Professional Documents
Culture Documents
Transformer PS Class
Current Transformer PS Class
Before understanding Knee Point Voltage of Current Transformer and
current transformer PS class we should recall the terms instrument
security factor of CT and accuracy limit factor.
For protection current transformer, the ratio of accuracy limit primary current
to the rated primary current. First we will explain, what is rated accuracy
limit primary current?.
Broadly, this is the maximum value of primary current, beyond which core of
the protection CT or simply protection core of of a CT starts saturated. The
value of rated accuracy limit primary current is always many times more
than the value of instrument limit primary current. Actually CT transforms
the fault current of the electrical power system for operation of the
protection relays connected to the secondary of that CT. If the core of the CT
becomes saturated at lower value of primary current, as in the case of
metering CT, the system fault will not reflect properly to the secondary,
which may cause, the relays remain inoperative even the fault level of the
system is large enough. That is why the core of the protection CT is made
such a way that saturation level of that core must be high enough. But still
there is a limit as because, it is impossible to make one magnetic core with
infinitely high saturation level and secondly most important reason is that
although the protection care should have high saturation level but that must
be limited up to certain level otherwise total transformation of primary
current during huge fault may badly damage the protection relays. So it is
clear from above explanation, rated accuracy limit primary current, should
not be so less, that it will not at all help the relays to be operated on the
other hand this value must not be so high that it can damage the relays.
So, accuracy limit factor or ALF should not have the value nearer to unit
and at the same time it should not be as high as 100. The standard values of
ALF as per IS-2705 are 5, 10, 15, 20 and 30.
current. This non-liner relation curve is also called B - H curve. Again from
the equation above, it is found that, secondary voltage of a current
transformer is directly proportional to flux . Hence one typical curve can be
drawn from this relation between secondary voltage and excitation current
as shown below. It is clear from the curve that, linear relation between V
and Ie is maintained from point A and K. The point A is known as ankle
point and point K is known as Knee Point.
The electrical power system load current always flows through current
transformer primary; irrespective of whether the current transformer is open
circuited or connected to burden at its secondary.