You are on page 1of 5

PROJECT : AL AMRI MALL

SCHEDULE OF FRESH AIR HANDLING UNIT WITH HEAT RECOVERY WHEEL


SR. NO.

AHU REF.

SERVING

TOTAL
CAPACITY
KW

SPECIFIED

FAHU 1

to fill

PROPOSED

FAHU 1

113.8

SPECIFIED

FAHU 2

to fill

PROPOSED

FAHU 2

177.02

SPECIFIED

FAHU 3

to fill

PROPOSED

FAHU 3

225.07

SPECIFIED

FAHU 4

to fill

PROPOSED

FAHU 4

210.56

RECOVERY WHEEL
SENSIBLE
CAPACITY

FRESH EXHAUST
AIR QTY AIR QTY

FRESH
AIR
TEMP.

EXHAUST
AIR TEMP.

ON COIL

OFF COIL

DEG C

DEG C

DEG C

to fill

18.0/17.0

KW

L/S

L/S

DEG C

to fill

4340

3800

46.0/30.0

71.69

4340

3800

46.0/30.0

41.8/ 26.62

31.4/23.55

18/17.25

6600

5875

46.0/30.0

to fill

to fill

18.0/17.0

6600

5875

46.0/30.0

41/26.08

31.2/23.38

18/16.88

7232

5375

46.0/30.0

to fill

to fill

18.0/17.0

7232

5375

33.3/24.74

18/17.49

6650

4850

to fill

18.0/17.0

6650

4850

33.2/24.45

18/16.96

to fill
106.21
to fill
135.04
to fill
124.23

46.0/30.0 42.23/26.38
46.0/30.0

to fill

46.0/30.0 42.68/26.67

ESP

QTY

PA

CHW
IN/OUT

TYPE

DEG C

550

6--12

ROOF MOUNTED
DOUBLE SKIN

550

6--12

ROOF MOUNTED
DOUBLE SKIN

550

6--12

550

6--12

550

6--12

550

6--12

550

6--12

550

6--12

ROOF MOUNTED
DOUBLE SKIN

ROOF MOUNTED
DOUBLE SKIN

ROOF MOUNTED
DOUBLE SKIN

SPECIFIED
PROPSOED

SCHEDULE OF CHILLER
SR.NO.
CAPACITY
FLOW
KW
L/S
CH 1-3
1580
63.2
CH-1-3
1598
63.5

POWER POWER SUPPLY


KW
607.5 400V/50HZ/3PH
663
400V/50HZ/3PH

AMBIENT
QTY
DEG C
46
3W
46
3W

You might also like