Professional Documents
Culture Documents
57
Air test
Air tests are sometimes used instead of the water or hydrostatic tests of completed installations.
Cast iron soil pipe and fittings joined with rubber compression joints or hubless mechanical cou-
58
INSTALLATION
plings are expected to have a reduction in air pressure during a 15-minute test. This drop in air pressure does not indicate a failure of the system or that the system will leak water. Because molecules
of air are much smaller than water molecules, a cast iron system is expected to have a reduction in
air pressure during the 15-minute test period.
Caution: Materials under pressure can explode, causing serious injury or death. Extreme
care should be exercised in conducting any air test. Persons conducting an air test must exercise care to avoid application of pressure above 6 psig to the system under test by using
appropriate pressure regulation and relief devices. Persons conducting the test are cautioned
to inspect for tightness of all system components prior to beginning the test and to avoid
adjustment of the system while under pressure. Proper protective equipment should be worn
by individuals in any area where an air test is being conducted.
Prior to performing the air test all, threaded openings shall be sealed with a manufacturers recommended sealant. All additional openings should be sealed using test plugs recommended for use
in performing the air test. Some manufacturers recommend the use of adhesive lubricants on the
gasketed joints when air testing.
The system shall be pressurized to a maximum of 6 PSI utilizing a gauge graduated to no more
than three times the test pressure. The gauge shall be monitored during the 15-minute test period. A
reduction of more than 1 PSI during the test period indicates failure of the test. Upon completion of
the test, depressurize the system and remove test plugs.
Water Test
A water or hydrostatic test is the most common of all tests used to inspect a completed cast iron
soil pipe installation. The purpose of the test is to locate any leaks at the joints and correct these
prior to putting the system in service. Because it is important to be able to visually inspect the
joints, water tests should be conducted prior to the closing in of the piping or backfill of the
underground piping.
As water fills a vertical cylinder or vertical pipe, it creates hydrostatic pressure. The pressure
increases as the height of the water in the vertical pipe increases. The Cast Iron Soil Pipe Institute
recommends ten feet of hydrostatic pressure (4.3 pounds per square inch); this is the recommended
test by most plumbing codes. To isolate each floor or section being tested, test plugs are inserted
through test tees installed in the stacks. All other openings should be plugged or capped with test
plugs or test caps. (See Figure 18.)
Prior to the beginning of the test, all bends, changes of direction, and ends of runs should be
properly restrained. During the test, thrust forces are exerted at these locations. Thrust is equal to the
hydrostatic pressure multiplied by area. Thrust pressures, if not restrained, will result in joint movement or separation, causing failure of the test. All air trapped in the system should be expelled prior
to beginning the tests.
Once the stack is filled to ten feet, an inspector makes a visual inspection of the section being
tested to check for joint leaks. In most cases, where these leaks are found, hubless couplings have
not been torqued to the recommended 60 in. lbs. Proper torquing will correct the problem. If leaks
occur during testing of hub-and-spigot materials, the joint should be disassembled and checked for
proper installation.
Fifteen minutes is a suitable time for the water test. Once the system has been successfully
tested, it should be drained and the next section should be prepared for test.
INSTALLATION
59
Smoke Test
When a smoke test is required by engineers, architects, or plumbing codes, it is applied to all
parts of the drainage and venting systems after all fixtures have been permanently connected
and all traps filled with water. A thick, penetrating smoke produced by one or more smoke
machines, not by a chemical mixture, is introduced into the system through a suitable opening.
As smoke appears at the stack opening on the roof, the opening is closed off and the introduction of smoke is continued until a pressure of 1 inch of water has been built up and maintained
for 15 minutes or longer as required for the system. Under this pressure, smoke should not be
visible at any point, connection, or fixture. All windows in the building should be closed until
the test is completed.
Peppermint Test
Some engineers, architects, and plumbing codes require a peppermint test to be applied to all
parts of the drainage and venting system after all fixtures have been permanently connected and
all trap seals filled with water. A mixture of two ounces of oil of peppermint and one gallon of
hot water is poured into the roof opening of the system, which is then tightly closed. There
should be no odor of peppermint within the building at any point, connection, or fixture as a
result of the peppermint mixture having been introduced into the system. Operators who pour the
peppermint mixture must not enter the building to do the testing. The peppermint test is usually
used in old installations to detect faulty plumbing.
60
INSTALLATION
Thrust Forces
Thrust or displacement forces are encountered as the pipe or cylinder is filled with water. The
higher the fill the greater the force acting to separate a joint. Table 1 shows the pounds of force
tending to cause joint separation when using pipe from 1 1/2 to 15 and a head of water from 10.
to 120.
PAINTING CAST IRON SOIL PIPE
Cast iron soil pipe and fittings that have been factory coated with a bituminous coating can be painted if desired. A primer coat of latex emulsion paint, which is readily available in retail outlets, is
applied. Following the latex prime coat, a finish coat of enamel may be applied.
The latex paint prevents the bleeding of the bituminous coating, and the finish coat of enamel
in an appropriate color blends the cast iron soil pipe and fittings with the interior surroundings.
SIZING SOIL, WASTE, AND VENT LINES
The sizing of soil, waste and vent lines should be based on fixture load. The most accurate method
of calculating fixture load is by using the fixture unit basis. One fixture unit is defined as 7.5 gallons of water per minute. A lavatory in a private home is considered to use approximately 7.5 gallons of water per minute under maximum conditions, and other fixtures are governed by this yard
stick. For example, a water closet requires more water than a lavatory, and thus it has a higher numTABLE 1
Thrust or Displacement Forces Encountered in
Hydrostatic Testing of CI No-Hub Cast Iron Soil Pipe.
Pipe Size
112
10
12
15
Thrust
lb.
Thrust
lb.
Thrust
lb.
Thrust
lb.
Thrust
lb.
Thrust
lb.
Thrust
lb.
Head,
Feet of
Water
Pressure
PSI
Thrust
lb.
Thrust
lb.
Thrust
lb.
10
4.3
12
19
38
65
95
134
237
377
538
847
20
8.7
25
38
77
131
192
271
480
762
1088
1714
30
13.0
37
56
115
196
287
405
717
1139
1636
2562
40
17.3
49
75
152
261
382
539
954
1515
2164
3409
50
21.7
62
94
191
327
479
676
1197
1900
2714
4276
60
26.0
74
113
229
392
574
810
1434
2277
3252
5124
70
30.3
86
132
267
457
668
944
1671
2654
3790
5971
80
34.7
99
151
306
523
765
1082
1914
3039
4340
6838
90
39.0
111
169
344
588
860
1216
2151
3416
4878
7685
100
43.4
123
188
382
654
957
1353
2394
3801
5429
8552
110
47.7
135
208
420
719
1052
1487
2631
4178
5967
9400
52.0
147
226
458
784
1147
1621
2868
4554
6505
10247
2.84
4.34
8.81
15.07
22.06
31.17
55.15
87.58
125.09
197.06
120
2