CALCULATION SHEET
a Checked By
Project METHER AiGuorons Calepetons | Theory | Amat] DH | Sheet
2DwIe seHeor. oF
Element Sheets
Aes using e. 6uic FES 2a]
CAL PAR + RoAD To Be Pokeus 4sPHAc.
ZRALDWIGE LOTH COMBED ROOF ARCH = SO8D wt
ALLOL? PESTACTED DISCHARGE THROUGH SOuw
DAMETER PIPE.
FeowA ATACHED CALCULATION, UMAX eUTFLOK) = 454 P/cec,
eveation Who ovtriowls) si b>,
Swaars, Ae 1G BAS
10 Sve 2712 Stok
Ss B35 40% 6017
30 4174 or 3457
LHe S214 bth ML
2. hae yr?
4 2b eS1 GSI a max .
6 240% ob 6-01
le 2% oO Wb-4d- ase
ar Bre 892-56 - Ib
AOR WARLEA LWwATERIOC Vol FORWLUG
Ces (240 Liles, slevee) <)> 610 ceun
Acsowe 2 BegP => $05 oe Avex,
2D 1OxB ceus
PEQORED .
= 12wrx 2hcbur x OSA wr OgEP Thue,
WTAL RADU CAR PAARL Ui
fxd Reswicroe AT oer TO 454 lihe)sd
t
GRAEME CRAIG CONSULTING ENGINEERS LTO.To calculate discharge rate from orifice of known size
Qa = Gy x A ye x os x A
055
0.001963
eat
0.90
Quy = 0550 x
= 0.004537
= 454 Us
Discharge rate in m/s
Coefficient: 0.55 for pipe or 0.58 for orifice
‘Area of Orifice in m? A= (3.14x42)/4, s0ford= 50 mm,A
CONSTANT (Gravity) k
Head of water in m
0.001963, x 981 x 090
mis
0.001963
mn?Projet 0b
Tedde Anguston Riding School
Graeme Craig Consulting | 62!=for Sian page roRevson
Engineers Lid Rainfall Run Off 1
14 Bn Accord Crescent Cas by ics cae ‘Checkedy [Chenkedasle | Appioweaby | Approved dato
‘Aberseen ckic | 191022015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Todds clean version 20.00
Location of catchment area Aberdeen
‘Storm duration D=5:min
Return period Period = 30 yr
Ratio 60 min to 2 day rainfall of 5 yr return period = 0.250
6-year return period rainfall of 60 minutes duration MS_6Omin = 14.8 mm
Increase of rainfall intensity due to global warming pans = 20 %
Factor Z1 (Wallingford procedure) Z1= 032
Rainfall for Smin storm with § year return period MS_Sminy = 1 x M5_60min x (1 + psn) = 5.5 mm
Factor Z2 (Wallingford procedure) 2221.45
Rainfall for Smin storm with 30 year retum period M30_Smin = Z2 x MS_Smin= 8.0 mm
Design rainfall intensity Inge = M3O_Smin / D = 96.6 mmr
Maximum surface water runoff
Catchment area ‘esos = 5000 m=
Percentage of area that is impermeable p= 100%
Maximum surface water runoff
nay = Acar x Px Ina = 132.7 UsProjoet rib
Teds ‘Anguston Riding Schoo!
Graeme Craig Consulting [eles or Sta page no Revision
Engineers Lid Rainfall Run Off 4
14 Bon Accor Crescent ‘cacty [eas ate Checked by [Ohenkea date | Approvedloy | Anproved date
verdeen cKic | 19/02/2015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Todd cleo vrsion 2000
Design rainfall intensity
Location of catchment area ‘Aberdeen,
‘Storm duration
Retu period
Ratio 60 min to 2 day rainfall of § yr return period
‘year return period rainfall of €0 minutes duration MS_60min
Increase of rainfall intensity due to global warming pine = 20 %
Factor 21 (Wallingford procedure) 0.47
Rainfall for 10min storm with § year retun period
Factor 22 (Wallingford procedure)
Rainfall for 10min storm with 30 year return period
Design rainfall intensity
‘Maximum surface water runoff
Catchment area Acar = 5000 mi?
Percentage of area that is impermeable p= 100%
Maximum surface water runoff rar = Acatn x BX Irae = 99.6 IsGraeme Craig Consulting | Cacso Stan page no Reason
Engineers Lid Rainfall Run Off 1
14 B0n Accord Cretcant cacsty (Gacedaia | Chackeaby [Crenked aslo | Appovediby | Approved asta
‘Aberdeen oxic | 1910272016
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Teds calodationverion 20.00,
Design rainfall intensity
Location of catchment area ‘Aberdeen,
‘Storm duration D=45 min
Return period Period = 30 yr
Ratio 60 min to 2 day rainfall of § yr return period r= 0.250
5-year relum period rainfall of €0 minutes duration M5_6Omin
Increase of rainfall intensity due to global warming pains = 20%
Factor Z1 (Wallingford procedure)
Rainfall for 15min storm with 5 year return period
Factor Z2 (Wallingford procedure)
14.5 mm
1x M5_6Omin x (1 + Pana) = 9.9 mm
Rainfall for 15min storm with 30 year return period M30_15min = 22 x M5_16min.= 14.7 mm
Design rainfall intensity Inox = M30_1Smin / D = 58.7 mm/h
Maximum surface water runoff
Catchment area ‘Aeon = 5000 m=
Percentage of area that is impermeable p= 100%
Maximum surface water runotf Qos = Ach P x Ines = 81.5 USPropet ebro
ret hangin og Seon
Graeme Craig Consulting [aes Stet page no Reason
Engineers Lid Rainfall Run Off 1
14 Bon Acco Crescent aie by Cates date [Ohecredby | Oheckeddaio | Anprovedty | Approved one
Aoerdeen cxic | 19022018
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Design rainfall intensity
Location of catchment area
‘Storm duration
Return period
Ratio 60 min to 2 day rainfall of § yr return period
‘5-year return period rainfall of 60 minutes duration
Increase of rainfall intensity due to global warming
Factor 21 (Wallingford procedure)
Rainfall for 30min storm with 5 year return period
Factor 22 (Wallingford procedure)
Rainfall fr 30min storm with 30 year return period
Design rainfall intensity
Maximum surface water runoff
Catchment area
Percentage of area that is impermeable
Maximum surface water runoff
“Ted caletaon version 20.09
3.4 mm
(M30_S0min = 22 x MS_30min, = 19.6 mm
Irax= MB0_3Omin/D = 39.4 mm/he
Assn = 5000 mn?
p= 100 %
Grae = Aesin x P x In
54.3 Usrele semua ir
Graeme Craig Consulting [oar Sta page na Revi
Engineers Lid Rainfall Run Off 1
14 Bon Accord Crescent feacs ty (Gace date[Creakadby | Cresred dale |Approvedlby | Approved dala
‘Aberdeen ckic | 1910272015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
“Teas eatin version 2000
Design rainfall intensity
Location of caichment area Aberdeen
‘Storm duration D=4he
Return period Period = 30 yr
Ratio 60 min to 2 day rainfall of 5 yr return period r= 0.250
‘5-year return period rainfall of €0 minutes duration M5_60min
Increase of rainfall intensity due to global warming pains = 20 %
Factor 21 (Wallingford procedure) 1.00
Rainfall for 1hr storm with 5 year return period
Factor Z2 (Wallingford procedure)
Rainfall for thr storm with 30 year return period
Design rainfall intensity
Maximum surface water runoff
Catchment area Aates = 5000 rm?
Percentage of area that is impermeable p= 100%
Maximum surface water runoff ‘Qn = Aaa xp x Ines = 36.9 US
14.5 mmProject sob no.
Teds Anguston Riding Schoo! See
Graeme Craig Consulting [S28 or Stan page no Revision
Engineers Lid Rainfall Run Off 1
14 Ban coors Crescent cacety (Calcedate ‘| heskedby | hecked dato | Approvediby | Approved cate
oerdeen ekic | 1910272015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Tedds calouation version 20.00,
Design rainfall intensity
Location of catchment area ‘Aberdeen
Storm duration D=2hr
Retum period Period = 30 yr
Ratio 60 min to 2 day rainfall ofS yr retum period r= 0.250
S.year return period rainfall of 0 minutes duration MS_60min = 44.8 mm
Increase of rainfall intensity due to global warming pais = 20%
Factor Z1 (Wallingford procedure) Z1=1.29
Rainfall for 2hr storm with 5 year return period MS_2hn = Z1 x M5_GOmin x (1 + panse) = 22.4 mm
Factor 22 (Wallingford procedure) 7221.47
Rainfall for 2hr storm with 30 year return period M30_2hr = Z2 x MS_2hn = 32.9 mm
Design rainfall intensity
Maximum surface water runoff
Catchment area
Percentage of area that is impermeable
Maximum surface water runoff
lnax = M30_2hr /D = 18.5 mrvhr
Aca = 5000 m2
p= 100%
Qh: = Acai» PX Inae = 22.9 UsProject a
Tedds ‘Anguston Riding Schoo!
Graeme Craig Consulting [S586 Siar pane ve Reason
Engineers Lid Rainfall Run OFF 1
14 80n Accord Crescent feaes ty (Gakcsdaie | Checkedby | Chenked date | Approvedby | Approved date
Aberdeen ckic 19/02/2015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
“Tedd caleuiston vorsion 2.0.09,
Design rainfall intensity
Location of catchment area
‘Storm duration
Return period
Ratio 60 min to 2 day rainfall of § yr retum period
6-year return period rainfall of 60 minutes duration
Increase of rainfall intensity due to global warming
Factor Z1 (Wallingford procedure)
Rainfall for 4hr storm with 5 year return period
Factor 22 (Wallingford procedure)
Rainfall for 4hr storm with 30 year return period M90_4hr = 22 x M5_4hni= 42.4 mm
293mm
Design rainfall intensity Inox = M30_shr /D = 10.6 mrnvbr
Maximum surface water runoff
Catchment area ‘Acsun = 6000 m?
Percentage of area that is impermeable p= 100 %
Maximum surface water runoff ra = Aes x Px Imax = 14.7 UsProject ob
Teds ‘Anguston Riding Schoo! Ha
Graeme Craig Consulting [aes or Sian page no ewson
Engineers Lid Rainfall Run Off 1
14 Ban Acsord Crescent cacaty [eacs cao (Checked by hooked dato | Appowedley | Approved data
verdeen Gkic 19/02/2015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Tadd caleaton version 2.000
Location of catchment area ‘Aberdeen,
‘Stor duration D=6hr
Retuin period Period = 30 yr
Ratio 60 min to 2 day rainfall of 5 yr return period = 0.250
‘year return period rainfall of 60 minutes duration M5_6Omin = 14.5 mm
Increase of rainfall intensity due to global warming pane = 20 %
Factor Z1 (Wallingford procedure) Z1=1.98
Rainfall for 6hr storm with 5 year return period ——-MS_6hn = Z1 x M5_6Omin x (1 + pein) = 34.1 mm
Factor Z2 (Wallingford procedure) 2221.43
Rainfell for 6hr storm with 30 year return period M30_8hr = 22 x M5_Shri= 48.8 mm
Design rainfall intensity
Maximum surface water runoff
Catchment area
Percentage of area that is impermeable
Maximum surface water runoff
lax = M30_6hr / D = 8.4 meine
Astor = 5000 me
p= 100%
nar = Assen ® PX beac = 14.3 USProject 200
Teds ‘Anguston Riding School
Graeme Craig Consulting [Cae for Stan page no Revision
Engineers Lic Rainfall Run Off 1
14 Bon Accord Cresent cacsty (Gace dale [Chenxedby [Checked dala | Aproved by | Approved dato
Averdeen ckic | 191022015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
“Ted caleiton vessen 20.09,
Design rainfall intensity
Location of catchment area Aberdeen,
‘Storm duration
Retutn period
Ratio 60 min to 2 day rainfall ofS yrretum period
‘5-year return period rainfall of 60 minutes duration MS_6Omin
D=40 br
Period = 30 yr
0.280
14.5 mm
Increase of rainfall intensity due to global warming pans = 20 %
Factor Z1 (Wallingford procedure)
Rainfall for 10hr storm with 5 year return period
Factor Z2 (Wallingford procedure)
Rainfall for 10hr storm with 30 year return period
Design rainfall intensity
Maximum surface water runoff
Catchment area
Percentage of area that is impermeable
Maximum surface water runoff
21=2.35
MB_10hn = 21 x M5_6Omin x (1 + perras) = 40.8 mm
2224.44
M30_A0hr = 22 x M5_10hn = 87.6 mm
Inox = M30_10hr / D = 6.8 mrwfhe
‘Acson = 5000 mm?
p= 100%
(das = Acton * Pf =
Osrele
Graeme Craig Consulting
Engineers Lid
148m Accord Crescent
‘Aberin
Propet Tebra
Anguston Riding School
Cacao Stat page ao/Revien
Rainfall Run Off 1
caisty [Caics date [heady [Checked dala | Approvedby [Approved dale
xic 1102/2015
DESIGN RAINFALL
In accordance with the Wallingford Procedure
Design rainfall intensity
Location of catchment area
‘Storm duration
Return period
Ratio 60 min to 2 day rainfall of 5 yr return period
‘5-year return period rainfall of €0 minutes duration
Increase of rainfall intensity due to global warming
Factor 21 (Wallingford procedure)
Rainfall for 24hr storm with 6 year return period
Factor 22 (Wallingford procedure)
Rainfall for 24hr storm with 30 year return period
Design rainfall intensity
‘Maximum surface water runoff
Catchment area
Percentage of area thal is impermeable
Maximum surface water runoff
MS_2ahn, = Z1 « MB_6Omin x (1+ pnw)
22= 1.36
M30_24hr = 22 x MS_24hn'= 77.4 mm
Ira = MB0_24h¢
Acar = 5000 mn?
p= 100%
3.2. mmihr
Gra = Aesie x Px Inae = 4.5 Us
“Ted cleat vrsion 2.000CALCULATION SHEET
checked By
Project METER Arcoeten, | SALONS |e —patmetia | Date | Sheet
Ripurcr ecrjoou = te
Element ou
| beneadee aos Feb 2016
Bod LAK IO FOUL Tune STAR = 10 liltds )pench|cby -
Aucwd way 100 veriers/ DAN — = 20 libra pemobfeleny
TerAL = IOO+ 2600
= 2AED iibrifelen -
PoPoLATIONS SRUALEWUT Foe PowesTe- = 20D = 2O PE,
Isc
ApoPr BALMORAL WUDEocRAE HC 20.
FOOL LOMDIG FLAS TALE FOU Bemed
WATER PobucaTiatt "FLO AUP LOARE~
PERCOLATIONA TECTS PRovr> GRemiD
CMO TABUL FOR WALTDATIOA RRAUMGE
=> PARTIAL SoAvedy THeoust ReRreRATED
PIPE To WATERCOORSE
GRAEME CRAIG CONSULTING ENGINEERS LTO