1. 6.1.13 6.1.13 The numerical 6.1.13 Our system is 6.1.13 The numerical M/s ALIND
relays shall be capable fix. and we should not relays shall be capable of comment is
of storing minimum go for field storing minimum 5000 acceptable and M/s
5000 events serially configuration. It will events serially with date ASHIDA comment is
with date and time increase unnecessary and time stamp of 1ms not acceptable as
stamp of 1ms accuracy. complication There is accuracy. The events the event definitions
The events definitions provision in SCADA definitions shall be may be configured
shall be configurable software to filter configurable and by relay
and generally include unwanted events generally include tripping manufacturers if felt
tripping of different of different protection necessary in future
protection elements, Firm should give elements, relay pickup, to meet the field
relay pickup, relay reset, mapping file for event relay reset, relay blocked requirement.
CB trip, CB close, so that it can be use due to harmonics or any
changed of status input, while SCADA other restraints, CB trip,
relay setting changed, integration CB close, changed of
trip circuit monitoring status input, relay
etc. The events shall be setting changed, trip
retrievable through an circuit monitoring etc.
external laptop/PC. The events shall be
retrievable through an
external laptop/PC.
2. 6.1.25 6.1.25 The module shall There is a difficulty in Accepted
also be capable to accommodating all the
display I (fault current), mentioned parameters in
V(voltage), clause 6.1.25 viz, fault
R(resistance), current, viltage,
X(reactance), Phase resistance, phase angle,
angle, Delta-I current, delta-I current, fault
fault clearing time and clearing time and fault
fault date & time date & time in LCD
(wherever applicable) of window. The current,
latest 100 faults at relay voltage, resistance and
LCD. The CTs & PTs reactance, phase angle,
provided at TSS may fault type and fault date
have different ratios, and time will be stamped
hence to display the with the corresponding
actual value (line value) event number. The delta-
of I, V, R, X ect. the CT I current and fault
primary current shall be clearing time can be
settable in the range of accessed with pressing
100 to 3000A in the one scroll key. This will
steps of 50A and PT maintain same event
primary voltage shall be number along with time
settable in the range of of occurrence of fault.
20000V to 30000V in
steps of 500V. On line
current, voltage,
Reactance & Resistance
shall also be displayed
on relay LCD.
International Standard
IEC 60255-26 has been
prepared by IEC
technical committee
95: Measuring relays
and protection
equipment.
This third edition
cancels and replaces
the second edition
published in 2008. This
third edition also
cancels and replaces
the following standards:
IEC 60255-22-1:2007,
IEC 60255-22-2:2008;
IEC 60255-22-3:2007,
IEC 60255-22-4:2008,
IEC 60255-22-5:2008,
IEC 60255-22-6:2001
and IEC 60255-22-
7:2003, IEC 60255-
11:2008, IEC 60255-
25:2000 and IEC
60255-26:2008