Key Plan

A
BL
QI
Notes

TOP OF SLAB
THREADED ANCHOR BOLT THREADED ANCHOR BOLT
WITH EXPANSION SHIELD WITH EXPANSION SHIELD
TOP OF SLAB
SOFFIT SLAB G.I. THREADED ROD G.I. THREADED ROD

VARIES
SOFFIT OF SLAB
'VARIES

PIPE HANGER PIPE HANGER


RISER NIPPLE

PIPE PIPE

'150mm
BRANCH PIPE
RISER NIPPLE

CROSS MAIN PIPE SUPPORT


CROSS MAIN
DOUBLE ESCUTCHEON
FALSE CEILING PIPE SIZE (mm) 25 32 40 50 65 80 100 150
FALSE CEILING
DISTANCE (M) 3.50 3.50 3.50 4.50 4.50 4.50 4.50 4.50
SPRINKLER HEAD DOUBLE ESCUTCHEON
ROD SIZE (mm) 10 10 10 10 10 10 10 12.7
SPRINKLER HEAD

A ISSUED FOR TENDER ARN BM* AH* 08.03.15

No Revision
Job Project
Drawn Manager Director Date

Note: * indicates signatures on original issue of drawing or last revision of drawing


Conditions of Use. This document may only be used by GHD's client (and any other
person who GHD has agreed can use this document) for the purpose for which it was
prepared and must not be used by any other person or for any other purpose.

01 - ARRANGEMENT OF RECESSED PENDENT 02 - PENDENT & UPRIGHT SPRINKLER HEAD DETAIL 04 - PIPE HANGER FOR SPRINKLER & WET PIPES
SPRINKLER HEAD DETAIL (DOUBLE LEVEL) TYPICAL DETAIL Master Developper / Owner
SCALE NTS SCALE NTS SCALE NTS

Abu Dhabi Airports Company PJSC


Planning & Development
PO Box 94449, Abu Dhabi, U.A.E
T: +971 (0) 2 505 5000
F: +971 (0) 2 575 8300

Lead Consultant

ANCHOR BOLT
GHD GLOBAL PTY LTD
PLATE WASHER G.I. (TYP.) 3rd Floor, Guardian Tower, Danet Community
WALL PO Box 45921 Abu Dhabi United Arab Emirates
CHANNEL SUPPORT G.I T 971 2 6968700 F 971 2 4472915
E abumail@ghd.com W www.ghd.com

Specialist Consultant
PIPE

G.I. CHANNEL
THREADED PIPE SILICON FOAM
STANDARD "U" BOLT PENETRATION SEAL Fire Life Safety, Planning
PIPE SIZE ROD SIZE FIRE RATED PENETRATION
(mm) (mm) SEAL (TYPICAL)
and Regulatory Specialist
HEX/ NUTS G.I. (TYP.) ANCHOR EXPANSION PIPE SLEEVE
25 10
TOP VIEW SIDE VIEW
32 10
Specialist Consultant
40 10
SILICON FOAM
50 10 PENETRATION SEAL
VARIES
PIPE PASSING
FIRE PIPE FIRE RATED Third Party
PIPE

65 10 THROUGH R.C.
PENETRATION SEAL FLOOR SLAB PIPE
(TYPICAL) Operational Advisor
FIRE PIPE PASSING
'U' CLAMP (DIA. RELATED PIPE SIZE) 80 10

100 10
PIPE PASSING
THROUGH WALL
G.I. U-BOLT 150 12.7
Client
ADAC
ANGLE - 50mm
Project
MIDFIELD TERMINAL FIRE
50x50x5mm
M.S. ANGLE STATION
TOP VIEW SIDE VIEW Title FIRE PROTECTION SERVICES -
ANGLE - 50mm MISCELLANEOUS DETAILS
SHEET 1 OF 4
UNIFIX & BOLT 10mm
Scale As indicated DO NOT SCALE
Drawn A. NOCEJA Designer P. MOHD.
Drafting Design
Check Check
Approved
03 - PIPE SUPPORT ON WALL FOR SPRINKLER & WET 05 - PIPE RISER SUPPORT FOR SPRINKLER & WET 06 - PIPE SLEEVE DETAIL (Project Director)
Date
PIPES TYPICAL DETAIL RISER PIPES TYPICAL DETAIL
SCALE NTS
This Drawing must not be used for Construction unless signed as Approved
SCALE NTS SCALE NTS Original Size
Drawing No:
A1
DETAIL DESIGN 76-10526- F002 Rev: A