SPLIT Pair
F-Series
[Applied Models]
z Non-Inverter Pair : Cooling Only
Si01-718
Outdoor Unit
R50BV1
R60BV1
Table of Contents
R50BVL
R60BVL
R50CV1A
R60CV1A
Si01-718
1. Introduction ............................................................................................ iv
1.1 Safety Cautions ....................................................................................... iv
1.2 Used Icons ............................................................................................ viii
ii
Si01-718
5. Check ....................................................................................................56
5.1 How to Check .........................................................................................56
Part 9 Appendix........................................................................... 89
1. Piping Diagrams....................................................................................90
1.1 Indoor Units ............................................................................................90
1.2 Outdoor Units .........................................................................................90
2. Wiring Diagrams....................................................................................91
2.1 Indoor Units ............................................................................................91
2.2 Outdoor Units .........................................................................................92
Index
............................................................................................. i
Table of Contents
iii
Introduction
Si01-718
1. Introduction
1.1
Safety Cautions
Cautions and
Warnings
Be sure to read the following safety cautions before conducting repair work.
The caution items are classified into
Warning and
Caution. The
Warning
items are especially important since they can lead to death or serious injury if they are not
followed closely. The
Caution items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates the item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates the prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates the action that must be taken, or the instruction.
The instruction is shown in the illustration or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment may
cause an electrical shock or fire.
iv
Si01-718
Introduction
Warning
Be sure to wear a safety helmet, gloves, and a safety belt when working at a
high place (more than 2m). Insufficient safety measures may cause a fall
accident.
In case of R410A refrigerant models, be sure to use pipes, flare nuts and tools
for the exclusive use of the R410A refrigerant.
The use of materials for R22 refrigerant models may cause a serious accident
such as a damage of refrigerant cycle as well as an equipment failure.
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down enough
before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
Introduction
Si01-718
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it may cause an electrical shock,
excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow the local
technical standards related to the electrical equipment, the internal wiring
regulations, and the instruction manual for installation when conducting
electrical work.
Insufficient power circuit capacity and improper electrical work may cause an
electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the terminal
cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause
an electrical shock, excessive heat generation or fire.
Do not mix air or gas other than the specified refrigerant (R410A / R22) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair it
before charging the refrigerant. After charging refrigerant, make sure that there
is no refrigerant leak.
If the leaking point cannot be located and the repair work must be stopped, be
sure to perform pump-down and close the service valve, to prevent the
refrigerant gas from leaking into the room. The refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such as fan
and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation site has
sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment may fall and cause injury.
vi
Si01-718
Introduction
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert
the plug into a power outlet securely.
If the plug has dust or loose connection, it may cause an electrical shock or fire.
Be sure to install the product securely in the installation frame mounted on the For unitary type
window frame.
only
If the unit is not securely mounted, it may fall and cause injury.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections may cause excessive heat generation,
fire or an electrical shock.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding may cause an electrical shock.
vii
Introduction
Si01-718
Caution
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause the water to enter the room and wet the furniture
and floor.
Be sure to install the packing and seal on the installation frame properly.
For unitary type
If the packing and seal are not installed properly, water may enter the room and only
wet the furniture and floor.
1.2
Used Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each
icon is described in the table below:
Icon
Type of
Information
Description
Note
Caution
Warning
Reference
Note:
Caution
Warning
viii
Si01-718
Part 1
List of Functions
1. List of Functions ......................................................................................2
List of Functions
List of Functions
Si01-718
Basic
Function
19.4
~46
19.4
~46
PAM Control
Compressor
Comfortable
Airflow
Comfort
Control
Operation
Lifestyle
Convenience
Functions
Inverter
(with Inverter Power Control)
FT50/60FVM
R50/60BVL
FT50/60FVM
R50/60BVL
Category
FT50/60FVM
R50/60BV1
FT50/60FVM
R50/60BV1
1. List of Functions
Category
Health &
Clean
Functions
Longlife Filter
Swing Compressor
Rotary Compressor
Reluctance DC Motor
Power-Airflow Flap
Washable Grille
Power-Airflow Diffuser
Auto-Restart
(after Power Failure)
Wide-Angle Louvers
Vertical Auto-Swing
(Up and Down)
Horizontal Auto-Swing
(Right and Left)
3-D Airflow
Timer
Worry Free
Reliability &
Durability
Intelligent Eye
Chargeless
10m
10m
Hot-Start Function
Power Selection
Automatic Defrosting
Automatic Operation
Fan Only
Priority-Room Setting
Temperature Display
Flexibility
Remote
Control
Remote
Controller
Wireless
Wired
List of Functions
Category
Basic
Function
Compressor
Comfortable
Airflow
Comfort
Control
Operation
Lifestyle
Convenience
Functions
Inverter
(with Inverter Power Control)
Category
Health &
Clean
Functions
FT50/60FVM
R50/60CV1A
List of Functions
FT50/60FVM
R50/60CV1A
Si01-718
19.4
~46
PAM Control
Longlife Filter
Swing Compressor
Rotary Compressor
Reluctance DC Motor
Power-Airflow Flap
Washable Grille
Power-Airflow Diffuser
Auto-Restart
(after Power Failure)
Wide-Angle Louvers
Vertical Auto-Swing
(Up and Down)
Horizontal Auto-Swing
(Right and Left)
3-D Airflow
Intelligent Eye
Chargeless
Timer
Worry Free
Reliability &
Durability
Flexibility
30m
Hot-Start Function
Power Selection
Automatic Defrosting
Automatic Operation
Fan Only
Priority-Room Setting
Temperature Display
Remote
Control
Remote
Controller
Wireless
Wired
List of Functions
List of Functions
Si01-718
List of Functions
Si01-718
Part 2
Specifications
1. Specifications ..........................................................................................6
Specifications
Specifications
Si01-718
1. Specifications
50Hz 220-230-240V
Models
Indoor Units
Outdoor Units
kW
Btu/h
kcal/h
A
W
%
W/W
mm
mm
mm
Capacity (Rated)
Running Current (Rated)
Power Consumption (Rated)
Power Factor
COP (Rated)
Liquid
Piping
Connections Gas
Drain
Heat Insulation
Max. Interunit Piping Length
Max. Interunit Height Difference
Chargeless
Amount of Additional Charge
of Refrigerant
Indoor Units
Front Panel Color
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current
Power Consumption
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L
Sound
Outdoor Units
Casing Color
Type
Compressor Model
Motor Output
Type
Refrigerant
Oil
Charge
Type
Refrigerant
Charge
Fan
Note:
m
m
m
g/m
m/min
(cfm)
FT50FVM
R50BV1
5.3
18,090
4,560
7.9-7.6-7.2
1,650
94.9-94.4-95.5
3.21
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
15
10
FT60FVM
R60BV1
6.6
22,530
5,630
11.6-11.1-10.6
2,460
96.4-96.4-96.7
2.68
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
15
10
20
20
mm
mm
kg
kg
FT50FVM
White
16.2 (572)
14.0 (494)
11.9 (420)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable/Washable/Mildew Proof
0.19-0.18-0.17
40
95.7-96.6-98.0
Microcomputer Control
2901,050238
3371,147366
12
17
FT60FVM
White
17.5 (618)
15.0 (530)
12.5 (441)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable/Washable/Mildew Proof
0.21-0.20-0.19
45
97.4-97.8-98.7
Microcomputer Control
2901,050238
3371,147366
12
17
dBA
45/41/35
47/42/36
R50BV1
Ivory White
Hermetically Sealed Rotary Type
RC60V1TNRT
1,500
SUNISO 4GSD. I.
0.85
R-22
1.35
40.0-40.5-41.0 (1,412-1,430-1,448)
()
Propeller
53
7.71-7.42-7.03
1,610
94.9-94.3-95.4
32-33.5-35
685800300
732955390
49
54
54-54-55
3D056213
R60BV1
Ivory White
Hermetically Sealed Rotary Type
NH41VMDT
2,200
MS-32
1.20
R-22
1.70
40.0-40.5-41.0 (1,412-1,430-1,448)
23.3-24.8-26.2 (823-876-925)
Propeller
53
11.39-10.90-10.41
2,415
96.4-96.3-96.7
55-57.5-60
685800300
732955390
61
66
54-54-55
3D056215
H
M
L
W
Steps
A
W
%
W
L
kg
H
L
W
A
W
%
A
mm
mm
kg
kg
dBA
The data are based on the conditions shown in the table below.
Cooling
Piping Length
Conversion Formulae
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
7.5m
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
Specifications
Si01-718
Specifications
60Hz 220V
Models
Indoor Units
Outdoor Units
kW
Btu/h
kcal/h
A
W
%
W/W
mm
mm
mm
Capacity (Rated)
Running Current (Rated)
Power Consumption (Rated)
Power Factor
COP (Rated)
Liquid
Piping
Gas
Connections
Drain
Heat Insulation
Max. Interunit Piping Length
Max. Interunit Height Difference
Chargeless
Amount of Additional Charge
of Refrigerant
Indoor Units
Front Panel Color
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current
Power Consumption
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L
Sound
Outdoor Units
Casing Color
Type
Compressor
Model
Motor Output
Type
Refrigerant Oil
Charge
Type
Refrigerant
Charge
Fan
m
m
m
g/m
m/min
(cfm)
m/min (cfm)
Type
Motor Output
Running Current (Rated)
Power Consumption (Rated)
Power Factor
Starting Current
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation Sound
Drawing No.
Fan
Note:
Specifications
FT50FVM
R50BVL
5.7
19,460
4,900
10.6
2,210
94.8
2.58
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
15
10
FT60FVM
R60BVL
6.9
23,560
5,930
12.5
2,710
98.5
2.55
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
15
10
20
20
mm
mm
kg
kg
FT50FVM
White
17.9 (632)
14.8 (523)
11.9 (420)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable/Washable/Mildew Proof
0.19
40
95.7
Microcomputer Control
2901,050238
3371,147366
12
17
FT60FVM
White
19.0 (671)
15.8 (558)
12.5 (441)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable/Washable/Mildew Proof
0.21
45
97.4
Microcomputer Control
2901,050238
3371,147366
12
17
dBA
45/41/35
47/42/36
R50BVL
Ivory White
Hermetically Sealed Rotary Type
RC60VHTNRT
1,500
SUNISO 4GSD.I.
0.85
R-22
1.25
30.0 (1,059)
()
Propeller
45
10.41
2,170
94.8
42
540750270
609940360
41
45
52
3D055911
R60BVL
Ivory White
Hermetically Sealed Rotary Type
RC75VHTR2T
1,800
SUNISO 4GSD.I.
1.00
R-22
1.60
44.0 (1,554)
20.3 (717)
Propeller
53
12.29
2,665
98.6
47
635800300
732955390
51
56
55
3D055912
H
M
L
W
Steps
A
W
%
W
L
kg
H
L
W
A
W
%
A
mm
mm
kg
kg
dBA
The data are based on the conditions shown in the table below.
Cooling
Piping Length
Conversion Formulae
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
7.5m
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
Specifications
Si01-718
50Hz 220-230-240V
Models
Indoor Units
Outdoor Units
kW
Btu/h
kcal/h
A
W
%
W/W
mm
mm
mm
Capacity (Rated)
Running Current (Rated)
Power Consumption (Rated)
Power Factor
COP (Rated)
Liquid
Piping
Connections Gas
Drain
Heat Insulation
Max. Interunit Piping Length
Max. Interunit Height Difference
Chargeless
Amount of Additional Charge
of Refrigerant
Indoor Units
Front Panel Color
Type
Motor Output
Speed
Air Direction Control
Air Filter
Running Current
Power Consumption
Power Factor
Temperature Control
Dimensions (HWD)
Packaged Dimensions (HWD)
Weight
Gross Weight
Operation
H/M/L
Sound
Outdoor Units
Casing Color
Type
Compressor Model
Motor Output
Type
Refrigerant
Oil
Charge
Type
Refrigerant
Charge
Fan
Note:
m
m
m
g/m
m/min
(cfm)
FT50FVM
R50CV1A
5.3
18,100
4,560
7.4-7.3-7.2
1,600
98.3-95.3-92.6
3.31
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
15
10
H
M
L
W
Steps
A
W
%
mm
mm
kg
kg
20
20
FT50FVM
White
16.2 (572)
14.0 (494)
11.9 (420)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable/Washable/Mildew Proof
0.19-0.18-0.17
40
95.7-96.6-98.0
Microcomputer Control
2901,050238
3371,147366
12
17
FT60FVM
White
17.5 (618)
15.0 (530)
12.5 (441)
Cross Flow Fan
43
5 Steps, Auto
Right, Left, Horizontal, Downward
Removable/Washable/Mildew Proof
0.21-0.20-0.19
45
97.4-97.8-98.7
Microcomputer Control
2901,050238
3371,147366
12
17
dBA
W
L
kg
H
L
W
A
W
%
A
mm
mm
kg
kg
dBA
FT60FVM
R60CV1A
6.6
22,500
5,680
11.0-10.9-10.8
2,390
98.8-95.3-92.2
2.76
6.4
15.9
18.0
Both Liquid and Gas Pipes
30
15
10
43/39/35
46/41/36
R50CV1A
Ivory White
Hermetically Sealed Rotary Type
RC60V1TNRT
1,500
SUNISO 4GSD. I.
0.85
R-22
1.35
40.0-40.5-41.0 (1,412-1,430-1,448)
()
Propeller
53
7.21-7.12-7.03
1,560
98.3-95.3-92.5
32-33.5-35
685800300
732955390
49
54
54-54-55
3D056214
R60CV1A
Ivory White
Hermetically Sealed Rotary Type
NH41VMDT
2,200
MS-32
1.20
R-22
1.70
40.0-40.5-41.0 (1,412-1,430-1,448)
23.3-24.8-26.2 (823-876-925)
Propeller
53
10.79-10.70-10.61
2,345
98.8-95.3-92.1
55-58-60
685800300
732955390
61
66
54-54-55
3D056216
The data are based on the conditions shown in the table below.
Cooling
Piping Length
Conversion Formulae
Indoor ; 27CDB/19CWB
Outdoor ; 35CDB/24CWB
7.5m
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
Specifications
Si01-718
Part 3
Printed Circuit Board
Connector Wiring Diagram
1. Printed Circuit Board Connector Wiring Diagram..................................10
1.1 Indoor Unit..............................................................................................10
Si01-718
Indoor Unit
1.1.1 FT50/60FVM
Connectors
S1
S6
S8
S21
S26
S28
S32
H1, H2, H3
Other designations
PCB (1) (Control PCB)
1) V1, V2
2) JA
JB
JC
3) FU1
4) LED A
Varistor
Address setting jumper
Fan speed setting when compressor is OFF on thermostat
Power failure recovery function
Refer to page 87 for detail.
Fuse (3.15A)
LED for service monitor (green)
ON/OFF switch
10
Si01-718
PCB Detail
S1
H2
V1
H3
FU1
H1
S21
S6
S8
LED A
JA
JB JC
S32 S28
S26
(R4003)
S27
SW1
S38
S29
(R2861)
RTH1
(R2862)
LED1
LED2
S37
(R3087)
11
12
Si01-718
Si01-718
Part 4
Details of Functions
1. Main Functions......................................................................................14
1.1
1.2
1.3
1.4
1.5
1.6
1.7
Details of Functions
13
Main Functions
Si01-718
1. Main Functions
1.1
Power-airflow
Dual Flaps
The large flaps send a large volume of air downwards to the floor. The flap provides an optimum
control area in cooling and dry mode.
Cooling Mode
During cooling mode, the flap retracts into the indoor unit. Then, cool air can be blown far and
pervaded all over the room.
Wide-Angle
Louvres
The louvres, made of elastic synthetic resin, provide a wide range of airflow that guarantees a
comfortable air distribution.
Auto-Swing
The following table explains the auto-swing process for cooling, dry, and fan :
Vertical Swing (up and down)
Cooling
40 10
40
35
5
5
5
55
35
(R2814)
Horizontal Swing
(right and left)
Fan
10
3-D Airflow
Dry
(R2815)
50
50
55
(R2816)
(R2817)
Alternative repetition of vertical and horizontal swing motions enables uniform air-
conditioning of the entire room. This function is effective for starting the air conditioner.
When the horizontal swing and vertical swing are both set to auto mode, the airflow become
3-D airflow and the horizontal swing and vertical swing motions are alternated. The order of
swing motion is such that it turns counterclockwise, starting from the right upper point as
viewed to the front side of the indoor unit.
(R1024)
14
Defails of Functions
Si01-718
1.2
Main Functions
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through rotation speed control and Hall IC
control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 52.
Fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
In automatic operation, the step SL is not available.
Step
Cooling
Dry mode
LL
L
ML
M
MH
H
(R2818)
HH (Powerful)
= Within this range the airflow rate is automatically controlled when the FAN setting
button is set to automatic.
Note:
Automatic Air
Flow Control for
Cooling
The following drawing explains the principle of fan speed control for cooling:
fan speed
M
+2C
ML
+1.5C
L
+1C
+0.5C
Thermostat
setting
temperature
Defails of Functions
Phase control
(R2820)
15
Main Functions
1.3
Si01-718
Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference is above the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes.)
Cooling / Dry
ON
C
B
Cooling : 2.0C
Dry : 2.5~2.0C
A
OFF
(R4668)
16
Defails of Functions
Si01-718
1.4
Main Functions
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
Set temperature
X
Thermostat ON point
Z
X 2.5C
X 0.5C
or
Y + 0.5C (zone B)
continues for 10 min.
X 2.0C
X 0.5C
or
Y + 0.5C (zone B)
continues for 10 min.
X 2.0C
X 0.5C = 17.5C
or
Y + 0.5C (zone B)
continues for 10 min.
24C or more
Room temperature at
startup
23.5C
~
18C
17.5C
18C
Zone C = Thermostat ON
Z
Zone B
Y
Zone B
+0.5C
(R6841)
Defails of Functions
17
Main Functions
1.5
Si01-718
The Night Set circuit continues cooling the room at the set temperature for the first one hour,
then automatically raises the temperature setting slightly for economical operations. This
prevents excessive cooling to ensure comfortable sleeping conditions, and also conserves
electricity.
Cooling Operation
18
Defails of Functions
Si01-718
1.6
Main Functions
POWERFUL Operation
Outline
In order to exploit the cooling capacity to full extent, operate the air conditioner by increasing the
indoor fan rotating speed and the compressor frequency.
Details of the
Control
When Powerful button is pushed in each operation mode, the fan speed/setting temperature will
be converted to the following states in a period of twenty minutes.
Operation mode
Cooling
Fan speed
H tap + 90 rpm
Dry
Fan
H tap + 90 rpm
Normally targeted
temperature in dry
operation; Approx. 2C
18C
Powerful ON
Powerful OFF
Fan
90rpm
H tap
Set tap
20min.
(R4834)
Defails of Functions
19
Main Functions
1.7
Si01-718
Other Functions
ON / OFF button
(R4835)
Push this button once to start operation. Push once again to stop it.
This button is useful when the remote controller is missing.
The operation mode refers to the following table.
Mode
Temperature setting
COOL
22C
AUTO
In the case of multi system operation, there are times when the unit does not activate with
this button.
20
Defails of Functions
Si01-718
Part 5
Operation Manual
1. System Configuration............................................................................22
2. Instructions............................................................................................23
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
Operation Manual
21
System Configuration
Si01-718
1. System Configuration
After the installation and test operation of the room air conditioner have been completed, it
should be operated and handled as described below. Every user would like to know the correct
method of operation of the room air conditioner, to check if it is capable of cooling well, and to
know a clever method of using it.
In order to meet this expectation of the users, giving sufficient explanations taking enough time
can be said to reduce about 80% of the requests for servicing. However good the installation
work is and however good the functions are, the customer may blame either the room air
conditioner or its installation work because of improper handling. The installation work and
handing over of the unit can only be considered to have been completed when its handling has
been explained to the user without using technical terms but giving full knowledge of the
equipment.
22
Operation Manual
Si01-718
Instructions
2. Instructions
2.1
Safety Precautions
Safety precautions
Keep this manual where the operator can easily find them.
Read this manual attentively before starting up the unit.
For safety reason the operator must read the following cautions carefully.
This manual classifies precautions into WARNING and CAUTION. Be sure to follow all precautions below: they are all
important for ensuring safety.
WARNING
CAUTION
If you do not follow these instructions exactly, the unit may If you do not follow these instructions exactly, the unit may
cause property damage, personal injury or loss of life.
cause minor or moderate property damage or personal injury.
Never do.
WARNING
In order to avoid fire, explosion or injury, do not operate the unit when harmful, among which flammable or
corrosive gases, are detected near the unit.
It is not good for health to expose your body to the air flow for a long time.
Do not put a finger, a rod or other objects into the air outlet or inlet. As the fan is rotating at a high speed, it will
cause injury.
Do not attempt to repair, relocate, modify or reinstall the air conditioner by yourself. Incorrect work will cause electric
shocks, fire etc.
For repairs and reinstallation, consult your Daikin dealer for advice and information.
The refrigerant used in the air conditioner is safe. Although leaks should not occur, if for
some reason any refrigerant happens to leak into the room, make sure it does not come in
contact with any flame as of gas heaters, kerosene heaters or gas range.
If the air conditioner is not cooling properly, the refrigerant may be leaking, so call your dealer.
When carrying out repairs accompanying adding refrigerant, check the content of the repairs with our service staff.
Do not attempt to install the air conditioner by your self. Incorrect work will result in water leakage, electric shocks or
fire. For installation, consult the dealer or a qualified technician.
In order to avoid electric shock, fire or injury, if you detect any abnormally such as smell of fire, stop the operation and
turn off the breaker. And call your dealer for instructions.
CAUTION
The air conditioner must be earthed. Incomplete earthing may result in electric shocks. Do not connect the
earth line to a gas pipe, water pipe, lightning rod, or a telephone earth line.
In order to avoid any quality deterioration, do not use the unit for cooling precision instruments, food, plants,
animals or works of art.
Never expose little children, plants or animals directly to the air flow.
Do not place appliances which produce open fire in places exposed to the air flow from the unit or under the
indoor unit. It may cause incomplete combustion or deformation of the unit due to the heat.
Do not block air inlets nor outlets. Impaired air flow may result in insufficient performance or trouble.
Operation Manual
23
Instructions
Si01-718
Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid injury.
Do not place anything under the indoor or outdoor unit that must be kept away from moisture. In certain conditions,
moisture in the air may condense and drip.
After a long use, check the unit stand and fittings for damage.
Do not touch the air inlet and alminum fins of outdoor unit. It may cause injury.
The appliance is not intended for use by young children or infirm persons without supervision.
Young children should be supervised to ensure that they do not play with the appliance.
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the
air conditioner.
Before cleaning, be sure to stop the operation, turn the breaker off or pull out the supply cord.
Do not connect the air conditioner to a power supply different from the one as specified. It may cause trouble or fire.
Depending on the environment, an earth leakage breaker must be installed. Lack of an earth leakage breaker may
result in electric shocks.
Arrange the drain hose to ensure smooth drainage. Incomplete draining may cause wetting of the building, furniture
etc.
Do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around
the unit.
Leaves are a hotbed for small animals which can enter the unit. Once in the unit, such animals can cause malfunctions, smoke or fire when making contact with electrical parts.
Do not operate the air conditioner with wet hands.
Do not wash the indoor unit with excessive water, only use a slightly wet cloth.
Do not place things such as vessels containing water or anything else on top of the unit. Water may penetrate into the unit and degrade electrical insulations, resulting in an electric shock.
Installation site.
To install the air conditioner in the following types of environments, consult the dealer.
Places with an oily ambient or where steam or soot occurs.
Salty environment such as coastal areas.
Places where sulfide gas occurs such as hot springs.
Places where snow may block the outdoor unit.
The drain from the outdoor unit must be discharged to a place of good drainage.
Electrical work.
For power supply, be sure to use a separate power circuit dedicated to the air conditioner.
System relocation.
Relocating the air conditioner requires specialized knowledge and skills. Please consult the dealer if relocation is necessary for moving or remodeling.
24
Operation Manual
Si01-718
2.2
Instructions
Names of Parts
Names of parts
Indoor Unit
3
2
10
6
7
11
14
12
13
Operation Manual
25
Instructions
Si01-718
Outdoor Unit
15
17
16
19
18
20
Indoor Unit
1. Air filter
3. Air inlet
4. Front panel
5. Panel tab
Mode
COOL
7. Display
8. Air outlet
Temperature
setting
22C
Outdoor Unit
15. Air inlet: (Back and side)
16. Air outlet
17. Refrigerant piping and inter-unit cable
18. Drain hose
26
Operation Manual
Si01-718
Instructions
Remote Controller
1
4
5
3
6
7
8
12
14
13
11
10
Operation Manual
27
Instructions
2.3
Si01-718
Position + and
correctly!
3
1
ATTENTION
About batteries
When replacing the batteries, use batteries of the same type, and replace the two old batteries
together.
When the system is not used for a long time, take the batteries out.
We recommend replacing once a year, although if the remote controller display begins to fade or if
reception deteriorates, please replace with new alkali batteries. Using manganese batteries reduces
the lifespan.
The attached batteries are provided for the initial use of the system.
The usable period of the batteries may be short depending on the manufactured date of the air
conditioner.
28
Operation Manual
Si01-718
Instructions
Receiver
Remote controller
holder
Set.
ATTENTION
About remote controller
Never expose the remote controller to direct sunlight.
Dust on the signal transmitter or receiver will reduce the sensitivity. Wipe off dust with soft cloth.
Signal communication may be disabled if an electronic-starter-type fluorescent lamp (such as
inverter-type lamps) is in the room. Consult the shop if that is the case.
If the remote controller signals happen to operate another appliance, move that appliance to somewhere else, or consult the shop.
Operation Manual
29
Instructions
Si01-718
1, 3
NOTE
Tips for saving energy
Be careful not to cool the room too much.
Keeping the temperature setting at a moderate level helps save energy.
Cover windows with a blind or a curtain.
Blocking sunlight and air from outdoors increases the cooling effect.
Clogged air filters cause inefficient operation and waste energy. Clean them
once in about every two weeks.
Please note
The air conditioner always consumes 15-35 watts of electricity even while it is not operating.
If you are not going to use the air conditioner for a long period, for example in spring or autumn, turn the breaker
OFF.
Use the air conditioner in the following conditions.
Mode
COOL
DRY
Operating conditions
Outdoor temperature: 20 to 46C
Indoor temperature: 18 to 32C
Indoor humidity: 80% max.
Outdoor temperature: 20 to 46C
Indoor temperature: 18 to 32C
Indoor humidity: 80% max.
Operation outside this humidity or temperature range may cause a safety device to disable the system.
30
Operation Manual
Si01-718
2.4
Instructions
To start operation
1. Press MODE selector button
and select a operation mode.
Each pressing of the button advances the
mode setting in sequence.
: DRY
2, 3
1
: COOL
: FAN
To stop operation
3. Press ON/OFF button again.
Then OPERATION lamp goes off.
COOL mode
Press
10
Operation Manual
31
Instructions
Si01-718
to
are available.
NOTE
Note on COOL operation
This air conditioner cools the room by blowing the hot air in the room outside, so if the
outside temperature is high, performance drops.
Note on DRY operation
The computer chip works to rid the room of humidity while maintaining the temperature as
much as possible. It automatically controls temperature and fan strength, so manual
adjustment of these functions is unavailable.
Note on air flow rate setting
At smaller air flow rates, the cooling effect is also smaller.
11
32
Operation Manual
Si01-718
2.5
Instructions
1, 2
STOP
COOL
approx. 10~40
DRY
approx. 5~35
In FAN mode
STOP
FAN
approx. 5~55
12
Operation Manual
33
Instructions
2.6
Si01-718
POWERFUL Operation
POWERFUL Operation
POWERFUL operation quickly maximizes the cooling
effect in any operation mode. You can get the maximum
capacity.
To start POWERFUL
operation
1. Press POWERFUL button.
POWERFUL operation ends in 20 minutes.
Then the system automatically operates
again with the settings which were used
before POWERFUL operation.
When using Powerful operation, there
are some functions which are not available.
is displayed on the LCD.
1, 2
To cancel POWERFUL
operation
2. Press POWERFUL button
again.
NOTE
Notes on POWERFUL operation
POWERFUL Operation can only be set when the unit is running. Pressing the operation stop button
causes the settings to be canceled, and the disappears from the LCD.
In COOL mode
The air flow rate is fixed to the maximum setting.
The temperature and air flow settings are not variable.
In DRY mode
The temperature setting is lowered by 2.5C and the air flow rate is slightly increased.
In FAN mode
The air flow rate is fixed to the maximum setting.
13
34
Operation Manual
Si01-718
2.7
Instructions
TIMER Operation
TIMER Operation
Timer functions are useful for automatically switching the
air conditioner on or off at night or in the morning. You can
also use OFF TIMER and ON TIMER in combination.
2
4
1, 3
NOTE
When TIMER is set, the present time is not displayed.
Once you set ON, OFF TIMER, the time setting is kept in the memory. (The memory is canceled when
remote controller batteries are replaced.)
When operating the unit via the ON/OFF Timer, the actual length of operation may vary from the time
entered by the user. (Maximum approx. 10 minutes)
NIGHT SET MODE
When the OFF TIMER is set, the air conditioner automatically adjusts the temperature setting (0.5C
up in COOL) to prevent excessive cooling for your pleasant sleep.
14
Operation Manual
35
Instructions
Si01-718
1, 3
4
2
Display
(Example)
Present time: 11:00 p.m.
(The unit operating)
OFF TIMER at 0:00 a.m.
ON TIMER at 7:00 a.m.
Combined
ATTENTION
In the following cases, set the timer again.
After a breaker has turned OFF.
After a power failure.
After replacing batteries in the remote controller.
15
36
Operation Manual
Si01-718
2.8
Instructions
Units
Indoor unit, Outdoor unit and Remote controller
1. Wipe them with dry soft cloth.
Front panel
1. Open the front panel.
Hold the panel by the tabs on the
two sides and lift it until it stops with
a click.
CAUTION
Dont touch the metal parts of the indoor unit. If you touch those parts, this may cause an injury.
When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
When removing or attaching the front panel, support the panel securely with hand to prevent it from falling.
For cleaning, do not use hot water above 40C, benzine, gasoline, thinner, nor other volatile oils,
polishing compound, scrubbing brushes, nor other hand stuff.
After cleaning, make sure that the front panel is securely fixed.
16
Operation Manual
37
Instructions
Si01-718
Filters
1. Open the front panel.
(page 16.)
2. Pull out the air filters.
Push a little upwards the tab at the
center of each air filter, then pull it
down.
tabs (3 at bottom)
Air Filter
1. Wash the air filters with water or clean them with vacuum cleaner.
If the dust does not come off easily, wash them with neutral detergent
thinned with lukewarm water, then dry them up in the shade.
It is recommended to clean the air filters every two weeks.
[ Maintenance ]
1.
2.
3.
4.
Remove dust with a vacuum cleaner and wash lightly with water.
If it is very dirty, soak it for 10 to 15 minutes in water mixed with a neutral cleaning agent.
After washing, shake off remaining water and dry in the shade.
Since the material is made out of polyester, do not wring out the filter
when removing water from it.
[ Replacement ]
1. Remove the tabs on the filter frame and replace with a new filter.
Dispose of the old filter as non-flammable waste.
17
38
Operation Manual
Si01-718
Instructions
NOTE
Operation with dirty filters:
(1) cannot deodorize the air.
(2) cannot clean the air.
(3) results in poor cooling.
(4) may cause odour.
To order Titanium Apatite Photocatalytic Air-Purifying Filter contact to the service shop
there you bought the air conditioner.
Dispose of old filters as non-flammable waste.
Item
Titanium Apatite Photocatalytic Air-Purifying Filter
(without frame) 1 set
Part No.
KAF952B42
Check
Check that the base, stand and other fittings of the outdoor unit are not decayed or corroded.
Check that nothing blocks the air inlets and the outlets of the indoor unit and the outdoor unit.
Check that the drain comes smoothly out of the drain hose during COOL or DRY operation.
If no drain water is seen, water may be leaking from the indoor unit. Stop operation and consult the service shop if this is the case.
2. After operation stops, turn off the breaker for the room air conditioner.
3. Clean the air filters and set them again.
4. Take out batteries from the remote controller.
18
Operation Manual
39
Instructions
2.9
Si01-718
Troubleshooting
Trouble Shooting
These cases are not troubles.
The following cases are not air conditioner troubles but have some reasons. You may just continue using it.
Case
Explanation
This happens when the air in the room is cooled into mist by
the cold air flow during cooling operation.
The indoor unit gives out odour. This happens when smells of the room, furniture, or
cigarettes are absorbed into the unit and discharged with the
air flow.
(If this happens, we recommend you to have the indoor unit
washed by a technician. Consult the service shop where you
bought the air conditioner.)
The outdoor fan rotates while
the air conditioner is not in
operation.
19
40
Operation Manual
Si01-718
Instructions
Check again.
Please check again before calling a repair person.
Case
Check
Hasnt a breaker turned OFF or a fuse blown?
Isnt it a power failure?
Are batteries set in the remote controller?
Is the timer setting correct?
An abnormal functioning
happens during operation.
20
Operation Manual
41
Instructions
Si01-718
WARNING
When an abnormality (such as a burning smell) occurs, stop operation and turn the breaker OFF.
Continued operation in an abnormal condition may result in troubles, electric shocks or fire.
Consult the service shop where you bought the air conditioner.
Do not attempt to repair or modify the air conditioner by yourself.
Incorrect work may result in electric shocks or fire.
Consult the service shop where you bought the air conditioner.
If one of the following symptoms takes place, call the service shop immediately.
Lightning
If lightning may strike the neighbouring area,
stop operation and turn the breaker OFF for
system protection.
21
3P192025-3
42
Operation Manual
Si01-718
Part 6
Service Diagnosis
1.
2.
3.
4.
5. Check ....................................................................................................56
5.1 How to Check .........................................................................................56
Service Diagnosis
43
Si01-718
Location of
Operation Lamp
FT50/60FVM
(R6945)
44
Service Diagnosis
Si01-718
Troubleshooting by Symptoms
2. Troubleshooting by Symptoms
Symptom
Check Item
Details of Measure
49
Service Diagnosis
Reference
Page
49
49
45
Si01-718
1. When the timer cancel button is held down for 5 seconds, a 00 indication flashes on the
temperature display section.
<ARC433A73>
(R6946)
2. Press the timer cancel button repeatedly until a continuous beep is produced.
The code indication changes in the sequence shown below, and notifies with a long beep.
Note:
46
No.
Code
No.
Code
No.
Code
1
2
00
U4
12
13
C7
H8
23
24
H0
E1
3
4
F3
E6
14
15
J3
A3
25
26
P4
L3
5
6
L5
A6
16
17
A1
C4
27
28
L4
H6
7
8
E5
F6
18
19
C5
H9
29
30
H7
U2
9
10
C9
U0
20
21
J6
UA
31
32
UH
EA
11
E7
22
A5
33
AH
Service Diagnosis
Si01-718
Check Method 2
1. Enter the diagnosis mode.
Press the 3 buttons (TEMP ,TEMP , MODE) simultaneously.
(R4272)
(R4273)
and change the digit until you hear the sound of beep or pi pi.
(R4274)
(R4275)
Service Diagnosis
47
Si01-718
(R4276)
and change the digit until you hear the sound of beep.
(R4277)
(R4278)
48
Service Diagnosis
Si01-718
Troubleshooting
4. Troubleshooting
4.1
00
A1
A5
A6
C4
C9
Service Diagnosis
Reference
Page
Normal
50
51
52
54
54
55
49
Troubleshooting
4.2
Si01-718
Remote
Controller
Display
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Is it normal?
NO
Correct connections.
YES
Replace PCBs.
(R1400)
Note:
50
Connector No.
All models
Service Diagnosis
Si01-718
4.3
Troubleshooting
Remote
Controller
Display
A5
Method of
Malfunction
Detection
The freeze-up protection control (operation halt) is activated during cooling operation
Malfunction
Decision
Conditions
Freeze-up protection
Supposed
Causes
according to the temperature detected by the indoor unit heat exchanger thermistor.
When the indoor unit heat exchanger temperature is below 0C during cooling operation.
Troubleshooting
Caution
Check No.06
Refer to P.57
Is there any
short-circuit?
YES
NO
Check the intake air filter.
Is it very dirty?
YES
NO
Check the dust accumulation on
the indoor unit heat exchanger.
Is it very dirty?
YES
NO
Check No. 06
Indoor unit heat exchanger
thermistor check
Does it conform to
the thermistor characteristic
chart?
NO
YES
Service Diagnosis
51
Troubleshooting
4.4
Si01-718
Remote
Controller
Display
A6
Method of
Malfunction
Detection
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Malfunction
Decision
Conditions
When the detected rotation speed does not reach the demanded rotation speed of the target
tap, and is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
52
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Operation halt due to faulty capacitor of the fan motor.
Detection error due to faulty indoor unit PCB.
Service Diagnosis
Si01-718
Troubleshooting
Troubleshooting
Caution
Check No.01
Refer to P.56
NO
YES
Turn power ON and
operate fan.
Does it rotate?
YES
Check No.01
Check output of fan
motor connector
Is motor
power voltage
DC 200V
generated?
NO
Replace indoor
unit PCB.
YES
Is motor
control power voltage
DC 15V
generated?
NO
Replace indoor
unit PCB.
YES
Turn off power supply and
disconnect fan motor
connector, then turn
power ON again.
Check No.01
Check output of fan
motor connector
Is rotation
number command
voltage DC 1~6V
generated?
YES
Check No.01
Check output of fan
motor connector
Is rotation
NO
number command pulse
generated?
NO
Check No.01
Check output of fan
motor connector
YES
Is rotation
number command pulse
generated?
YES
NO
Replace indoor
unit PCB.
Replace fan motor.
Replace indoor
unit PCB.
(R3098)
Service Diagnosis
53
Troubleshooting
4.5
Si01-718
Remote
Controller
Display
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation.
(reference)
When above about 212C (less than 120 ohms) or below about 50C (more than 1,860
kohms).
Note:
Supposed
Causes
Troubleshooting
Caution
Check No.06
Refer to P.57
Is it normal?
NO
YES
Check No. 06
Thermistor resistance check
Is it normal?
NO
YES
54
Service Diagnosis
Si01-718
4.6
Troubleshooting
Remote
Controller
Display
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
*Noise
*Momentary voltage drop.
*Momentary power failure, etc.
Faulty indoor unit PCB.
Troubleshooting
Caution
NO
YES
Check the grounding. (earth)
NO
YES
The malfunction may be
caused by an external
factor, rather than defective
parts. Locate the cause of
the noise, etc., and correct
the situation.
(R1881)
Service Diagnosis
55
Check
Si01-718
5. Check
5.1
How to Check
1.
2.
3.
4.
5.
56
Service Diagnosis
Si01-718
Check
Remove the connectors of the thermistors on the PCB, and measure the resistance of each
thermistor using tester.
The relationship between normal temperature and resistance is shown in the graph and the
table below.
Thermistor R25C=20k B=3950
Service Diagnosis
Temperature (C)
20
211.0 (k)
15
10
150
116.5
5
0
88
67.2
5
10
51.9
40
15
20
31.8
25
25
30
20
16
35
40
13
10.6
45
50
8.7
7.2
57
Check
58
Si01-718
Service Diagnosis
Si01-718
Part 7
Removal Procedure
1. FT50/60FVM .........................................................................................60
1.1
1.2
1.3
1.4
1.5
1.6
Note:
The removal procedures for R50BVL are not described.
Removal Procedure
59
FT50/60FVM
Si01-718
1. FT50/60FVM
1.1
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Step
Points
1. Features
Operation lamp
Signal receiver
ON/OFF
Timer lamp
ON/OFF switch
Front panel
(R6701)
interchangeable.
Insert the air filters along
Air filter
60
Removal Procedure
Si01-718
Step
3. Remove an titanium
apatite photocatalytic air
purifying filter.
1 Push up the bottom of
an air purifying filter to
undo the hooks (2 on
lower, 3 on upper) and
take the filter out.
Removal Procedure
FT50/60FVM
Procedure
Points
interchangeable.
61
FT50/60FVM
Step
Si01-718
Procedure
Points
62
Removal Procedure
Si01-718
1.2
FT50/60FVM
Procedure
Step
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
inside it.
You can remove the front
Removal Procedure
63
FT50/60FVM
Procedure
Step
64
Si01-718
Points
Removal Procedure
Si01-718
1.3
FT50/60FVM
Procedure
Step
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
Horizontal blades
(R6703)
Left pivot
(R6704)
Installation procedure
1. Since key pattern hook is
provided, rotate the blades
and fit it to the right pivot
first.
2. Fit the blades to the center
and left pivots.
Removal Procedure
65
FT50/60FVM
Si01-718
Procedure
Step
Points
(R6706)
66
Removal Procedure
Si01-718
1.4
FT50/60FVM
Procedure
Step
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
(R6707)
Earth
Removal Procedure
(R6708)
67
FT50/60FVM
Si01-718
Procedure
Step
Points
Disconnect the
connectors for fan
motor (S1).
Disconnect the
connectors for swing
motor (S6, S8).
68
Removal Procedure
Si01-718
FT50/60FVM
Procedure
Step
Points
Screw: M416
Removal Procedure
69
FT50/60FVM
Procedure
Step
Si01-718
Points
upper side.
10
11
12
available.
Fix it as it was before.
70
Removal Procedure
Si01-718
Step
FT50/60FVM
Procedure
Points
Removal Procedure
71
FT50/60FVM
Procedure
Step
72
Si01-718
Points
Removal Procedure
Si01-718
1.5
FT50/60FVM
Procedure
Step
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
box.
1. Disconnect the refrigerant
piping.
1 Hold the indoor unit up
by a piece of wood etc.
Caution
If gas leaks, repair the spot of
leaking, then collect all
refrigerant from the unit. After
conducting vacuum drying,
recharge proper amount of
refrigerant.
Caution
Do not contaminate any gas
(including air) other than the
specified refrigerant (R-22 or
R-410A, depending on the
model) into refrigerant cycle.
(Contaminating of air or other
gas causes abnormal high
pressure in refrigerating
cycle, and this results in pipe
breakage or personal
injuries.)
Pay attention so that the
Removal Procedure
73
FT50/60FVM
Step
Si01-718
Procedure
Points
74
At an angle of 10~20
Removal Procedure
Si01-718
FT50/60FVM
Procedure
Step
Removal Procedure
Points
Caution
When removing or
reinstalling heat exchanger,
be sure to wear protective
gloves or wrap the heat
exchanger with cloths. (Fins
can cut fingers.)
75
FT50/60FVM
1.6
Si01-718
Procedure
Step
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
76
Removal Procedure
Si01-718
FT50/60FVM
Procedure
Step
Points
Side face of
bottom frame
Removal Procedure
5mm
(R2808)
77
Si01-718
Removal of Panels
Procedure
Step
78
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
Removal Procedure
Si01-718
2.2
Procedure
Step
1 Remove the wire
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
harness connectors
from the PCB.
Removal Procedure
79
Step
3
Si01-718
Procedure
Points
Remove compressor
protective device and
three terminals together
with mounting plate.
80
Removal Procedure
Si01-718
Step
Procedure
Removal Procedure
Points
81
2.3
Si01-718
Removal of Compressor
Procedure
Step
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
82
WARNING
If refrigerant gas leaks during
servicing work, ventilate the
area. (If refrigerant gas
contacts flames, hazardous
gas can generate.)
When removing sound
blanket, do not pull it with
excessive force, since it is
inserted between pipes.
Removal Procedure
Si01-718
Step
Procedure
After disconnecting
refrigerant pipes,
remove three washer
nuts that secure
compressor in place.
Use open-end wrench
to remove washer nut
(a) located on right front
side.
Removal Procedure
Points
83
84
Si01-718
Removal Procedure
Si01-718
Part 8
Others
1. Others ...................................................................................................86
1.1 Test Run from the Remote Controller ....................................................86
1.2 Jumper Settings .....................................................................................87
Others
85
Others
Si01-718
1. Others
1.1
ARC433 series
(3)
(2)
ON/OFF
(3)
86
POWERFUL
TEMP
MODE
FAN
(1) (4)
(R4007)
Others
Si01-718
1.2
Others
Jumper Settings
JA
ADDRESS
J4
JA ADDRESS
J4 ADDRESS
EXIST
CUT
EXIST
CUT
1
2
1
2
(R4417)
(R4418)
JB
Others
When connected
(factory set)
Auto re-start
When cut
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
87
Others
88
Si01-718
Others
Si01-718
Part 9
Appendix
1. Piping Diagrams....................................................................................90
1.1 Indoor Units ............................................................................................90
1.2 Outdoor Units .........................................................................................90
2. Wiring Diagrams....................................................................................91
2.1 Indoor Units ............................................................................................91
2.2 Outdoor Units .........................................................................................92
Appendix
89
Piping Diagrams
Si01-718
1. Piping Diagrams
1.1
Indoor Units
FT50FVM, FT60FVM
INDOOR UNIT
(7.9CuT)
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
FIELD PIPING
(6.4CuT)
FIELD PIPING
(15.9CuT)
M
FAN MOTOR
(12.7CuT)
REFRIGERANT FLOW
COOLING
4D050919E
1.2
Outdoor Units
OUTDOOR UNIT
R60BVL
OUTDOOR UNIT
HEAT EXCHANGER
HEAT EXCHANGER
M
LIQUID STOP
VALVE
FIELD PIPING
(6.4CuT)
CAPILLARY TUBE
PROPELLER FAN
FIELD PIPING
(15.9CuT)
ACCUMULATOR
LIQUID STOP
VALVE
ACCUMULATOR
FIELD PIPING
(6.4CuT)
FIELD PIPING
(15.9CuT)
COMPRESSOR
COMPRESSOR
REFRIGERANT FLOW
COOLING
REFRIGERANT FLOW
COOLING
DW521-856N
90
DW527-236D
Appendix
Si01-718
Wiring Diagrams
2. Wiring Diagrams
2.1
Indoor Units
FT50FVM, FT60FVM
FIELD WIRING.
PCB3
S27
S26
PCB1
~
RECTIFIER
X1M
H1
Fu
3.15A
V1
H2
H3
SA1
V2
WHT
BLK
GRN/
YLW
MR2
R1T
S38
RED
LED1
LED2
H1P
H2P
S21
FG
PCB2
SIGNAL
RECEIVER
WIRELESS
REMOTE
CONTROLLER
Appendix
S1W
S32
t
S29
S6
R2T
M
M1S
M1F
RED
ORG
YLW
PNK
BLU
S28
RED
INDOOR
3
OUTDOOR
CAUTION
NOTE THAT OPERATION WILL
RESTART AUTOMATICALLY IF
THE MAIN POWER SUPPLY IS
TURNED OFF AND THEN BACK
ON AGAIN.
S1
BLU
BRN
ORG
WHT
PCB4
S37
FG
Fu
H1~H3
H1P, H2P
M1F
M1S
MR2
PCB1~PCB4
R1T, R2T
S1~S38
S1W
SA1
V1, V2
X1M
: FRAME GROUND
: FUSE
: HARNESS
: PILOT LAMP
: FAN MOTOR
: SWING MOTOR
: MAGNETTIC RELAY
: PRINTED CIRCUIT BOARD
: THERMISTOR
: CONNECTOR
: OPERATION SWITCH
: SURGE ARRESTER
: VARISTOR
: TERMINAL STRIP
: PROTECTIVE EARTH
3D038655E
91
Wiring Diagrams
2.2
Si01-718
Outdoor Units
R50BV1
X1M
RED
TO INDOOR UNIT
1
RED
WHT
BLU
C
S
YLW
RED
RED
RED
C11R
3.15A
BLK
BLK
BLK
14
13
BLK
M
BLK
A2
A1
F1S
Q1L
RED
WHT
C12R
K1M
M1F
X11A
NOTES
1. REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
1~
RED
RED
POWER SUPPLY
M1C
F1U
ORG
M
1~
3D040743A
R60BV1
RED
X1M
TO INDOOR UNIT
RED
BLU
C11R
2
YLW
WHT
RED
RED
RED
L
H
3.15A
BLK
BLK
14
WHT
BLK
BLK
RED
BLK
ORG
M
1~
RED
A1
A2
K1M
RED
WHT
C12R
M1C
S1T
F1U
N
POWER SUPPLY
13
M
1~
X11A
M1F
F1S
C11R, C12R
F1S
F1U
K1M
L
M1C
: RUNNING CAPACITOR
: SURGE ARRESTER
: FUSE
: COMPRESSOR RELAY
: LIVE
: COMPRESSOR MOTOR
NOTES
1.REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
3D032200A
92
Appendix
Si01-718
Wiring Diagrams
R50BVL
X1M
RED
RED
WHT
BLU
RED
RED
C11R
3.15A
BLK
BLK
BLK
13
14
BLK
BLK
X11A
F1U
M1C
M
1~
RED
WHT
RED
M1F
C12R
K1M
ORG
RED
POWER SUPPLY
A2
A1
BLK
M
1~
YLW
RED
TO INDOOR UNIT
Q1L
F1S
C11R, C12R
F1U
F1S
K1M
L
M1C
: RUNNING CAPACITOR
: FUSE
: SURGE ARRESTER
: COMPRESSOR RELAY
: LIVE
: COMPRESSOR MOTOR
M1F
N
Q1L
X11A
X1M
: FAN MOTOR
: NEUTRAL
: OVERLOAD PROTECTOR
: CONNECTOR
: TERMINAL STRIP
NOTES
1.REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
3D032199B
R60BVL
INDOOR
RED
X1M
1
OUTDOOR
1
RED
BLU
C11R
2
WHT
RED
YLW
RED
RED
L
3
BLK
H
3.15A
RED
BLK
POWER SUPPLY
~220V 60Hz
F1U
C11R,C12R
F1S
F1U
K1M
L
N
Appendix
:RUNNING CAPACITOR
: SURGE ARRESTER
: FUSE
: COMPRESSOR RELAY
: LIVE
: NEUTRAL
A2
A1
BLK
F1S
FIELD WIRING.
BLK
ORG
14
13
WHT
M
1~
M1C
S1T
L
C
H
RED
K1M
C12R
BLK
BLK
ORG
ORG
RED
RED
WHT
WHT
M
1~
M1F
X11A
Q1L
M1C
S1T
M1F
Q1L
X1M
X11A
: COMPRESSOR MOTOR
: THERMOSTAT
: FAN MOTOR
: OVERLOAD PROTECTOR
: TERMINAL STRIP
: CONNECTOR
NOTE
REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
PROTECTIVE EARTH
3D032198C
93
Wiring Diagrams
Si01-718
R50CV1A
X1M
RED
FIELD WIRING.
indoor
RED
WHT
BLU
YLW
RED
RED
RED
C11R
BLK
BLK
GRN
/ YLW
13
3.15A
F1U
A2
A1
ORG
BLK
RED
RED
GRN
/ YLW
POWER SUPPLY
~50Hz 220-240V
M
~
WHT
C12R
K1M
M1C
X11A
M1F
Q1L
BLK
BLK
RED
L
N
14
M
~
outdoor
F1S
NOTES
1.REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
: RUNNING CAPACITOR
F1S
: SURGE ARRESTER
: NEUTRAL
F1U
: FUSE
X11A : CONNECTOR
K1M
: COMPRESSOR RELAY
: LIVE
: PROTECTIVE EARTH
3D045730A
R60CV1A
indoor
FIELD WIRING.
RED
X1M
1
RED
BLU
C11R
1
YLW
WHT
2
3
RED
RED
YLW
RED
BLK
BLK
3.15A
F1U
L
RED
POWER SUPPLY
~50Hz 220-240V
13
14
GRN
/ YLW
WHT
A1
A2
RED
K1M
BLK
F1S
M
~
M1C
S1T
L BLK
C
H
M
~
ORG
RED
BLK
L
N
94
3
GRN
WHT
X11A
C12R
M1F
outdoor
: LIVE
M1C
: COMPRESSOR MOTOR
M1F
: FAN MOTOR
: NEUTRAL
S1T
: THERMOSTAT
F1S
: SURGE ARRESTER
X11A
: CONNECTOR
F1U
: FUSE
X1M
: TERMINAL STRIP
K1M
: COMPRESSOR RELAY
: PROTECTIVE EARTH
NOTES
1. REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
3D045733
Appendix
Si01-718
Index
Numerics
00 ...........................................................................49
3 minutes stand-by .................................................20
A
A1 ...........................................................................50
A5 ...........................................................................51
A6 ...........................................................................52
address setting jumper ...........................................10
air filter ...................................................................60
ARC433A ...............................................................46
auto-restart .............................................................87
auto-restart function ...............................................20
auto-swing ..............................................................14
B
buzzer PCB ............................................................11
C
C4 ...........................................................................54
C9 ...........................................................................54
centralized control ..................................................10
check
fan motor connector output check ...................56
thermistor resistance check .............................57
check No.01 ...........................................................56
check No.06 ...........................................................57
compressor ............................................................82
compressor protective device ................................80
connectors ..............................................................10
control PCB (indoor unit) ............................11, 50, 71
D
diagnosis mode ......................................................47
discharge pipe ........................................................82
display PCB ............................................................11
drain hose ..............................................................73
drip proof plate .......................................................67
E
earth .......................................................................67
electrical box ....................................................68, 79
error codes
00 .....................................................................49
A1 ....................................................................50
A5 ....................................................................51
A6 ....................................................................52
C4 ....................................................................54
C9 ....................................................................54
error codes and description ....................................49
F
fan motor ..........................................................68, 76
fan motor connector output check ..........................56
fan motor or related abnormality ............................52
Index
G
gas piping .............................................................. 73
H
H1 .......................................................................... 10
H2 .......................................................................... 10
H3 .......................................................................... 10
HA ................................................................... 10, 71
Hall IC ............................................................. 15, 52
heat exchanger ..................................................... 73
horizontal blade ..................................................... 65
I
indoor heat exchanger thermistor ................... 54, 67
indoor unit PCB abnormality ........................... 50, 55
instructions ............................................................ 23
insulation material ................................................. 80
J
J4 .......................................................................... 87
JA .................................................................... 10, 87
JB .................................................................... 10, 87
JC .................................................................... 10, 87
jumper settings ...................................................... 87
L
LED A .................................................................... 10
LED1 ..................................................................... 10
LED2 ..................................................................... 10
liquid piping ........................................................... 73
list of functions ........................................................ 2
M
main functions ....................................................... 14
mold proof air filter (prefilter) ................................. 20
N
night set mode ....................................................... 18
O
ON/OFF button on indoor unit ............................... 20
operation lamp ...................................................... 44
i
Si01-718
P
piping diagrams ......................................................90
power failure recovery function ........................10, 87
power-airflow dual flaps .........................................14
POWERFUL operation ...........................................19
printed circuit board (PCB)
buzzer PCB .....................................................11
control PCB (indoor unit) .....................11, 50, 71
display PCB .....................................................11
signal receiver PCB .........................................11
programme dry function .........................................17
V
V1 .......................................................................... 10
V2 .......................................................................... 10
varistor .................................................................. 10
vertical blade ......................................................... 66
W
wide-angle louvres ................................................ 14
wiring diagrams ..................................................... 91
R
receiver units ..........................................................70
remote controller ....................................................46
room temperature thermistor ..................................54
RTH1 ......................................................................10
S
S1 ...............................................................10, 68, 71
S21 ...................................................................10, 71
S26 ...................................................................10, 71
S27 .........................................................................10
S28 ...................................................................10, 71
S29 .........................................................................10
S32 ...................................................................10, 71
S37 .........................................................................10
S38 .........................................................................10
S6 .....................................................................10, 68
S8 .....................................................................10, 68
safety precautions ..................................................23
self-diagnosis digital display ...................................20
service check function ............................................46
service cover ....................................................63, 78
shelter ....................................................................69
side panel ...............................................................78
signal receiver ........................................................60
signal receiver PCB ................................................11
signal receiving sign ...............................................20
sound blanket .........................................................82
specifications ............................................................6
suction pipe ............................................................82
SW1 .......................................................................10
swing motor ................................................68, 71, 72
swing motor assembly ............................................72
T
terminal cover .........................................................80
terminal strip .....................................................50, 68
test run ...................................................................86
thermistor
indoor heat exchanger thermistor ..............54, 67
outdoor air thermistor ......................................79
outdoor heat exchanger thermistor ..................79
room temperature thermistor ...........................54
thermistor or related abnormality (indoor unit) .......54
thermistor resistance check ...................................57
thermostat control ..................................................16
ii
Index
Si01-718
ARC433A ...............................................................46
auto-swing ..............................................................14
B
buzzer PCB ............................................................11
C
check No.01 ...........................................................56
check No.06 ...........................................................57
control PCB (indoor unit) ........................................11
D
diagnosis mode ......................................................47
display PCB ............................................................11
F
fan motor connector output check ..........................56
fan motor or related abnormality ............................52
fan speed control for indoor units ...........................15
freeze-up protection control ...................................51
W
wiring diagram
FT50FVM ........................................................ 91
FT60FVM ........................................................ 91
indoor units ..................................................... 91
outdoor units ................................................... 92
R50BV1 .......................................................... 92
R50BVL .......................................................... 93
R50CV1A ........................................................ 94
R60BV1 .......................................................... 92
R60BVL .......................................................... 93
R60CV1A ........................................................ 94
I
indoor unit PCB abnormality ............................50, 55
J
jumper settings .......................................................87
N
night set mode ........................................................18
O
ON/OFF button on indoor unit ................................20
operation lamp, location .........................................44
P
piping diagram
FT50FVM .........................................................90
FT60FVM .........................................................90
indoor units ......................................................90
outdoor units ....................................................90
R50BV1 ...........................................................90
R50BVL ...........................................................90
R50CV1A .........................................................90
R60BV1 ...........................................................90
R60BVL ...........................................................90
R60CV1A .........................................................90
POWERFUL operation ...........................................19
programme dry function .........................................17
R
remote controller ....................................................46
Drawings & Flow Charts
iii
Specifications, designs and other content appearing in this brochure are current as of March 2007 but subject to change without notice.