GENERAL SPECIFICATION

Majax-2 axial flow fans are manufactured in


diameters ranging from 315mm to 2000mm
(available in 2250mm on request), and incorporate
manually adjustable pitch aluminium bladed
impellers.
The following configurations are
available:

IMPELLER FINISH

Impellers are dynamically balanced to ISO 1940 grade G6,3.

Direct driven units with the impellers attached directly onto the
shafts of totally enclosed motors mounted directly in the
airstream.
Belt-driven units with the motors mounted out of the airstream
on the outside of the fan casings.
Bifurcated units with motors mounted in bifurcations, out of the
airstream.
BELLAX fans with impellers attached directly onto the shafts of
totally enclosed motors and mounted on fibreglass plates with
bell shaped entries.
Majax-2 Plate mounted with the impellers attached directly onto
the shafts of totally enclosed motors and mounted on carbon
steel plates.
Vertical jet, roof mounted extraction units, available in two
ranges (HVJ-2 & HVJ-2S). See roof unit brochure for further
information.

APPLICATIONS
This range of fans is ideally suited for moving large volumes of air
against low and medium pressures in the following applications:
- General ventilation: kitchen canopies, supermarkets, airport
buildings, underground car parks, stairwell pressurization,
gymnasiums and stadium cloak rooms, industrial buildings, etc.
- Air-conditioning.
- Smoke control and exhausting heat from buildings.
- Condenser cooling.
- Cooling towers.
Combinations of motor speeds, impeller blade pitch settings, and
the number of blades per impeller (full and half solidity), provide
flexibility in terms of selection. Fans offering good efficiencies can
be selected over a range of volumes from 0,1m3/s to 85m3/s at total
pressures up to 1,0 kPa.

SIZES
The MAJAX-2 range is available in the following sizes:
- Standard direct drive fans in 12 sizes:
from 315mm to 2000mm (available in 2250mm on request).
- Standard belt drive fans in 11 sizes:
from 400mm to 2000mm.
- Bifurcated fans in 7 sizes:
from 400mm to 1250mm.
- BELLAX in 7 sizes:
from 315mm to 1000mm.
- Plate mounted axial fans in 8 sizes:
from 400mm to 1000mm.
- Vertical jet roof units:
HVJ-2 in 3 sizes from 630mm to 1000mm.
HVJ-2S in 7 sizes from 400mm to 900mm.
Sizes vary in accordance with the preferred increments covered in
ISO 497 - 1973 (E) R20. The sizes are: 315, 400, 500, 560, 630, 710,
800, 900, 1000, 1250, 1600, 2000 and 2250.

IMPELLERS
Impellers incorporate die-cast aluminium alloy blades of aerofoil
section, which are clamped in split steel hubs (Majax-2 1250H
impellers have split aluminium cast hubs). Blade pitch adjustment is
achieved by slackening the hub clamping bolts and setting the
blades to the required pitch prior to re-tensioning the clamp bolts.

Majax-2 315-1000 and 1250-F hubs are electro-coated, Majax-2


1250H hubs are aluminium cast, Majax-2 1600 to 2250 hubs are
fabricated and hot dip galvanised. Aluminium surface finishes are
left natural. All fasteners are zinc plated.

BALANCING
CASINGS - DIRECT DRIVE
Standard casing lengths (SL) usually cover the impeller and motor
assemblies. External terminal boxes are provided on the casings of
fans fitted with standard totally enclosed motors (see brochure for
connection details). Where flame-proof motors are fitted, a length
of armoured cable, which passes through the fan casing, is
connected to the motor. The free ends of these cables are to be
connected to fittings appropriate to the installation.
Smoke extraction fans are fitted with external, certified terminal
boxes and conduit for the selected application.
Casings incorporate viewing ports unless access panels are
provided.

CASINGS - BELT DRIVE


Standard casing lengths cover the overall length of the impeller and
belt drive assemblies. Generally, motors would not project beyond
the casing flanges.
Standard belt drive fans incorporate casing access panels.

FLANGE DIMENSIONS AND DRILLINGS


Flange dimensions and drillings are in accordance with BS 6339.
See brochure for details.

CASING FINISH
Casings are hot-dip galvanized to ISO 1461. All fasteners are zinc
plated.

MOTORS

PERFORMANCE

Up to frame size 160, pad mounted motors are used in most direct
driven fans. For all other applications foot mounted motors are
used. Both pad and foot mounted motors are totally enclosed.
Minimum protection is IP55 for pad and foot mounted motors.
Standard motors have Class F insulation. Standard voltages are 400
volt three phase and 220/230 volt single phase, 50Hz. Electrical
performance complies with IEC 34.
Motors with non-standard classes of insulation, special grease for
high/low temperature operation, flameproof construction, special
voltages, multi-speed, etc., may be available on application.

All performance data is based on tests carried out in accordance


with BS 848: Part 1 - Test method No. 1. Ratings are based on
standard air density of 1,20kg/m3 corresponding to an air
temperature of 20C, a barometric pressure of 101,325 kPa and a
relative humidity of 62%. Power values given reflect fan shaft power
without provision for drive losses.

MOTOR SUPPORTS
Direct driven fans up to size 1000, driven by pad mounted motors
up to frame 132, have motors mounted in plates suspended in
rubber mountings to minimize noise and vibration. All other pad
mounted motors are mounted by means of support rods.
Belt driven fans utilize foot mounted motors fitted to motor supports
mounted externally on the fan casings.

DIRECTION OF AIR FLOW


Forms B, BD and BU are standard arrangements for direct drive
fans, having motors mounted downstream of the fan impellers.

AD
A

BD

SOUND DATA
The sound data indicated on the performance graphs are "In-duct"
values obtained from tests conducted in accordance with BS 848:
Part 2 - In-duct method. The higher values on the Sound Level
contours are Overall Sound Power Levels (suffixed dBW), and the
lower values are Average Sound Pressure Levels, under free field
conditions, at a distance of 3 impeller diameters from the fan inlet or
outlet. Sound Power Levels are given in decibels re: 10-12 Watts.
Sound Pressure Levels are given in decibels re: 2 x 10-5 Pa.
An octave band analysis can be obtained by subtracting the
spectrum constants, tabulated on each performance graph, from the
Overall Sound Levels.
A-Scale levels are obtained by subtracting an A-Scale correction
constant, given on each performance graph, from the Overall Sound
Level.
"Free-field" sound levels incorporating inlet/outlet end reflection
losses, are obtained by subtracting the following constants from the
"In-duct" Octave Band Sound Levels.
OCTAVE BAND MEAN FREQUENCY

AU

BU

Forms A, AD and AU are standard arrangements for belt drive fans,


having the bearing and drive assemblies mounted upstream of the
fan impellers. These forms can also be used on direct drive fans.
Mechanical details and bearing selections on all MAJAX-2 fans,
whether direct or belt drive, are suitable for any of these attitudes.
However, impellers require changing from Form A to Form B
running.

BEARING LIFE (L10)


Direct driven 2 pole units are designed to have a 20 000 hour
statistical bearing life, and 4,6 and 8 pole units are designed to have
a 40 000 hour statistical bearing life. Belt driven units are designed
to have a statistical 40 000 hour bearing life.

TEMPERATURE LIMITATIONS
MAJAX-2 fans are suitable for operating within the following
temperature ranges:
- Standard direct drive fans:
- 20C to + 50C.
- Standard belt drive fans:
- 10C to + 50C.
- Bifurcated fans:
- 20C to + 200C.
- BELLAX:
- 20C to + 50C.
Impellers from 500 to 1000 have been successfully tested in
accordance with BS 7346 : Part 2: 1990 at 300C for 2 hours.
Impeller diameter 1600 has been successfully tested in accordance
with BS 7346: Part 2: 1990 at 300C for 1 hour.

MOISTURE TREATMENT
Standard fans are suitable for continuous operation in relative
humidities up to 95%. Special treatment of fans is available to render
them suitable for continuous operation in moisture laden
atmospheres. This treatment involves additional mechanical and
electrical sealing procedures.

FAN
SIZE
315
400
500
560
630
800
1000
1250
1600
2000

63
14
13
11
10
9
7
6
5
3
2

125
9
8
6
5
5
3
1
1
0
0

250
5
3
2
2
1
1
0
0
0
0

500
2
1
0
0
0
0
0
0
0
0

1000 &
ABOVE
0
0
0
0
0
0
0
0
0
0

REVERSAL OF AIR FLOW


The direction of air flow of a standard impeller can be reversed by
changing the direction of fan rotation. Equal volume flow in either
direction can be provided by means of special blade adjustments.
The approximate resultant fan performance for the above
conditions when compared with standard fan performance is as
follows:

Volume Reduction
Pressure Reduction
Power Reduction

STANDARD
IMPELLER

REVERSIBLE
IMPELLER

30%
55%
25%

15%
25%
20%

OPTIONAL FEATURES
Mounting feet, counter flanges, wire screens, conical inlets, antivibration mountings, casing access panels & flexible connections.
Hand, motor or airstream operated dampers.
Cylindrical attenuators of matching sizes.
Non-standard casing lengths & special protective coatings.
Belt guards & belt fairings (belt drive fans).

All technical information contained herein is subject to change without prior notice.

FAN
DIRECT DRIVE
BELT DRIVE
SIZE FAN SPEED (rpm) - MOTOR POWER (kW)
MOTOR POWER
A
2 POLE
4 POLE
6 POLE
8 POLE
(kW)
315

0.25 to 0.75 0.08 to 0.55


0.55 to 2.2 0.18 to 0.55
400
0.75 to 2.2 0.18 to 1.5
500 3.0 to 4.0
1.1 to 2.2 0.37 to 1.5
3.0 to 4.0
560 5.5 to 7.5
0.37 to 1.5
630 3.0 to 4.0 2.2 to 3.0
5.5 to 7.5
11.0
0.55 to 1.5
710
2.2 to 4.0
5.5 to 7.5
0.75 to 1.5
800
2.2 to 4.0
5.5 to 7.5
11.0
1.1 to 1.5
900
2.2 to 4.0
5.5 to 7.5
11.0 to 15.0
3.0 to 4.0
5.5 to 7.5
1000
11.0 to 15.0
18.5 to 22.0
11.0 to 15.0
18.5 to 22.0
1250 H
30.0
37.0 to 45.0
55.0 to 75.0
90.0
1250 F
-

0.06 to 0.55
0.12 to 0.55
0.12 to o.55
0.12 to 0.55
0.12 to 1.1
0.55 to 1.2
1.5 to 2.2
3.0 to 5.5
0.55 to 1.1
1.5 to 2.2
3.0
0.55 to 1.1
1.5 to 2.2
3.0 to 5.5
1.1
1.5 to 2.2
3.0 to 5.5
7.5 to 11.0
3.0 to 5.5
7.5 to 11.0
15.0
18.5 to 22.0
30.0
2.2
3.0 to 5.5
7.5 to 11.0
15.0
18.5 to 22.0

0.27
0.75 to 1.5
0.27
0.75 to 1.5
0.75 to 1.5
2.2 to 3.0
0.75 to 1.5
2.2 to 3.0
4.0
1.1 to 1.5
2.2 to 3.0
4.0 to 7.5
11.0
-

0.25 to 0.75
1.1 to 1.5
2.2 to 4.0
0.25 to 0.75
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
0.25 to 0.75
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
11.0 to 15.0
0.25 to 0.75
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
0.55 to 0.75
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
0.75
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
0.75
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
11.0 to 15.0
1.1 to 1.5
2.2 to 4.0
5.5 to 7.5
11.0 to 15.0
18.5 to 22.0
30.0
37.0
5.5 to 7.5
11.0 to 15.0
18.5 to 22.0
30.0
37.0 to 45.0
55.0 to 75.0
-

Mass Mass
K
L

315
400
400
400
400
400
500
400
400
500
630
400
400
500
400
400
500
710
400
400
500
630
400
400
560
770
770
560
800
800
850
1000
1000
1120
560
560
800
800
850

355

380

11

450

485

13

560

607

12

13

512
585
627
573
626
688
725
627
680
722
759
874
666
718
761
798
689
742
804
841
737
790
852
889
810
863
905
942
1066
915
957
994
1119
1159
1172
1238
1172
1250
1290
1312
1378
1514
-

22
22
22
22
22
22
22
22
22
22
34
22
22
22
22
22
22
34
22
22
22
34
22
22
22
34
34
22
34
34
42
22
22
34
34
42

27
38
47
75
44
79
110
47
81
116
167
54
89
123
64
98
132
223
86
123
160
233
94
133
180
279
337
300
420
480
540
670
879
1112
195
243
363
418
478

620

667

12

13

690

737

12

13

770

817

16

13

860

907

16

13

970

1039

16

13

1070

1141

16

15

1320

1392

20

15

1320

1392

20

15

All technical information contained herein is subject to change without prior notice.

500

500
500
500
500
500
740
500

500

500
500
500
500
500
740
500
500
500
740
740
990
990
710
800
800
850
850
1000
-

51
60
91
62
71
103
135
67
76
108
139
246
71
80
112
145
75
84
116
149
87
95
129
161
110
120
152
184
324
131
164
194
362
412
573
670
330
454
513
612
704
1101
-

FAN
DIRECT DRIVE
BELT DRIVE
SIZE FAN SPEED (rpm) - MOTOR POWER (kW)
MOTOR POWER
A
2 POLE
4 POLE
6 POLE
8 POLE
(kW)

1600

2000

11
15.0
18.5 to 22.0
30.0
37.0 to 45.0
55.0 to 75.0
-

4.0 to 7.5
11.0
15.0
18.5 to 22.0
30.0 to 37.0
11.0
15.0
18.5 to 22.0
30.0 to 37.0
45.0 to 55.0
75.0

5.5 to 7.5
11.0 to 15.0
15.0 to 22.0
30.0
37.0 to 45.0
55.0 to 75.0
18.5 to 22.0
30.0
37.0 to 45.0
55.0 to 75.0
90.0 to 110.0
-

740
740
990
1190
1190
1490
740
990
1190
1190
1490
1490

FAN
FAN
SIZE
SIZE

315
400
500
560
630
710
800
900
1000
1250
1600
2000

355
450
560
620
690
770
860
970
1070
1320
1680
2080

320
405
507
567
637
717
807
909
1011
1262
1613
2013

FAN
SIZE
(A)

C
P

D
Q

E
R

MASS

315
400
500
560
630
710
800
900
1000
1250
1600
2000

56
71
90
100
112
125
140
162
181
224
280
355

422
524
648
720
804
905
1006
1170
1286
1603
2050
2537

372
474
598
670
754
855
956
1090
1206
1503
1920
2407

3.99
6.09
9.11
10.39
12.04
15.38
17.85
31.18
35.67
50.41
89.09
142.22

8
8
12
12
12
16
16
16
16
20
24
24

11
13
13
13
13
13
13
13
15
15
19
19

1680

1743

24

19

2080

2173

24

19

Mass Mass
K
L

1350
1431
1471
1500
1566
1704
1670
1704
1770
1914
1968
-

740
990
990
990
990
1190
990
990
990
1190
1190
-

34
34
42
34
42
-

514
572
708
905
1072
1313
737
883
1127
1274
1593
1806

MASS
Kg
1.52
2.64
4.12
4.56
5.08
5.68
12.68
18.28
20.7
25.52
32.28
49.56

FAN
FAN
SIZE
SIZE
(A)
(A)

BS

315
400
500
560
630
710
800
900
1000
1250
1600
2000

120
120
120
120
120
120
120
120
120
160
160
160

FAN
FAN
SIZE
SIZE
(A)
(A)

KG

IVC dimensions available on request

FAN
FAN
SIZE
SIZE

315
400
500
560
630
710
800
900
1000
1250
1600
2000

35
40
40
39
39
39
39
54
59
60
75
75

20
22
22
22
22
22
22
30
35
35
40
40

11
13
13
13
13
13
13
15
15
15
19
19

125
162
232
232
262
282
332
355
385
525
590
790

140
180
250
250
280
300
350
380
410
555
625
825

MASS
MASS
Kg

240 0.41
285 0.59
355 1.28
385 1.91
420 2.20
465 2.21
518 3.81
595 4.86
653 7.59
812 13.05
1035 20.54
1234 29.19

All technical information contained herein is subject to change without prior notice.

431
616
672
779
867
1280
841
958
1045
1480
1792
-

MASS
MASS
Kg
1.60
2.77
4.33
4.79
5.33
5.96
13.31
19.19
21.74
26.80
33.89
52.04

MASS
MASS
S

315 220
400 260
500 300
560 310
630 345
710 385
800 430
900 480
1000 530
1250 655
1600 830
2000 1030

Kg
13
18
25
29
34
48
58
85
102
157
340
421

Majax-2 (2 Pole - 2880 r/min Performance Curves)

Majax-2 (4 Pole - 1440 r/min Performance Curves)

Majax-2 (6 Pole - 960 r/min Performance Curves)

Majax-2 (8 Pole - 720 r/min Performance Curves)

Majax-2 (10 Pole - 580 r/min Performance Curves)

TYPICAL ELECTRICAL CONNECTIONS


3 PHASE FANS - STAR WIRED

SINGLE PHASE FANS


L

N E

L1

L2

L3

L3
W1
N

L2

V1
U1 U2 V2

W2

L1

380-415V 3 Ph 50Hz

3 PHASE FANS DELTA WIRED 11kW & ABOVE

3 PHASE FANS DELTA WIRED UP TO 7.5kW


L1

L2

L3

L2

L1

L1

L3

U1

V2

L3

L2
V1

U1
W1

L3

W1

V1

W1

U2
V1
L2

U1

W2

U2

W2

V2

L1
U2

W2

V2

380-415V 3 Ph 50Hz

380-415V 3 Ph 50Hz

Factory Fitted Link Wires

Factory Fitted Link Wires

You might also like