Writing option code


To Indoor unit
2013. 06
Samsung Electronics

No of digits to set

Code structure

Indoor unit product


option code(Basic)

24 [20]

01xxxx-1xxxxx-2xxxxx-3xxxxx

Installation option 1

02xxxx-1xxxxx-2xxxxx-3xxxxx

Installation option 2

24 [19]
24 [19]

Indoor unit address


(MAIN/RMC)

24[8]

0Axxxx-1xxxxx-2xxxxx-3xxxxx

Specific bit setting


(option, address,)

24[5]

0Dxxxx-1xxxxx-2xxxxx-3xxxxx

Function

( Logical [physical] )

(Logical)

05xxxx-1xxxxx-2xxxxx-3xxxxx

1. Remove the battery.


2. Put the battery back with the
"Temp" UP/DOWN buttons
kept pressing.
3. Press the "Fan Speed" button
to change the value.

Initial display

down : 1st digit. / up : 2nd digit.


4. Press the Mode button to move to the next two bits.
5. Press the On/Off button two times to set the option setting.
Pressing once : checking current option value of IDU
/ pressing one more time : confirmation

Press

Press

1 : Product Opt.
2 : Installation Opt.
5 : Installation Opt.
A : Address
D : Specific Digit

ex)

015223 1901BA
200000 300000

Every 2 bits are differentiated by the combination of operation mode icons and
the ON/OFF timer icons
Seg1,7,13,19 are page number which is ignored for setting with wireless R/C

0Axxxx 1xxxxx 2xxxxx 3xxxxx

D2 D3

D2 : Setting mode

D3 : MAIN address
0 - No setting
1 - Setting

D4 D5

D4 : Hundreds digit of
MAIN address
- Must be set to 0

D5 : Tens digit of MAIN


address
0~6

D6

D6 : Ones digit of MAIN


address
0~9

0Axxxx 1xxxxx 2xxxxx 3xxxxx

D8

D8 : -

D9 D10

D9 : RMC address
0 - No setting
1 - Setting

D10 : -

D11 D12

D11 : RMC channel(RMC1)


0~F
(=On Off Controller add.)

D12 : RMC address(RMC2)


0~F
(=On Off Controller Button)

02xxxx 1xxxxx 2xxxxx 3xxxxx

D2 D3

D2 : Setting mode

D3 : RESERVED

D4 D5

D4 : Remote Temp.
sensor
0 - No use 1 - Use

D5 : Central control
0 - No use
1 - Use(default)

D6 D8

D6 : RPM UP
0-No use 1-RPM Compensation
2-High ceiling kit

D8 : Drain pump
0 - No use
1 - Use (No delay)
2 - Use (3-minute delay)

NOTE : 1/2/4way cassettes are set to Use with 3-min delay regardless of D8 setting

02xxxx 1xxxxx 2xxxxx 3xxxxx

D9 D10

D9 : Hot water heater


0 - No use
1 - Use

D10 : RESERVED

D11 D12

D11 : EEV stop step


in heating mode
0 Default
1 Use(noise decreasing)

D12 : RESERVED

D14 D15

D14 : External control


0 - No use
1 - On/Off control
2 - Off-only control
3 - Window on/off control

D15 : Ext. contact output


0 : Thermo on
1 : Operation on

02xxxx 1xxxxx 2xxxxx 3xxxxx

D16 D17

D16 : SPI
0 - No use

1 - Use

D18 D20

D21 D22

D18 : Filter time (hr)

D21 : Heating temp.


compensation

2 - 1000, 6 - 2000

D17 : Buzzer sound


0-Use
1-No use

D20 : Wireless R/C address


0,1 - Indoor 1, 2 - Indoor 2
3 - Indoor 3, 4 - Indoor 4

0-Default
1-2
2-5

D22 : EEV step of stopped unit


during oil return/defrost mode
0 - default
1 - Noise decreasing

NOTE : The default on D21 means heating compensation temperature is applied by product option of SEG6

02xxxx 1xxxxx 2xxxxx 3xxxxx

D23 D24

D23 : Motion detect sensor


Mode

Soft off

Hard off

20 min.

30 min.

40 min.

60 min.

80 min.

120 min.

120 min.

180 min.

20 min.

30 min.

40 min.

60 min.

80 min.

120 min.

120 min.

180 min.

No use

Standard mode

Premium mode

Communication wiring between outdoor unit and indoor units(F1/F2)


Set the quantity of indoor units(@ outdoor unit PCB)
Turn on the power of kit and check the tracking procedure.
Set the MAIN address to 17,18&19 with wireless R/C
1) Write down the ADDRESS option of 6 digits to set.
2) Set the MAIN address with wireless R/C

Set the INSTALLATION option code with wireless R/C


Drain pump : use (SEG 8 : 2) / SPI : use (SEG 16 : 1) / Filter reset : 2000 hour (SEG 18 : 6)
1) Write down the INSTALLATION option of 24 digits to set.
2) Set the INSTALLATION option with wireless R/C

I. Wireless remote controller


The specific digit setting mode is primarily used to set a specific digit without setting all unnecessary digits.

0Dxxxx 1xxxxx 2xxxxx 3xxxxx

D2 D3

D4 D5

D2 : Setting mode

D4 : Tens digit of position


of digits to change
0~9

D3 : Mode to change

D5 : Ones digit of position


of digits to change
0~9

1 Product Option
2/5 Installation Option
A - MAIN/RMC Address

D6

D6 : Digit to change
0~F

I. Wireless remote controller


- To set external control to Off-only

02xxxx 1xxxxx 22xxxx 3xxxxx


D14 : External control

14th digit

0 - No use
1 - On/Off control
2 - Off-only control
3 - Window On/Off

- To set the specific digit of the 2 mode

0D2142 1xxxxx 2xxxxx 3xxxxx

Table of specific optional function setting


Install option

Robot cleaning

Remote sensor
Central control

RPM UP

Drain pump

Hot water
EEV stop step
In heating

Digit setting

Operation

0D2030 1xxxxx 2xxxxx 3xxxxx

No use

0D2031 1xxxxx 2xxxxx 3xxxxx

Use

0D2040 1xxxxx 2xxxxx 3xxxxx

No use

0D2041 1xxxxx 2xxxxx 3xxxxx

Use

0D2050 1xxxxx 2xxxxx 3xxxxx

No use

0D2051 1xxxxx 2xxxxx 3xxxxx

Use

0D2060 1xxxxx 2xxxxx 3xxxxx

No use

0D2061 1xxxxx 2xxxxx 3xxxxx

RPM compensation

0D2062 1xxxxx 2xxxxx 3xxxxx

High ceiling kit

0D2080 1xxxxx 2xxxxx 3xxxxx

No use

0D2081 1xxxxx 2xxxxx 3xxxxx

Use (No delay)

0D2082 1xxxxx 2xxxxx 3xxxxx

Use (3-minute delay)

0D2090 1xxxxx 2xxxxx 3xxxxx

No use

0D2091 1xxxxx 2xxxxx 3xxxxx

Use

0D2110 1xxxxx 2xxxxx 3xxxxx

default

0D2111 1xxxxx 2xxxxx 3xxxxx

Use (Noise decreasing)

Table of specific optional function setting


Install option

Indoor unit display on


wired R/C

External control

Indoor unit
operation output
SPI

Buzzer sound

Filter time

Digit setting

Operation

0D2120 1xxxxx 2xxxxx 3xxxxx

Slave (low priority)

0D2121 1xxxxx 2xxxxx 3xxxxx

Master (high priority)

0D2140 1xxxxx 2xxxxx 3xxxxx

No use

0D2141 1xxxxx 2xxxxx 3xxxxx

ON/OFF control

0D2142 1xxxxx 2xxxxx 3xxxxx

OFF-only control

0D2143 1xxxxx 2xxxxx 3xxxxx

Window ON/OFF

0D2150 1xxxxx 2xxxxx 3xxxxx

Thermo ON

0D2151 1xxxxx 2xxxxx 3xxxxx

Operation ON

0D2160 1xxxxx 2xxxxx 3xxxxx

No use

0D2161 1xxxxx 2xxxxx 3xxxxx

Use

0D2170 1xxxxx 2xxxxx 3xxxxx

use buzzer

0D2171 1xxxxx 2xxxxx 3xxxxx

no use buzzer

0D2182 1xxxxx 2xxxxx 3xxxxx

1000 hours

0D2186 1xxxxx 2xxxxx 3xxxxx

2000 hours

Table of specific optional function setting


Install option

Wireless remote
control address

Heating temperature
compensation
EEV opening of IDU
stopped during oil
return or defrost

Motion detect sensor

0D2201
0D2202
0D2203
0D2204
0D2210
0D2211
0D2212
0D2220

Digit setting
1xxxxx 2xxxxx
1xxxxx 2xxxxx
1xxxxx 2xxxxx
1xxxxx 2xxxxx
1xxxxx 2xxxxx
1xxxxx 2xxxxx
1xxxxx 2xxxxx
1xxxxx 2xxxxx

3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx

Operation

Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 4
default

2
5
Default

0D2221 1xxxxx 2xxxxx 3xxxxx

Use(Noise decreasing)

0D2230
0D2231
0D2232
0D2233
0D2234
0D2235
0D2236
0D2237
0D2238

No use
Standard mode / Auto set off 30 min.
Standard mode / Auto set off 60 min.
Standard mode / Auto set off 120 min.
Standard mode / Auto set off 180 min.
Premium mode / Auto set off 30 min.
Premium mode / Auto set off 60 min.
Premium mode / Auto set off 120 min.
Premium mode / Auto set off 180 min.

1xxxxx
1xxxxx
1xxxxx
1xxxxx
1xxxxx
1xxxxx
1xxxxx
1xxxxx
1xxxxx

2xxxxx
2xxxxx
2xxxxx
2xxxxx
2xxxxx
2xxxxx
2xxxxx
2xxxxx
2xxxxx

3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx
3xxxxx

Eliminate buzzer sound of indoor unit with wireless R/C


Control individual blade of 4way cassette type indoor unit.
Set the MULTI CHANNEL option of indoor units to 1,2 & 3 with wireless R/C
(Specific digit setting mode : SEG 20 : 1/2/3 0D2201 / 0D2202 / 0D2203)
1) Write down the INSTALLATION option of 6 digits to set.
2) Set the INSTALLATION option with wireless R/C
3) Control one of the indoor units with multi channel function of wireless R/C.