Medium Voltage Power Cables

XLPE Insulated, with Longitudinal


Water Barrier, PE Sheathed
Single Core Cables for Fixed
Installations, 6/10 kV;
12/20 kV; 18/30 kV
APPLICATION:
For indoor or outdoor installation in open air in
tray, trough and conduit or for direct burial in free
draining soil or inside duct where no mechanical
damage is to be expected. Power cable for utilities
medium voltage underground distribution systems
and in commercial buildings, industrial plants,
power stations and substations. For rated voltages
U0/U(Um): 6/10(12) kV; 12/20(24) kV or 18/30(36)
kV at maximum conductor temperatures of 90 C
for continuous normal operation and 250 C for
short circuit.

Short Circuit rating


conductor (1 sec) (1)

In air (3)

In ground (4)

In air (3)

In ground (4)

Reactance @50Hz (5)

Capacitance

Standard supply
lengths

mm

Current Rating (2)

Max. conductor DC
resistance at 20C

mm

PACKAGING:
Standard supply lengths are given in the tables
hereunder. Other bobbin lengths or cut to
length - available upon request.

Minimum bending
radius

mm

- standard voltages: 3.6/6kV & 8.7/15 kV


- tree-retardant XLPE insulation
- EPR insulation
- easy strippable insulation screen
- no water barrier
- aluminium wire armour
- PVC outer red sheath.
Consult us on fire retardant and /or halogen
free constructions.

Approximate cable
weight

Approximate outer
diameter

CONSTRUCTION:
A copper or aluminium compacted circular
conductor has a triple single head extruded
smooth conductor screen, XLPE (cross-linked
polyethylene) insulation and bonded insulation
screen, all dry nitrogen cured; water blocked
metal screen made of solid bare copper wires
uniformly spaced around the cable and a counter
helix copper tape; ST7 surface printed black PE
oversheath is extruded over all.
The following alternatives are available upon
request:

Nominal sheath
thickness

No. x mm2/mm2

3. Conformance to various European standards,


available upon request.

Nominal insulation
thickness

Minimum No. of
wires in conductor

Catalog
Number

No., Nominal cross


sectional area of
conductors & screen

STANDARDS:
1. Conforms to Israeli Standard IS 1516-2:
Power cables with extruded insulation and
their accessories for rated voltages from
1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Part 2: Cables for rated voltages of
6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
for the types N2XS(F)2Y and NA2XS(F)2Y .
2. Conforms to IEC 60502-2 Standard:
Power cables with extruded insulation and
their accessories for rated voltages from
1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Part 2: Cables for rated voltages of
6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV).

kg/km

mm

/km

kA

/km

F/km

(12) kV COPPER CONDUCTOR


750
315
0.524
5.0
197
900
360
0.387
7.2
236
1100
383
0.268
10.0
294
1450
405
0.193
13.6
358
1700
428
0.153
17.2
413
2000
458
0.124
21.5
468
2400
495
0.0991
26.5
535
2950
525
0.0754
34.3
631
3530
563
0.0601
42.9
722
4500
615
0.0470
57.2
827
5500
660
0.0366
71.5
949
7050
720
0.0283
90.1
1066

1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/25
1x185/25
1x240/25
1x300/25
1x400/35
1x500/35
1x630/35

6
6
12
15
18
18
30
34
34
53
53
53

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

187
220
268
320
363
405
457
526
591
662
744
832

235
282
350
426
491
549
625
731
831
920
1043
1162

212
249
302
359
405
442
493
563
626
675
748
835

0.133
0.127
0.119
0.114
0.109
0.106
0.102
0.098
0.095
0.091
0.089
0.087

0.23
0.25
0.28
0.32
0.35
0.37
0.41
0.46
0.50
0.56
0.61
0.67

1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500

168029
168046
168074
168088
168130
168148
168179
168238
168307
168408
168490
168626

1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/25
1x185/25
1x240/25
1x300/25
1x400/35
1x500/35
1x630/35

6
6
12
15
15
15
30
30
30
53
53
53

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

NA2XS(F)2Y 6/10 (12) kV ALUMINIUM CONDUCTOR


1.8
21
500
145
3.29
315
153
0.868
1.8
24
580
171
4.7
360
183
0.641
1.8
25.5
680
208
6.6
383
228
0.443
1.8
27
810
248
8.9
405
278
0.320
1.8
28.5
950
283
11.3
428
321
0.253
1.9
30.5
1100
315
14.1
458
364
0.206
1.9
33
1210
357
17.4
495
418
0.164
2.0
35
1420
413
22.6
525
494
0.125
2.0
37.5
1730
466
28.2
563
568
0.100
2.1
41
2100
529
37.6
615
660
0.0778
2.2
44
2520
602
47
660
767
0.0605
2.3
48
3000
694
59.2
720
882
0.0469

182
219
273
333
384
432
496
583
666
755
868
881

165
194
236
281
318
350
394
452
506
558
627
712

0.133
0.127
0.119
0.114
0.109
0.106
0.102
0.098
0.095
0.091
0.089
0.087

0.23
0.25
0.28
0.32
0.35
0.37
0.41
0.46
0.50
0.56
0.61
0.67

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

Tel: (972) 4-8466222


Fax: (972) 4-8466286
e-mail: export@synergy-cables.com
http://www.synergy-cables.com

PCD 45-13, October 2007

168030
168049
168075
168092
168131
168147
168191
168239
168312
168414
168491
168627

N2XS(F)2Y 6/10
1.8
21
1.8
24
1.8
25.5
1.8
27
1.8
28.5
1.9
30.5
1.9
33
2.0
35
2.0
37.5
2.1
41
2.2
44
2.3
48

Approximate outer
diameter

Approximate cable
weight

Minimum Bending
Radius

Max. conductor DC
resistance at 20C

Short Circuit rating


conductor (1 sec) (1)

In air (3)

In ground (4)

In air (3)

In ground (4)

Reactance @50Hz (5)

Capacitance

Standard supply
lengths

Current Rating (2)

Nominal sheath
thickness

No. x mm2/mm2

Medium Voltage Power Cables

Nominal insulation
thickness

Minimum No. of
wires in conductor

Catalog
Number

No., Nominal cross


sectional area of
conductors & screen

Medium Voltage Power Cables

mm

mm

mm

kg/km

mm

/km

kA

/km

F/km

168037
168053
168077
1680940
168118
168156
1681790
1682470
168306
168402
168500
168632

1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/25
1x185/25
1x240/25
1x300/25
1x400/35
1x500/35
1x630/35

6
6
12
15
18
18
30
34
34
53
53
53

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

168038
1680460
168078
1680941
168119
1681491
168194
168245
1683101
168410
168499
168633

1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/25
1x185/25
1x240/25
1x300/25
1x400/35
1x500/35
1x630/35

6
6
12
15
15
15
30
30
30
53
53
53

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

168050
168072
168095
168125
168150
168185
168241
168300
168400
168502
168635

1x50/16
1x70/16
1x95/16
1x120/16
1x150/25
1x185/25
1x240/25
1x300/25
1x400/35
1x500/35
1x630/35

6
12
15
18
18
30
34
34
53
53
53

8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0

168047
168073
168090
168129
168162
168193
168242
1683001
168411
168503
168636

1x50/16
1x70/16
1x95/16
1x120/16
1x150/25
1x185/25
1x240/25
1x300/25
1x400/35
1x500/35
1x630/35

6
12
15
15
15
30
30
30
53
53
53

8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0

N2XS(F)2Y 12/20 (24) kV COPPER CONDUCTOR


1.8
26
900
390
0.524
5.0
200 187
1.8
27.5
1050
413
0.387
7.2
239 222
1.9
29
1300
435
0.268
10.0
297 271
1.9
31
1600
465
0.193
13.6
361 323
2.0
33
1900
495
0.153
17.2
416 367
2.0
34.5
2200
518
0.124
21.5
470 409
2.1
36
2550
540
0.0991
26.5
538 461
2.1
38.5
3200
578
0.0754
34.3
634 532
2.2
41
3800
615
0.0601
42.9
724 599
2.3
45
4750
675
0.0470
57.2
829 671
2.4
48
5700
720
0.0366
71.5
953 754
2.5
53
7250
795
0.0283
90.1
1070 843
NA2XS(F)2Y 12/20 (24) kV ALUMINIUM CONDUCTOR
154
1.8
26
700
390
0.868
3.29
145
185
1.8
27.5
800
413
0.641
4.7
172
231
1.9
29
900
435
0.443
6.6
210
280
1.9
31
1050
465
0.320
8.9
251
323
2.0
33
1200
495
0.253
11.3
285
366
2.0
34.5
1300
518
0.206
14.1
319
420
2.1
36
1500
540
0.164
17.4
361
496
2.1
38.5
1650
578
0.125
22.6
417
569
2.2
41
1950
615
0.100
28.2
471
660
2.3
45
2300
675
0.0778
37.6
535
766
2.4
48
2800
720
0.0605
47
609
882
2.5
53
3300
795
0.0469
59.2
701
N2XS(F)2Y 18/30 (36) kV COPPER CONDUCTOR
2.0
33
1400
495
0.387
7.2
241 225
2.0
35
1650
525
0.268
10.0
299 274
2.1
37
2000
555
0.193
13.6
363 327
2.1
38
2250
570
0.153
17.2
418 371
2.2
40
2700
600
0.124
21.5
472 414
2.2
42
3100
630
0.0991
26.5
539 466
2.3
44
3750
660
0.0754
34.3
635 539
2.4
47
4300
705
0.0601
42.9
725 606
2.5
52
5200
780
0.0470
57.2
831 680
2.6
54
6450
810
0.0366
71.5
953 765
2.7
60
7900
900
0.0283
90.1
1070 855
NA2XS(F)2Y 18/30 (36) kV ALUMINIUM CONDUCTOR
2.0
33
1000
495
0.641
4.7
174
187
2.0
35
1200
525
0.443
6.6
213
232
2.1
37
1400
555
0.320
8.9
254
282
2.1
38
1500
570
0.253
11.3
289
325
2.2
40
1850
600
0.206
14.1
322
367
2.2
42
1900
630
0.164
17.4
364
421
2.3
44
2200
660
0.125
22.6
422
496
2.4
47
2500
705
0.100
28.2
476
568
2.5
52
2850
780
0.0778
37.6
541
659
2.6
54
3300
810
0.0605
47
616
764
2.7
60
3800
900
0.0469
59.2
709
880

235
282
351
426
491
549
625
731
830
923
1045
1160

213
250
303
360
407
445
498
568
633
685
760
848

0.144
0.137
0.129
0.123
0.118
0.114
0.110
0.105
0.102
0.098
0.094
0.092

0.16
0.17
0.19
0.21
0.23
0.25
0.27
0.30
0.32
0.36
0.40
0.44

1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
250

183
219
273
332
384
432
494
581
663
753
866
880

166
195
237
282
319
352
396
455
510
564
634
730

0.144
0.137
0.129
0.123
0.118
0.114
0.110
0.105
0.102
0.098
0.094
0.092

0.16
0.17
0.19
0.21
0.23
0.25
0.27
0.30
0.32
0.36
0.40
0.44

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

282
350
425
488
548
624
728
828
922
1045
1160

251
304
362
409
449
502
574
640
695
773
861

0.146
0.137
0.131
0.125
0.121
0.117
0.112
0.108
0.103
0.100
0.098

0.13
0.15
0.16
0.18
0.19
0.20
0.22
0.24
0.27
0.29
0.32

1000
1000
1000
1000
1000
1000
500
500
500
500
500

219
273
331
382
429
492
578
659
750
861
880

195
238
283
321
354
399
458
514
570
642
736

0.146
0.137
0.131
0.125
0.121
0.117
0.112
0.108
0.103
0.100
0.098

0.13
0.15
0.16
0.18
0.19
0.20
0.22
0.24
0.27
0.29
0.32

1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500

25
1.04
0.96

30
1.00
0.93

The information given in this page is subject to change without notice.

35
0.96
0.89

40
0.91
0.85

45
0.87
0.80

50
0.82
0.76

55
0.76
-

60
0.71
-

65
0.65
-

STANDARDS
The following standards shall form a part of
this specification to the extent specified herein:
- Israeli Standard IS 1516-2: Power cables
with extruded insulation and their
accessories for rated voltages from 1 kV
(Um = 1,2 kV) up to 30 kV (Um = 36 kV)
Part 2: Cables for rated voltages of 6 kV
(Um = 7,2 kV) up to 30 kV (Um = 36 kV)
for the types N2XS(F)2Y and NA2XS(F)2Y.
- IEC 60502-2 Standard: Power cables with
extruded insulation and their accessories
for rated voltages from 1 kV (Um = 1,2 kV)
up to 30 kV (Um = 36 kV) Part 2: Cables
for rated voltages of 6 kV (Um = 7,2 kV) up
to 30 kV (Um = 36 kV).
CONDUCTORS
- Annealed, high conductivity copper
compacted circular stranded conductor
according to IEC 60228, Class 2.
- Aluminium compacted circular stranded
conductor according to IEC 60228,
Class 2.
CONDUCTOR SCREEN
The conductors shall be covered with a layer
of extruded smooth conducting cross-linked
polyolefin compound, firmly bonded to the
insulation and which shall meet the
requirements of Israeli Standard 1516-2 and
IEC 60502-2 Standard.

INSULATION
- Directly over the conductor screen shall be
applied a homogeneous wall of XLPE
insulation. The thickness shall be in
accordance with Israeli Standard 1516-2 and
IEC 60502-2 Standard.
- Properties of the insulation shall be in
accordance with Israeli Standard 1516-2 and
IEC 60502-2 Standard.
- Ethylene propylene rubber insulation, in
accordance with Israeli Standard 1516-2 and
IEC 60502-2 Standard, is available upon
request.
INSULATION SCREEN AND LONGITUDINAL
WATER BARRIER
- The insulation screen shall consist of a nonmetallic extruded semi-conducting layer in
combination with semi-conducting tape and
a metallic layer.
- The extruded semi-conducting layer shall
consist of smooth cross-linked polyolefin
compound bonded to the insulation and
meeting the requirements of Israeli Standard
1516-2 and IEC 60502-2 Standard.
- The conductor screen, the insulation and the
insulation screen shall be applied in a single
head triple extrusion process with dry nitrogen
curing.
- A semi-conducting tape shall be applied on
the extruded semi-conducting insulation
screen.
- The metallic layer shall consist of a number
of bare copper wires, uniformly spaced and
helically applied on top of the semiconducting tape. An open helix applied
copper tape shall bind the wires together.
- The cross sectional area of the metallic layer
shall be the one specified in the tables above
to provide an earth fault current path. Other
cross sectional areas can be supplied upon
request.
- A separating tape shall be applied over all.
- The semi-conducting and separating tapes
shall be swelling to the extent required to
enable the final cable to pass the longitudinal
water penetration test on the screen region
as specified in Annex D of the
IEC 60502-2 Standard.

OVERSHEATH
- An extruded black UV resistant PE sheath
shall be applied on the assembly.
- Properties of the sheath shall be in accordance
with Israeli Standard 1516-2 and
IEC 60502-2 Standard for the ST7 type.
TESTS
The cable shall be tested in accordance with
the Israeli Standard 1516-2 and
IEC 60502-2 Standard.
CHARACTERISTICS
Mechanical resistance
to impacts
Flexibility
Minimum installation
temperature
Temperature range
Weather resistance

Low
Semi-flexible
-20 C
-40 to +90 C
Good

PCD 33-24/3.02 March 6, 2002

TEMPERATURE RATING FACTORS


Ambient Temperature C
20
Correction factor air
1.08
Correction factor ground
1.00

SCOPE
This specification describes XLPE insulated PE
sheathed single core cables for fixed
installations underground and in the air in
commercial, industrial and utilities plants.
They are intended for use on single phase and
three phase installations of 6/10 kV, 12/20 kV
or 18/30 kV at maximum conductor
temperatures of 90C for continuous normal
operation and 250 C for short circuit
maximum conductor temperature.

Specification

PCD 45-13, October 2007

(1) The conductor short circuit rating is based on an initial conductor temperature of 90 C and a final temperature of 250 C.
(2) Current rating based upon operation at 90 C conductor, three-phase a.c. load in trefoil touching formation or flat formation with one cable diameter
clearance. The screens are bonded and earthed at both ends of the cables. According to VDE 0276-620.
(3) Cable laid in freely circulating air at 30 C, protected against direct thermal radiation due to sun, etc.
(4) Cable directly buried at 0.7 m deep in soil at 20 C, with 1 K . m/W thermal resistivity. Load factor 0.7.
(5) Calculated inductive reactance per core in trefoil touching formation. The screens are bonded and earthed at both ends of the cables.

XLPE Insulated, with Longitudinal


Water Barrier, PE Sheathed
Single Core Cables for Fixed
Installations, 6/10 kV;
12/20 kV; 18/30 kV