Table of contents
1.0
2.0
3.0
4.0
5.0
6.0

Intent
Reference documents/ drawings
System description
Design inputs
Design calculation
Summary

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP

!"
$ %
&

&

&
&

'

"#

())*" +,

Sizing Calculation
1.0 Intent
Intent for this document is to calculate UAT (unit auxiliary transformer) and UST (unit station transformer) LV
side current transformer sizes (and various parameters) being adapted in the proposed power project.
2.0 Reference documents/ drawings
a. DBR Electrical system:
b. Key SLD:
c. Metering & protection SLD
Generator/ GT/ UAT/ UST:

ABB document 3VYN931101-A, Rev 4


ABB drawing 3VYN931101, Rev 4
ABB drawing 3VYN931102, Rev 1

3.0 System description


The project involves two identical steam turbine generator units rated for 150MW, 15.75kV, 3-ph, 50Hz, 0.8pf
each. Evacuation of generated electric power is envisaged at 400kV by interconnecting the power plant to
RSEB/ PGCIL 400kV grid.
6.6kV and 415V plant unit loads shall be fed from UAT-1 for unit 1 and UAT-2 for unit 2. UATs shall be directly connected to respective generator terminals through isolated phase busduct (IPBD). LV side (6.6kV) of
UATs shall be connected to 6.6kV unit auxiliary switchgear through segregated phase busduct (SPBD).
6.6kV and 415V common plant station loads shall be fed from UST-1 and UST-2. USTs shall be directly connected to respective generator terminals through isolated phase busduct (IPBD). LV side (6.6kV) of USTs
shall be connected to 6.6kV unit station switchgear through segregated phase busduct (SPBD).
LV neutral of all UATs/ USTs shall be grounded through neutral grounding resistor (NGR) by cable.
4.0 Design inputs
Following design inputs have been considered while sizing CTs being provided on UAT and UST LV side,
Description
Unit auxiliary transformer (UAT)
Rated capacity
Rated primary voltage
Rated secondary voltage
Rated impedance
Unit station transformer (UST)
Rated capacity
Rated primary voltage
Rated secondary voltage
Rated impedance
Cable
2.5mm cable (for -/1A CT) resistance at 70C

Value
20MVA
15.75kV
6.9kV
8 at base MVA of 20
25MVA
15.75kV
6.9kV
10 at base MVA of 25
8.8 /kM

5.0 Design calculation


As per ABB relay standard,
........................................(equation 1)
..........................................(equation 2)
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP

!"
$ %
&
Where,
Inf
I1f
Isn
Ipn
Ir
RCT
RL
Sr

&

&
&

())*

'

"#
+,

rated current (amps)


maximum primary fundamental frequency current (amps) that passes through two main CTs
rated secondary CT current (amps)
rated primary CT current (amps)
rated secondary current (amps) of protection IED
CT resistance ( )
loop resistance ( )
burden (VA) of IED current input channel

The knee point voltage should be greater than Eal.


UAT LV (6.6kV) phase side REF protection CT sizing calculation
Description
UAT rating
Primary voltage
Secondary voltage
Percentage impedance (%Z)
CT ratio
Cable length between CT and relay (approx)
Cable resistance (2.5mm )
Loop resistance
UAT calculated secondary current
Maximum secondary fundamental frequency
current that passes through CT and UAT =

Unit
MVA
kV
kV

RL
Inf
I1f

Value
20
15.75
6.9
8
2000/1
150
8
2.4
1673.47
20918.49

Isn
RCT
Ipn
Ir
Sr

1
5
2000
1
0.02

Eal Ealreq (using ABB equation 1)


Vk = 0.8 * Eal
10% margin on Vk

186.25
149.00
163.90

volts
volts
volts

Eal Ealreq (using ABB equation 2)


Vk = 0.8 * Eal
10% margin on Vk

155.21
124.17
136.58

volts
volts
volts

!" #$"% &&


'(%)*+%,

Rated CT secondary current


CT secondary resistance
Rated CT primary current
Rated secondary current of protection IED
Burden of IED current input channel

A
meter
/kM
A
A

A
A
VA/channel

Offered CT 2000/1A, Vk- 200V, RCT- 5 , Imag-30mA at (Vk/2)


UST LV (6.6kV) phase side REF protection CT sizing calculation
Description
UST rating
Primary voltage
Secondary voltage
Percentage impedance (%Z)
CT ratio
Cable length between CT and relay (approx)
Cable resistance (2.5mm )

Value
25
15.75
6.9
10
2500/1
150
8

Unit
MVA
kV
kV
A
meter
/kM

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP

!"
$ %
&

&

&

&

())*6 +,

'

Loop resistance
UST calculated primary current
Maximum primary fundamental frequency current that passes through CT and UST =

RL
Inf
I1f

2.4
2091.849
20918.49

Rated CT secondary current


CT secondary resistance
Rated CT primary current
Rated secondary current of protection IED
Burden of IED current input channel

Isn
RCT
Ipn
Ir
Sr

1
5
2500
1
0.02

Eal Ealreq (using ABB equation 1)


Vk = 0.8 * Eal
10% margin on Vk

186.25
149.00
163.90

volts
volts
volts

Eal Ealreq (using ABB equation 2)


Vk = 0.8 * Eal
10% margin on Vk

124.17
99.33
109.27

volts
volts
volts

#$"% &&
(%)*+%
&
'

"#

A
A

A
A
VA/channel

Offered CT 2500/1A, Vk- 200V, RCT- 5 , Imag-30mA at (Vk/2)


UAT/ UST LV (6.6kV) neutral side REF protection CT sizing calculation
Description
Limited fault current at UAT secondary
CT ratio
Cable length between CT and relay (approx)
Cable resistance (2.5mm )
Loop resistance
Rated CT secondary current
CT secondary resistance
Rated CT primary current
Rated secondary current of protection IED
Burden of IED current input channel
.
/0
-#

RL
Isn
RCT
Ipn
Ir
Sr

Value
300
300/1
150
8
2.4
1
1
300
1
0.02
3.42

Unit
A
A
meter
/kM
A
A
A
VA/channel
volts

Offered CT 300/1A, Vk- 100V, RCT- 1 , Imag-30mA at (Vk/2)


6.0 Summary
Following specifications are chosen for UAT and UST LV side CTs:
Location
UAT LV
side Phases
CTs
UAT LV
side Neutral
CTs
UST LV
side -

Ratio
2000/1A

Purpose
UAT REF
protection

Class
PS

300/1A

UAT REF
protection
UAT SEF
protection
UST REF
protection

PS

300/1A
2500/1A

5P20
PS

Vk
200V

Imag
30mA
at Vk/2

RCT
5

100V

30mA
at Vk/2
-

200V

30mA
at Vk/2

VA
-

Accuracy
-

ISF
-

10

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP

!"
$ %
&
Location
Phases
CTs
UST LV
side Neutral
CTs

&

Ratio

Purpose

Class

300/1A

UST REF
protection
UST SEF
protection

PS

300/1A

&

5P20

&
Vk
100V
-

())*, +,

'
Imag
30mA
at Vk/2
-

"#

RCT
1
-

VA

Accuracy

ISF

10

******

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.