Professional Documents
Culture Documents
The following set of pages are designed as a tutorial for pump users and
manufacturers who want to learn more about pump NPSH margin. The
information displayed here is based on the ANSI/HI 9.6.1 Centrifugal/Vertical
NPSH standard which can be found in the E-Store.
Join the NPSH margin discussion forum to post questions and learn more about
what people are saying.
See the ANSI/HI 1.6 Centrifugal Pump Tests for further details on the
definitions of NPSHA and NPSHR.
By Hydraulic Institute definition, the NPSHR of a pump is the NPSH that will
cause the total head (first stage head of multistage pumps) to be reduced by
3%, due to flow blockage from cavitation vapor in the impeller vanes. NPSHR is
by no means the point at which cavitation starts; that level is referred to as
incipient cavitation.The NPSH at incipient cavitation can be from 2 to 20 times
the 3% NPSHR value, depending on pump design. The higher ratios are
normally associated with high suction energy pumps or pumps with large impeller inlet areas.
The 3% head drop criteria was selected for the NPSHR value based on the ease
of determining the exact head drop off point. Most standard low suction energy
pumps can operate with little or no margin above the NPSHR value, without
seriously affecting the service life of the pump. The full published pump head
will not, however, be achieved (by definition) when the NPSHA equals the
NPSHR of the pump. The head will be 3% less than the fully developed head
value (see Figure 9.6.1.1). It can take up to 2.5 times the NPSHR value just to
achieve the 100 percent head value. Just because the definition uses the word
Required, does not mean that providing that much NPSHA will necessarily give
satisfactory pump life. It is also recognized that, as the suction energy of a
centrifugal pump increases, so does the need for a larger NPSH margin above
the 3% NPSHR of the pump, to avoid excessive noise, vibration, and possible
cavitation erosion and seal damage.
Most pump manufacturers use the industry standard 3% head drop for NPSHR
values and provide the NPSH Margin recommendations separately. A few
manufacturers do include the NPSH Margin in their pump NPSHR curves which
then supersede the guidelines spelled out in this standard. Unless advised
otherwise, however, the user must assume that there is no margin in the
published NPSHR, and that it is based solely on the 3% head drop criteria.
Suction Energy
The suction energy level of a pump increases with the casing suction nozzle
size, the pump speed, the suction specific speed and the specific gravity of the
pumped liquid. Anything that increases the velocity in the pump impeller eye,
the rate of flow of the pump, or the specific gravity, increases the suction
energy of the pump. The suction nozzle size is used for simplicity because it
approximates the impeller eye diameter and ties to the rate of flow of the
pump. The rpm ties directly to the inlet tip speed of the impeller and relative
inlet velocities, and the suction specific speed is also dependant on rpm and
rate of flow. The NPSHR in the suction specific speed is appropriate as a
measure of suction energy in that larger impeller eye diameters are normally
required for lower NPSHR values, which increases the impeller tip speed.
Factors in Suction Energy
Many factors are known to contribute to the suction energy level, and resulting
NPSH margin requirements of a pump, more than used in the above definition.
Those used in the above definition are factors which are typically available from
standard pump manufacturers technical literature. Manufacturers of custom
engineered pumps may use alternate evaluation methods to establish NPSH
margin requirements and these would supersede the guidelines spelled out in
this standard. For general information a list of suction energy factors is
provided below:
The peripheral velocity at the O.D. of the impeller eye. Values below
approximately 15 m/sec. (50 ft/sec) are generally considered low suction
energy, while values above approximately 35 m/ sec. (120 ft/sec) are
considered high suction energy.
The suction specific speed of the pump (S = n (Q^) /(NPSHR) ).
Suction specific speed values below approximately 8,000 metric (7,000
U.S. units) generally represent low suction energy, while above
approximately 23,000 metric (20,000 U.S. units) are considered high
suction energy. See Figure 9.6.1.3 for suction specific speeds between
these values. (Note: Q is the BEP rate of flow entering the impeller eye. In
double suction pumps, use one half total rate of flow. NPSHR is based on
3% head drop at BEP.)
The specific gravity of the liquid pumped. The higher the value the higher
the suction energy.
Thermodynamic properties of the liquid. Cold water has one of the highest
energy levels for imploding cavitation bubbles. See section on Electric
Power pumps for more details.
The geometry of the pump inlet. The greater the variation in velocity
across the impeller inlet and the higher the magnitude of velocities, the
higher the energy level. For this reason, radial inlets, as found in split case
pumps have higher suction energy levels due to the right angle turn in
front of the impeller.
The overlap of the impeller vanes. Overlap values less than approximately
15 degrees, such as found on two or three vane impellers (see Figure 2),
can allow the high discharge pressure (energy) to recirculate into the
impeller suction at low rates of flow. Overlap is defined as the angular
amount that the trailing edge of one vane (low pressure side) overlaps the
inlet leading edge of the following adjacent vane (at the outer diameter).
The incidence angle between the inlet impeller vanes and the approaching
liquid. Typically an impelleris designed to have a zero incidence angle at
design rate of flow. Higher or lower rates of flow cause a mismatch
between the angle of the approaching liquid and the impeller vane inlet
tips. The greater the incidence the greater the turbulence and suction
energy.
The geometry of the inlet piping to the pump. The turbulence (added
suction energy) that is generated at the pump inlet from piping turns and
large changes in pipe diameter adds to the suction energy at the pump
inlet.
Operation away from the best efficiency point (BEP) of the pump. At
reduced rates of flow the pump may operate in its suction recirculation
region. Operation off BEP rate of flow also increases the incidence angle to
the impeller vanes, and suction recirculation adds to the suction energy
level. See ANSI/HI 9.6.3-1997, Centrifugal and Vertical Pumps for
Allowable Operating Region, for more information.
For two vane impellers and impeller trims with less than 15 degrees vane
overlap, (see Figure 9.6.1.2) increase suction nozzle size by one or two
sizes before using Figure 9.6.1.3.
Inducers, which are generally beyond the scope of this document, should
have the suction nozzle decreased by at least one size before using Figure
9.6.1.3.
For axial split case (side Suction) pumps, decrease nozzle size by one size,
before using Figure 9.6.1.3.
For pump speeds higher than 3600 rpm, the suction nozzle sizes should
be increased, proportional to the increase in speed, and enter the graph at
3600 rpm. For example, increase the nozzle size by 2 times if the speed is
doubled.
For vertical turbine (line shaft diffuser) type pumps, the Impeller Inlet eye
diameter should be obtained from the supplier and used as the suction
nozzle size, when using Figure 9.6.1.3.
Multistage pumps, such as used for boiler feed and pipeline services, are
excluded from this figure due to the typically large shaft diameters in the
impeller eye, which distorts the relationship between the impeller eye
diameter and the suction nozzle size.
The impeller material. Rigid plastics and composites are normally the least
cavitation resistant materials. Cast iron and brass will experience the most
damage of commonly used metals, while stainless steel, titanium and
nickel aluminum bronze will have much less damage, under the same
cavitation conditions.
Pump size. Large pumps (impeller inlets over 450 mm (18 in) in diameter
can be more prone to cavitation damage than smaller pumps.
The gas content of the liquid. Small amounts of entrained gas (1 to 2%)
cushion the forces from the collapsing cavitation bubbles, and can reduce
the resulting noise, vibration and erosion damage. The lack of any
entrained gas can have the opposite effect. Warmer liquids tend to release
less dissolved gas, which increases the noise level of a pump. On the
other hand gas can collect in the inlet of a pump which will block portions
of the flow area, thus increasing the inlet velocity of the liquid and
creating even more cavitation. This increases the apparent NPSHR of the
pump. The net result of these two counter effects of gas content on pump
noise and vibration will vary based on the suction energy level of the
pump. In the case of low to high suction energy levels, the net effect of
gas may be to quiet the pump, since the cushioning may more than offset
the added cavitation. However, with very high suction energy pumps, the
force of the collapsing cavitation bubbles may be too great for any real
cushioning, so the noise and damage will increase with increasing gas
content.
Additives in the liquid. Additives in the liquid which increase vapor
pressure can increase cavitation damage. For example, cooling tower
water treatment agents.
The corrosive properties of the liquid. This can accelerate the damage.
Solids/abrasives in the liquid. Adding abrasives to the high implosive
velocities from the collapsing vapor bubbles increases the wear rate.
The duty cycle of the pump. Cavitation damage is time related. The longer
a pump runs under cavitation conditions, the greater the extent of
damage. Fire pumps, which run intermittently, rarely have a problem with
cavitation damage for this reason.
turbine pumps, since they generally have Low Suction Energy, and cavitation
noise is normally not an issue. NPSHA must, however, be equal to or larger
than the NPSHR over the allowable operating region of the pump, including at
low water level. The determination of the minimum submergence required to
avoid the formation of sump vortices around the pump inlet must be considered
independently from NPSHA, since they are a separate phenomena. (See
ANSI/HI 9.8-1998, Pump Intake Design).
Application Considerations
The following is a list of current Application Considerations:
Summary
In summary, the following key points should be understood about cavitation in
a centrifugal pump, NPSH Margin requirements, and how they are affected by
the Suction Energy level of the pump:
These factors emphasize the need to apply large NPSH margins when selecting
pumps.
Taking these issues into consideration, the following NPSH Margin guidelines
are proposed for Chemical Process pumps to account for the many
uncertainties:
For low suction energy pumps, the margin should be 10% of the NPSHR or
0.6m (2 ft), whichever is greater.
For high suction energy pumps the margin should be 30% of the NPSHR
or 1.5m (5 ft), whichever is greater. NPSH tests are recommended if the
pump specific speed is above 2,300 metric (2,000 U.S. units).
Vertical turbine type pumps used as condensate pumps are normally installed
in a barrel or can as shown in Figure 2.6 of ANSI/HI 2.1-2.2, Vertical Pumps for
Nomenclature and Definitions.
Water/wastewater
The following considerations apply to pumps for this application:
1. During variable speed operation, all possible wet well levels, pump
speeds, and rates of flow exist. It is important that the pump can function
properly over the full operating range of the system curve. A flow duration
diagram can be used to determine where the pump will operate most
frequently. In the on/off mode of operation, the speed and rate of flow will
be relatively constant, but the sump level will vary between a maximum
water level and a minimum water level. The change of the water level in
the sump will also change the pumps total head, also slightly changing
the speed and rate of flow of the pump, but the duty point will be nearly
constant compared to variable speed operation.
2. Actual system head curves often differ from the calculated values. This
will cause the NPSH Margin calculation to be incorrect. It is, therefore,
very important to ensure that the calculated system head curves be as
close as possible to the actual. For existing systems, it is possible to
measure the head at a number of points to develop the system head
curve. Two system curves should be calculated for new installations: one
for the system as it will be installed; and a second to represent the
condition of the system after some increase in pipe roughness has
occurred.
3. Many pumps are installed in wastewater applications with elbows mounted
in front of the impeller eye. When suction elbows are necessary, it is best
to use reducing or long radius elbows.
4. Materials of construction are typically cast iron (wastewater) or cast iron /
bronze fitted (water). These materials are preferred for water/wastewater,
but they do not stand up well under heavy cavitation. The protective layer
that is built up under normal operation is destroyed by cavitation, causing
abnormal material removal rates. It is advisable to change to tougher
materials such as stainless steel or aluminum bronze alloys if the pump
must withstand destructive cavitation levels, however, this will not help
the seals or bearings.
5. Pump stations often operate unattended, and the malfunction of a pump
must be avoided. A failed pump station processing water or wastewater
will cause considerable inconvenience to the public, and should be
designed to be as trouble-free as possible.
6. Single, two and three vane impeller designs are common in wastewater
applications, with no or minimal vane overlap. Increase the suction nozzle
sizes by one or two sizes for pumps with one to three vane impellers
before using Figure 9.6.1.3.
7. Vertical Turbine barrel or can type pumps on water booster services are
generally applied with little or no NPSH Margin, since they are mostly low
suction energy applications.
The above items are listed to illustrate the uncertainties related to the NPSHA
calculations, and at the same time demonstrate the importance of accuracy
when determining the required NPSHA. It seems as though the simple answer
General industrial
Pumps for this application are used to pump a great variety of liquids, ranging
from water to concentrated chemicals. These pumps are often sold as standard
catalog, pumps. They are generally low suction energy designs.
Due to the variety of liquids pumped through an extreme range of
temperatures, the specifier must carefully calculate the NPSHA in the system,
taking into account the vapor pressure of the liquid at the extreme operating
temperature. The use of hose connections and the associated piping bends
must be accounted for. The use of hose or tubing connections with internal
diameters smaller than the pump suction inlet should not be used on the
suction side of the pump.
NPSHA on tank draining applications should be calculated for the lowest
possible level of the liquid in the tank during the pumping process.
Another consideration in the NPSH Margin of catalog type pumps is the
common changes in flow rates experienced during process changes, as well as
the physical expansion of process systems to meet higher production rates. In
general an NPSHR versus rate of flow curve has a parabolic shape. This may
cause large changes in NPSHR especially if the pump is being run to the right of
the best efficiency point.
Building Services
Fluid systems for the building trades or HVAC Industry are comprised of both
closed and open pumping systems. NPSH is generally not a concern when
designing closed pumping systems. The typical closed system is filled and then
pressurized to a fill pressure of 4 to 10 psig. If an inadequate NPSH available
(NPSHA) condition should occur, it can usually be remedied by increasing the
fill pressure.
For open systems, NPSH margin is a very important consideration. As a
guideline, the NPSHA for open systems should exceed the pump manufacturers
stated NPSH-required (NPSHR) by a minimum of 0.6m, (2 ft) or 1.1 times the
NPSHR for Low Suction Energy Pumps. For High Suction Energy pumps the
margin ratio should be increased to at least 1.3, or a minimum of 1.5m (5 ft).
Pumps operating at these established minimum NPSH margins may experience
some degree of impeller erosion and/or noise but these effects should be
minimal. System construction may contribute to the problem of noise, and
cavitation. Increasing the NPSH margin will improve pump operation and
reliability.
Slurry
Pumps used in slurry service are frequently constructed of either hard metals or
elastic materials. It is also common for the slurry concentration and flow rates
to change rapidly, imposing significant loads on the impeller, shaft and
bearings. Because of this, and the erosive nature of many slurries, slurry
pumps are of an extremely rugged design, making them relatively insensitive
to the mechanical effects of cavitation.
Also, to minimize erosive effects, slurry pumps often operate at low speeds
(less than 1200 RPM). As a result of this, they normally fall into the Low
Suction Energy category, and have NPSHR values below 6m (20 ft).
Slurries are typically water based and at ambient temperatures. Suction flow is
usually gravity fed. Consequently the NPSHA is normally in excess of 9m (30
ft), giving NPSHA/NPSHR ratios in excess of 1.5.
The recommended NPSH Margin Ratio for slurry pumps is 1.1 or a margin of
0.6m (2 ft) whichever is greater. For applications where the margin is less,
characteristics of the slurry, and the NPSHR performance of the pump, should
be reviewed to assure satisfactory performance.
Pipeline
For this paper, pipelines are defined as hundreds of miles in length for the
transport of hydrocarbons or water. Pumps used for pipeline service normally
share the following application criteria:
1. Customers more often request the NPSH Required values to be based on
a 1% head drop.
2. The NPSHA Margin, over NPSHR (3%), is often incorporated in the NPSH
Required curve by the manufacturer.
3. Some pipeline designers and operators request two NPSH Required
curves. One being the conventional NPSHR curve based on a 3% head
drop, and a second based on the NPSH required to guarantee a 40,000
hour impeller life.
4. Specifications frequently require that the NPSHA exceed the NPSH
Required (40,000 hrs) over the full Allowable Operating Region for the
pump (Minimum to Maximum Flow).
5. There is no standard method for determining the NPSH Required for
40,000 hours impeller life, however it is a function of:
i. Suction Energy Level.
ii. Material of impeller.
iii. Acidity of pumpage (pH).
iv. Temperature of pumpage.
v. Suction Specific Speed.
vi. Operating rate of flow vs pump best efficiency point.
vii. The NPSH Required (0%) vs NPSHR (3%) ratio throughout the
Allowable Operating Region flow range.