Key Plan

860

800 N
80mm FIRE FIGHTING RISER 360
500 250 FIRE EXTINGUISHERS
FIRE EXTINGUISHERS CABINET

A
BL
CABINET

QI
PIPE SUPPORT Notes

THREADED ANCHOR BOLT (G.I)

DOOR HANDLE

WALL
BRACKET
40mm FIRE HOSE

950

950
RACK 30M LENGTH
WALL
PRESSURE GAUGE
FIRE EXTINGUISHER
PRV
G.I. U-BOLT

VARIES
1500

1500
40mm LSV

65mm LANDING VALVE 1600


FIRE PIPE
BUILT IN PRV

PRESSURE ADJUSTMENT

ANGLE SUPPORT
HANDLE WALL
1150

FE-1 FE-2 SIDE VIEW FRONT VIEW


900

A ISSUED FOR TENDER ARN BM* AH* 08.03.15


FFL
No Revision
Job Project
Drawn Manager Director Date
FE-1 (WATER TYPE 9 LITERS)
FE-2 (CO2 TYPE 5 KGS.) FRONT VIEW SIDE VIEW
300

Note: * indicates signatures on original issue of drawing or last revision of drawing


Conditions of Use. This document may only be used by GHD's client (and any other
person who GHD has agreed can use this document) for the purpose for which it was
FFL prepared and must not be used by any other person or for any other purpose.

ELEVATION SIDE VIEW


Master Developper / Owner

RECESSED FIRE EXTINGUISHER CABINET (FE) 09 - FIXED SUPPORT ON CEILING FOR SPRINKLER &
07 - FIRE HOSE CABINET (FHC) SCALE NTS WET PIPES TYPICAL DETAIL Abu Dhabi Airports Company PJSC
SCALE NTS Planning & Development
SCALE NTS PO Box 94449, Abu Dhabi, U.A.E
T: +971 (0) 2 505 5000
F: +971 (0) 2 575 8300

Lead Consultant

TO FIRE ALARM SYSTEM


GHD GLOBAL PTY LTD
3rd Floor, Guardian Tower, Danet Community
PO Box 45921 Abu Dhabi United Arab Emirates
BUTTERFLY VALVE WITH T 971 2 6968700 F 971 2 4472915
SUPERVISORY SWITCH E abumail@ghd.com W www.ghd.com
SPRINKLER MAIN RISER

PRESSURE GAUGE
WATER FLOW SWITCH Specialist Consultant
CONCRETE TANK WALL

TO FIRE ALARM SYSTEM THRUST BLOCK


GROOVE WITH
2mm DEPTH Fire Life Safety, Planning
PIPE SEALING
and Regulatory Specialist
FREE FLANGE
(316) '100mm

TO SPRINKLER PIPE
NETWORK

'200mm (AROUND)
50mm TO THE
NEAREST DRAIN POINT UNDERGROUND FIRE PROTECTION Specialist Consultant
PIPE
50mm WELDED OPEN '100mm
INSPECTOR TEST & DRAIN VALVE RING (316) Third Party
Operational Advisor
OUTER RING
10mm THICKNESS 15mm THICKNESS
WITH GROOVE
ON BOTH SIDES

ZONE CONTROL VALVE DETAIL (NOTE: REFER TO NFA 13 FOR MORE DETAILS)
Client
ADAC
NOT TO SCALE
Project
MIDFIELD TERMINAL FIRE
STATION
Title FIRE PROTECTION SERVICES -
MISCELLANEOUS DETAILS
SHEET 2 OF 4
Scale As indicated DO NOT SCALE
Drawn A. NOCEJA Designer P. MOHD.
Drafting Design
11 - ZONE CONTROL VALVE DETAIL 10 - THRUST BLOCK DETAIL 12 - PUDDLE FLANGE DETAIL Check Check

SCALE NTS SCALE NTS SCALE NTS Approved


(Project Director)
Date
This Drawing must not be used for Construction unless signed as Approved
Original Size
Drawing No:
A1
DETAIL DESIGN 76-10526- F003 Rev: A
Plot Date: 7/03/2015 10:14:41 PM Cad File No: C:\Users\fvillete\Documents\76-10526_Midfield Fire Station MEP-Central_fvillete.rvt