You are on page 1of 7

STATICAL CALCULATION

Project:
Subject:

Client:
Project No.

Rev

280 mm Thick SLAB

Date:

08-DEC-16

CUPLOCK Formwork System for 280 mm Thick Slab


Load Computations
Design assumptions
3

26 kN/m
2
1.5 kN/m

Weight of Fresh Concrete:


Live Load:

0.5 kN/m

Formwork Weight:

Loading Data
Load Computation
3)

Load

Concrete (KN/m

Slab

26

Thickness
(m)
0.28

Live Load
2)
(KN/m

Formwork
Weight

1.5

Element Data
H20 Timber
H = 200 mm
W = 80 mm
2
EI = 500 KN-m
Permissible Shear = 11 KN
Permissible Moment = 5 KN-m

Load acting on secondary beam = 4.4 Kn/m


Analysis Results
Check on H20 Secondary Beam spaced @ 488 mm C.C.
Max. Shear = 4.15 KN < 11 KN OK
Max. Moment = 1.27-m < 5.0 kN.m. OK
Deflection = 0.1 mm < L/500
Check on Two H20 Primary Beam spaced @ 1600mm C/C.
Max. Shear = 9.88 KN < 22.0 KN OK
Max. Moment = -3.54 KN-m < 10.00 KN-m OK
Deflection = 0.10 mm < L/300
U head Load = 19.77KN < 33 KN OK

USE MAX BAY SIZE 1.8*1.6 M2

(KN/m

0.5

2)

Computed
Load
2

(KN/m )

9.28

STATICAL CALCULATION
Project:
Subject:

Client:
Project No.

Rev

400 mm Thick SLAB

Date:

08-DEC-16

CUPLOCK Formwork System for 400 mm Thick Slab


Load Computations
Design assumptions
3

26 kN/m
2
1.5 kN/m

Weight of Fresh Concrete:


Live Load:

0.5 kN/m

Formwork Weight:

Loading Data
Load Computation
3)

Load

Concrete (KN/m

Slab

Thickness
(m)

26

0.4

Live Load
2)
(KN/m

Formwork
Weight

1.5

Element Data
H20 Timber Beam
H = 200 mm
W = 80 mm
2
EI = 500 KN-m
Permissible Shear = 11 KN
Permissible Moment = 5 KN-m

Load acting on secondary beam = 5.8 Kn/m


Analysis Results
Check on H20 Secondary Beam spaced @ 488 mm C.C.
Max. Shear = 4.28KN < 11 KN OK
Max. Moment = -0.93-m < 5.0 kN.m. OK
Deflection = 0.1 mm < L/500
Check on TWO H20 Primary Beam spaced @ 1300mm C/C.
Max. Shear = 11.16 KN < 22.0 KN OK
Max. Moment = -3.99 KN-m < 10.00 KN-m OK
Deflection = 0.10 mm < L/300
U head Load = 22.31 KN < 33.0 KN OK

USE MAX BAY SIZE 1.8*1.3 M2

(KN/m

0.5

2)

Computed
Load
2

(KN/m )

12.4

STATICAL CALCULATION
Project:
Subject:

Rev

800 mm Thick beam

Client:
Project No.
Date:

08-DEC-16

CUPLOCK Formwork System for 800 mm Thick Slab


Load Computations
Design assumptions
Weight of Fresh Concrete:

26 kN/m

Live Load:

1.5 kN/m

Formwork Weight:

0.5 kN/m

3
2
2

Loading Data
Load Computation
3)

Load

Concrete (KN/m

Slab

Thickness
(m)

26

0.8

Live Load
2)
(KN/m

Formwork
Weight

1.5

Element Data
H20 Timber Beam
H = 200 mm
W = 80 mm
2
EI = 500 KN-m
Permissible Shear = 11 KN
Permissible Moment = 5 KN-m

Load acting on secondary beam = 8.00 Kn/m


Analysis Results
Check on H20 Secondary Beam spaced @ 350 mm C.C.
Max. Shear = 6.40 KN < 11 KN OK
Max. Moment = 1.10-m < 5.0 kN.m. OK
Deflection = 0.1 mm < L/500
Check on TWO H20 Primary Beam spaced @ 1600mm C/C.
Max. Shear = 12.27 KN <22.0 KN OK
Max. Moment = 4.39 KN-m < 10.00 KN-m OK
Deflection = 0.10 mm < L/500
U head Load = 24.54 KN < 33.0 KN OK

USE MAX BAY SIZE 1.8*1.6 M2

(KN/m

0.5

2)

Computed
Load
2

(KN/m )

22.8

SECONDARY BEAM DESIGN


SLAB THICKNESS 280mm

SLAB THICKNESS 400mm

TRANSFERING BEAM WITH 800 mm DEPTH

PRIMARY BEAM DESIGN


H20 BEAM AS PRIMARY for 280mm thick slab

Hence use 2 H20beams for safe.


H20 BEAM AS PRIMARY FOR 400mm thick slab

Hence use 2 H20beams for safe.


H20 BEAM AS PRIMARY FOR TRANSFERING BEAM

Hence use 2 H20beams for safe.