You are on page 1of 3

Datasheet TOTAL 3 PAGES

(Including Cover)

Purpose

PROJECT CODE : LAC_CL005


X For Information
PROJECT NAME : ANDES PROJECT
For Review

DOCUMENT No. : AD488-EZ460-00004


For Construction

TITLE : RD1-Cable MV Cable 630mm2

PACKAGE : Datasheets

OWNER : ET SOLAR DE CHILE SPA

B Apr 2015 M.C. M.C. S.V For Approval

PREPARED REVIEWED APPROVED CHECKED REVIEWED APPROVED


Rev.
DATE DESCRIPTION
No. ET SOLAR DE CHILE SPA AES GENER
Owner

Contractor Supplier
Technical Data for XLPE Insulated Cables

Single-core cable with aluminium round compacted conductor, XLPE insulation, copper tape screen, PVC oversheath
General Description:
Cable code: 75010102253245
Standard specification: IEC:60502-2
Type of cable: XLPE/CTS/PVC
Rated voltage Uo/U (Umax): 18/30 (36) kV
Number of cores x Nominal cross-section: 1x630 mm
Approximate cable overall diameter: 53 mm
Approximate cable overall weight: 3.5 kg/m
Nominal drum length (Tolerance): 1500 m ( 5%)
Oversheath marking by embossing or ink (Manufacturers option) as follows:
CABLEL 0317 2014* ELECTRIC CABLE 18/30 KV IEC 60502-2 1x630 AL
* Year of manufacture
Meter marking at one-meter intervals by ink on oversheath
Cable structure:
1 - Conductor:
Aluminium round stranded compacted class 2 IEC 60228 of nominal cross-section equal to 630 sq.mm
Approximate conductor diameter: 30 mm
2 - Conductor non-metallic extruded screen:
Extruded semiconducting compound
3 - Insulation:
XLPE according to IEC 60502-2 of 8.0 mm nominal thickness
Approximate insulation diameter: 46 mm
4 - Core non-metallic extruded screen:
Extruded semiconducting compound strippable
5 - Metallic screen consisting of copper tape of 0.1 mm nominal thickness laid with overlap
6 - Sheath:
PVC type ST2 according to IEC 60502 of 2.7 mm nominal thickness with anti-rodent and anti-termite additive.
Sheath colour: Black

Y..: 1590A/2014 Research & Development Department


T.M.K.: 565/2014 Issued by: D. Chatzipetros, I. Markopoulou
Date Revision: 17/04/2015 1 Reviewed by: K. Tastavridis
Client Destination country: ICME-ROMANIA Approved by: G. Georgallis

Page 1 of 2
Notes:
Minimum bending radius during laying: 1060 mm
Minimum bending radius adjacent to joints or terminations: 800 mm
Insulation resistance at 20oC: 660 M.km
Maximum DC resistance of conductor at 20oC (according to IEC 60228): 0.0469 /km
Maximum short-circuit withstand capability of the conductor (90oC-250oC, adiabatic method): 59.5 kA/1 s.
Maximum short circuit withstand capability of the metallic sheath (80oC-200oC, non adiabatic method): 0.8 kA/1sec
Capacitance (calculated): 0.347 F/km
Inductance (calculated regarding trefoil touching formation): 0.306 mH/km
Inductance (calculated regarding flat formation with a clearance of one cable diameter): 0.491 mH/km
Current carrying capacity directly buried - trefoil touching formation: 609 A
Current carrying capacity directly buried - flat formation with a clearance of one cable diameter: 662 A
Installation conditions:
- Ground temperature: 20oC
- Ground thermal resistivity: 1.5 K.m/W
- Depth of laying: 0.8 m
- Metallic sheaths in trefoil formation are bonded at both ends.
- Metallic sheaths in flat formation are single point bonded.
- Conductor temperature: 90oC
Current carrying capacity in air - trefoil touching formation: 824 A
Current carrying capacity in air - flat formation with a clearance of one cable diameter: 948 A
Installation conditions:
- Air temperature: 40oC
- Conductor temperature: 90oC
- Distance from a vertical wall 0.5xcable diameter
- Metallic sheaths in trefoil formation are bonded at both ends.
- Metallic sheaths in flat formation are single point bonded.
- Shaded cables.
Routine voltage test: 63 kV/5 min (according to IEC 60502-2, par. 16.4)
Positive/Negative/Zero sequence - trefoil touching formation
- Positive and Negative sequence Resistance R @ 90oC: 0.063 /km
- Positive and Negative sequence Reactance X @ 90oC: 0.096 /km
- Positive and Negative sequence Susceptance B: 109.0 S/km (capacitive)
- Zero sequence Resistance R @ 20oC: 5.529 /km
- Zero sequence Reactance X @ 20oC: 0.046 /km
- Zero sequence Susceptance B: 109.0 S/km (capacitive)
Positive/Negative/Zero sequence - flat formation with a clearance of one cable diameter
- Positive and Negative sequence Resistance R @ 90oC: 0.065 /km
- Positive and Negative sequence Reactance X @ 90oC: 0.154 /km
- Positive and Negative sequence Susceptance B: 109.0 S/km (capacitive)
- Zero sequence Resistance R @ 20oC: 5.529 /km
- Zero sequence Reactance X @ 20oC: 0.046 /km
- Zero sequence Susceptance B: 109.0 S/km (capacitive)

Positive/Negative sequence calculations assume solid point bonding (sheath currents present).
Zero sequence calculations assume all return in the sheath only.

Y..: 1590A/2014 Research & Development Department


T.M.K.: 565/2014 Issued by: D. Chatzipetros, I. Markopoulou
Date Revision: 17/04/2015 1 Reviewed by: K. Tastavridis
Client Destination country: ICME-ROMANIA Approved by: G. Georgallis

Page 2 of 2