Kit Contents
All items are listed per phase.
As a minimum, the following items should be included in this kit:
1
1
2
1
1
1
1
1
1
*
* 1 skirt for 8 kV, 2 for 15 kV, 3 for 25 kV, and 4 for 35 kV.
General Instructions
Suggested Installation Equipment (not supplied with kit)
Cable preparation tools
Raychem P63 cable preparation kit or
cable manufacturer approved solvent
Safety Instructions
Warning: When installing electrical
power system accessories, failure to
follow applicable personal safety
requirements and written installation
instructions could result in fire or
explosion and serious or fatal injuries.
Regulator Pressure
FH-2616A1
Full pressure
FH-2629
15 psig
PII-54715, Rev AM
DCR C58817
PCN 102083-000
Effective Date: August 18, 1998
Installation Instructions
1. Product selection.
Check kit selection with cable
diameter dimensions in Table 1.
Table 1
Kit
Conductor Size
HVT-80-G(SG)
HVT-81-G(SG)
HVT-82-G(SG)
HVT-83-G(SG)
HVT-84-G(SG)
5kV
#4-#1AWG
1/0-250 kcmil
300-500 kcmil
600-1750 kcmil
1500-2500 kcmil
Minimum/Maximum
Insulation Diameter
Maximum
Jacket Diameter
0.35-0.60"
0.60-0.95"
0.80-1.25"
1.10-1.75"
1.60-2.45"
(9-15mm)
(15-24mm)
(20-32mm)
(28-44mm)
(41-62mm)
0.95"
1.20"
1.50"
2.10"
2.75
(24mm)
(30mm)
(38mm)
(53mm)
(70mm)
15kV
HVT-151-G(SG)
HVT-152-G(SG)
HVT-153-G(SG)
HVT-154-G(SG)
15kV
#4-1/0 AWG
2/0-350 kcmil
400-1000 kcmil
1250-2500 kcmil
0.60-0.95"
0.80-1.25"
1.10-1.65"
1.60-2.45"
(15-24mm)
(20-32mm)
(28-42mm)
(41-62mm)
1.20"
1.50"
2.10"
2.75"
(30mm)
(38mm)
(53mm)
(70mm)
25kV
HVT-252-G(SG)
HVT-253-G(SG)
HVT-254-G(SG)
HVT-255-G(SG)
25kV
#2-250 AWG
300-750 kcmil
1000-1750 kcmil
2000-2500 kcmil
0.80-1.25"
1.10-1.70"
1.60-2.45"
2.05-3.30"
(20-32mm)
(28-43mm)
(41-62mm)
(52-84mm)
1.50"
2.10"
2.75"
3.45"
(38mm)
(53mm)
(70mm)
(88mm)
35kV
HVT-352-G(SG)
HVT-353-G(SG)
HVT-354-G(SG)
HVT-355-G(SG)
35kV
#1-1/0 AWG
2/0-500 kcmil
750-1750 kcmil
2000-2500 kcmil
0.80-1.25"
1.10-1.85"
1.60-2.45"
2.05-3.30"
(20-32mm)
(28-47mm)
(41-62mm)
(52-84mm)
1.50"
2.10"
2.75"
3.45"
(38mm)
(53mm)
(70mm)
(88mm)
PII-54715, Rev AM
DCR C58817
PCN 102083-000
Effective Date: August 18, 1998
Installation Instructions
2. Prepare cables.
Table 2
Voltage
Class
5 & 8kV
15kV
25kV
35kV
Jacket Cutback
A+Z
6-1/2" + Z (160mm + Z)
11" + Z
(275mm + Z)
22" + Z
(550mm + Z)
29" + Z
(730mm + Z)
Z
"Z"
Insulation
Cutback
1/2"
(10mm)
"Y"
Length of
Lug Barrel
1/2"
(10mm)
481
Y
A+Z
CHOICE 1
2"
(50mm)
1/2"
(13mm)
512
1-1/2"(38mm)
A+Z
CHOICE 2
2"
(50mm)
513
CHOICE 3
A+Z
If UniShield Cable
2"
(50mm)
Go to Step 4, Page 5.
514
A+Z
CHOICE 4
2"
(50mm)
1"(25mm)
Go to Step 3, Page 5.
PII-54715, Rev AM
DCR C58817
1"(25mm)
PCN 102083-000
Effective Date: August 18, 1998
512a
Installation Instructions
3a. For Copper Tape Shield cable
only: Install ground braid.
Wire and Unishield cables, Go to
Step 4.
Moisture
Block
Spring Clamp
Ground
Braid
3
519
Moisture
Block
Ground
Braid
519b
PII-54715, Rev AM
DCR C58817
Clean
Lug
Taper insulation,
if needed
516
PCN 102083-000
Effective Date: August 18, 1998
Installation Instructions
5. If 25 or 35kV termination with
lug
If 5, 8, or 15kV, Go to Step 6.
Apply red sealant on lug barrel.
Using light tension, wrap two layers
of red sealant around the lug barrel.
Red Sealant
517
Shim Tube
518
Install shim.
Place the shim tube over the red
sealant butted against the insulation
and shrink into place. Apply heat
with a smooth, brushing motion.
6. Abrade insulation; clean cable.
Abrade the insulation, if necessary, to
remove imbedded semi-con. Using
an oil-free solvent, clean the cable as
shown.
Note: A copper tape cable termination is used as an example. Any
cable discussed earlier can be used.
Clean &
Abrade
Jacket
Tape
Shield
Insulation
Semi-Con
515
1/4" (5mm)
Insulation Overlap
1/4"(5mm)
Semi-con Overlap
522
PII-54715, Rev AM
DCR C58817
1"
(25mm)
PCN 102083-000
Effective Date: August 18, 1998
Installation Instructions
9. Complete grounding.
Choose the cable type (Choice 1-2)
and follow the directions given.
Clean
2-1/2"
(60mm)
CHOICE 1
If Copper Tape Shield or Lead
Sheath Cable
Lift ground braid away from the
cable jacket. Using an oil-free
solvent, clean the jacket for 2-1/2"
(60mm) below the jacket cutback
point.
524
2 Layers
Red Sealant
525
2 Layers
Red Sealant
526
Clean 2-1/2"
(60mm)
Drain Wires
520
2 Layers
Red Sealant
521
2 Layers
Red Sealant
PCN 102083-000
Effective Date: August 18, 1998
Installation Instructions
10. Apply red sealant.
b. Without lug
Red Sealant
2 Layers
Red Sealant
b. Without Lug
Wrap two layers of red sealant onto
the cable insulation as shown.
1/2" (10mm)
Insulation
Overlap
Insulation
492
HV Tube
527
PII-54715, Rev AM
DCR C58817
528
PCN 102083-000
Effective Date: August 18, 1998
Installation Instructions
13. Outdoor terminations only.
Position skirt; shrink in place.
6"
(152mm)
5"
(127mm)
530
Total
Skirts Used
5 & 8kV
15kV
25kV
35kV
1
2
3
4
Standard Termination
4-1/2"
(110mm)
531
4-1/2"
(110mm)
532
PII-54715, Rev AM
DCR C58817, PCN 102083-000
Effective Date: August 18, 1998
Instructivo de Instalacin
PII-54715, Rev AM
DCR C58817
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Ajustando el soplete
Ajuste el regulador y el soplete como se
requiere, para as proporcionar una
flama espesa de un total de 12
pulgadas.
Instrucciones Generales de
Termocontraccin
Aplique el extremo exterior de 3 a 4
pulgadas de la flama, al material
termocontrctil al calor con un suave
movimiento de cepillado.
Mantenga la flama movindose para
obtenr una termocontraccin uniforme
y evitar el chamusqueo.
PII-54715, Rev AM
DCR C58817
FH-2616A1
FH-2629
Presin completa
15 psig
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Instructivo de Instalacin
1. Seleccin del Producto
Verifique la seleccin del kit con las
dimensiones del cable en la tabla 1.
Tabla 1
Calibre del Conductor
MINIMO-MAXIMO
Diametro sobre
Aislamiento
MINIMO-MAXIMO
5kV
#4-#1AWG
1/0-250 kcmil
300-500 kcmil
600-1750 kcmil
1500-2500 kcmil
0.35-0.60"
0.60-0.95"
0.80-1.25"
1.10-1.75"
1.60-2.45"
(9-15mm)
(15-24mm)
(20-32mm)
(28-44mm)
(41-62mm)
0.95"
1.20"
1.50"
2.10"
2.75
(24mm)
(30mm)
(38mm)
(53mm)
(70mm)
15kV
HVT-151-G(SG)
HVT-152-G(SG)
HVT-153-G(SG)
HVT-154-G(SG)
15kV
#4-1/0 AWG
2/0-350 kcmil
400-1000 kcmil
1250-2500 kcmil
0.60-0.95"
0.80-1.25"
1.10-1.65"
1.60-2.45"
(15-24mm)
(20-32mm)
(28-42mm)
(41-62mm)
1.20"
1.50"
2.10"
2.75"
(30mm)
(38mm)
(53mm)
(70mm)
25kV
HVT-252-G(SG)
HVT-253-G(SG)
HVT-254-G(SG)
HVT-255-G(SG)
25kV
#2-250 AWG
300-750 kcmil
1000-1750 kcmil
2000-2500 kcmil
0.80-1.25"
1.10-1.70"
1.60-2.45"
2.05-3.30"
(20-32mm)
(28-43mm)
(41-62mm)
(52-84mm)
1.50"
2.10"
2.75"
3.45"
(38mm)
(53mm)
(70mm)
(88mm)
35kV
HVT-352-G(SG)
HVT-353-G(SG)
HVT-354-G(SG)
HVT-355-G(SG)
35kV
#1-1/0 AWG
2/0-500 kcmil
750-1750 kcmil
2000-2500 kcmil
0.80-1.25"
1.10-1.85"
1.60-2.45"
2.05-3.30"
(20-32mm)
(28-47mm)
(41-62mm)
(52-84mm)
1.50"
2.10"
2.75"
3.45"
(38mm)
(53mm)
(70mm)
(88mm)
Kit
HVT-80-G(SG)
HVT-81-G(SG)
HVT-82-G(SG)
HVT-83-G(SG)
HVT-84-G(SG)
PII-54715, Rev AM
DCR C58817
Diametro sobre
Cubierta
Maximo
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Instructivo de Instalacin
2. Preparacin de Cables
TABLA 2
Tensin
5 & 8kV
15kV
25kV
35kV
Z
Z
Y"Y"
"Z"
Corte
del == Longitud
del
Insulation
Length of
Cutback
Lug Barrel
Aislamiento
Barril
1/2"
(10mm)
++
1/2"1/2
(10mm)
(10mm)
481
Y
A+Z
TIPO 1
2"
(50mm)
1/2"
(13mm)
512
1-1/2"(38mm)
A+Z
TIPO 2
2"
(50mm)
513
TIPO 3
Cable UniShield
A+Z
2"
(50mm)
Z
514
TIPO 4
2"
(50mm)
1"(25mm)
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
512a
Instructivo de Instalacin
3a. Para Cable con Pantalla de Cinta de Cobre
Unicamente: Instale la zoguilla de tierra.
Cables con pantalla de Alambre y
no apantallados y cables unishield,
vaya al paso 4.
Bloqueo
Moisture
de
Block
Humedad
Abrazadera
Spring
Clamp
de Resorte
Ground
Zoguilla
Braid
3
519
Bloqueo
Zoguilla
Ground
Moisture
de
Braid
Block
Humedad
519a
519b
1" (25mm)
Clean
Limpie
Lug
Rebaje
borde si
Taperelinsulation,
if needed
es necesario
516
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Instructivo de Instalacin
5. Terminales de 25 35 kV con Zapata.
Si utiliza 5, 8 15 kV, vaya al paso 6.
Aplique sellador rojo sobre el barril
de la zapata.
Utilizando tensin ligera, enrolle 2
capas de mastique rojo alrededor del
barril de la zapata.
Mastique
Rojo
Red Sealant
517
518
PII-54715, Rev AM
DCR C58817
Tape
Cubierta
Jacket
Pantalla
Shield
Aislamiento
Insulation
Semiconductora
Semi-Con
515
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Instructivo de Instalacin
7. Aplique el Mastique Relevador de
Esfuerzos (SRM) o mastique amarillo
en el corte de la semiconductora.
Retire el plstico separador del mastique.
Coloque la punta del SRM en el corte de
la semiconductora y estrelo hasta que
tenga la mitad de su ancho original.
Enrrolle con suficiente tensin de 3 a 4
vueltas para cubrir suficiente aislamiento y
semiconductora. Traslape la
semiconductora y el aislamiento como se
muestra. No forme protuberancias.
NOTA: Si utiliza cable UniShield, aplique
SRM como se muestra para rellenar el
paso a la cubierta conductiva.
Adelgace
el SRM
a 5mm
Stretch
SRM
to
1/4"(5mm) wide
1/4"
(5mm)
la semiconductora
Insulation Overlap
522
523
1"
(25mm)
Tubo Negro de
Black
Control Tube
ControlStress
de Campo
TIPO 1
2-1/2"
(60mm)
524
2 Capas de
2 LayersRojo
Mastique
Red Sealant
525
22 Capas
Layersde
Mastique
Rojo
Red Sealant
526
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Instructivo de Instalacin
TIPO 2
Limpie
Clean 2-1/2"
(60mm)
Alambres
de Tierra
Drain
Wires
520
2 Capas de
2 Layers
Mastique
Rojo
Red Sealant
521
2 Capas de
2 Layers
Mastique
Rojo
Red Sealant
b. Sin zapata
a. Con zapata
2 Capas de
2 Layers
Mastique
Rojo
Red Sealant
Mastique
Rojo
Red Sealant
b. Sin zapata
Enrolle 2 capas de mastique rojo sobre el
aislamiento del cable como se muestra.
Traslape
1/2"
(10mm)
Sobre
Insulation
Overlap
Aislamiento
Aislamiento
Insulation
492
HV
Tube
Tubo
HV
527
PCN 102083-000
Fecha Efectiva: Augosto 18, 1998
Instructivo de Instalacin
12. Corte el Tubo HV.
NOTA: Antes de seguir, permita que el
tubo se enfre lo suficiente como para
tocarse.
Corte
Trim
528
Terminal Normal
6"
(152mm)
529
Terminal Invertida
5"
(127mm)
530
Clase
Campanas Usadas
5 y 8kV
15kV
25kV
35kV
1
2
3
4
4-1/2"
(110mm)
531
Terminal Invertida
4-1/2"
(110mm)
532
PII-54715, Rev AM
DCR C58817, PCN 102083-000
Fecha Efectiva: Augosto 18, 1998