RET 670
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G
Issued: February 2007
Data subject to change without notice
Page 1
Features
High sensitivity
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 2
Application
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 3
TRIP BUSBAR
50BF
3I>
51/67
3I>
94/86
TRIP CB1
CB1
4
4
I->O
51N/67N
IN>
4
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
51N/67N
IN>
4
4
51/67
3I>
4
4
94/86
TRIP CB2
50BF
I->O
3I>
25
SC/VC
59
CB2
3U>
TRIP BUSBAR
2
2
27
3U<
2
2
en05000272.vsd
Figure 1:
A typical protection application for a two winding transformer in single breaker arrangements is
shown on the figure. The system earthing principle and connection group will vary which gives
different detailed arrangements for each application.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 4
TRIP BUSBAR&CB2
TRIP CB1/3
50BF
3I>
51/67
3I>
94/86
TRIP CB1
CB1
50BF
3I>
4
4
I->O
51N/67N
94/86
TRIP CB2
IN>
4
4
I->O
CB2
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
51N/67N
IN>
4
4
51/67
3I>
4
4
94/86
TRIP CB3
50BF
3I>
I->O
3U>
TRIP BUSBAR
&CB1/2
25
SC/VC
59
2
2
CB3
27
3U<
2
2
en05000273.vsd
Figure 2:
A typical protection application for a two winding transformer in multi breaker arrangements is
shown on the figure. The system earthing principle and connection group will vary which gives
different detailed arrangements for each application. Breaker failure function is here provided for
each breaker.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 5
TRIP BUSBAR
50BF
3I>
51/67
3I>
4
4
94/86
TRIP CB1
I->O
CB1
51N/67N
IN>
4
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
50BF
TRIP BUSBAR
&CB1/2
51N/67N
3I>
IN>
4
4
3I>
4
4
51/67
3I>
94/86
TRIP CB2
94/86
4
4
50BF
3I>
I->O
59
3U>
TRIP BUSBAR
&CB1/2/3
2
2
I->O
TRIP
CB3
25
SC/
VC
CB2
59N
UN>
27
3U<
t2 2
2
2
2
en05000274.vsd
Figure 3:
A typical protection application for a three winding transformer in single breaker arrangements is
shown on the figure. The system earthing principle and connection group will vary which gives
different detailed arrangements for each application.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 6
TRIP BUSBAR&CB2/3/4
50BF
3I>
51/67
94/86
TRIP CB1
I->O
94/86
TRIP CB2
I->O
3I>
CB1
TRIP CB1/3/4/X
50BF
3I>
4
4
51N/67N
IN>
4
4
CB2
87N
IdN/I>
87T
3Id/I>
87N
TRIP BUSBAR 50BF
3I>
&CB1/2/3
IdN/I>
51N/67N
IN>
4
4
94/86
TRIP CB3
I->O
51/67
3I>
4
4
50BF
3I>
94/86
I->O
TRIP
CB4
25
SC/VC
59
3U>
TRIP BUSBAR
&CB1/2/4
3I>
4
4
2
2
27
3U<
CB3
59N
UN>
t2 2
2
2
2
en05000275.vsd
Figure 4:
A typical protection application for a three winding transformer in multi breaker arrangements is
shown on the figure. The system earthing principle and connection group will vary which gives
different detailed arrangements for each application. Breaker failure function is here provided for
each breaker.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 7
Available
functions
ANSI
Function description
Single breaker,
2 winding (A30)
Multi breaker,
2 winding (B30)
Single breaker,
3 winding (A40)
Multi breaker,
3 winding (B40)
Basic
Basic
Basic
Basic
Option
(Qty/
option
design)
Option
(Qty/
option
design)
Option
(Qty/
option
design)
Option
(Qty/
option
design)
Differential protection
87T
87T
87N
1/A01
1/A01
87
3/A02
3/A02
3/A02
3/A02
Distance protection
21
4/B02
4/B02
4/B02
4/B02
21
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
1/B02
78
Current protection
50
51/67
50N
49
1/C05
50BF
52PD
2/D02
1/C05
1/C05
1/C05
Voltage protection
27
1/D01
1/D01
2/D02
59
1/D01
1/D01
2/D02
2/D02
59N
1/D01
1/D01
2/D02
2/D02
24
1/D03
1/D03
2/D04
2/D04
Frequency protection
81
6/E01
6/E01
6/E01
6/E01
81
6/E01
6/E01
6/E01
6/E01
81
6/E01
6/E01
6/E01
6/E01
6/F02
6/F02
6/F02
6/F02
Multipurpose protection
General current and voltage protection (GAPC)
Secondary system supervision
Current circuit supervision (RDIF)
2/H01
3/H02
4/H03
1/H08
1/H08
1/H08
1/H09
12
12
12
12
3/10/3
3/10/3
3/10/3
3/10/3
Control
25
Logic
94
Monitoring
Measurements (MMXU)
Event counter (GGIO)
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 8
ANSI
Function description
Single breaker,
2 winding (A30)
Multi breaker,
2 winding (B30)
Single breaker,
3 winding (A40)
Multi breaker,
3 winding (B40)
Basic
Basic
Basic
Basic
Option
(Qty/
option
design)
Option
(Qty/
option
design)
Option
(Qty/
option
design)
Option
(Qty/
option
design)
16
16
16
16
IEC61850-8-1 Communication
60/10
60/10
60/10
60/10
Metering
Pulse counter logic (GGIO)
Station communication
Functionality
Differential protection
Transformer differential
protection (PDIF, 87T)
The RET 670 differential function for two winding
and three winding transformers is provided with
internal CT ratio matching and vector group compensation, which allows connection directly to star
connected main CTs. Zero sequence current elimination is made internally in the software.
xx05000052.vsd
xx05000053.vsd
2-winding applications
2-winding power transformer
xx05000057.vsd
xx05000048.vsd
Figure 5:
xx05000049.vsd
xx05000051.vsd
3-winding applications
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 9
The distance protection zones can operate, independent of each other, in directional (forward or
reverse) or non-directional mode.
Current protection
Instantaneous phase overcurrent
protection (PIOC, 50)
The instantaneous three phase overcurrent function
has a low transient overreach and short tripping
time to allow use as a high set short-circuit protection function, with the reach limited to less than
typical eighty percent of the power transformer at
minimum source impedance.
Four step phase overcurrent
protection (POCM, 51_67)
The four step phase overcurrent function has an
inverse or definite time delay independent for each
step separately.
All IEC and ANSI time delayed characteristics are
available together with an optional user defined
time characteristic.
xx05000058.vsd
Figure 6:
Distance protection
Distance protection zones (PDIS, 21)
The distance protection is a four zone full scheme
protection with three fault loops for phase to phase
faults and three fault loops for phase to earth fault
for each of the independent zones. Individual settings for each zone resistive and reactive reach
gives flexibility for use as back-up protection for
transformer connected to overhead lines and
cables.
The function has a functionality for load encroachment which increases the possibility to detect high
resistive faults on heavily loaded lines.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 10
Voltage protection
Two step undervoltage
protection (PUVM, 27)
Undervoltages can occur in the power system during faults or abnormal conditions. The function
can be used to open circuit breakers to prepare for
system restoration at power outages or as
long-time delayed back-up to primary protection.
The function has two voltage steps, each with
inverse or definite time delay.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 11
Frequency protection
Underfrequency protection (PTUF, 81)
Underfrequency occurs as a result of lack of generation in the network.
The function can be used for load shedding systems, remedial action schemes, gas turbine start-up
etc.
The function is provided with an undervoltage
blocking. The operation may be based on single
phase, phase-to-phase or positive sequence voltage
measurement.
Up to six independent under frequency function
instances are available.
Overfrequency protection (PTOF, 81)
Overfrequency will occur at sudden load drops or
shunt faults in the power network. In some cases
close to generating part governor problems can
also cause overfrequency.
The function can be used for generation shedding,
remedial action schemes etc. It can also be used as
a sub-nominal frequency stage initiating load
restoring.
The function is provided with an undervoltage
blocking. The operation may be based on single
phase, phase-to-phase or positive sequence voltage
measurement.
Up to six independent over frequency function
instances are available.
Rate-of-change frequency
protection (PFRC, 81)
Rate of change of frequency function gives an
early indication of a main disturbance in the system.
The function can be used for generation shedding,
load shedding, remedial action schemes etc.
The function is provided with an undervoltage
blocking. The operation may be based on single
phase, phase-to-phase or positive sequence voltage
measurement.
Each step can discriminate between positive or
negative change of frequency.
Up to six independent rate-of-change frequency
function instances are available.
Multipurpose protection
General current and voltage
protection (GAPC)
The protection module is recommended as a general backup protection with many possible application areas due to its flexible measuring and setting
facilities.
The built-in overcurrent protection feature has two
settable current levels. Both of them can be used
either with definite time or inverse time characteristic. The overcurrent protection steps can be made
directional with selectable voltage polarizing
quantity. Additionally they can be voltage and/or
current controlled/restrained. 2nd harmonic
restraining facility is available as well. At too low
polarizing voltage the overcurrent feature can be
either blocked, made non directional or ordered to
use voltage memory in accordance with a parameter setting.
Additionally two overvoltage and two undervoltage steps, either with definite time or inverse time
characteristic, are available within each function.
The general function suits applications with underimpedance and voltage controlled overcurrent
solutions. The general function can also be utilized
for generator transformer protection applications
where positive, negative or zero sequence components of current and voltage quantities is typically
required.
Additionally generator applications such as loss of
field, inadvertent energizing, stator or rotor overload, circuit breaker head flash-over and open
phase detection are just a few of possible protection arrangements with these functions.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 12
Control
Synchrocheck and energizing check
(RSYN, 25)
The synchrocheck function checks that the voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure
that closing can be done safely.
The function includes a built-in voltage selection
scheme for double bus and one- and a half or ring
busbar arrangements.
Manual closing as well as automatic reclosing can
be checked by the function and can have different
settings, e.g. the allowed frequency difference can
be set to allow wider limits for the auto-reclose
attempt than for the manual closing.
Apparatus control (APC)
The apparatus control is a function for control and
supervision of circuit breakers, disconnectors and
earthing switches within a bay. Permission to operate is given after evaluation of conditions from
other functions such as interlocking, synchrocheck, operator place selection and external or
internal blockings.
Interlocking
The interlocking function blocks the possibility to
operate primary switching devices, for instance
when a disconnector is under load, in order to prevent material damage and/or accidental human
injury.
Each apparatus control function has interlocking
modules included for different switchyard arrangements, where each function handles interlocking of
Logic
Tripping logic (PTRC, 94)
A function block for protection tripping is provided for each circuit breaker involved in the tripping of the fault. It provides the pulse prolongation
to ensure a trip pulse of sufficient length, as well as
all functionality necessary for correct co-operation
with autoreclosing functions.
The trip function block includes functionality for
evolving faults and breaker lock-out.
Trip matrix logic (GGIO, 94X)
Twelve trip matrix logic blocks are included in the
IED. The function blocks are used in the configuration of the IED to route trip signals and/or other
logical output signals to the different output relays.
The matrix and the physical outputs will be seen in
the PCM 600 engineering tool and this allows the
user to adapt the signals to the physical tripping
outputs according to the specific application needs.
Configurable logic blocks
A high number of logic blocks and timers are
available for user to adapt the configuration to the
specific application needs.
Fixed signal function block
The fixed signals function block generates a number of pre-set (fixed) signals that can be used in the
configuration of an IED, either for forcing the
unused inputs in the other function blocks to a certain level/value, or for creating a certain logic.
Monitoring
Measurements (MMXU)
The service value function is used to get on-line
information from the IED. These service values
makes it possible to display on-line information on
the local HMI and on the Substation automation
system about:
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 13
mA,
pulse counters,
Indications (IND)
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 14
Metering
Pulse counter logic (GGIO)
The pulse counter logic function counts externally
generated binary pulses, for instance pulses coming from an external energy meter, for calculation
of energy consumption values. The pulses are captured by the binary input module and then read by
the pulse counter function. A scaled service value
is available over the station bus. The special
Binary input module with enhanced pulse counting
capabilities must be ordered to achieve this functionality.
Keypad with push buttons for control and navigation purposes, switch for selection between
local and remote control and reset
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 15
Figure 8:
Station communication
Overview
Each IED is provided with a communication interface, enabling it to connect to one or many substa-
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 16
Remote communication
Binary signal transfer to remote end,
6 x 32 signals
Each of the six binary signal transfer function
blocks can be used for sending and receiving of 32
signals, transfer trip and/or other binary signals
between local and/or remote IEDs. An IED can
communicate with up to IEDs by means of the
data communication module (LDCM).
Line data communication module, short,
medium and long range (LDCM)
The line data communication module (LDCM) is
used for communication between the IEDs situated
at distances <150 km or from the IED to optical to
Hardware
description
Hardware modules
Power supply module (PSM)
The power supply module is used to provide the
correct internal voltages and full isolation between
the terminal and the battery system. An internal
fail alarm output is available.
Binary input module (BIM)
The binary input module has 16 optically isolated
inputs and is available in two versions, one standard and one with enhanced pulse counting capabilities on the inputs to be used with the pulse
counter function. The binary inputs are freely programmable and can be used for the input of logical
signals to any of the functions. They can also be
included in the disturbance recording and
event-recording functions. This enables extensive
monitoring and evaluation of operation of the IED
and for all associated electrical circuits.
Binary output modules (BOM)
The binary output module has 24 independent output relays and is used for trip output or any signalling purpose.
Binary input/output module (IOM)
The binary input/output module is used when only
a few input and output channels are needed. The
ten standard output channels are used for trip output or any signalling purpose. The two high speed
signal output channels are used for applications
where short operating time is essential. Eight optically isolated binary inputs cater for required
binary input information.
mA input module (MIM)
The milli-ampere input module is used to interface
transducer signals in the 20 to +20 mA range
from for example OLTC position, temperature or
electrical converter with G.703 or G.703E1 interface located on a distances <3 km away. The
LDCM module sends and receives data, to and
from another LDCM module. The IEEE/ANSI
C37.94 standard format is used.
The line data communication module is used for
binary signal transfer. The module has one optical
port with ST connectors.
Galvanic interface G.703
The external galvanic data communication converter G.703 makes an optical-to-galvanic conversion for connection to a multiplexer. These units
are designed for 64 kbit/s operation. The converter
is delivered with 19 rack mounting accessories.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 17
E
A
C
D
xx05000003.vsd
xx05000004.vsd
Figure 9:
Case size
6U, 1/2 x 19
265.9
223.7
201.1
242.1
252.9
205.7
6U, 3/4 x 19
265.9
336.0
201.1
242.1
252.9
318.0
6U, 1/1 x 19
265.9
448.1
201.1
242.1
252.9
430.3
(mm)
Mounting alternatives
Following mounting alternatives (IP40 protection
from the front) are available:
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 18
Connection
diagrams
Table 1:
Module
Rear Positions
PSM
X11
BIM, BOM or IOM X31 and X32 etc. to X51 and X52
Table 2:
Table 3:
GSM
X51
SLM
X301:A, B, C, D
OEM
X311:A, B, C, D
LDCM
X312:A, B
LDCM
X313:A, B
TRM
X401
Rear Positions
PSM
X11
GSM
X71
SLM
X301:A, B, C, D
LDCM
X302:A, B
LDCM
X303:A, B
OEM
X311:A, B, C, D
LDCM
X312:A, B
LDCM
X313:A, B
TRM
X401, 411
Rear Positions
PSM
X11
MIM
GSM
X131
SLM
X301:A, B, C, D
OEM
X311:A, B, C, D
LDCM
X312:A, B
LDCM
X313:A, B
TRM 1
X401
TRM 2
X411
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 19
AI08
AI09
AI10
9I and 3U, 1A
1A
1A
1A
1A
1A
1A
1A
1A
1A
9I and 3U, 5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
1A
1A
1A
1A
1A
5A
5A
5A
5A
6I and 6U, 1A
1A
1A
1A
1A
1A
1A
6I and 6U, 5A
5A
5A
5A
5A
5A
5A
6I, 1A
1A
1A
1A
1A
1A
1A
6I, 5A
5A
5A
5A
5A
5A
5A
AI11
AI12
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 20
Figure 14: Binary in/out module (IOM). Input contacts named XA corresponds to rear 2)
position X31, X41, etc. and output contacts named XB to rear position X32, 3)
X42, etc.
4)
5)
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 21
Figure 18: Binary output module (BOM). Output contacts named XA corresponds to rear position X31,
X41, etc. and output contacts named XB to rear position X32, X42, etc.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 22
BUS A
BUS B
BBP-TRIP
QB1-OPEN
QB1-CL
BLOCK LW 3I>
BBP STEP
QB2-OPEN
QB2-CL
-QB1
ST BFP 3PH
-QB2
BUCH TRIP
SUDDEN P
-QA1
OT TRIP
CLOSE QA1
CLOSE Reinf
WT TRIP
C
C
TRIP QA1
TRIP Reinf
OT WARN
T
C
MAIN 2 TRIP
T
C
QA1-OPEN
QA1-CL
WT WARN
OIL LOW
QA1-SPR UNCH
GAS ALARM
-BI1
P1
TRM1:1-3
TO MAIN 2 RELAY
FAULT
SIGNALLING
TO BUS PROT
TRM1:7
=
MIM1:1
-T1
-N.BI1
TAP POS
-N.BI1
TC IN MAN
TRM1:8
TC IN AUTO
MCB OR
FUSE
TC IN LOC.
TRM1:11-12
TC RAISE
TC LOWER
-BU1
MCB-OK
TO BUS PROT
HV BUSBAR TRIP
-BI1
MV BUSBAR TRIP
TO MAIN 2 RELAY
MAN SC OK
TRM1:4-6
P1
QA1-OPEN
QA1-CL
-QA1
SPR UNCH
CLOSE QA1
C
C
CLOSE Reinf
TRIP QA1
T
C
T
C
TRIP Reinf
TRM1:10
MCB OK
-BU1
IRF
- +
en05000262.vsd
Figure 19: Typical connection diagram for two winding transformer in a single breaker arrangement. Note! Including IO for control option.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 23
BUS A
BBP-TRIP
-QB1
QB1-OPEN
QB1-CL
BLOCK LW 3I>
BBP STEP
QB6-OPEN
QB6-CL
-QB62
-BI1
ST BFP 3PH
TRM1:4-6
BUCH TRIP
P1
-QA1
SUDDEN P
OT TRIP
WT TRIP
=1-QA1-OPEN
OT WARN
=2-Q0-OPEN
WT WARN
=2-Q0-CL
OIL LOW
CLOSE QA1
CLOSE Reinf
C
C
TRIP QA1
TRIP Reinf
MAIN 2 TRIP
T
C
=1-QA1-CL
T
C
=1-QA1-SPR UNCH
=2-Q0-SPR UNCH
GAS ALARM
TO MAIN 2
-BI1
TRM1:1-3
P1
-QA1
CLOSE QA1
C
C
FAULT
SIGNALLING
QB6-OPEN
QB6-CL
QB61-OPEN
QB61-CL
T
C
MAIN 2 TRIP
TO BB PROT
-QB61
-QB6
QB9-OPEN
QB9-CL
-QB9
O
TRM2:4
-T1
W
=
MIM1:1
T
C
TAP POS
TC IN MAN
TRM2:5
TC IN AUTO
TC IN LOC.
TRM1:10-12
TC RAISE
TC LOWER
MCB OR
FUSE
-BU1
MCB-OK
TO BUS PROT
-BI1
HV BUSBAR TRIP
MV BUSBAR TRIP
TO MAIN 2 RELAY
MAN SC OK
QA1-OPEN
QA1-CL
-QA1
SPR UNCH
CLOSE QA1
CLOSE Reinf
C
C
TRIP QA1
TRIP Reinf
T
C
T
C
BBP-TRIP
TRM2:10
MCB OK
-BU1
IRF
-
+
en05000263.vsd
Figure 20: Typical connection diagram for two winding transformer in a multi breaker arrangement. Note! Including IO for control option.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 24
BUS A
BUS B
BBP-TRIP
QB1-OPEN
QB1-CL
ST BFP
3PH
QB2-OPEN
QB2-CL
BLOCK TW 3I>
BBP STEP
-QB1
-QB2
BUCH TRIP
-QA1
SUDDEN P
OT TRIP
WT TRIP
OT WARN
CLOSE QA1
CLOSE Reinf
C
C
TRIP QA1
TRIP Reinf
MAIN 2 TRIP
T
C
T
C
QA1-OPEN
QA1-CL
WT WARN
OIL LOW
QA1-SPR UNCH
GAS ALARM
-BI1
P1
TRM1:1-3
QA1-OPEN
QA1-CL
TO MAIN 2 RELAY
FAULT
SIGNALLING
SPR UNCH
TO BUS PROT
CLOSE QA1
CLOSE Reinf
TRIP QA1
TRIP Reinf
O
W
TRM1:7
MIM1:1
TAP POS
TC IN MAN
TRM1:8
TC IN AUTO
TC IN LOC.
TRM2:7-9
TC RAISE
TC LOWER
MCB OR
FUSE
-BU1
MCB-OK
-BI1
-BI1
TO BUS PROT
HV BUSBAR TRIP
TRM2:4-6
MV BUSBAR TRIP
-QA1
TO MAIN 2 RELAY
P1
MAN SC OK
C
C
TRM2:1-3
P1
QA1-OPEN
QA1-CL
T
C
T
C
-QA1
SPR UNCH
CLOSE QA1
CLOSE Reinf
C
C
TRIP QA1
TRIP Reinf
T
C
T
C
TRM1:11
-BU1
MCB OK
TRM1:12
IRF
- +
-BU1
Res. for Bus 2
VT
en05000265.vsd
Figure 21: Typical connection diagram for three winding transformer in a single breaker arrangement. Note! Including IO for control option.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 25
BUS A
BBP-TRIP
QB1-OPEN
QB1-CL
BLOCK TW 3I>
BBP STEP
TO SECOND BAY
-QB1
QB62-OPEN
QB62-CL
-QB62
ST BFP 3PH
-BI1
BUCH TRIP
P1
TRM1:4-36
-QA1
SUDDEN P
CLOSE QA1
OT TRIP
WT TRIP
OT WARN
=2-Q0-OPEN
=2-Q0-CL
WT WARN
TRIP Reinf
MAIN 2 TRIP
=1-Q0-OPEN
=1-Q0-CL
T
C
T
C
=1-Q0-SPR UNCH
=2-Q0-SPR UNCH
OIL LOW
TO MAIN 2
C
C
CLOSE Reinf
TRIP QA1
-BI1
TRM1:1-3
GAS ALARM
P1
-QA1
CLOSE QA1
CLOSE Reinf
TRIP QA1
TRIP Reinf
FAULT
SIGNALLING
QB6-OPEN
QB6-CL
C
C
TO MAIN 2
T
C
MAIN 2 TRIP
TO BB PROT
-QB6
QB61-OPEN
QB61-CL
Q9-OPEN
Q9-CL
T
C
-QB61
-Q9
-T1
TRM1:7
TAP POS
TC IN MAN
TRM1:8
TC IN AUTO
TC IN LOC.
MCB-OK
MCB OR
FUSE
TC RAISE
TC LOWER
-BU1
TRM2:7-9
-BI1
TO BUS PROT
HV BUSBAR TRIP
-BI1
TRM2:4-6
MV BUSBAR TRIP
TRIP QA1
TRIP Reinf
QA1-OPEN
QA1-CL
SPR UNCH
-QA1
TO MAIN 2 RELAY
CLOSE QA1
CLOSE Reinf
MAN SC OK
P1
C
C
TRM2:1-3
P1
QA1-OPEN
QA1-CL
T
C
T
C
-QA1
SPR UNCH
CLOSE QA1
C
C
CLOSE Reinf
TRIP QA1
T
C
TRIP Reinf
T
C
TRM1:11
-BU1
MCB OK
TRM1:12
IRF
-
-BU1
Res. for Bus 2
VT
en05000259.vsd
Figure 22: Typical connection diagram for three winding transformer in a multi breaker arrangement. Note! Including IO for control option.
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 26
Technical data
General
Definitions
Reference value:
The specified value of an influencing factor to which are referred the characteristics of the equipment.
Nominal range:
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements.
Operative range:
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform
its intended functions according to the specified requirements.
Current
Ir = 1 or 5 A
Operative range
(0.02-100) x Ir
Permissive overload
4 Ir cont.
Nominal range
(0.2-40) Ir
100 Ir for 1 s *)
Burden
< 0.25 VA at Ir = 1 or 5 A
Ac voltage
Ur = 110 V
Operative range
(0340) V
Permissive overload
420 V cont.
0.5288 V
450 V 10 s
Burden
Frequency
*)
fr = 50/60 Hz
5%
Table 5:
Quantity:
Input range
Rated value:
Nominal range:
5, 10, 20mA
Power consumption
each mA-board
4W
each mA input
0.1 W
Auxiliary DC voltage
Table 6:
Quantity
Nominal range
EL = (24 - 60) V
EL 20%
EL = (90 - 250) V
EL 20%
Power consumption
50 W typically
Nominal range
Binary inputs
16
DC voltage, RL
RL24 (24/40) V
RL 20%
RL48 (48/60) V
RL 20%
RL110 (110/125) V
RL 20%
RL220 (220/250) V
RL 20%
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 27
Quantity
Rated value
Nominal range
RL24 = (24/40) V
RL48 = (48/60) V
RL110 = (110/125) V
RL220 = (220/250) V
10 pulses/s max
Power consumption
Binary inputs
16
DC voltage, RL
RL24 (24/40) V
RL 20%
RL48 (48/60) V
RL 20%
RL110 (110/125) V
RL 20%
RL220 (220/250) V
RL 20%
RL24 = (24/40) V
RL48 = (48/60) V
RL110 = (110/125) V
RL220 = (220/250) V
10 pulses/s max
40 pulses/s max
Power consumption
Nominal range
Binary inputs
DC voltage, RL
RL24 = (24/40) V
RL 20%
RL48 = (48/60) V
RL 20%
RL110 = (110/125) V
RL 20%
RL220 = (220/250) V
RL 20%
Power consumption
RL24 = (24/40) V
RL48 = (48/60) V
RL110 = (110/125) V
RL220 = (220/250) V
Table 10:
IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and signal relays
Fast signal relays (parallel reed relay)
Binary outputs
10
250 V AC, DC
250 V AC, DC
800 V DC
8A
8A
1s
10 A
10 A
0.2 s
30 A
0.4 A
1.0 s
10 A
0.4 A
250 V/8.0 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
220 V/0.2 A
250 V/0.15 A
250 V/0.15 A
10 nF
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 28
Table 11:
BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and Signal relays
Binary outputs
24
250 V AC, DC
1000 V rms
8A
1s
10 A
30 A
1.0 s
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
Influencing factors
Table 12:
Parameter
Nominal range
Influence
+20 C
-10 C to +55 C
0.02% /C
Relative humidity
10%-90%
10%-90%
Operative range
0%-95%
Storage temperature
-40 C to +70 C
Table 13:
Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Reference value
Within nominal range
Influence
max. 2%
12% of EL
0.01% /%
Operative range
20% of EL
0.01% /%
24-60 V DC 20%
90-250 V DC 20%
Interruption interval
050 ms
No restart
0 s
Correct behaviour at
power down
Restart time
<140 s
Table 14:
Frequency influence (reference standard: IEC 602556)
Dependence on
Within nominal range
Frequency dependence, operate value
fr 2.5 Hz for 50 Hz
Influence
1.0% / Hz
fr 3.0 Hz for 60 Hz
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr
content)
1.0%
6.0%
Electromagnetic compatibility
Type test values
Reference standards
2.5 kV
2.5 kV
Electrostatic discharge
15 kV air discharge
Direct applicaton
8 kV contact discharge
Indirect application
8 kV contact discharge
4 kV
IEC 60255-22-5
high energy
Power frequency immunity test
150-300 V,
50 Hz
Power frequency magnetic field test
1000 A/m, 3 s
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 29
Test
Reference standards
EN 61000-4-3
IEEE/ANSI C37.90.2
26-1000 MHz
Conducted electromagnetic field disturbance
10 V, 0.15-80 MHz
IEC 60255-22-6
Radiated emission
30-1000 MHz
IEC 60255-25
Conducted emission
0.15-30 MHz
IEC 60255-25
Table 16:
Test
Insulation
Type test values
Reference standard
Dielectric test
IEC 60255-5
Insulation resistance
Table 17:
Test
Environmental tests
Type test value
Reference standard
Cold test
IEC 60068-2-1
Storage test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-3
IEC 60068-2-30
Table 18:
Test
CE compliance
According to
Immunity
EN 61000-6-2
Emissivity
EN 61000-6-4
EN 50178
Table 19:
Test
Mechanical tests
Type test values
Reference standards
Vibration
Class I
IEC 60255-21-1
Class I
IEC 60255-21-2
Seismic
Class I
IEC 60255-21-3
Differential protection
Table 20:
Function
Accuracy
2.0% of Ir for I < Ir
Operating characteristic
Adaptable
Reset ratio
> 95%
(10-60)% of Ibase
Y-wye or D-delta
2.0% of Ir
25 ms typically at 0 to 2 x Id
20 ms typically at 2 to 0 x Id
12 ms typically at 0 to 5 x Id
25 ms typically at 5 to 0 x Id
2 ms typically at 0 to 5 x Id
Table 21:
Function
Operate characteristic
Adaptable
Reset ratio
>95%
(4.0-100.0)% of Ibase
2.0% of Ir
Directional characteristic
2.0 degree
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 30
Function
Range or value
Accuracy
Operate time
20 ms typically at 0 to 10 x Id
Reset time
25 ms typically at 10 to 0 x Id
(5.0-100.0)% of fundamental
2.0% of Ir
Table 22:
Function
Accuracy
1.0% of Ur for U < Ur
Operate voltage
(20-400) V
Reset ratio
>95%
Operate time
10 ms typically at 0 to 10 x Ud
Reset time
90 ms typically at 10 to 0 x Ud
2 ms typically at 0 to 10 x Ud
Distance protection
Table 23:
Function
Accuracy
Number of zones
(10-30)% of Ibase
(0.50-3000.00) /phase
(0.10-1000.00) /phase
(0.50-9000.00) /phase
Conditions:
(0.50-3000.00) /phase
(1.00-9000.00) /loop
(1.00-3000.00) /loop
Dynamic overreach
(0.000-60.000) s
0.5% 10 ms
Operate time
24 ms typically
Reset ratio
105% typically
Reset time
30 ms typically
Table 24:
Function
(5-30)% of Ibase
(0.101000.00) /phase
(0.503000.00) /phase
Accuracy
1.0% of Ir
2.0% static accuracy
2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees
(0.503000.00) /loop
(1.003000.00) /phase
105% typically
Power swing detection (RPSB, 78)
Range or value
(0.10-3000.00) /phase
Accuracy
2.0% static accuracy
2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Resistive reach
(0.101000.00) /loop
Timers
(0.000-60.000) s
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 31
Current protection
Table 26:
Function
Accuracy
1.0% of Ir at I Ir
Operate current
(1-2500)% of lbase
Reset ratio
> 95%
Operate time
25 ms typically at 0 to 2 x Iset
Reset time
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
Operate time
10 ms typically at 0 to 10 x Iset
Reset time
35 ms typically at 10 to 0 x Iset
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at = 100 ms
1.0% of I at I > Ir
Table 27:
Function
Accuracy
1.0% of Ir at I Ir
Operate current
(1-2500)% of lbase
Reset ratio
> 95%
(1-100)% of lbase
1.0% of Ir
2.0 degrees
(40.070.0) degrees
2.0 degrees
(75.090.0) degrees
2.0 degrees
(5100)% of fundamental
2.0% of Ir
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
19 curve types
25 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
15 ms typically
1.0% of I at I > Ir
Table 28:
Function
Accuracy
1.0% of Ir at I Ir
Operate current
(1-2500)% of lbase
Reset ratio
> 95%
Operate time
25 ms typically at 0 to 2 x Iset
Reset time
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
Operate time
10 ms typically at 0 to 10 x Iset
Reset time
35 ms typically at 10 to 0 x Iset
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at = 100 ms
1.0% of I at I > Ir
Table 29:
Function
Operate current
(1-2500)% of lbase
Reset ratio
> 95%
Accuracy
1.0% of Ir at I Ir
1.0% of I at I > Ir
-
1.0% of Ir
Timers
(0.000-60.000) s
0.5% 10 ms
19 curve types
(5100)% of fundamental
2.0% of Ir
2.0 degrees
(1100)% of Ubase
1.0% of Ur
25 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
15 ms typically
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 32
Table 30:
Function
(30250)% of Ibase
Operate time:
I 2 I p2
t = ln 2
I Ib 2
I = Imeasured
Alarm level 1 and 2
Operate current
(50250)% of Ibase
1.0% of Ir
Table 31:
Function
Accuracy
1.0% of Ir at I Ir
(5-200)% of lbase
> 95%
(2-200)% of lbase
1.0% of Ir at I Ir
> 95%
1.0% of I at I > Ir
1.0% of I at I > Ir
-
1.0% of Ir at I Ir
Reset ratio
> 95%
Timers
(0.000-60.000) s
0.5% 10 ms
10 ms typically
15 ms maximum
Table 32:
Function
1.0% of I at I > Ir
Accuracy
Operate current
(0100% of Ibase
1.0% of Ir
Time delay
(0.000-60.000) s
0.5% 10 ms
Voltage protection
Table 33:
Function
Accuracy
(1100)% of Ubase
1.0% of Ur
Absolute hysteresis
(0100)% of Ubase
1.0% of Ur
(1100)% of Ubase
1.0% of Ur
See table 67
(0.000-60.000) s
0.5% 10 ms
(0.00060.000) s
0.5% 10 ms
25 ms typically at 2 to 0 x Uset
25 ms typically at 0 to 2 x Uset
10 ms typically at 2 to 0 x Uset
15 ms typically
Table 34:
Function
Accuracy
1.0% of Ur at U < Ur
(1-200)% of Ubase
Absolute hysteresis
(0100)% of Ubase
See table 68
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
25 ms typically at 0 to 2 x Uset
1.0% of U at U > Ur
1.0% of Ur at U < Ur
1.0% of U at U > Ur
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 33
Function
Range or value
Accuracy
25 ms typically at 2 to 0 x Uset
10 ms typically at 0 to 2 x Uset
15 ms typically
Table 35:
Function
Accuracy
(1-200)% of Ubase
Absolute hysteresis
(0100)% of Ubase
1.0% of Ur at U < Ur
See table 69
(0.00060.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
25 ms typically at 0 to 2 x Uset
25 ms typically at 2 to 0 x Uset
10 ms typically at 0 to 2 x Uset
15 ms typically
1.0% of U at U > Ur
Table 36:
Function
Accuracy
(100180)% of (Ubase/frated)
1.0% of U
1.0% of Ur at U Ur
(100200)% of (Ubase/frated)
1.0% of U
Curve type
Class 5 + 40 ms
1.0% of U at U > Ur
IEEE : t =
(0.18 k )
( M 1) 2
0.5% 10 ms
(0.009000.00) s
0.5% 10 ms
(0.00060.000) s
0.5% 10 ms
Frequency protection
Table 37:
Function
Accuracy
(35.00-75.00) Hz
2.0 mHz
100 ms typically
100 ms typically
(0.000-60.000)s
0.5% + 10 ms
(0.000-60.000)s
0.5% + 10 ms
Settings:
Class 5 + 200 ms
UNom=(50-150)% of Ubase
U UMin
t=
UNom UMin
Exponent
UMin=(50-150)% of Ubase
tMax=(0.001-60.000)s
tMin=(0.000-60.000)s
U=Umeasured
Table 38:
Function
Exponent=0.0-5.0
Accuracy
(35.00-75.00) Hz
2.0 mHz
100 ms typically
100 ms typically
(0.000-60.000)s
0.5% + 10 ms
(0.000-60.000)s
0.5% + 10 ms
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 34
Table 39:
Function
Accuracy
(-10.00-10.00) Hz/s
10.0 mHz/s
(0-100)% of Ubase
1.0% of Ur
100 ms typically
Multipurpose protection
Table 40:
Function
Accuracy
Base current
(1 - 99999) A
Base voltage
(0.05 - 2000.00) kV
(2 - 5000)% of Ibase
(2 - 150)% of Ibase
(0.00 - 6000.00) s
0.5% 10 ms
25 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
25 ms typically at 2 to 0 x Iset
25 ms typically at 0 to 2 x Iset
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory
takes over
1.0% of Ur
25 ms typically at 0 to 2 x Uset
25 ms typically at 2 to 0 x Uset
25 ms typically 2 to 0 x Uset
25 ms typically at 0 to 2 x Uset
Directional function
2.0 degrees
(1 to 90) degrees
2.0 degrees
> 95%
< 105%
> 95%
< 105%
10 ms typically at 0 to 2 x Iset
15 ms typically
Overcurrent:
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 35
Function
Range or value
Accuracy
10 ms typically at 2 to 0 x Iset
15 ms typically
10 ms typically at 0 to 2 x Uset
15 ms typically
10 ms typically at 2 to 0 x Uset
15 ms typically
Undercurrent:
Overvoltage:
Undervoltage:
Operate current
(5-200)% of Ir
Block current
(5-500)% of Ir
Accuracy
10.0% of Ir at I Ir
10.0% of I at I > Ir
5.0% of Ir at I Ir
5.0% of I at I > Ir
Table 42:
Function
Accuracy
(1-100)% of Ubase
1.0% of Ur
(1100)% of Ibase
1.0% of Ir
(1100)% of Ubase
1.0% of Ur
(1100)% of Ibase
1.0% of Ir
(1100)% of Ubase
5.0% of Ur
(1100)% of Ibase
5.0% of Ir
Control
Table 43:
Function
Accuracy
(0.20-5.00)% of Ubase
(50.0-120.0)% of Ubase
1.0% of Ur at U Ur
> 95%
1.0% of U at U > Ur
-
2.0 mHz
(5.0-90.0) degrees
2.0 degrees
(2.0-50.0)% of Ubase
1.0% of Ur
(0.000-60.000) s
0.5% 10 ms
(50.0-120.0)% of Ubase
1.0% of Ur at U Ur
> 95%
(10.0-80.0)% of Ubase
1.0% of Ur
< 105%
(80.0-140.0)% of Ubase
1.0% of Ur at U Ur
(0.000-60.000) s
1.0% of U at U > Ur
1.0% of U at U > Ur
0.5% 10 ms
80 ms typically
Logic
Table 44:
Function
Accuracy
Trip action
(0.000-60.000) s
0.5% 10 ms
Timers
(0.000-60.000) s
0.5% 10 ms
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 36
Table 45:
Logic block
Range or value
Accuracy
160
160
10
20
30
30
80
LogicSRMemory
10
10
20
LogicGate
10
10
20
LogicTimer
10
10
20
(0.00090000.000) s 0.5% 10 ms
LogicPulseTimer
10
10
20
(0.00090000.000) s 0.5% 10 ms
LogicTimerSet
10
10
20
(0.00090000.000) s 0.5% 10 ms
LogicLoopDelay
10
10
20
(0.00090000.000) s 0.5% 10 ms
fast
medium
normal
LogicAND
60
60
LogicOR
60
60
LogicXOR
10
LogicInverter
Monitoring
Table 46:
Function
Measurements (MMXU)
Range or value
Accuracy
Frequency
(0.95-1.05) fr
2.0 mHz
Voltage
(0.1-1.5) Ur
0.5% of Ur at U Ur
Connected current
(0.2-4.0) Ir
Active power, P
1.0% of Sr at S Sr
1.0% of S at S > Sr
1.0% of Sr at S Sr
1.0% of S at S > Sr
1.0% of Sr at S Sr
1.0% of S at S > Sr
0.02
0.5% of U at U > Ur
0.5% of Ir at I Ir
0.5% of I at I > Ir
Reactive power, Q
Apparent power, S
Power factor, cos ()
mA measuring function
5, 10, 20 mA
Accuracy
0.1 % of set value 0.005 mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(0.0-20.0) mA
Table 48:
Function
Accuracy
Counter value
0-10000
10 pulses/s
Table 49:
Function
Accuracy
Pre-fault time
(0.050.30) s
Post-fault time
(0.15.0) s
Limit time
(0.56.0) s
100
1 ms
96
96
150
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 37
Function
Range or value
Accuracy
1 kHz at 50 Hz
1.2 kHz at 60 Hz
Recording bandwidth
(5-300) Hz
Metering
Table 50:
Function
Input frequency
Accuracy
Station communication
Table 51:
Function
Protocol
IEC 61850-8-1
100BASE-FX
Table 52:
Function
Value
Protocol
LON
Communication speed
1.25 Mbit/s
Table 53:
Function
Value
Protocol
SPA
Communication speed
Slave number
1 to 899
Table 54:
Function
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
Table 55:
Quantity
Optical connector
Fibre diameter
Plastic fibre: 1 mm
*) depending on optical budget calculation
Table 56:
Quantity
Optical connector
Fibre diameter
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 38
Remote communication
Table 57:
Quantity
Type of fibre
Wave length
820 nm
Optical budget
Graded-index multimode 62.5/125 m
13 dB (typical distance 3 km *)
9 dB (typical distance 2 km *)
Optical connector
Type ST
Protocol
C37.94
Data transmission
Synchronous
Transmission rate
64 kbit/s
Clock source
Hardware
IED
Table 58:
Material
Case
Steel sheet
Front plate
Surface treatment
Finish
Table 59:
Front
IP20
Weight
Weight
6U, 1/2 x 19
10 kg
6U, 3/4 x 19
15 kg
6U, 1/1 x 19
18 kg
Connection system
Table 61:
CT and VT circuit connectors
Connector type
Rated voltage and current
4 mm2
250 V AC, 20 A
Table 62:
Binary I/O connection system
Connector type
Rated voltage
2.5 mm2
250 V AC
2 1 mm2
Recording manner
List size
Table 64:
Function
1.0 ms typically
1.0 ms typically
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 39
Inverse characteristics
Table 65:
Function
Operate characteristic:
Accuracy
t =
A
P
( I 1)
+ B k
Reset characteristic:
t =
(I
tr
2
I = Imeasured/Iset
Accuracy
(0.000-60.000) s
A=0.14, P=0.02
A=13.5, P=1.0
IEC Inverse no 11
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
Operate characteristic:
t =
A
P
k
( I 1)
I = Imeasured/Iset
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 40
Function
Range or value
Accuracy
Operate characteristic:
A=(0.005-200.000) in steps of
0.001
A
=
(I P C )
+ B k
Reset characteristic:
t =
(I
TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
TR
PR
CR
PR=(0.005-3.000) in steps of
0.001
I = Imeasured/Iset
RI inverse characteristic no 18
t =
0.339
0.236
I
I = Imeasured/Iset
Logarithmic inverse characteristic no 19
t = 5.8 1.35 In
I
k
I = Imeasured/Iset
Table 67:
Function
Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
Range or value
Accuracy
Type A curve:
t =
U < U
U<
U< = Uset
U = Umeasured
Type B curve:
t =
k 480
32 U < U 0.5
U <
2.0
+ 0.055
U< = Uset
U = Umeasured
Programmable curve:
kA
+D
t =
P
U < U
C
B
U <
U< = Uset
U = Umeasured
Class 5 +40 ms
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 41
Table 68:
Function
Inverse time characteristics for Two step overvoltage protection (POVM, 59)
Range or value
Accuracy
Type A curve:
t =
U U >
U>
U> = Uset
U = Umeasured
Type B curve:
t =
k 480
32 U U > 0.5
U >
2.0
0.035
Type C curve:
t =
k 480
32 U U > 0.5
U >
3.0
0.035
Programmable curve:
t =
kA
B U U >
U >
+D
B = (0.50-100.00) in steps of
0.01
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Class 5 +40 ms
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 42
Table 69:
Function
Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N)
Range or value
Accuracy
Type A curve:
t =
U U >
U>
U> = Uset
U = Umeasured
Type B curve:
t =
k 480
32 U U > 0.5
U >
2.0
0.035
Type C curve:
t =
k 480
32 U U > 0.5
U >
3.0
0.035
Programmable curve:
t =
kA
B U U >
U >
+D
B = (0.50-100.00) in steps of
0.01
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in steps of
0.001
P = (0.000-3.000) in steps of
0.001
Class 5 +40 ms
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 43
Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the function matrix for included software functions given in
each software option package. Please observe that the character length of the software option section varies depending on the included options.
Enter option codes in the shaded spaces to complete the ordering number. To obtain the complete ordering code, please combined code from sheet 1 and sheet
2, as given in the example below. 1 BIM and 1 BOM is basic. Order futher I/O as required.
Sheet 1
RET 670*
Sheet 2
-
SOFTWARE
Version number
XX
Latest version
1.0
Version No
Configuration alternatives
A30
Single Breaker, 2 winding
A40
Single Breaker, 3 winding
B30
Multi Breaker, 2 winding
B40
Multi Breaker, 3 winding
CAP configuration
X00
ABB standard configuration
Software options
No option
Restricted earth fault protection
High impedance differential protection
Transformer distance protection
Thermal overload protection
Voltage protection, 1 bus
Voltage protection, 2 buses
X00
A01
D01
D02
D03
D04
E01
F02
H01
H02
H03
H08
H09
X0
A1
A2
A3
A4
A5
A6
A7
A8
A9
Casing
1/2 19 case
3/4 19 case 2TRM slots
1/1 19 case 2TRM slots
A
C
E
A
B
C
D
E
F
A
B
A
B
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 44
Sheet 2
-
A3
A4
A5
X0 Note: 2 TRM in A40, B30 and B40
A3
A4
A5
Example:
RET 670*1.0-A30-A01B02D02D03F02-X0-A-A-B-A-A5X0-DAX-X-XD
X
A
X
A
X
A
X
A
X
A
B
C
D
E
F
B
C
D
E
F
B
C
D
E
F
B
C
D
E
F
B
C
D
E
F
B
C
D
E
F
B
C
D
E
F
L
M
N
L
M
N
L
M
N
L
M
N
L
M
N
L
M
N
L
M
N
X
A
X311
X
A
X312
X131
X61
X51
X71
X
A
X301
X41
X31
Binary input and output, mA and time synchronizating boards. Note! Basic 1 BIM and 1 BOM included.
Slot position (rear view)
Note! Max 3 positins in 1/2 rack and 11 in 1/1 rack with 2 TRM and 14 in 1/1 rack
wiht 1 TRM (=grey fields)
1/2 Case with 1 TRM (A30)
Note! Only for A30.
3/4 Case with 2 TRM
1/1 Case with 2 TRM
X
X
No board in this slot
A
A
A
Binary output module 24 output relays
Note! Maximum 4 (BOM + MIM) boards
(BOM)
B
B
B
BIM 16 inputs, RL24-30 VDC
C
C
C
BIM 16 inputs, RL48-60 VDC
D
D
D
BIM 16 inputs, RL110-125 VDC
E
E
E
BIM 16 inputs, RL220-250 VDC
F
F
BIMp 16 inputs, RL24-30 VDC for pulse
counting
G
G
BIMp 16 inputs, RL48-60 VDC for pulse
counting
H
H
BIMp 16 inputs, RL110-125 VDC for
pulse counting
K
K
BIMp 16 inputs, RL220-250 VDC for
pulse counting
L
L
IOM 8 inputs, 10+2 output, RL24-30 VDC
M
M
IOM 8 inputs, 10+2 output, RL48-60 VDC
N
N
IOM 8 inputs, 10+2 output, RL110-125
VDC
P
P
IOM 8 inputs, 10+2 output, RL220-250
VDC
R
mA input module 6 channels (MIM)
Note! Max 4 (BOM + MIM) board in 1/1
case. Max 1 MIM + 3 BOM in 3/4 case. No
MIM board in 1/2 case
Serial communication unit for remote end communication
Slot position (rear view)
X121
A6
A7
A8
A9
X111
X101
X91
X81
X
X
A
B
C
D
E
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 45
Accessories
Interface converter (for remote end data communication)
External interface converter from C37.94 to G703 including 1U 19
rack mounting accessories
Test switch
The test system COMBITEST intended for use
with the IED670 products is described in 1MRK
512 001-BEN and 1MRK 001024-CA. Please refer
to the website www.abb.com/substationautomation
and ABB Product Guide > High Voltage Products
> Protection and Control > Modular Relay > Test
Equipment for detailed information
Due to the high flexibility of our product and the
wide variety of applications possible the test
switches needs to be selected for each specific
application.
Select your suitable test switch based on the available contacts arrangements shown in the reference
documentation.
However our proposal for suitable variants are:
Two winding transformer with internal neutral on
current circuits. Two pcs can be used in applications for three winding transformers in single or
multi-breaker arrangement (ordering number
RK926 215-BD)
Quantity:
Mounting details
19 rack mounting kit for one test switch
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 46
High impedance resistor unit 1-ph with resistor and voltage dependent
resistor 20-100V
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 20-100V
3
RK795101-MA
Quantity:
RK795101-MB
High impedance resistor unit 1-ph with resistor and voltage dependent
resistor 100-400V
High impedance resistor unit 3-ph with resistor and voltage dependent
resistor 100-400V
Quantity:
Quantity:
RK795101-CB
Quantity:
RK795101-DC
Combiflex
Key switch for lock-out of settings via LCD-HMI
Quantity:
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Side-by-side mounting kit
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
PCM 600 ver. 1.1, Engineering Pro, IED Manager + CAP 531 + CCT
for IEC 61850-8-1 configuration of IED
Manuals
Note: One (1) IED Connect CD containing user documentation (Operators manual, Technical reference manual, Installation and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested
Quantity:
Quantity:
Quantity:
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 47
Quantity:
Quantity:
Application manual
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country:
End user:
Station name:
Voltage level:
kV
Related documents
Documents related to RET 670
Identity number
Operators manual
Application manual
Buyers guide
Configuration diagram A, Two winding transf. with single or double busbar but with a single 1MRK 004 500-93
breaker arr. on both sides
Configuration diagram B, Two winding transf. in multi breaker arr. on one or both sides
Configuration diagram C, Three winding transf. with single or double busbar but with a sin- 1MRK 004 500-95
gle breaker arr. on both sides
Configuration diagram D, Two winding transf. in multi breaker arr. on one or both sides
1KHA001027UEN
1MRS755552
Manufacturer
ABB Power Technologies AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation
Buyer's Guide
Pre-configured
1MRK 504 080-BEN
Revision: G, Page 48