Air Humidity Control

Installation, Operation and Maintenance Manual


AIR DEHUMIDIFIER DESICCANT ROTOR TYPE

MODEL DFRC-0400-E
SERIAL N: 1062006/07

According to the current European Union Rules on Machinery Safety, the


reading of these instructions is Imperative before installing the unit.

FISAIR, S.L.
Uranio,20 - P.I. AIMAYR
28330 San Martin de la Vega
MADRID (SPAIN)
+34-91 692 15 14 -

+34-91 691 64 56
e-mail : info@fisair.com
www.fisair.com

DISTRIBUTOR :

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

INDEX
1. Introduction............................................................................................................................................ 2
1.1 Operating instructions ............................................................................................................................. 2
1.2 Typographic distinctions ......................................................................................................................... 2
2. Safety notes ............................................................................................................................................ 2
2.1 General .................................................................................................................................................. 2
2.2 Operational safety notes ......................................................................................................................... 2
3. Transport ................................................................................................................................................ 3
3.1 General .................................................................................................................................................. 3
3.2 Packing .................................................................................................................................................. 3
3.3 Interim storage ....................................................................................................................................... 3
3.4 Check for com plete and correct del ivery of goods .................................................................................. 3
4. General description ................................................................................................................................. 4
4.1 Background ............................................................................................................................................ 4
4.2 The desiccant wheel. Operating princi ple................................................................................................ 4
4.3 Dehumidif ier main com ponents identification.......................................................................................... 5
4.4 Options and ancil lary components .......................................................................................................... 5
4.5 Regulation and control............................................................................................................................ 5

5. Installation.............................................................................................................................................. 6
5.1 Locating the unit ..................................................................................................................................... 6
5.2 Servi ce areas ......................................................................................................................................... 6
5.3 Air duct connect ions ............................................................................................................................... 7
5.4 Electric mains connections ..................................................................................................................... 8
5.5 Thermal f luids connections ..................................................................................................................... 8
5.6 Control equipm ent locations and connections ......................................................................................... 8
6. Start up ................................................................................................................................................... 8
6.1 Unit start up ............................................................................................................................................ 8
6.2 Stopping the unit .................................................................................................................................... 9
6.3 Electrical safety com ponents .................................................................................................................. 9
7. Maintenance ........................................................................................................................................... 9
7.1 Preventative m aintenance ...................................................................................................................... 9
7.2 Correctiv e maintenance.......................................................................................................................... 9
7.3 Desiccant wheel service ....................................................................................................................... 10
8. Fault finding ......................................................................................................................................... 11
9. General technical data sheet ............................................................................................................... 12
10. Overall dimensions ............................................................................................................................ 13
Addenda
A
Delivered unit specification and ancillary components (when applicable).
B
Overall Dimensions.
C
Wiri ng diagram.
D
Spare parts list.
E
Fan operating curv es.
F
Non electrical reactiv ation heater instal lation scheme (when applicable).
G
PRE- or POST- cooling coil technical data (when applicable).
H
Filters certifications (when applicable).

F-2832

-1-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
2.

Safety notes

Dear customer,

2.1

General

The FISAIR dehumidifier is our answer to today's


technical requirements. It satisfies them by means of its
operational safety, its operational comfort and its
economic efficiency.

These safety notes are required by law. They are


for your protection and to prevent accidents.

To be sure of operating your FISAIR Dehumidifier


efficiently please read these Operation and
Maintenance Instructions.

The following safety symbols shown in the text will warn


about dangers and danger sources. Get familiar with
these symbols.

1.

Introduction

Warning notes and safety symbols:

Use the steam humidifier only in proper and safe


conditions, paying attention to all notes in these
instructions.

Attention: Not observing this warning can lead to


injury or danger to your life and/or damage to the
unit.

If you have any questions...please contact us:

Attention,Voltage: Dangerous electrical current.


Not observing this warning can lead to injury or
danger to your life.

Fisair S.L.
Tel.: (34) 91-6921514
Fax: (34) 91-6916456

Note: Materials/operational equipment; must be


handled and/or disposed of according to the law.

Or your local dealer

1.1

Operating instructions

The correct use of the steam humidifier also includes


adherence to our installation, dismantling, refitting,
commissioning, operation and maintenance instruction
as well as taking correct disposal steps.
Only qualified and authorised personnel may operate
the unit. Persons transporting or working on the unit,
must have read and understood the corresponding
parts of the Operation and Maintenance Instruction and
especially the chapter Safety Notes. Additionally,
operating personnel must be informed of any possible
dangers. You should place a copy of the Operation and
Maintenance Instruction at the unit's operational
location (or near the unit).

1.2

2.2

Operational safety notes.

In general:

Observe all safety and warning notices.


If there should be malfunctions, shut down the unit
immediately and secure against being restarted. Faults
should be rectified immediately.
During repair work, guarantee operational safety of the
unit by using qualified personnel.
Only use original FISAIR spare-parts.

Typographic distinctions
Enumeration with preceding heading: General
enumeration.

Enumeration with preceding double chevron: Work


or maintenance steps that must be folllowed
sequentially.

For the effective operation of this unit refer to any national


regulations restricting or governing its use.

Accident prevention regulations

Observe the accident prevention regulations:


"Electrical Installation and Electrical Equipment" or
equivalent national codes. In this way you can prevent
injury to yourself or others.

Sequential step to be checked.

F-2832

Note: Further explanation or cross-references to


other sections of the text in the Operation and
Maintenance Instructions.

-2-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
!

Operation of the unit.

3.3

Do not impair the safety of the unit.


Periodically check all protection and warning devices
for proper functioning.
Safety equipment is not to be removed or put out of
operation.

Interim storage.

During storage, keep the unit dry and protected from


frost.

3.4

Check for complete and correct delivery


of goods.

Upon receipt of the unit, make sure that:

Installation, dismantling, maintenance and


repair of the Unit.

Type and serial number on the name plate


correspond to the order and supply information,

Turn off power, when doing maintenance work or


repairs to the unit.

Equipment is complete and in perfect condition.

Extensions to the unit or installation of additional


equipment is only allowed after obtaining written
approval from the manufacturer.

Note: Immediately file a written claim with your


shipping agent in case of transport damage or
missing parts.

Electrical parts.

Work on electrical parts must be carried out by qualified


electricians.
Turn off the power and secure against restart when
working on electrical parts.
Immediately turn the unit off when faults occur in the
electrical energy supply.
Only use original type fuses of correct rating.
Make periodical checks of the electrical equipment.
Defects, like loose connections or burned cables must
be repaired immediately.
Test all installed protective devices after installation or
repairs (e.g. grounding).

3.

Transport.

3.1

General.

F
3.2

Note: Transport the air dehumidifier carefully.


Prevent damage from careless loading and
unloading and avoid the use of unnecessary force

Packing.
Note: Observe the pictograms displayed on the
carton.

F-2832

-3-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

WET
AIR
PROCESS
AIR

REACTIVATION
(90)

HEATER

DRYING (270)

REACTIVATION
AIR

DRY
AIR
4.

General description.

4.1

Background.

4.2

Modern standards concerning human comfort and the


environmental requirements for manufacturing, storage
& preservation of products and materials, make
increasing demands on the control of moisture content
in the working environment.
Where the natural or treated environment have an
ambient condition holding more water vapour than the
specified or desirable conditions, it is necessary to
integrate equipment which can reduce humidity to the
desired level.
FISAIR ROTARY DESICCANT DEHUMIDIFIER
provide the solution.
The FISAIR dehumidifier is simple to install, reliable in
operation and will provide long lasting humidity control
at a reasonable running cost.

The desiccant wheel. Operating


principle.

FISAIR series DFRA dehumidifiers operate on the


adsorption property of a desiccant synthesised activated
silica gel manufactured into a cylindrical wheel shape
with multiple axial channels.
The face of the cylinder is divided in two zones, one is
for the process air and the other for a heated auxiliary air
stream to reactivate the desiccant. Thus a large surface
area is presented to the air streams ensuring that a rapid
drying process takes place.
The process air section occupies 75% or 270 degrees
of the face. In this section the desiccant removes
moisture from the process air passing through the
rotating desiccant cylinder. The reactivation air, using a
pre-heater, passes counterflow through the remaining 90
degrees section of the rotating cylinder, removing
moisture from the desiccant to prepare it for the drying
cycle once again.
A gear motor via a pulley and driving belt rotates the
cylinder at low speed to provide a continuous and uniform
operation. Air seals separate the two sections and
prevent air loss at the perimeter of the rotor to ensure
maximum performance.

F-2832

-4-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

9
8

3
4

1.a

1.b

Figura 3. DFRA-E series explode.

4.3

2.- Dry/Process air fan, centrifugal single entry with


forward curved blades. Direct motor driven.

Dehumidifier main components


identification (fig. 3).

The FISAIR series DFRA dehumidifiers consist of the


following main components.
1.- Housing module, manufactured in galvanised steel
sheet with a phosphate primer coat and an enamel
finish. Internally the casing is arranged to provide two
separate air streams for process/dry air and
regeneration/wet air with tight seals. The module is
easily accessed to ensure simple inspections and
maintenance of the unit. Inside is:
1.a. A desiccant rotor on a horizontal axis, the shaft is
fixed and the wheel rotates on its hub.
1.b. The driving geared motor with a pulley and a
peripheral belt driving the rotor.

F-2832

-5-

3.- Process air filter G4 standard.


4.- Aluminium process air flow control damper located at
the air intake.
5.- Wet air/regeneration fan, centrifugal, single entry
with forward curved blades, direct motor driven.
6.- Regeneration air filter G4 standard.
7.- Aluminium regeneration air flow control damper
located at the air intake.
8.- Reactivation air heater (inside of main module for
electrically regenerated models up to 63 kW. power).
9.- Electric control and protection box.

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
4.4

Options and ancillary components.

On demand, DFRA series of FISAIR Dehumidifiers can


be provided with:

!
!
!
!
!
!
!
!
!
!
!
!
!

Stainless steel casings.


High pressure Fans (up to 600 mm WC available).
Backwards curved blades fans.
Fans with stainless steel impellers/casings.
Pulley/Belt driven fans.
More efficient air filters (up to F9).
Cold water or direct expansion pre-cooling coil, with or
without droplets separator.
Post-cooling coil.
Dry air indirect evaporative cooler.
Wet air heat recovering.
Wet air condenser to operate in closed circuit.
Double coil (electric/steam or other thermal fluid) for the
reactivation air.
Integral regulating and control systems.

4.5

Regulation and control.

Desiccant rotor dehumidifier drying capacity can be


regulated by acting on:

! Reactivation heater power (lower power = lower drying


capacity).

! Reactivation air flow (lower air flow = lower drying


capacity).

! Process air flow, by-passing part of it over the rotor


(higher by-pass = lower drying capacity).

When you select the unit you have to define regulation,


so that it is not a matter of this manual to extend in this
aspect, but only to give an idea about possible
alternatives.

Note: As standard, FISAIR dehumidifiers are


supplied with a hygrostat connection for On/Off
operation. For electrically regenerated models,
control of heater and the total unit is s u p p l i e d
(bridges H1,H2 or H3 of wiring diagram).

F-2832

-5-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
5.

Installation.

5.1

Locating the unit.

Before installing FISAIR dehumidifiers the following


points should be considered.
If the dehumidifier has to be stored for a significant
period prior to installation it should be protected from
external damage and dust and construction material.
In the case of outdoor storage, weatherproof covers
should be employed.
The FISAIR DFRA dehumidifier is designed for internal
installation, for outdoor use please apply to your local
representative for special construction details.
Once final location is defined ensure that there is
enough space for servicing to be carried out. Take
care to ensure that ducting connections are made
without stressing the unit.

5.2

Service areas.

Using the attached dimensioned drawings of the relevant


model, consider periodically:
Air filters must be cleaned or changed.
The desiccant wheel faces should be inspected and
cleaned and the air seals adjusted as necessary.
Driving belt should be checked for fatigue and its
tightness checked.

Note: In the case of the motor or belt failure they


should be replaced. To do this dismount the front
door which will provide space for dismounting the
desiccant wheel driving device.

F-2832

-6-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

IN VERTICAL DUCTS:
IN VERTICAL TRACTS, DRILL A
HOLE AT THE LOWEST PART OF
THE DUCT TO DRAIN.

IN HORIZONTAL DUCTS:
DESCENDING DUCTS IN
HORIZONTAL TRACTS TO
EVACUATE CONDENSATIONS.

WET
AIR

SEPARATION > 3m

ISOLATING DUCTS
PREVENTS CONDENSATING
AIR
TO
PROCESS

AIR FROM PROCESS


OR OUTSIDE

GRILL +
MESH

5.3

Air duct connections.

Check the operation of fans and motors and the


reactivation heater. In case of failure, repair or
replace.
Check the components in the control box, service
or change as necessary.
Duct connections should be made using normal
industry standards for air transmission systems.
However, the following particular items should
considered:
Make sure that available external pressures stated
in the unit data-sheet have been considered when
designing the ducts sizes and layout, allowing that
the dehumidifier will operate with the nominal air
flows.

F-2832

-7 -

REACTIVATION
AIR

The FISAIR dehumidifier is normally delivered with air


dampers in both air streams, in order to adjust the
flows to the nominal values.
The outdoor air intakes must be designed with
grilles/wire meshes to avoid the involuntary carryover
of raindrops, leaves, insects, etc. that could affect the
correct unit operation.
The wet air outlet (normally saturated air) must be
placed as far as possible from the air intakes, to avoid
losses of performance.
Also, the wet air duct must facilitate the draining of the
condensing water produced when this air becomes
cooler due to heat transmission. To achieve this the
duct must slope downstream and, if possible, be
insulated. When this duct runs vertically upwards, a
small drilled hole ( 5 mm. aprox.) should be arranged
at the lowest part of the duct to drain the condensate
that could go back to the unit or block the air duct.
Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
5.4

Electric mains connections.

6.

Attention : The dehumidifier works with


medium electrical power and voltage and its
connection to the mains must be done by
qualified personnel and according to the
applicable local electrical regulations.

Once the ductwork has been completed and the


equipment is connected to the electrical mains (and to
thermal fluids supply when applicable), as well as to the
control equipment, proceed in this way:

The unit must be connected to the electrical network


of the installation through a short circuiting and ground
leakage protection line, with wires section/sensitivity as
corresponds to the dehumidifier power.
The unit has a terminal block into the electric box sized
according to the electrical standards, to connect the
supply wires.

5.5

Thermal fluids connections.

Dehumidifier models with steam, hot/superheated


water or thermal oil reactivation coils as well as the
ones with pre-or after cooling coils should be
connected to the supply/return line according to good
practice and local regulations.
The piping layout must incorporate air vents, traps,
filters, shut-off or modulating valves, and measuring
devices that are demanded by the coil type of the
dehumidifier.
As the most usual thermal fluid is steam, this manual
includes at the annex a suitable guide for steam.

5.6 Control equipment locations and


connections.

6.1

Start up.

Unit start up.


Attention: Before using the control panel, verify
that all mechanical elements can work freely and
the unit has no installation debris inside.

Check that hygrostat set point is demanding the


equipment operation (this figure should be at least 10% 15% lower than environmental humidity), or its terminals
have a bridge.
Check that the air flow regulation dampers are at least
50% opened.
Make sure that all screwed electrical terminals into the
electric control box are rightly tightened to avoid faulty
connections. Then, turn on the isolator switch and check
that the power lamp is on. (REMARK: Do not use the
isolator switch to operate the unit).
Check that the phases are connected in the correct
order = fan motors and gear-motor are rotating in the right
direction. To do it, switch on the equipment for a few
seconds by the control switch.

The location and mounting instruction for the control


equipment are normally specified by the corresponding
supplier.
If the dehumidifier is designed to work on-off by using
the H1/H2 terminals of the electric control box, make
sure that it operated by switching the whole unit of the
heaters only.

F-2832

If fans/gear-motor do not rotate in the correct direction,


change the phases order at the equipment supply.
Start the unit again.

(See paragraph 4.5 of this manual)

-8-

Note: The electrically regenerated models


include a temporal relay RT, wiring diag. that
keeps the fans and gear-motor working for a few
minutes to dissipate the resistance heat and to
avoid that the manually resetable over
temperature cut out be activated.

Note: It is advisable to check the electric


consumption of the main elements and to verify
that they correspond to the nominal values.

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
Adjust the air flows if necessary.

Note: The nominal reactivation air flow with


standard heater will heat this air stream 100C
(aprox.) above the inlet temperature. So, you
can use the thermometer reading to roughly
adjust the reactivation air flow.

A safety thermostat set at 160C (aprox.). It switches


off the units completely and turns on the fault lamp.
The serviceman will have them to inspect personally
what was the fault at the unit.
A timer relay operating as described before.

After working for enough time to reach its standard


operation (at least 30 minutes), make suitable
thermohygrometric measurements.

All these components are of course included into the


electrically reactivated models only. The steam/thermal
oil units have a simple thermometer.

6.2

7.

Maintenance

The equipment can be stopped manually or


automatically.

7.1

Preventative maintenance.

Manual mode:

The following service schedule can be used.

Just operate the control switch to its "OFF" position.


As indicated in 6.1, electrically reactivated models
include a timer that keeps running the fans and gearmotor for a few minutes to cool the unit.

OPERATION
Filters cleaning
Rotor driv ing check
Fan impellers inspection
Inner inspection (desiccant rotor
surfaces) driv ing belt tension
and absence of unexpected
materials.
Electrical consumption and
terminals tightening
General cleaning

Stopping the unit.

Attention: Do not stop the equipment by the


isolating switch because then the timer
operation will be eliminated.
Automatic mode:
In case of On-Off control, the hygrostat will
automatically shut-off the unit when the selected set
point is reached. The electrically reactivated units can
be totally stopped (after motors temporisation) or the
heater only, by choosing the corresponding terminals
on the wiring diagram.

6.3 Security and control components


Apart from the usual electrical components protections
(against shortcuts and overload at the motors, with
manual reset) the electrical panel of the dehumidifier is
counting with the following security and control
components:
An operating thermostat (double in larger models)
regulated at 150C (135/145C) to protect the
heaters in case of lack of a reactivation air flow.

Note: This is an automatically resetable


thermostat and switches-off the heaters only.

F-2832

-9-

7.2

FREQUENCY
Weekly
Weekly
Monthly
Every
second
month

Every
month
Yearly

second

Corrective maintenance

The (desiccant rotor type) FISAIR dehumidifiers series


DFRA have a very simple design and their components
should have very few problems.
The fans/motors are of standard manufacture and in
case of electrical or mechanical damages any skilled
serviceman may do the repairing. The heaters can be
easily changed or serviced when necessary (normally
after a very long working period) like any other
conventional air heater element.
Also, minor components like filters, dampers, driving belt
and electric box components could be replaced after
their useful life and the user will have to define the
necessity of storing these parts, depending on their
availability through local dealers.

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
Also, minor components like filters, dampers, driving
belt and electric box components could be replaced
after their useful life and the user will have to define the
necessity of storing these parts, depending on their
availability through local dealers.

7.3

Desiccant wheel service.

This is the only dehumidifier component that needs any


special attention.
Concerning the mechanical operation, the rotor should
not require attention for a very long time. Its rotation
speed is so low (20-24 r.p.h.) that the bearings and
desiccant material housing cannot suffer any
mechanical damage normally. However, it is very
important to verify periodically the correct operation of
the driving device because it directly affects the drying
process.
Regarding the water vapour adsorption process, the
main rotor component, activated silica gel, works by
fixing the water vapour molecules in its
micro pores in the process air stream, leaving them
when the heated reactivation air stream passes
through the rotor channels.
This process is not affected by the normal
environmental air conditions, nor by accidents of the
installation that can be expected (for example, water
direct action on the rotor does not affect the material,
which is also fireproof).
Usual dust deposits on rotor surfaces can be removed
by vacuum or blowing as well as by washing (please
contact your dealer for written method when needed).

F-2832

- 10 -

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
8. Fault finding
Inmediately switch off the dehumidifier if a fault occurs. Faults are only to be remedied
by qualified personnel following the proper safety instructions.

Fault
The unit has stopped

Measures
Check the following points
Electric mains are powered and the pilot lights on. If not, reset the
mains protections.
The fault lamp is off. If it is on, check what thermal protection
(motors and heaters) switched on the lamp and stopped the unit.
When you have re-set the faulty one, check and carry out corrective
actions - find the reason for the failure.
If fault lamp is off, check that the hygrostat set point or other signal
control is demanding the equipment operation.
If after these verifications the equipment does not work, please, ask
the dehumidifier supplier for technical assistance.

The unit works, but it


does not perform as
expected.

Check the following points:

The desiccant rotor rotates evenly at 20-24 r.p.h. and if not, do the
necessary service; shortening the drive belt, fixing the pulley,
repairing/replacing the gear motor or adjusting the air seals, whatever
is applicable.
The radial and peripheral air sealings are maintaining a seal between
both air streams and the outside. If not, carry out required action.
The reactivation air flow, which could be reduced by clogging on the
filter, damper or inlet/outlet duct.
The reactivation air temperature, if this is lower than 100C above
the inlet air temperature. In this case, check the heaters operation and
the regeneration air flow. If this flow is excessive, dehumidification
capacity may decrease.
The process air flow could be much larger than the nominal flow.
Then the specific dehumidification capacity will be lower. Regulate
it by the damper.
The front rotor surfaces, that could be partially blocked.

F-2832

- 11 -

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

9. General technical data sheet.

Model
DFRA-0065
DFRA-0100
DFRA-0130
DFRA-0160
DFRA-0175
DFRA-0200
DFRA-0230
DFRA-0300
DFRA-0400
DFRA-0500
DFRA-0650
DFRA-0900
DFRA-1100
DFRA-1300
DFRA-1700
DFRA-2100
DFRA-2900
DFRA-3500

FISAIR dehumidifier technical data


Dry Air
Nominal Capacity
m3/h
Kg/h(*)
450
3
700
4
900
5,2
1100
7,1
1200
8,3
1400
9,4
1600
10,5
2100
12,5
2700
17
3600
21
4500
28
6000
36
7500
48
9000
58
12000
76
15000
95
20000
125
24000
145

Reactivation Power KW
(**)
4,5
6,8
9,0
11,3
13,5
15,8
18,0
22,5
27,0
36,0
45,0
63,0
81,0
99,0
126,0
162,0
200,0
240,0

* Nominal capaci ty for 20C and 60% R.H conditions. Other conditions call us.
** Carried out by electric heaters, steam thermal oil, gas or superheated water according t o
especifications.

Note: Technical dat a are subjected to change without prior notice.

F-2832

- 12 -

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series
10. Overall dimensions.

FISAIR

4
3

1) Process Air.
2) Dry Air.
3) Reactivation Air.
4) Wet Air.

REFERENCIA
DEL
EQUIPO

F
F-2832

DIMENSIONES
GENERALES

MEDIDAS DE CONEXIONES A CONDUCTOS


L3

H3

L4

H4

PESO
(Kg)

L1

H1

L2

H2

DFRA-0065-E

1580

635

935

200

514

200

214

80

105

80

105

150

DFRA-0100-E

1610

635

935

200

514

200

214

100

120

80

105

160

DFRA-0130-E

1630

770

1045

250

614

250

314

115

140

80

105

175

DFRA-0160-E

1630

770

1045

250

614

250

314

115

140

80

105

185

DFRA-0175-E

1650

770

1045

250

614

250

314

115

140

103

125

185

DFRA-0200-E

1700

770

1045

250

614

250

314

130

160

103

125

190

DFRA-0230-E

1700

810

1045

250

614

250

314

130

160

115

140

200

DFRA-0300-E

1780

880

1045

250

614

250

314

140

216

160

230

140

350

160

385

DFRA-0400-E

1780

970

1265

350

614

350

414

140

216

130
5
115

DFRA-0500-E

1890

1110

1265

350

614

350

414

200

320

130

DFRA-0650-E

2050

1230

1525

450

1114

450

514

228

280

130

160

520

DFRA-0900-E

2195

1325

1525

450

1114

450

514

250

320

140

216

560

DFRA-1100-E

2195

1450

1825

575

1214

575

514

250

320

140

216

710

DFRA-1300-E

2195

1450

1825

575

1214

575

514

250

320

140

216

750

DFRA-1700-E

2705

1950

1980

600

1514

600

714

315

451

228

280

1000

DFRA-2100-E

2885

2095

1980

600

1514

600

714

410

600

228

280

1150

DFRA-2900-E

2945

2300

2525

600

1714

600

814

410

600

250

321

1850

DFRA-3500-E

2945

2300

2525

600

1714

600

814

410

600

250

321

1950

Note : Data show correspond to electrical reactivation models. Units with other type of
reactivation heater have different data.
- 13 -

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

Air Dehumidifier DFRC-0400-E

FISAIR

TECHNICAL DATA - SHEET


TECHNICAL DATA

SPECIFIC CAPACITY DIAGRAM.

2700

m3/h

FISAIR DEHUMIDIFIERS.
(g/kg).

(C)
Xe/Xs

REACTIVATION AIR FLOW

AVAILABLE PRESSURE
FOR DUCTING
NOMINAL DRYING
CAPACITY(*)

800
810

400
17

Pa

DRY AIR MOISTURE CONTENT (Xs)

AVAILABLE PRESSURE
FOR DUCTING

m /h

Pa
kg/h

Xe/Ts

50

48
46

44

42

40

38
36

34

32

0
5

TOTAL
POWER SUPPLY

30

MOTORS POWER

DRY AIR TEMPERATURE (Ts)

PROCESS/DRY
AIR FLOW

CAPACITY DIAGRAM.(*)

10

11

12

13

30
14 (g/kg).

kW
PROCESS AIR MOISTURE CONTENT (Xe)

kW

04/04 F-00605-02/B

SETTLED PARAMETERS :

REACTIVATION
HEATER POWER
ELECTRICAL SUPPLY

27

kW

PROCESS/REACTIVATION AIR TEMPERATURE : 20 C

T REACTIVATION HEATER ACCORDING TO NOMINAL POWER

EQUAL PROCESS/REACTIVATION AIR MOISTURE CONTENT

400V/III/50 Hz

(*) Nominal capacity: 20C and 60% R.H.

F-2833

(*) At other operating conditions.pls.ask for the


corresponding performances.

- 14-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

B. Overall Dimensions

F-2833

- 15-

Technical Data Subject to alterations

Installation, Operation and Maintenance Manual


Desiccant Rotor Type Air Dehumidifiers DFRA series

D. Spare part list for the dehumidifier DFRC-0400-E

Item
1

Main component
Main module

Description

Part n

Quant.

Dessicant rotor.

200110

Set of seals.

303020

6,4 m

303022

1,2 m

205206

Belt

211101

2, 75m

Connector

211105

Pulley

213034

Drive m otor
Transmission belt with connector

Dry air fan

Complete

201024

Dry air filter

Filter 400X610X100

231004

Dry air damper

Complete

203040

Wet air fan

Complete

201025

Wet air filter

Filter 343x 460x100

231005

Wet air damper

Complete

203120

Reactivation air heater

Electrical heater

207030

Electric control box

Pressure differential switch

243035

Temperature sensor JUMBO

241093

Microstat.

255138

Over tem perature thermostat.

255140

Motors time relay.

241095

Complete

209155

F-2832

Pre-cooling coil

Technical Data Subject to alterations

Manual de Instalacin y Mantenimiento


Deshumidificador de Aire por Rotor Desecante DFRA

VENTILADOR DE PROCESO DEL DFRC-0400-E


CMP-922-2T-3

140

2700
DATOS TCNICOS:
A
B
H
C
C1
C2
D1
DE
DE1
DE2
E
H1
I
J
J1
K
K2
L
O
O1
V
VE
X
X1

F-2832

en mm
388,5
455
280
430,5
357
73,5
224
278
256
M8
180
134
204
282,5
128
140
180
215
9,5
10,5
290
220
114
50

400V/III/50Hz.
Qnominal (m3/h)= 2700 m3/h.
QMximo (m3/h)= 2900 m3/h.
Pt a 2700m3/h (Pa)= 1373 Pa.
S (rpm)= 2860 rpm.
Imax. 230V= 7,8 A.
Imax. 400V= 4,5 A.
P (kW)= 2,2 kW.
NPS= 74 dB(A).
ESPECTRO SONORO:
Hz.
63
125
250
500
1000
2000
4000
8000

Lw (dBA)
49
59
70
77
81
78
76
69

El fabricante se reserva el derecho de cambiar las especificaciones sin previo aviso

Manual de Instalacin y Mantenimiento


Deshumidificador de Aire por Rotor Desecante DFRA

VENTILADOR DE REACTIVACIN DEL DFRC-0400-E


CMP-718-2T

98

810
A
B1
B2
C
C1
C2
D1
DE
DE1
DE2
E
H1
I
J
J1
J2
K
K2
L
O

F-2832

en mm
322
377
223
335,5
267
68,5
200
247
230
M6
137,5
137
184
213
94,5
189
130
160
156
9

DATOS TCNICOS:
400V/III/50Hz.
Qnominal (m3/h)= 810 m3/h.
QMximo (m3/h)= 1350 m3/h.
Pt a 810 m3/h (Pa)= 961 Pa.
S (rpm)= 2850 rpm.
Imax. 230V= 2,94 A.
Imax. 400V= 1,7 A.
P (kW)= 0,75 kW.
NPS= 70 dB(A).
ESPECTRO SONORO:
Hz.
63
125
250
500
1000
2000
4000
8000

Lw (dBA)
45
55
66
73
87
74
72
65

El fabricante se reserva el derecho de cambiar las especificaciones sin previo aviso

POLITEX A40

Code

SF350AR4

Name

A40

Description

SYNTHETIC FILTER MEDIA

Ventilation and industrial or civil conditioning plants. Pre-filtration and separation of particulates
with medium low granulometry.

dimensions

roll 2x20

composition

polyester fiber

regeneration

yes

thickness

14-16

mm

max. working temperature

100

max. working R.H.

100

product density

350 g/m

advisable cross speed

1,5

m/s

34

Pa

250

Pa

90,8

initial pressure drop


final pressure drop
avarage gravimetric efficiency
dust holding capacity

575 g/m

classification ( EN 779:2002)

G4

flame resistance

F1 - DIN.53438
rev. 00_05

Sede - Headquarter
Via S.Luca, 51
31038 Paese (TV) Italy
Tel +39.0422.4594
Fax +39.0422.459590
info@generalfilter.com
www.generalfilter.com

Div. Commerciale - Trade Office


Via Caracciolo, 13
20010 Barbaiana di Lainate (MI) Italy
Tel +39.02.93550640
Fax +39.02.93255670
sales.ita@generalfilter.com
www.generalfilter.com

General Filter Italia spa si riserva il diritto di cambiare i dati della presente scheda senza alcun preavviso.

CONTROL DE HUMEDAD AMBIENTAL


FISAIR, S.L.
Departamento Direccin Tcnica
Abteilung Technische Leitug

Department of Technical Management


Dpartment de Direction Technique

} C/. Uranio, 20 - Pol. Ind. Aimayr - 28330 SAN MARTIN DE LA VEGA (Madrid Espaa)
Tf 91 6921514 Fax 91 691 64 56

DECLARACION CE DE CONFORMIDAD - EC CONFORMITY DECLARATION


EG KONFORMITATSERLARNG - DECLARATION CE DE CONFORMIT

DECLARAMOS Bajo nuestra nica responsabilidad que el deshumidificador de aire:


WE DECLARE, under our sole responsability that the air dehumidifier:
UNTER AUSSCHLIELICHER, verantwortung wird hiermit Erklrt, da der luftentfeuchter:
NOUS DECLARONS, sous notre unique responsabilit que le deshydrateur d'air:

MARCA/MAKE/MARKE/MARQUE

MODELO/MODEL/MODELL/MODELE

FISAIR
N SERIE/SERIAL NUMBER/
SERIENNUMMER/N DE SERIE:

1062006/07
Se adapta a las normas:

DFRC-0400-E
AO DE FABRICACION/YEAR OF MANUFACTURE/
BAUJAHR/ANNE DE FABRICATION:

2006

Den Normen entspricht:

Meets the regulations:


S'adapte aux normes:

. UNE EN ISO 12.100-1 :2004


. UNE EN 60204-1:1999

. UNE EN ISO 12.100-2 :2004


. UNE EN 294:1993

Y es conforme a los requisitos esenciales de las Directivas:


And conforms to the essential requirements of the Directives:
Und den von den Richtlinien aufgestellten Grundvoraussetzungen Rechnung trgt:
Et est conforme aux conditions essentielles des Directives:
. D98/37/CEE
. D73/23/CEE (Modificada por 93/68/CEE)
. D89/336/CEE (Modificada por 92/31/CEE y la 93/68/CEE)
Con exclusin de responsabilidades sobre las partes o componentes adicionados o montados por
el cliente.
With no liability for the parts or components added or assembled by the customer.
Unter Ausschlu der Verantwortung ber die vom Kunden bereitgestellten und/oder angebauten Teile.
Avec exclusion des responsabilits concernant les parties ou les composants ajouts ou assembls par le client.

Departamento Direccin Tcnica/Department of Technical Management/Dpartment de Direction Technique

Juan Boeta Tejera.


San Martin de la Vega, Septiembre 2006