In
1.2

STEP SIZE

0.01*In
0.005
N/A

0.01*In
0.005
N/A

MAXIMUM

STEP SIZE

Derived
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inverse, IEEE V
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

MAXIMUM

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

Under Voltage
Phase-phase

Phase-phase phaseNeutral

V<1 Function

DT

Disabled, DT ,IDMT

V<1 voltage set


V<1 time delay
V<2 status
Under Voltage

99
2
Disabled

10V
0
Enabled, Disabled

Phase-phase

Phase-phase phaseNeutral

V>1 Function

DT

Disabled, DT ,IDMT

V>1 voltage set


V>1 time delay
V>2 status

115.5
2
Disabled

60V
0
Enabled, Disabled

V< meas't mode

V< meas't mode

N/A

120V
100

1V
0.01S
N/A
N/A

185V
100

1V
0.01S
N/A

LARSEN & TOUBRO LTD

Project

PATLIPUTRA GRINDING UNIT

Title

Relay Setting

L & T Doc No
Date
Revision
Prepared

14.1.2016
0

Checked
PGT

JS

Approved
PRM

6.6KV INCOMER SETTING


GROUP 1: OVERCURRENT
MENU TEXT

RECOMMEND SETTING

SETTING RANGE
MINIMUM

I>1 Function

IEC S Inverse

I>1 Direction
I>1 Current Set
I>1 TMS
I>2Status

Non-directional
0.96
0.267
Disabled

0.08*In
0.025
Enabled, Disabled

I>3 Function

DT

I>3 Direction
I>3 Current Set
I>3Time Delay
I>4 Status
GROUP 1: EARTH FAULT

Non Directional
10.93
0.6
Disabled

MENU TEXT

RECOMMEND SETTING

IN>1Input

0.08*In
0.025
Enabled, Disabled

MAXIMUM
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE
V Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inverse, IEEE V
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
32*In
1.2

STEP SIZE

0.01*In
0.005
N/A

0.01*In
0.005
N/A

SETTING RANGE
MINIMUM

MAXIMUM

STEP SIZE

Measured

Measured

IN>1Input

IEC S Inverse

I>1 Direction
I>1 Current Set
I>1 TMS

Non-directional
0.1
0.089

0.08*In
0.025

I>2 Function

DT

I>2 Direction
I>2 Current Set
I>2 Time Delay
I>3 Status

Non Directional
0.09
0.6
Disabled

Derived
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE
V Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2
Disabled, DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inverse, IEEE V
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

0.08*In
0.025
Enabled, Disabled

0.01*In
0.005

0.01*In
0.005
N/A

GROUP 1: VOLTAGE PROTECTION


MENU TEXT

RECOMMEND SETTING

SETTING RANGE
MINIMUM

MAXIMUM

STEP SIZE

Under Voltage
V< meas't mode

Phase-phase

Phase-phase phase-Neutral

V<1 Function

DT

Disabled, DT ,IDMT

V<1 voltage set


V<1 time delay
V<2 status
Under Voltage

99
2
Disabled

V< meas't mode

10V
0

120V
100
Enabled, Disabled

1V
0.01S
N/A
N/A

Phase-phase

Phase-phase phase-Neutral

V>1 Function

DT

Disabled, DT ,IDMT

V>1 voltage set


V>1 time delay
V>2 status

115.5
2
Disabled

60V
0
Enabled, Disabled

N/A

185V
100

1V
0.01S
N/A

LARSEN & TOUBRO LTD

6.6KV ICOG SETTING


MENU TEXT

RECOMMEND SETTING

I>1 Function

IEC S Inverse

I>1 Direction
I>1 Current Set
I>1 TMS
I>2Status

Non-directional
0.96
0.303
Disabled

I>3 Function

DT

I>3 Direction
I>3 Current Set
I>3Time Delay
I>4 Status
GROUP 1: EARTH FAULT

Non Directional
10.93
0.8
Disabled

MENU TEXT

RECOMMEND SETTING

IN>1Input

Measured

IN>1Input

IEC S Inverse

I>1 Direction
I>1 Current Set
I>1 TMS

Non-directional
0.1
0.109

I>2 Function

DT

I>2 Direction
I>2 Current Set
I>2 Time Delay
I>3 Status

Non Directional
0.09
0.8
Disabled

GROUP 1: VOLTAGE PROTECTION


MENU TEXT

RECOMMEND SETTING

Under Voltage
V< meas't mode

Phase-phase

V<1 Function

DT

V<1 voltage set


V<1 time delay
V<2 status
Under Voltage

99
2
Disabled

V< meas't mode

Phase-phase

V>1 Function

DT

V>1 voltage set


V>1 time delay
V>2 status

115.5
2
Disabled

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
SETTING RANGE
MINIMUM
0.08*In
0.025
Enabled, Disabled

0.08*In
0.025
Enabled, Disabled

MINIMUM
Measured
0.08*In
0.025

0.08*In
0.025
Enabled, Disabled

MINIMUM

10V
0

60V
0
Enabled, Disabled

RINDING UNIT

Checked
PGT

MAXIMUM

EC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M I


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

EC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
32*In
1.2

SETTING RANGE
MAXIMUM

Derived
EC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M I
Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2
EC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M In
Inverse,IEEE E Inverse, US Inverse, US ST Inverse

Non-directional,Directional Fwd,Directional Rev


4*In
1.2

SETTING RANGE
MAXIMUM
Phase-phase phase-Neutral
Disabled, DT ,IDMT
120V
100
Enabled, Disabled
Phase-phase phase-Neutral
Disabled, DT ,IDMT
185V
100

Approved
PRM

STEP SIZE

0.01*In
0.005
N/A

0.01*In
0.005
N/A

STEP SIZE
1

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

N/A

1V
0.01S
N/A
N/A

1V
0.01S
N/A

LARSEN & TOUBRO LTD

33KV TTRANSFORMER FEEDE


MENU TEXT

I>1 Function
I>1 Direction
I>1 Current Set
I>1 TMS
I>2Status
I>3 Function
I>3 Direction
I>3 Current Set
I>3Time Delay
I>4 Status
GROUP 1: EARTH FAULT
MENU TEXT
IN>1Input
IN>1Input
I>1 Direction
I>1 Current Set
I>1 TMS

I>2 Function
I>2 Direction
I>2 Current Set
I>2 Time Delay
I>3 Status
GROUP 1: VOLTAGE PROTECTION
MENU TEXT
Under Voltage
V< meas't mode
V<1 Function
V<1 voltage set
V<1 time delay
V<2 status
Under Voltage
V< meas't mode
V>1 Function
V>1 voltage set
V>1 time delay
V>2 status
GROUP 1: FREQUENCY PROTECTION
MENU TEXT
Under Frequency
F<1 status
F<1 Frequency
F<1 time delay

F<2 status
Over Frequency
F>1 Status
F>1 Frequency
V>1 time delay
V>2 status

Project
Title
L & T Doc No
Date
Revision
Prepared
JS

& TOUBRO LTD

FEEDER SETTINGS
RECOMMEND SETTING

SETTING RANGE
MINIMUM

IEC S Inverse

Non-directional
0.88
0.39
Disabled

0.08*In
0.025
Enabled, Disabled

DT
Non Directional
20
0.9
Disabled

0.08*In
0.025
Enabled, Disabled

RTH FAULT
RECOMMEND SETTING

MINIMUM

Measured

Measured

IEC S Inverse

Non-directional
0.1
0.243

0.08*In
0.025

DT
Non Directional
0.09
0.8
Disabled

0.08*In
0.025
Enabled, Disabled

AGE PROTECTION
RECOMMEND SETTING

MINIMUM

Phase-phase
DT
99
2
Disabled

10V
0

Phase-phase
DT
115.5
2
Disabled

60V
0
Enabled, Disabled

UENCY PROTECTION
RECOMMEND SETTING

MINIMUM

Enabled
49.5
0.2

45Hz
0

Disabled
Enabled
50.5
0
Disabled

45Hz
0
Enabled, Disabled

RA GRINDING UNIT
ng

Checked
PGT

MAXIMUM

DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE
IEEE V Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE


IEEE V Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
32*In
1.2

SETTING RANGE
MAXIMUM

Derived
DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE
IEEE V Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

DT, IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE


IEEE V Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

SETTING RANGE
MAXIMUM
Phase-phase phase-Neutral
Disabled, DT ,IDMT
120V
100
Enabled, Disabled
Phase-phase phase-Neutral
Disabled, DT ,IDMT
185V
100

SETTING RANGE
MAXIMUM
Disabled, Enabled
65Hz
100

Enabled, Disabled
Disabled, DT ,IDMT
65Hz
100

Approved
PRM

STEP SIZE

0.01*In
0.005
N/A

0.01*In
0.005
N/A

STEP SIZE
1

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

N/A

1V
0.01S
N/A
N/A

1V
0.01S
N/A

STEP SIZE

0.01Hz
0.01S

N/A

0.01
0.01S
N/A

LARSEN & TOUBRO LTD

MENU TEXT

RECOMMEND SETTING

I>1 Function

IEC S Inverse

I>1 Direction

Non-directional

I>1 Current Set

0.88

I>1 TMS

0.529

I>2Status

Disabled

I>3 Function

DT

I>3 Direction

Non Directional

I>3 Current Set

32

I>3Time Delay

I>4 Status

Disabled

GROUP 1: EARTH FAULT


MENU TEXT

RECOMMEND SETTING

IN>1Input

Measured

IN>1Input

IEC S Inverse

I>1 Direction

Non-directional

I>1 Current Set

0.1

I>1 TMS

0.287

I>2 Function

DT

I>2 Direction

Non Directional

I>2 Current Set

0.08

I>2 Time Delay

I>3 Status

Disabled

GROUP 1: VOLTAGE PROTECTION


MENU TEXT

RECOMMEND SETTING

Under Voltage
V< meas't mode

Phase-phase

V<1 Function

DT

V<1 voltage set

99

V<1 time delay

V<2 status

Disabled

Under Voltage
V< meas't mode

Phase-phase

V>1 Function

DT

V>1 voltage set

115.5

V>1 time delay

V>2 status

Disabled

GROUP 1: FREQUENCY PROTECTION


MENU TEXT

RECOMMEND SETTING

Under Frequency
F<1 status

Enabled

F<1 Frequency

49.5

F<1 time delay

0.2

F<2 status

Disabled

Over Frequency
F>1 Status

Enabled

F>1 Frequency

50.5

V>1 time delay

V>2 status

Disabled

Project
Title
L & T Doc No
Date
Revision
Prepared
JS

33KV ICO
SETTING RANGE
MINIMUM

0.08*In
0.025
Enabled, Disabled

0.08*In
0.025
Enabled, Disabled

MINIMUM

Measured
-

0.08*In
0.025

0.08*In
0.025
Enabled, Disabled

SETTING RANGE
MINIMUM
Phase-phase phaseNeutral
Disabled, DT ,IDMT
10V
0
Enabled, Disabled
Phase-phase phaseNeutral
Disabled, DT ,IDMT
60V
0

Enabled, Disabled

SETTING RANGE
MINIMUM

Disabled, Enabled
45Hz
0
Enabled, Disabled

Disabled, DT ,IDMT
45Hz
0
Enabled, Disabled

GRINDING UNIT

Checked
PGT

33KV ICOG SETTING

MAXIMUM

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
32*In
1.2

SETTING RANGE
MAXIMUM

Derived

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

MAXIMUM

120V
100

185V
100

MAXIMUM

65Hz
100

65Hz
100

Approved
PRM

STEP SIZE

0.01*In
0.005
N/A

0.01*In
0.005
N/A

STEP SIZE

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

N/A

1V
0.01S
N/A

N/A

1V
0.01S

N/A

STEP SIZE

0.01Hz
0.01S
N/A

0.01
0.01S
N/A

LARSEN & TOUBRO LTD

GROUP 1: OVERCURRENT
MENU TEXT

RECOMMEND SETTING

I>1 Function

IEC S Inverse

I>1 Direction

Non-directional

I>1 Current Set

0.96

I>1 TMS

0.099

I>2 Function

DT

I>2 Direction

Non Directional

I>2 Current Set

14.25

I>2 Time Delay

0.1

I>3 Status

Disabled

GROUP 1: EARTH FAULT


MENU TEXT

RECOMMEND SETTING

IN>1Input

Measured

IN>1Input

IEC S Inverse

I>1 Direction

Non-directional

I>1 Current Set

0.1

I>1 TMS

0.044

I>2 Function

DT

I>2 Direction

Non Directional

I>2 Current Set

0.09

I>2 Time Delay

0.1

I>3 Status

Disabled

GROUP 1: Voltage Protection

MENU TEXT

RECOMMEND SETTING

Under Voltage
V< meas't mode

Phase-phase

V<1 Function

DT

V<1 voltage set

99

V<1 time delay

V<2 status

Disabled

Under Voltage
V< meas't mode

Phase-phase

V>1 Function

DT

V>1 voltage set

115.5

V>1 time delay

V>2 status

Disabled

Project
Title
L & T Doc No
Date
Revision
Prepared
JS

PMCC -2 SE

SETTING T

MINIMUM
-

0.08*In
0.025

0.08*In
0.025
Enabled, Disabled

MINIMUM
Measured
-

0.08*In
0.025

0.08*In
0.025
Enabled, Disabled

MINIMUM

10V
0

60V
0

GRINDING UNIT

Checked
PGT

MCC -2 SETTING
SETTING TABLE:

SETTING RANGE
MAXIMUM

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inv


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev

4*In
1.2

SETTING RANGE
MAXIMUM
Derived

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inv


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

SETTING RANGE
MAXIMUM

Phase-phase phase-Neutral
Disabled, DT ,IDMT
120V
100
Enabled, Disabled

Phase-phase phase-Neutral
Disabled, DT ,IDMT
185V
100
Enabled, Disabled

Approved
PRM

STEP SIZE

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE
1

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

N/A

1V
0.01S
N/A

N/A

1V
0.01S
N/A

LARSEN & TOUBRO LTD

GROUP 1: OVERCURRENT
MENU TEXT
I>1 Function
I>1 Direction
I>1 Current Set
I>1 TMS
I>2 Function
I>2 Direction

I>2 Current Set


I>2 Time Delay
I>3 Status
GROUP 1: EARTH FAULT
MENU TEXT
IN>1Input
IN>1Input
I>1 Direction
I>1 Current Set
I>1 TMS
I>2 Function
I>2 Direction
I>2 Current Set
I>2 Time Delay
I>3 Status

GROUP 1: Voltage Protection

MENU TEXT
Under Voltage
V< meas't mode
V<1 Function
V<1 voltage set
V<1 time delay
V<2 status
Under Voltage
V< meas't mode
V>1 Function
V>1 voltage set
V>1 time delay
V>2 status

Project

N & TOUBRO LTD

Title
L & T Doc No
Date
Revision
Prepared
JS

RCURRENT
RECOMMEND SETTING
IEC S Inverse

MINIMUM
-

Non-directional
0.96

0.08*In

0.095

0.025

DT
Non Directional

12.95

0.08*In

0.1

0.025

Disabled

Enabled, Disabled

TH FAULT

e Protection

RECOMMEND SETTING

MINIMUM

Measured

Measured

IEC S Inverse

Non-directional
0.1

0.08*In

0.044

0.025

DT
Non Directional
0.09

0.08*In

0.1

0.025

Disabled

Enabled, Disabled

RECOMMEND SETTING

MINIMUM

Phase-phase
DT
99

10V

Disabled

Phase-phase
DT
115.5

60V

Disabled

GRINDING UNIT

Checked
PGT

MCC -3 SETTING

SETTING TABLE:

SETTING RANGE
MAXIMUM

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inv


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev

4*In
1.2

SETTING RANGE
MAXIMUM
Derived

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M In


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Rev,Directional Fwd
4*In
1.2

IEC S Inverse, IEC V Inverse,IEC E Inverse, UK LT Inverse, UK Rectifier,RI, IEEE M Inv


Inverse,IEEE E Inverse, US Inverse, US ST Inverse
Non-directional,Directional Fwd,Directional Rev
4*In
1.2

SETTING RANGE
MAXIMUM

Phase-phase phase-Neutral
Disabled, DT ,IDMT
120V
100
Enabled, Disabled

Phase-phase phase-Neutral
Disabled, DT ,IDMT
185V
100
Enabled, Disabled

Approved
PRM

STEP SIZE

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE
1

0.01*In
0.005

0.01*In
0.005
N/A

STEP SIZE

N/A

1V
0.01S
N/A

N/A

1V
0.01S
N/A

LARSEN & TOUBRO LTD

1.0

INPUT SYSTEM DETAILS

a)

System Voltage

b)

Fault current - Own terminal


Desired Operating time

c)

Full load current

d)

Transformer rating

2.0

CT DETAILS

a)

Primary Current

b)

Secondary current

3.0

RELAY DETAILS

a)

Type

b)

Make

c)

Curve

d)

Setting Range

GROUP 1 OVERCURRENT SETTINGS

i) I>1 Function

i) I>1 Current setting


ii) I>1 TMS

i) I2> Function

ii) I2>Direction
iii) I2>current set
iv) I2 Time Delay

ii) I3>Function

iii) I3>current set


iv) I3 Time Delay
Earth-Fault (51N)
IN>1 Input
i) IN1>1 Function
i) IN1>1 Current setting
ii) IN1>1 TMS

i) IN1>2 Function

iii) IN1>2current set


iv) IN1>2 Time Delay
Over Voltage Set (59)
i) V> Measurement Mode
ii) v>1 Function
iii) V>1 voltage set
iv) V>1 time delay
Under Voltage (27)
i) V< Measurement Mode
ii) V<1 Function
iii) V<1 voltage set
iv) V<1 time delay
4.0

RELAY SETTING

4.1

SETTINGS FOR IDMT OC-51


Over Current Setting (Calculated)
i) I>1 current setting
FAULT AT ITS OWN TERMINAL
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.2

INSTANTANEOUS ELEMENT
i) Current Setting

50

Setting Adopted
ii) Time Delay
4.3

EARTH FAULT ELEMENT

50N

i) Earth fault setting

Earth fault setting Adopted


ii) Operating time ( Definite time characteristic )
4.4

SETTINGS FOR IDMT OC-51N


Desired operating time

Pickup Earth fault current


Iearth fault
Pickup Earth fault current in CT secondary
Earth Fault current as per ETAP
ii) Current setting at Fault current

PSM

iii) Relay Operating time at TMS=1.0

iv) TMS Required

4.4

UNDER VOLTAGE

27

i) Under voltage setting


ii) Select under voltage setting
iii) time setting for 27

4.5

OVER VOLTAGE
i) Over Voltage setting
Select over voltage setting
Time setting 59

59

Project
Title
L & T Doc No
Date
Revision
Prepared
JS
6.6kV Incomer

:
:
:
:
:

:
:

:
:
:

:
:

:
:
:

:
:
:
:
:
:

:
:

:
:
:
:
:
:
:
:

:
:
:

:
:
:

:
:

:
I>1 TMS

:
:
:

I3>current set
I3>time delay

:
:

:
:
:
IN2>Current

IN2> time delay

:
:
:
:
:
:
:
:

:
:
:
:
I>1 TMS

:
:

:
:
:

:
:
:
:
:

:
:
:
:
:
Prepared
JS
6.6kV Incomer

6600
17700
0.90
1399.64
16.00

1600
1

MICOM-P141
Schneider
Normal Inverse

* Setting range are taken from Relay Manual

0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User curve 4
0.05-4 In
0.025-1.2 s
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
Non-directional
Directional Fwd
Directional Rev
0.08-4In
0.025-1
Disabled, DT, IEC S Inverse, IEC V Inverse,
IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.05-32In
0 to 100
Measured
0=Disabled,1=DT,2=IEC S Inverse,3=IEC V
Inverse,4=IEC E Inverse,5=UK LT Inverse,6=UK
Rectifier,7=RI,8=IEEE M Inverse,9=IEEE V
Inverse,10=IEEE E Inverse,11=US Inverse,12=US ST
Inverse,13=User curve 1,14=User curve 2,15=User curve
3,16=User
0.05-4 In curve 4
0.025-1.2 s

Disabled, DT, IEC S Inverse, IEC V Inverse,


IEC E Inverse, UK LT Inverse, UK Rectifier,
RI, IEEE M Inverse, IEEE V Inverse,
IEEE E Inverse, US Inverse, US ST Inverse
0.08-4In
0-200

Phase-Phase or Phase-neutral
Disabled
DT
IDMT
60-185 V
0-100 s
Phase-Phase or Phase-neutral
Disabled
DT
IDMT
10-120 V
0-100 s

1.1 * Full Load load current /CT Ratio


0.96
0.96

Fault current /(CT Ratio * PS)


17700/(1600/1*0.96)
11.5

0.14
PSM^0.02 - 1

2.79
Desired Operating time
Relay Operating time at TMS=1.0
0.9 / 2.79
0.322

Rated fault Current/CTR


11.0625
11.063
11.063
0.70

0.10 times of Full load current/CTR


0.09
0.09
0.09
0.7

0.7

0.10*CT primary current


160.00
Iearthfault/CT ratio
0.1
625
Fault current /(CT Ratio * PS)
625/(1600/1*0.1)
3.9

0.14
PSM^0.02 - 1
5.07
Relay Operating time at TMS=1.0
0.7 / 5.07
0.138

0.90*6600
5940
99
1

1.05*6600
6930
115.5
1

Desired Operating time

PATLIPUTRA GRINDING UNIT


Relay Setting calculations

1/3/2017
0
Checked
PGT

Approved
PRM

V
A
S
A

From ETAP
Down stream breaker operating time+ time grading(0.70+0.20)
Note: Load current is calculated considering 2.5MVA

MVA

5P10

0.02
0.14

In

(for PSM>10,PSM=10)

In
S

(for PSM>10,PSM=10)
S

V
S

V
S

Approved
PRM

ting time+ time grading(0.70+0.20)

lculated considering 2.5MVA