You are on page 1of 1

CALCULOS DE REGULACION

PROYECTO FARMATODO

PROYECTO:

CANT

15

TEMP COND=

Voltaje=
75

208
C

FORMULA USADA=( PXL)X(KX100)X(R Cos + X Sen)/(V^2)

Voltios

CARGA EN VA
TIPO
CONDU

CONFI
SISTEM

CORRIENTE (AMPERS)

Regul Max=

ACOMETIDA

PROTEC

DESCRIP
LONG
TRAM

TIPO CARGA Luces y Tomas

Aires
Acond

S-TOTAL

Luc y Tom

A Acon

I-TOTAL

BREAK

Fases

Cond/fas

Cal-Fase

Neut

Cond/
Neutr

CANT

CANT

COND

COND

ACTIVOS

ALIMENT

TIPO

%
FACT-

DIAMET TUBERIA
REGULAC

N
NILOS

GND

COND

CANT

DIAME
PARCIAL

CANALIZ

CU

CN

TRAFO

TAB-G/RAL

40

CONTINUA

112.500

112.500

390,3474196

390,3474196

3X400

4/0

4/0

19

CARCA

CU

CN

TAB-G/RAL

TMB-TOMAS

25

CONTINUA

19.460

19460

67,52142921

67,52142921

3X75

19

PVC

20,81852905

19

10

TOTAL

LLENAD

0,688245794 0,688245794

1-1/4"

0,469755243 1,158001038

0,8

3/4"

0,595207222 1,283453016

TAB-G/RAL

TMB-ILUMINACION

28

CONTINUA

6.000

6000

20,81852905

3X30

PVC

CU

SN

TAB-G/RAL

TMB-AACOND

35

CONTINUA

61.950

61950

214,9513124

214,9513124

3X225

4/0

4/0

19

2"

0,757455268 1,445701062

SN

TAB-G/RAL

TMB-UPS

20

CONTINUA

5.000

5000

30,04807692

30,04807692

2X40

19

10

PVC

1/2"

0,354290013 1,042535807

CU

SN

TAB-G/RAL

B. C INCENDIO

12

CONTINUA

67.190

67190

233,1328278

233,1328278

3X250

250M

250M

19

3
2
3

PVC

CU

IMC

3"

0,241693135 0,92993893

CU

SN

CARGA TOTAL INSTALADA

159.600

VA

SIN BOMBA C INCENDIO

You might also like