Professional Documents
Culture Documents
ISOFAST
IN WARRANTY
TECHNICAL HELPLINE
01773 828100
ISOFAST F 28 E - ISOFAST F 35 E
Note!
The boiler serial number is marked on the label attached to the inside of the drop down door. Refer to the
'Introduction' section page 3 for a description of the basic functions of the boiler. The 'Users' section
describes how to safely operate the boiler.
SERVICING SECTION
COMMISSIONING
Gas safety (Installation and use) Regulations Overheating safety
In your interests and that of gas safety, it is the law In the event of a problem, the overheating safety
that ALL gas appliances are installed and serviced devices cause safety shutdown of the boiler. If this
by a competent person in accordance with the happens, call your Installation/Servicing company.
above regulations.
Boiler controls
Gas leak or fault The control panel, located at the lower front of the
If a gas leak or fault exists or is suspected, turn the boiler casing, see diagram 1, allows the boiler to
boiler off and consult the local gas supply com- be started, shut down, controlled and monitored
pany or your installation/service company. during use.
8 7 6 5 4 3 2 1
O I
1 - On/Off button
2 - Summer/Winter mode selector 3
2 1 24 23
22
4
20 19 18 17
0
4 - Hot water set point display 1
9
16
10
15
14 13 12 11
5 - Graphic display
1.5 bar
mode
Diagram 1
1
2 1 24 23
3
22
4
21
8 7 6 5
20
0
19 18 1
1
7
16
10
15
14 13 12 11
1.5 bar
mode
Hab 264
To stop the boiler : Press button (1)
The flamelorsque
Apparat symbolleappears
brleur The actual temperature
Temprature actuelle Illuminates
Apparat when
lorsque le
when
est enthe boiler is running
fonctionnement of thele
dans heating system
circuit chauffage the boiler
brleur lights
fonctionne
Press + orsur
Appuyer - to
+ adjust theajuster
ou - pour maximum temperature
la temprature Press + orsur
Appuyer - to+ adjust the ajuster
ou - pour maximum temperature
la temprature
of the hot de
maximale water (38
l'eau C to 60sanitaire
chaude C) (38C 60C) of the heating
maximale (38Cdu
souhaite 87C) chauffage
to circuit
Visual indication
Visualisation de laof set temperature
temprature demande Visual indication
Visualisation de laof set temperature
temprature demande
50 60C
mode mode
C
Hab 261
To obtain domestic hot water, open a hot water tap. Hot water always has priority over central heating.
Upper position
Heating On/Off as set by the
tappets.
Middle position
Heating Off continuously
Reg 050
Diagram 2 Diagram 3
DRAINING
Protection against freezing Draining and filling
If the boiler is to be out of use for any long periods Caution: The boiler is installed as part of a sealed
during severe weather conditions, it is recom- system which must only be drained and filled by a
mended that the whole system, including the boiler, competent person.
be drained to avoid the risk of freezing. Heating safety valve
If in doubt, consult your servicing company. CAUTION: A heating safety valve with a discharge
pipe is fitted to this boiler.
The ISOFAST has a built in frost protection device The valve MUST NOT BE TOUCHED except by a com-
that protects the boiler from freezing. If the boiler is petent person. If the valve discharges at any time,
to be left and there is a risk of frost, ensure that the switch the boiler off and isolate it from the electri-
gas and electrical supplies are left connected. The cal supply. Contact your installation/service com-
frost protection device will light the boiler when the pany.
temperature of the boiler water falls below 6C.
When the temperature reaches 16C, the boiler Pressure relief valve
stops. CAUTION: A domestic hot water pressure relief
Note: This device works irrespective of any room valve, with a discharge pipe is fitted to this boiler.
thermostat setting and will protect the complete The valve MUST NOT BE TOUCHED except by a com-
heating system. petent person. If the valve discharges at any time,
switch the boiler off and isolate it from the electri-
cal supply. Contact your installation/service com-
pany.
SERVICING/MAINTENANCE
To ensure the continued efficient and safe opera- Cleaning
tion of the boiler, it is recommended that it is The boiler casing can be cleaned with a damp
checked and serviced at regular intervals. cloth followed by a dry cloth to polish.
Do not use abrasive or solvent cleaners.
The frequency of servicing will depend upon the
installation conditions and usage but, in general, Boiler casing
once a year should be enough. CAUTION. Do not remove or adjust the casing in
any way, as incorrect fitting may result in faulty
operation. If in doubt, consult your installation/serv-
ice company.
ISOFAST F 28 E
ISOFAST F 35 E
ISOFAST F 28 E
ISOFAST F 35 E
Heating Hot water
Heating output ajustable from ... (kW) 10,4 11,7 Hot water output
to ... (kW) 27,6 34,6 automatically variable from ... (kW) 10,4 11,7
from ... (BTU/H) 35,485 39,920 to ... (kW) 27,6 34,6
to ... (BTU/H) 94,170 118,053 from ... (BTU/H) 35,485 39,920
Efficiency (%) 82 83 to ... (BTU/H) 94,170 118,053
Maximum heating temperature (C) 87 87 Maximum hot water temperature (C) 60 60
Expansion vessel effective capacity (l) 7 12 Specific flow rate (for 30C temp rise)
Expansion vessel charge pressure (bar) 0,5 0,5 (l/min.) 13,2 16,5
Maximum system capacity at 75C (l) 160 275 Threshold flow rate (l/min.) 1 1
Safety valve, Nominal water flow rate (l/min.) 11,3 16,5
maximum service pressure (bar) 3 3 Maximum supply pressure (bar) 8 8
Products outlet diameter (mm) 60 60 Minimum operating pressure (bar) 0,7 0,7
Fresh air inlet diameter (mm) 100 100
Pump 28 kW Pump 35 kW
60 80
Available pressure (kPa) between
50 1 70
2
3
60
40 1
4 2
50 4 3
5 5
30 40
30
20
20
Pom 010 a
Pom 058
10
10
0 0
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
Flow rate through heating system (I/h) Flow rate through heating system (I/h)
(10 kPa = 1 m WG) (10 kPa = 1 m WG)
1 Bypass fully shut 2 Open 1/4 turn 3 Open 1/2 turn 4 Open 1 turn 5 Open 2 turns
234
65
Weight: 51,2 kg
890
X = 470 (Isofast F 28 E)
552 (Isofast F 35 E)
X
7422
0
38
Diagram 5
BOILER SCHEMATIC
1 - Domestic thermistor
2 - Three way valve
3 - Gas valve
4 - Gas valve ignition module
5 - Heating element 12
6 - Micro accumulation vessel
7 - Burner 11
8 - Ignition electrode
9 - Combustion chamber 23
10 - Micro accumulation vessel thermistor
21 9
11 - Main heat exchanger
12 - Air pressure switch
22 8
13 - Heating safety valve (3 bar)
14 - Electronic control (PCB)
20 7
15 - Domestic water flow sensor
16 - Bypass 19
17 - Domestic heat exchanger
18 - Pump 18
19 - Expansion vessel
20 - Heating thermistor 17 4
21 - Overheat safety thermostat
22 - Flame sense electrode 16 3
23 - Fan
24 - Domestic safety valve 15 2
25 - Loss of water sensor
14 1
A - Heating return
B - Cold water inlet 25 24
C - Heating flow
D - Domestic hot water outlet 13
E - Gas
A B C D F
Shy 120
Diagram 6
u
A B G C r D F
v m t q
Pla 213
Diagram 7
Diagram 8
Ins 050b
using suitable screws.
Check that the hanging bracket is level. Diagram 9
For horizontal flue system, mark the position for
the flue hole as follows: nal. There must NEVER be a downward incline to-
wards the boiler.
Flue to rear of boiler
Mark correct position of hole from template. Terminal position
The minimum acceptable spacings from the ter-
Flue to side of boiler minal to obstructions and ventilation openings are
Mark the horizontal centre line for the hole on the shown in diagram 10.
rear wall. Extend the horizontal centre line to the The boiler must be installed so that the terminal is
side wall and mark the vertical centre line of flue exposed to the external air.
hole as shown in diagram 9. Should any doubt exist as to the permissible posi-
tion of the terminal, contact the Saunier Duval
Cutting the flue hole Technical Helpline 01773 828400.
Making allowance for the slope of the flue, cut
hole in external wall, preferably using a core drill. Terminal guard
For installations with internal and external access If a terminal guard is required, a suitable guard can
use a 10 5 mm diameter core drill. be obtained from your supplier, Saunier Duval part
For installations with internal access only use a 125 number 85373.
mm diameter core drill.
Cupboard or compartment ventilation
Important The boiler can be fitted in a cupboard or compart-
When cutting the flue hole and when extending ment without the need for permanent ventilation.
the flue centre line to a side wall, remember that
the flue system must have a fall of about 35 mm
per metre of flue DOWNWARD towards the termi-
Diagram 10
1 0
FLUE INSTALLATION
Top outlet flue - kit 85090
The boiler is only suitable for top outlet flue con- L2 L2
nection. L1 L1
Hab 210/30a
X X
When the dimension X measured on site is greater
than that given in table 2, a flue extension kit will Diagram 11
be required, refer to table 3 for details.
Diagram 12
Outer pipe
Extended flue
The horizontal flue is extended by using one or more
of the 1000 mm extension pipes, Saunier Duval part
Cutting length
number 85091. These are connected together by
push fit type joints, clamps and seals.
12. Cut both the inner and outer pipes to the di-
Cutting length
mensions given in table 4
1 1
B
Installation of flue assembly
Fit rubber sealing collar (A), see diagram 13, into
groove at the outer end of pipe (B).
Fit outer pipe (B) into wall with groove to the out-
D F
side.
Pull pipe inwards to bring rubber sealing collar
hard up against external wall, see diagram 14. E
Fit internal plastic flange (C) onto outer pipe. Push A C G H
Pho 088
along the pipe until engaged against internal wall.
From inside, insert inner pipe (D) into outer pipe. Diagram 13 I
Fit both O rings (E) into the flue elbow (F), one
at the inlet, one at the outlet. By necessity, they
are a loose fit, apply a small amount of silicone
grease to each O ring when fitting.
Slacken the two screws and fit the clamp and
seal (G) onto the elbow.
Take hold of the inner flue and push gently onto
the elbow outlet taking care not to tear the O
Pho 087
ring.
Important: If the flue has been cut, ensure that there
Diagram 14
are no burrs that could damage the O ring.
Push the elbow clamp and seal over the outer Remove the backing from the self adhesive gas-
flue. ket (H) and carefully fit gasket to base of flue el-
For flue systems less than 1,5 m long, leave the bow.
restrictor (a) fitted in the fan outlet, see diagram Fit elbow onto boiler and secure with the four
15. screws (I).
Gasket
a
Hab 249a
Diagram 15
1 2
Ins 060
ance with these instructions. Any fault arising from
incorrect wiring cannot be put right under the terms Diagram 16
of the Saunier Duval guarantee.
External controls
The ISOFAST boiler is designed to operate at maxi-
mum efficiency at all times, but will be most effi- Leave link in place for no external controls.
cient and economical when connected to a room
thermostat.
A suitable room thermostat is available as an ac-
Sch 171
Diagram 17 E
Without room
Do not use thermostat
Sch 172
E E
1 3
Gas installation
It is recommended that any air is purged from the
supply at the gas inlet test point on the gas valve,
see diagram 18.
Reg 018
Filling the system
The warning light will illuminate The display will indicate 0 bar pressure in the system
O I
3
2 1 24 23 1
22
4
21
8 7 6 5
20 19 18 17
0
1
9
16
10
15
14 13 12 11
0.0 bar
mode
Hab 265
3
Undo cap
on auto-
matic air
vent on
top of
q
Pla 213
v m
pump and
leave un-
done.
Open the boiler isolating valves (v and q), the slot of the screw
2 corresponds to flow direction.
Fully open valve m by unscrewing anti-clockwise. Reg 008
Open the tap (t) on the filling device and fill the system until the pressure indicated on the display
4 is between 1 and 2 bar. The pressure must be between 1 and 2 bar
1.5 bar
mod
t
Hab 265
Pla 213
1 4
Reg 008
Ins 061
Ins 062
Make sure the display indicates a system pressure of between 1 and 2 bar. Re-fill system as
8 necessary.
O I
2 1 24 23
3
22
4
21
8 7 6 5
20 19 18 17
0
1
9
16
10
15
14 13 12 11
1.5 bar
mode
Hab 265
1 5
1
2 1 24 23
3
22
4
21
8 7 6 5
20
0
19 18 1
1
7
16
10
15
14 13 12 11
1.5 bar
mode
Hab 264
To stop the boiler : Press button (1)
Press + orsur
Appuyer - to+ adjust the ajuster
ou - pour maximum temperature
la temprature
of the heating
maximale (38C du
souhaite to 87 C) chauffage
circuit
Visual indication
Visualisation de laof set temperature
temprature demande
60C
mode
Hab 261
1 6
Reg 051/UK
to the 'Servicing Instructions' for further details.
The heating output, in kW, is shown on the left hand 5s
side of the display, see diagram 21.
Remove the blanking plug from the front of the Diagram 20
control panel to gain access to the heating ad-
justing screw. Setting the heating output
Adjust the heating output by turning the screw
clockwise to increase, anti-clockwise to decrease.
Refit blanking plug.
Note: Adjustment of the heating output does not
affect the domestic hot water output. Adjustment screw
Reg 052
16 54,590 26 88,710
18 61,420 28 95,540 Diagram 21
kW Btu/hr
30 102,360
32 109,180
34 116,000
35 119,420
Reg 053
The maximum heating temperature can be preset
SAFETY DEVICES
The ISOFAST incorporates a visual display that indi- Should the boiler fail to operate during Commis-
cates fault conditions, should they occur. sioning, the most likely fault is that the gas supply
In the event of a fault, the diplay will indicate, by to the boiler has not been turned on or purged suf-
means of pictograms and/or letters and numbers, ficiently or that there is no pressure in the heating
exactly in which area the fault lies. system. These are indicated as follows :
1 7
1 8
Minimum setting
Remove one electrical connector from the
modulating gas valve coil, see diagram 23.
Connect a suitable pressure gauge.
Turn the OFF/Summer/Winter switch to the Sum-
mer position.
Turn the domestic hot water temperature adjuster
to maximum setting.
Remove the protective cover from the gas valve
adjuster.
Turn nut A, see diagram 23:
CLOCKWISE: To increase the pressure.
ANTICLOCKWISE: To decrease the pressure.
Maximum setting
Reconnect the electrical connector removed
Reg 020
from the modulating gas valve coil.
Remove the protective cover from the gas valve Diagram 23
adjuster.
Turn nut B, see diagram 23:
CLOCKWISE: To increase the pressure.
ANTICLOCKWISE: To decrease the pressure.
After adjustment, refit the cover to the gas valve
adjuster. a
Bypass
The ISOFAST has a built-in bypass. This must be ad-
justed according to the requirements of the system,
refer to the flow rate pressure curve (diagram 4).
The boiler is supplied with the built-in bypass open
a half a turn. It is adjusted by turning the bypass
screw (a), see diagram 24. Turn the screw clock-
wise to close the bypass.When using thermostatic
radiator valves (TRVs) on all of the radiators, it is
essential that a separate, adjustable bypass of 15
mm minimum diameter is fitted between the flow
Reg 054
and return of the heating circuit, see diagram 8.
Any bypass must be fitted before system controls. Diagram 24
1 9
Car 025
Lift cover up and off boiler.
Diagram 1
Front control panel
Lift control panel up and lower forwards to gain
access to lower part of boiler.
Side panels
Unscrew and remove the four screws securing
lower grille onto boiler. Unhook grille from rear of
boiler and remove.
Remove three screws from front of each side panel.
Unclip the toggle clips securing top of each panel.
Lift each panel up and then forward to remove.
Ech 041
Combustion chamber cover
Unclip two toggle clips and unscrew two screws Diagram 2
securing combustion chamber cover to combus-
tion chamber, see diagram 2. Heat exchanger
Remove combustion chamber cover from boiler. Disconnect power supply leads and earth lead
Undo, but do not remove, two burner support screws from fan.
at rear of burner chamber. Unscrew and remove, two fan retaining screws
at front edge of fan mounting plate.
Burner Remove fan with mounting plate attached by
Undo main gas supply nut from burner. pulling forwards out of boiler.
Pull off the ignition and flame sense leads from the Remove air pressure switch sensing tube from
gas valve remove burner from boiler by lifting up and sensing probe on flue hood.
pulling forwards from keyhole slots. Unscrew and remove screws securing flue hood
Note: The washer between main burner and main to rear panel.
burner gas supply must be kept for use on Withdraw flue hood from boiler.
reassembly. Examine heat exchanger for any blockages or
Remove ignition and flame sense electrodes from build up of deposits.
burner. Clean heat exchanger with soft brush or vacuum
Unscrew and remove injector bar retaining cleaner. Do not use any tool likely to damage
screws and separate injector bar from burner. painted finish of heat exchanger.
Examine and clean injectors as necessary.
Note: DO NOT use a wire or sharp instrument on Reassembly of parts removed for servicing
the holes. All parts are replaced in reverse order to removal.
Clean burner by washing in soapy water. Dry thor-
oughly before re-fitting.
2 0
u
A B G C r D F
Pla 213
v m t q
Diagram 3
REPLACEMENT OF PARTS
For replacement of the following components it will Note: These valves are closed when slots are at right
be necessary to remove boiler casing panels as de- angles to direction of flow.
scribed in Routine Cleaning and Inspection. Drain boiler by opening drain valves (r) and (u),
see diagram 3.
WARNING: Before commencing the replacement
of any component, isolate appliance from electri- Note: It is not necessary to drain down entire heat-
cal supply and turn off gas at service cock. ing system to carry out this work.
Close isolating valve/throttle (m) on cold water
To replace domestic hot water thermistor isolating cock, see diagram 3.
Locate domestic hot water thermistor on hot wa- Note: This valve is closed when screwed fully clock-
ter flow pipe on right hand side of boiler adjacent wise.
to gas valve. Open one or more hot water taps to drain boiler
Unclip thermistor from pipe. circuit.
Disconnect leads from thermistor. Disconnect flue system.
Fit replacement thermistor. Disconnect boiler pipes onto fixing jig.
Fit leads to replacement thermistor, the polarity Disconnect mains cable and any external con-
is not important. trols cables.
Remove boiler from wall.
To replace central heating thermistor From rear of boiler, disconnect domestic pipes
Locate central heating thermistor on heating flow from storage vessel.
pipe on centre of boiler. Disconnect electrical connections from vessel.
Unclip thermistor from pipe. Unclip vessel from boiler frame and remove from
Disconnect leads from thermistor. boiler.
Fit replacement thermistor. Slide off plastic strap and separate two halves of
Fit leads to replacement thermistor, the polarity vessel insulation.
is not important. Locate thermistor at top of insulation.
Replace thermistor in same position as old ther-
To replace storage vessel thermistor mistor.
For this operation the boiler must be removed from Refit vessel in reverse order to removal.
the wall. Refit boiler onto fixing jig, tighten all connections
Drain down heating and hot water circuit of the ensuring that all sealing washers are fitted before
boiler only, as follows: tightening.
Close isolating valves (q) and (v) on central heat- Reconnect flue making sure that all joints are
ing isolating cocks (a) and (c), see diagram 3. properly connected.
2 1
Ins 064
sensor.
Pull out slotted metal clip securing cold water in- Diagram 4
Acc 010/Acc011
Diagram 5
2 2
mounting and 3-way valve/bypass housing.
Remove heat exchanger from boiler.
Fit replacement heat exchanger in reverse order
to removal using new seals, supplied.
Pho 375
Note: Heat exchanger mounting screws are offset
to ensure correct fitting of replacement. Diagram 6
work.
Diagram 7
To replace 3-way valve/bypass housing
Drain down heating and hot water circuit of boiler
only as described previously.
Note: It is not necessary to drain down entire heat-
ing system to carry out this work.
Remove 3-way valve head as described previ-
ously.
Remove domestic hot water heat exchanger as
described previously.
Undo pipe connection from 3-way valve/bypass
housing to primary heat exchanger, see diagram 7.
Pull out slotted metal clips and remove bypass
pipe.
Ins 063
2 3
To replace central heating safety valve
If safety valve seating is damaged, it will be neces-
sary to replace safety valve as a complete unit,
repair is not possible.
Drain down heating circuit of boiler only as de-
scribed previously.
Disconnect safety valve discharge pipe from
safety valve.
Mec 111
Remove wire clip securing safety valve to fixing
jig and remove safety valve, see diagram 10.
Diagram 9 Fit replacement safety valve in reverse order to
removal.
Remove screw securing cover onto gas valve
module, see diagram 9. Note: Apply a small quantity of silicon grease to
Remove cover and disconnect multi-plug from the safety valve 'O' ring prior to fitting.
module. Open isolating valves on flow and return connec-
Disconnect ignition and flame sense leads from tions, refill, vent and pressurise boiler.
module. Check for leaks.
Withdraw module from gas valve.
Fit replacement module, ensuring it is of the cor- To replace storage vessel safety valve
rect type for the boiler, in reverse order to removal. If safety valve seating is damaged, it will be neces-
Reconnect ignition and flame sense leads, the sary to replace safety valve as a complete unit,
connections are uniquely sized to ensure correct repair is not possible.
replacement. Drain down hot water circuit of boiler only as de-
Reconnect multi-plug onto replacement module. scribed previously.
Refit cover ensuring all sealing grommets are cor- Disconnect safety valve discharge pipe from
rectly located in module body. safety valve.
Remove wire clip securing safety valve to fixing
To replace gas valve jig and remove safety valve, see diagram 10.
Ensure that gas supply to boiler is turned off at Fit replacement safety valve in reverse order to
gas cock. removal.
Remove gas valve module as described previ- Note: Apply a small quantity of silicon grease to
ously. the safety valve 'O' ring prior to fitting.
Disconnect electrical connections to gas valve
modulating coil, see diagram 9.
Undo main gas supply nut from main burner.
Note: The washer must be kept for use on
reassembly.
Undo main gas union nut between gas valve sup-
ply pipe and gas inlet valve.
Note: The washer must be kept for use on
reassembly.
Disconnect plastic sensing pipe from gas valve
to base of sealed chamber.
Unscrew and remove screws securing gas valve
2 4
Side panels:
Pull out side panels.
To replace burner
Remove burner as described in 'Routine Clean-
ing and Inspection'.
Assemble replacement burner, supplied in parts, as
follows:
Ech 040
2 5
12
11
23
21 9
22 8
20 7
19
18
17 4
16 3
15 2
14 1
25 24
13
A B C D F
Shy 120
Diagram 12
2 6
ISOFAST F 28 E
ISOFAST F 35 E
ISOFAST F 28 E
ISOFAST F 35 E
Heating Hot water
Heating output ajustable from ... (kW) 10,4 11,7 Hot water output
to ... (kW) 27,6 34,6 automatically variable from ... (kW) 10,4 11,7
from ... (BTU/H) 35,485 39,920 to ... (kW) 27,6 34,6
to ... (BTU/H) 94,170 118,053 from ... (BTU/H) 35,485 39,920
Efficiency (%) 82 83 to ... (BTU/H) 94,170 118,053
Maximum heating temperature (C) 87 87 Maximum hot water temperature (C) 60 60
Expansion vessel effective capacity (l) 7 12 Specific flow rate (for 30C temp rise)
Expansion vessel charge pressure (bar) 0,5 0,5 (l/min.) 13,2 16,5
Maximum system capacity at 75C (l) 160 275 Threshold flow rate (l/min.) 1 1
Safety valve, Nominal water flow rate (l/min.) 11,3 16,5
maximum service pressure (bar) 3 3 Maximum supply pressure (bar) 8 8
Products outlet diameter (mm) 60 60 Minimum operating pressure (bar) 0,7 0,7
Fresh air inlet diameter (mm) 100 100
Pump 28 kW Pump 35 kW
60 80
Available pressure (kPa) between
50 1 70
2
3
60
40 1
4 2
50 4 3
5 5
30 40
30
20
20
Pom 010 a
Pom 058
10
10
0 0
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
Flow rate through heating system (I/h) Flow rate through heating system (I/h)
(10 kPa = 1 m WG) (10 kPa = 1 m WG)
1 Bypass fully shut 2 Open 1/4 turn 3 Open 1/2 turn 4 Open 1 turn 5 Open 2 turns
2 7
Ramoneur
B61 B81
Pr
B63 B82 P
B64 B33
B62 B12
B29
Opt. H61
B210 Db
H6.2
B211
B24 B113
L L1
M/A B114
Cp
N h8.1 B115
h8.2 B17
h4.1 B18
R V1
B110 J1
h4.3
h3.1 B31 1
TA
B32 2
Ex h3.3
B33 3
Ra
h1.1 B34 4
B26 5
P
h1.2 B25
K4 CTN 3
h2.4 B15
h2.2
h2.3 B16
CTN 2
h2.5 B14
h2.1
B13
V CH h5.2
CTN 1
10 11 9 8 3 COM h5.3
DA N Ph V b51
SAN h5.1
ACF b52
1 B28
b54
B27 HL
Sch 185a
Flam 2
b55
B35
B73
B36
B72
B71
B41
B42
B43
B44
B24
B21
B22
GND
Vitesse
S
Extracteur
FA FL Ve (option)
INTERFACE CD SE
Diagram 14
2 8
Table 1
The ISOFAST has an on-board fault diagnostic system. Should a fault occur on the boiler, the warning LED at
the top of the user display will illuminate and the LCD display will indicate the precise area where the
fault has occured.
09 FF Sec 052
A fault code is displayed on the left hand side of the LCD display, whilst at the same time, the letters FF
appear with a telephone symbol.
2 9
00 No fault
05 Overheating
10 Fan fault
11 Pump blockage
20 Communication fault
3 0
SPARE PARTS
When ordering spare parts, quote the part number and description, stating the appliance model number
and serial number from the data badge.
3 1