For practical design of light gauge sections to EN1993, designers will normally use software
or refer to manufacturers data. This example is presented for illustrative purposes
Basic Data
Height of stud H = 2,75 m
Spacing between studs S = 0,6 m
Span of floor L=5m
S = 0,6 m
This material is copyright - all rights reserved. Use of this document is subject to the terms and conditions of the Access Steel Licence Agreement
ULS Limit State concentrated load from upper level and roof: Q = 10,0 kN
EN1993-1-3
Partial factors M0 = 1,0
2(3)
M1 = 1,0
G = 1,35 permanent loads EN1990
Q = 1,50 variable loads
where: EN1993-1-3
6.1.3
N c, Rd = Aeff f yb M0
6.1.4
M cz, Rd, com = Weff, com f yb / M0
M z,Ed = 0