Site condition report for

SERVICE BLOCK:
Basement+Ground+Roof

ELECTRICAL ROOM(Basement Floor)


B

BEM/SCR/SHKV/001-Rev.00

Page 28

DB-SMDB-MECH FED FROM SMDB-SB-1

CT not connected.

BEM/SCR/SHKV/001-Rev.00

Page 28

AUTOMATIC DOSING PUMP(Basement Floor)

Automatic dosing pump control panel connected from isolator.

BEM/SCR/SHKV/001-Rev.00

Page 28

CHILLED WATER LEAK DETECTION PANEL(Basement Floor)

Chilled water leak detection panel showing faulty alarm.

CHILLED WATER SECONDRY PUMPS (PUMP-1&2)

BEM/SCR/SHKV/001-Rev.00

Page 28

C
hilled water secondary pumps (pump-1&2) tripped.
Check for abnormal vibration and heating.

ELECTRICAL ROOM (BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

Missing circuit breakers in DB-SB-E panel.


Load schedule not available inside panel.
HOT WATER PUMP ROOM(BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

Softener booster pump room isolator knob damaged.

220KVAR CAPACITOR BANK(BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

Capacitor bank fed from MCC showing under current.

FILTERATION PUMPROOM(BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

4No.s of water filtration unit not working/showing display.


2No.s of duplex softener set not working.

FILTERATION PUMP(BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

Both pumps need to be serviced due to abnormal vibration.

ELECTRICAL ROOM(BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

ACBs display not working.

BEM/SCR/SHKV/001-Rev.00

Page 28

CHILLED WATER PUMPROOM(BASEMENT FLOOR)

Chilled water pump room (secondary pump-1&2) drain required.

BEM/SCR/SHKV/001-Rev.00

Page 28

PUMP ROOM (BASEMENT FLOOR)

Butterfly valve leakage.

ELECTRICAL ROOM(BASEMENT FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

All the split units in basement floor not working.

LAUNDRY ROOM(GROUND FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

Floor drain not fixed.

Male staff room(Ground floor)

BEM/SCR/SHKV/001-Rev.00

Page 28

Lighting switch not working due to water leakage in male staff bedroom-4.

Male staff bedroom-2&3(Ground floor)

BEM/SCR/SHKV/001-Rev.00

Page 28

Remote control for AC-SPU-G10 not working.

SERVICE BLOCK(GROUND FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

Hand spray damaged.

Laundry room(First floor)

BEM/SCR/SHKV/001-Rev.00

Page 28

Lighting switch front plate missing.


Meeting Room (First floor)

Meeting room in first floor ceiling lights not working.


STAFF BEDROOM(FIRST FLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

AC-SPU-F-18 Not working in bedroom suite-1.


5 nos light not working in bedroom suit-1.
3 nos light not working in bedroom suit-1.

SERVICE BLOCK(ROOF)

BEM/SCR/SHKV/001-Rev.00

Page 28

3Nos of compressors not working in chiller unit.


Need to be check all parameters.

SERVICEBLOCK(ROOF)

BEM/SCR/SHKV/001-Rev.00

Page 28

Needs to be serviced.

SERVICE BLOCK(Roof)

BEM/SCR/SHKV/001-Rev.00

Page 28

EF-S1 motor needs to be serviced due to abnormal noise.


Lights not working.
Kitchen exhaust fans not working.

SERVICE BLOCK(ROOF)

BEM/SCR/SHKV/001-Rev.00

Page 28

Electrical panels on roof top needs to be covered with sunshades.

SERVICE BLOCK(ROOF)

BEM/SCR/SHKV/001-Rev.00

Page 28

Cable tray cover needs to be fixed properly.

SERVICE BLOCK(ROOF)

BEM/SCR/SHKV/001-Rev.00

Page 28

Cable tray and trunking not fixed and cables needs to be dressed properly.

BEM/SCR/SHKV/001-Rev.00

Page 28

Drain not connected from AHU.

BEM/SCR/SHKV/001-Rev.00

Page 28

Site condition report for


MAJLIS: Ground+FIRST+Roof

FIRSTFLOOR

BEM/SCR/SHKV/001-Rev.00

Page 28

No access panel for future maintenance.

FIRSTFLOOR

BEM/SCR/SHKV/001-Rev.00

Page 28

Pressure drop in hot water line.

ELECTRICAL ROOM (FIRSTFLOOR)

BEM/SCR/SHKV/001-Rev.00

Page 28

DB door damaged.

OTHER OBSERVATIONS
Load schedule missing in all electrical panels.
Labeling required for all wiring accessories.
B

BEM/SCR/SHKV/001-Rev.00

Page 28

All electrical panel keys with room wise required.


Chilled water is not clear needs to be checked in the lab.
All split units required servicing.
One Switch is used for controlling lights and makeup fan in kitchen.

BEM/SCR/SHKV/001-Rev.00

Page 28