Professional Documents
Culture Documents
F
or many years, high-voltage
DC testing has been the tra-
ditionally accepted method to
judge the serviceability of
medium-voltage cables. DC
high-potential (hipot) tests
worked well as a withstand and condi-
tion assessment test for paper- and oil-
insulated, lead-covered (PILC) cable.
Even when plastic insulated cables were
first introduced in the ’60s, it was still the
preferred method.
Although applicable industry stan-
dards began to change in 1994, manufac-
turers, testing firms, and standards
groups still agreed that DC hipot test
equipment could be used to perform fac-
tory tests, acceptance tests, and mainte-
nance tests. As far as the installer or main-
tenance electrician was concerned, cables
that withstood the DC hipot test were good
enough to be placed—or placed back— An IEEE study on water trees shows electrical trees will likely progress to failure quickly, so PD
into service. But recent research and field testing is more valuable if performed along with dissipation factor/power factor (DF/PF) testing.
data is calling that practice into question
and raising serious doubts about whether new medium voltage cable doesn’t cause try standards began to change is only just
DC hipot testing might damage or cause any reduction in cable life. now gaining industry-wide acceptance.
extruded cables—especially field aged As noted in IEEE Standard 400-2001, Current versions of some of these stan-
cross-linked polyethylene (XLPE) insu- Guide for Field Testing and Evaluation of dards no longer provide for DC hipot
lated cable—to fail prematurely. Shielded Power Cable Systems, “testing testing of extruded cables as a mainte-
After receiving reports in the early ’90s of cables that have been service aged in a nance test. Of those that still do, all have
that DC hipot testing could be to blame wet environment (specifically, XLPE) reduced the recommended test duration
for latent damage experienced by ex- with DC at the currently recommended from 15 min to only 5 min. None endorses
truded medium-voltage cable insulation, DC voltage levels may cause the cables DC hipot testing as a factory test for ex-
the Electric Power Research Institute to fail after they are returned to service. truded cables, but all continue to provide
(EPRI) funded two studies relating to The failures would not have occurred at for DC hipot testing as an acceptance test
XLPE and ethylene propylene rubber that point in time if the cables had re- on newly installed extruded cable. These
(EPR) cables. These studies, EPRI Reports mained in service and had not been tested industry standards also no longer endorse
TR-101245 and EL-6902, yielded the fol- with DC.” This standard also indicates DC hipot testing as a maintenance test
lowing conclusions regarding XLPE cable: other testing has shown that “even mas- for extruded cables that have been in ser-
• DC hipot testing of field-aged sive insulation defects in extruded dielec- vice for more than five years.
cable reduces its life. tric insulation cannot be detected with
• DC hipot testing of field-aged cable DC at the recommended voltage levels.” Deterioration mechanisms. Partial
generally increases water tree growth. The shift in opinion of hipot testing discharge (PD) and water intrusion are the
• DC hipot testing before energizing that began in 1994 when applicable indus- two age-related deterioration mechanisms